DIVISION 9: FINISHES

SECTION 092813 CALCIUM SILICATE BOARD

SECTION 092813 CALCIUM SILICATE BOARD CEILING (CSB)

1.0 GENERAL

1.1 DESCRIPTION

The scope of works includes the supply and installation of a proprietary system of A)
12mm thick calcium silicate board ceiling (CSB) and B) Ceiling Access Panels
as shown on the drawings.

The ceiling works shall include everything necessary for and incidental to the
execution and completion of the ceiling system as shown in the drawings and
specified herein, and reference to the Bills of quantities and contract documents in
general.

1.2 STANDARDS

Calcium Silicate Board ceiling is to be tested for ignitability and fire propagation in
accordance with BS 476: part 6, and for flame spread in accordance with part 7, to
achieve Class 1, or equivalent proposed by the Contractor subject to approval .

1.3 SUBMITTALS

1. Shop Drawings

Shop drawings showing the dimensions, details of installation, layout pattern,


methods and locations of forming openings for mechanical and electrical works
and services shall be submitted for approval. No ordering of material and
installation shall be carried out until all the shop drawings are approved.

2. Coordination Drawings

The Contractor shall provide service co-ordination drawings and ceiling co-
ordination drawings for approval. No work shall be carried out until the approval is
given.

3. Samples

Samples of the type of ceiling and the colour of the panels are to be submitted for
approval with no claim for additional cost or time to be incurred in doing so.
Subsequent material delivered to site is to be equal to the samples approved.

4. Structural Calculations

For details and structural calculations of the ceiling support systems a PE engaged
by the Contractor is to endorse all design calculations submitted.

5. Test Reports
Reports of tests carried out by accredited laboratory are to also be submitted.

6. As-Built Drawings
Submit As-Built Drawings upon completion and hand over of the system.
TS/A/SECTION 092813 /1
DIVISION 9: FINISHES
SECTION 092813 CALCIUM SILICATE BOARD

1.4 PERFORMANCE

A) Calcium Silicate Board Ceiling

1. Material

The ceiling shall consist of 12mm thick, autoclaved calcium silicate boards, asbestos
and magnesium free, with a sand face. The physical properties shall be as proposed
by the Contractor subject to approval:
3
a) Normal dry density 910 kg/m ±10%
2
b) Weight 9.5 kg/m ±15%
2
c) Flexural strength, across grain 10.0 MN/m
2
d) Flexural strength, along grain 6.0 MN/m

2. Physical Performance

The physical performance of the board shall be as follows:

a) Appearance

The board is off-white in colour with a sanded fair face and a lightly textured
reverse face.

b) Asbestos content

The board must be formulated without asbestos and magnesium or any


other inorganic fibre.

TS/A/SECTION 092813 /2
DIVISION 9: FINISHES
SECTION 092813 CALCIUM SILICATE BOARD

c) Fire performance

The board should have some fire performance. It should generate minimal
levels of smoke or toxic gases in a fire.

d) Moisture tolerance

The board must have moisture tolerance and not deteriorate in wet or humid
conditions, even when used in applications where it is continuously exposed
at atmospheric moisture.

e) Resistance to chemical

The board must have resistance to dilute chemicals such as brine, bleaches
and chlorine solutions in order that it can withstand industrial cleaning
agents.

f) Dimensional stability

The board should be resistant to swelling, shrinking or warping when


changes in temperature or humidity occur. When fully saturated the board
should expand by no more than 0.3% from normal state.

g) Alkalinity

The board should be neutral or mildly alkaline, with a pH value between 7


and 10.

h) Biological

The board must be resistant to attacks by insects or vermin. It should not


nourish mould growth.

i) Ease of use

The board should be capable of being cut, drilled or sanded using


conventional tools. It must also be capable of accepting decorating
materials without the need for further surface preparation.

j) Compatibility

The board must be compatible with all common building materials, be non-
caustic and not promote corrosion.

k) Proven

The board must be manufactured by a reputable company with proper


quality control procedures. It must have been widely used in previous
projects and have a good track record.

TS/A/SECTION 092813 /3
DIVISION 9: FINISHES
SECTION 092813 CALCIUM SILICATE BOARD

l) Fire performance

British Standard BS 476: Part 6 - Fire Propagation


The board must satisfy the requirement of BS 476 : Part 6

British Standard BS 476: Part 7 – Surface Spread of Flame

The board must achieve Class 1 rating, a material of limited combustibility,


or proposed by Contractor subject to approval

m) Building Regulations

The board must be approved for use in areas where ceilings or partitions
having a surface flame spread rating of class O or lower is required, or
proposed by Contractor subject to approval.

B) Ceiling Access Panel

1. Proprietary ceiling access panels for Calcium Silicate Board ceiling shall be
provided at the following locations:

a) At the locations where there are fire damper access panels;

b) At the locations where there are sprinkler drain valves, VAV boxes;

c) At every 6 metres on bothways in every room;

d) At every structural bay;

f) At every location of CCTV control boxes and power points;

g) At the locations required for maintenance purpose;

h) At the location identified by the Employer.

2. The ceiling access panels shall not be less than 600x600mm in size and
integrated visually with the ceiling system.

3. The ceiling access panels shall be supported independently from the


secondary grid or concrete soffit or other supports and not resting on the
ceiling system.

4. Where steel are used for the supports, they shall be of galvanized steel.

5. The ceiling access panels shall be provided with locksets complete with keys
and concealed hinges. No access panel shall be allowed to drop freely when
opened. A total of 10 keys with stainless steel key tags for every key shall be
provided.

TS/A/SECTION 092813 /4
DIVISION 9: FINISHES
SECTION 092813 CALCIUM SILICATE BOARD

2.0 PRODUCTS

Product submitted by Contractor is to be from an approved supplier to meet all


requirements as specified in Performance Requirements.

3.0 EXECUTION

1. Installation

a) The installation of the ceiling works is to be carried out in strict compliance with the
manufacturer’s recommendations.

b) The ceiling shall be suspended and fixed to a concealed framing system.

c) The ceiling shall have its own supporting system and shall consist of suspension rods
of 9mm diameter minimum in galvanised steel of hangers of 50 x 50mm galvanised
channels, anchorages and levelling devices, runners, couplings and clips, wall
mouldings, joint trimming and other accessories necessary for suspending from the
structural ceiling, making levelling adjustment and the proper assembling of the
ceiling sytem.

d) The suspension system shall be designed to carry the total load of the ceiling and
constructed of 38mm x 38mm x 0.91mm steel main tee spanning at maximum
600mm centres. Similarly, the cross tee of the same guage shall be spanned at the
maximum of 1200mm centres.

e) The 12mm thick calcium silicate board shall be fixed onto the suspension system with
15mm x no 6 self tapping screws at 300mm centres on main tees and 600mm
centres on cross tees.

f) The angle hanger support shall be suspended from the secondary grid system using
9mm diameter galvanised steel suspension rods looped around the ceiling
secondary grid and secured with bolts and nuts.

g) The calcium silicate board shall be waterproofed complying with the following:

i) A layer of approved thin coat expanded metal mesh wing angle bed shall be
installed at all the external corners of the boards up to 100mm above ceiling
level for edge protection.

ii) The calcium silicate boards shall have a minimum 30mm width tapered edge
along the sheet supplied as standard from the factory.

iii) The calcium silicate board shall be prepared for plastering, for filling the joints
with finishing plaster and pressing into the plaster dry reinforcing perforate
jute scrim cloth 50mm wide, trowelled smooth and flush with the boards.
Linen gauze or self-adhesive fibreglass tapes shall not be used.

TS/A/SECTION 092813 /5
DIVISION 9: FINISHES
SECTION 092813 CALCIUM SILICATE BOARD

iv) The finished coat at the joint when almost set, is to be trowelled to a smooth
surface using as little water as possible applied with a brush. The admixture
of lime with gypsum plaster applied to the board shall not be used.

h) All joints shall not be visible after painting and the completed ceiling shall be
prepared to receive painting work.

TS/A/SECTION 092813 /6