Professional Documents
Culture Documents
Design Guide
-
v
&
v
A
*
The Institute of Plumbing
Plumbing Engineering Services
Design Guide
Administration Support
Emma Tolley
Lorraine Courtman
Janice Grande
Jenni Cannavan
ISBN 1 871956 40 4
Published 2002
© The institute of Plumbing
Foreword
It is my pleasure to provide the foreword for this edition of the
Plumbing Engineering Services Design Guide. For many years
now, the Institute of Plumbing has supported the construction
industry on the wide range of issues that are concerned with
plumbing engineering services and this design guide has been
key to the success of that support.
As with other sectors of the construction industry, plumbing
engineering services is an area that is rapidly developing with new,
improved and innovative technologies and the role of the Institute
Dr Alan Whitehead MP
of Plumbing in this is an important one. The Guide has needed to
Minister for Building Regulations
Department for Transport, evolve with the advances in industry practice and techniques.
Local Government
and the Regions Since the guide was first launched in 1977 it has continued to be
May 2002
an indispensable reference source for designers, engineers and
Note: On 29 May 2002 the trades -persons and this is reflected by the constant demand for it,
Department of Transport, Local
Government and the Regions both from home and abroad.
(DTLR) was disbanded and
responsibility for Building This new edition will provide additional information and guidance
Regulations in England and Wales
was transferred to the Office of the on current technologies and practices and will, no doubt, continue
Deputy Prime Minister. to be a valuable source of information for those engaged in the
design, approval, and installation of plumbing engineering
services.
I commend it to the plumbing industry.
Dr Alan Whitehead MP
Preface
This Design Guide 2002 replaces the previous edition published in 1988.
The object of the Guide is to advance knowledge of plumbing technology
to those engaged in plumbing design and system installation.
The Guide has been considerably enhanced utilising an easier to read
three-column format, bound within a silver cover to celebrate the
25th Anniversary since the original Data Book was published.
Technology in the plumbing industry has changed considerably in the
14 years since the guide was last published. This edition seeks to include
as much information as possible, on new technologies. Indeed, the Guide
reflects as many of the changes related to UK plumbing technology of
which we are aware.
Throughout the publication, several British Standards have been replaced
by European Harmonised Standards. Many BS/EN Standards have now
been brought together within the standards, codes and miscellaneous
data section.
The water services section has been greatly expanded to include many
additional design considerations and to take account of the statutory
requirements of the Water Supply (Water Fittings) Regulations 1999 in
England and Wales and the Water Byelaws 2000 in Scotland.
The heating section has been completely re-written to concentrate on gas,
as the most widely used heating medium. It also includes information on
systems and heating appliances currently in use, including condensing
boilers and wet under floor heating systems.
The sanitary plumbing and drainage section has changed significantly to
reflect the requirements of BS EN 12056, which replaced BS 5572.
This section has also been extended to include information on the
technologies involved in vacuum drainage and syphonic rainwater
disposal systems.
The piped gases section has undergone a major review and the section
on steam now includes condensate recovery information.
Information on the design and installation of residential sprinkler systems
is included for the first time, along with completely new sections on
resource efficient design and swimming pools.
As co-ordinator of this Guide, I acknowledge the unstinting voluntary work
of the many people associated with its production. I’m especially grateful
to the Institute’s full time head office technical team, consisting of
Dale Courtman and Emma Tolley.
Finally, my thanks also go to the authors, manufacturers and professional
organisations who have contributed to this publication. Their essential
participation should be appreciated by all who adopt the Guide as a
source of reference for the design of plumbing engineering services.
1
Hot and cold water supplies Plumbing Engineering Services Design Guide
2
Plumbing Engineering Services Design Guide Hot and cold water supplies
2. Number of occupants, permanent or decision firmly on the consumers. with canteen 45 Person
transitional - without canteen 40 Person
Table 2 provides guidance on typical
Factory
3. Requirement for fire protection water usage within buildings over a 24
hour period. - with canteen 45 Person
systems. - without canteen 40 Person
4. Landscape and water features. In designing storage capacities, account
Schools
needs to be taken of the building and its
- Nursery 15 Pupil
In dwellings the resident's water location.
consumption is divided between the - Primary 15 Pupil
many appliances. A typical percentage 1. Period and hours of occupation - Secondary 20 Pupil
break down provided by the Environment 2. Pattern of water usage - 6th Form College 20 Pupil
Agency is: • Boarding 90 Pupil
3. Potential for an interruption of supply
Hospitals
1. WC suite 32%
4. Available mains pressure, and any - District General 600 Bed
2. Washing machine 12% inadequacies during the hours of - Surgical ward 250 Bed
3. Kitchen sink 15% building use - Medical ward 220 Bed
4. Bath 15% 5. Health & Safety, prevention of - Paediatric ward 300 Bed
bacteria, including legionella. • Geriatric ward 140 Bed
5. Basin 9% Sports Changing
If a building is occupied 24 hours a day,
6. Shower 5% then an interruption of supply will have a - Sports Hall 35 Person
• Swimming Pool 20 Person
7. Outside supply 3% greater impact than that for say an office,
which may only be occupied for eight to • Field Sports 35 Person
8. Miscellaneous 9% ten hours. Where a building is occupied - AH weather pitch 35 Person
Overall consumption increases by around by elderly or infirmed people then Places of Assembly (excl. staff
10% during warmer months when out avoiding any disruption of the water - Art Gallery 6 Person
door usage increases to over 25%. In supply is an important consideration as - Library 6 Person
general, consumption per person they would be unable to easily leave the
building should water become
- Museum 6 Person
decreases with an increase in dwelling - Theatre 3 Person
size given the shared facilities. unavailable.
- Cinema 3 Person
For guidance on the total water demand Clients, such as the National Health - Bars 4 Person
for typical types of buildings refer to Table Service, require their buildings to be - Night Club (3) 4 Person
2 for daily water demand. The figures provided with storage to safeguard - Restaurant 7 Cover
stated have been assembled from a against an interruption of the mains
number of sources, including BS 6700, supply. Industrial clients may well require SUPPORTING INFORMATION
Chartered Institute of Building Services storage to ensure their business and/or If the number of building occupants are not
Engineers (CIBSE) and Environmental production is not interrupted. If water accurately known then as a guide the
Agency studies and can be used as a ceases to be available within a building following criteria can be used.
then the occupiers will eventually leave Offices, one person per 14m2 of the gross
basis for good practice.
as toilet facilities will become unusable. It building floor area.
is likely that when an interruption of Sports hall, four persons per badminton court
supply occurs then the water available area per hour open, maximum.
Swimming pool, one person per cubical per
would be conserved as much as hour open, with a factor of 0.6 for diversity.
possible, thereby extending the time of Field sports changing, persons per teams per
occupancy beyond that anticipated under number of pitches, per day.
normal usage rates.
3
Hot and cold water supplies Plumbing Engineering Services Design Guide
All Weather Field, persons per teams per The type of water system will need to be
hours used. Incoming supply
one or a combination of the following: (balanced pipes not critical)
Museums, Art Galleries, Libraries, One
person per 30m2 of the gross building floor a. Direct mains fed
area.
Restaurants, One person per 1.0m 2 of the
b. High level storage with gravity down
dining area. feed
Cisterns, rectangular,
Bars, One person per 0.8m 2 of the public c. Pumped from a break cistern or in parallel
bar/seating area.. storage provision.
When the water supply companies, Potentially a one or two storey building in
regulations, or client requirements do not a locality where an interruption of water Outlets, from opposite I
l
comers of inlet, and
specifically dictate the period to cover an supply is very infrequent and causing strictly balanced In length
interruption of a mains supply then Table little inconvenience, there is an option for and configuration
3 provides recommendations for the water supply to be direct from the
reasonable periods of storage, expressed mains without storage being provided. If NOTE
as a percentage of the daily water the provision of storage is possible at Valves to be provided to enable one cistem/tank to
demand. high level then the system could be be isolated whilst other remains open.
enhanced to provide storage coupled
Figure 2 Storage cistemAank layout
with it becoming a gravity down feed
Table 3 Period of storage system. See Figure 1. Sectional tanks commonly have flanges,
Type of Building % of the
being internal or external. External
daily demand Option of gravity feed flanges permit tightening without needing
Hospitals 50% tank at high level . :::: to enter the tank, and on the base permit
the tank to be self draining through a
Nursing Homes 50%
single drain point, without further draining
Dwellings
Hotels, Hostels
Offices
0 • 50%
50%
0 - 50%
Rising main,
and drop to
draw-off
L of any entrapped water between flanges.
Such a feature reduces maintenance and
assists the prevention of water stagnation
Shops 0 - 25% points which can lead to harmful bacteria
growth, including legionella.
Library, Museum, Art Galleries
Cinema, Theatre
Bars, night-club
0 - 25%
0 - 25%
0 - 25%
Ground level
L In calculating the storage capacity a free
board allowance is necessary to
Sports Facilities 0 - 25% accommodate the float valve, over flow
Schools, Colleges, Universities 50% Utility Co. installations and any expansion from the
Boarding Schools 50% mains O’ hot water system. Depending on pipe
sizes, commonly a 250 - 300 mm free
board depth is required on ciserns/tanks
Figure 1 Supply to a two storey building having a capacity greater than 2500
Water distribution litres. Raised ball ( float) valve housings in
conjunction with a weir overflow can
Storage tanks provide an increased depth of water
The water distribution installation A building requiring a large water storage stored over the main area of the
requires to be able to deliver the correct provision may not be able to cistern/tank(s).
flow and volume of hot and cold water accommodate it at high level, in which The location of the inlet and outlet
when and where it is needed. The mains case a low level location will be needed, connections is important. A cross flow
pressure can provide the initial means of in conjunction with a pumped distribution through the cistern/tank needs to be
delivering water into the building. The system. achieved to assist the complete regular
water supply companies are required to turn over of water throughout the storage
deliver their water to the boundary with a A combination of high and low storage
can be considered if a gravity distribution period.
minimum pressure of 1.0 bar. Often their
delivery pressure can be higher, however is preferred for all or part of the building. Sub divided, twin and multiple
at times of high demand, the pressure This has an advantage of providing some cisterns/tanks ideally should be installed
will be closer to the minimum provision. storage in the event of an interruption of in parallel to each other. The inlets
the water supply, or power supply to the require to be positioned at the same level
pumps. A storage ratio of 2 : 1 low/high to ensure they supply the cisterns/tanks
type of system level is a typical arrangement. in unison, and as far as possible the
Storage can comprise of two same flow rate to assist a balanced
The type and style of water distribution
compartments or cisterns/tanks in order throughput. The outlet connections and
needed for a particular building will manifold pipe work needs to be arranged
depend mainly on the building height and that maintenance can be carried out
without interrupting distribution. with symmetrical and equal lengths, also
its use. to provide, as far as is possible a
a. The building height will determine
For small storage quantities one piece balanced flow from the tanks.
whether pumping will be required to cisterns can be used, which generally
are of a low height construction. For The use of a delayed action float valve
deliver water to the highest level may also be considered to ensure a
storage of 2500 litres or more, sectional
b. The building use will determine the panel tanks may be considered more greater turn over of water.
amount of storage that will be appropriate with a centre divide.
required.
Above 4000 litres storage twin
cisterns/tanks may be considered
appropriate. See Figure 2.
4
Plumbing Engineering Services Design Guide Hot and cold water supplies
b. No pump running costs e. Cold water and hot water cold feed
Access to storage gravity distribution.
cisterns/tanks c. Potentially less noise due to lower
pipe flow velocities. The low level pump set can be sized to
Access for installation and maintenance provide a low volume, more frequent
The disadvantages are:
is required. Table 4 is a guide. operation and high head to deliver the
a. Greater structural support water to the tanks at roof level.
For large buildings, accommodation for
water storage has an significant impact. b. Larger pipe sizes due to limited If a ‘mains' water supply is required to be
Table 5 provides an outline guide to the available head, when compared to provided specifically for drinking water
space that may be required. pumps points or drink making equipment, then
either of these can be supplied from the
c. Lower delivery pressures. incoming main up to the number of floors
Table 4 Access to storage cistems/tanks that the available mains pressure will
reach, and from the pumped rising main
Location ( mm) Pumped supplies above that level; or entirely from the
Around 750 The delivery of water by pumping will pumped rising main. See Figure 6.
Between, tanks 750 provide flexibility in the positioning of the Whilst all water supplied for domestic
Above, allowing beams to intrude 1000 storage cisterns/tanks. The delivery flow uses has to be suitable for drinking
Below, between supports 600 rate and pressure demanded by the purposes, supplying drinking water points
For outlet pipe work, incl. access 1500 system are met entirely by selecting the direct from incoming mains or pumped
Tank construction thickness 100 correct duty for the pumps. The pump set mains provides a cooler, more
Insulation (may form part of tank) 25
is required to deliver a constantly varying oxygenated supply for taste purposes.
flow rate as draw-off points are randomly
Raised float valve housing 300
used by the occupants. The use of multi-
Entry to tank BOO dia stage variable duty and/or inverters is an
advantage. See Figure 4. CistemsAank ( s)
Table 5 Water storage plant room area on roof or roof
Generally a minimum of two pumps are plant room
Storage Tank Height used, each having 100% system duty level
(Litres) 1.5 metre 2 metre 3 metre and controlled to enable them to be a
stand by to each other. To prevent high
5,000 18 m2 18 m2
pressure overrun when demand is less
10,000 31m2 23m2 than the design demand, a pressure
20,000 50m2 40m2 limiting or variable control flow device
40,000 72m2 60m2 50m3 needs to be fitted on the outlet from the
60,000 80m2 60m2 pumps.
100,000 10m2 80m2 Low level break
For high buildings a combination of or storage tank
pumped and gravity may be appropriate.
Gravity supplies
For gravity supplies to be effective, the
The advantage of this is to provide a
proportion of the daily water usage in a
cisterns/tank(s) at roof level, which would
e
storage requires to be at a sufficient provide a gravity down feed service, and Pump set
height to deliver the water to the draw-off continue to provide water in the event of O Incoming main
point at the required flow rate and a failure of the pump. See Figure 5. Such
pressure. The available head is the a system would comprise of:
dimension between the bottom of the Figure 5 Combined pump and gravity
storage cistern/tank(s) and the highest a. An incoming main
draw-off point, or draw-off point with the b. Low level break or storage
Figure 6 ‘Mains ' water for drinking
greatest head/pressure loss. See Figure 3. cistern/tank
The advantages of gravity supplies are: c. Pump set
a. Availability of water in the event of d. High level cistem/tank(s)
water mains or power failure Pumped ‘mains’
to drinking
points and
drinks machines
Figure 3 Gravity supplies available head Figure 4 Pumped supply layout
Utility ‘mains' to
drinking points
Head of water
Duty of pumps
= static lift plus , T and drinks
machines
pressure available in distribution j
loss and Low level
"
A " delivery
pressure, in
| cistern/tank
j
metres S
Pump set
~~
* LT ^ Incoming main
5
Hot and cold water supplies Plumbing Engineering Services Design Guide
Table 6 Hot water demand Sports hall, Four persons per badminton court
Hot water Type of building Daily Stored Unit
area per hour open, maximum.
production Dwellings
( litres) ( litres) Swimming pool, One person per cubical per
hour open, with a factor of 0.6 for diversity.
Field sports changing , persons per teams per
- 1 bedroom 115 115 Bedroom number of pitches, per day.
Hot water can be generated by a differing
- 2 bedroom 75 115 Bedroom
number of methods, and the selection All weather field, persons per teams per hours
will depend mainly on the quantities of - 3 + bedrooms 55 115 Bedroom
used.
hot water required and the types of - Student en-suite 70 20 Bedroom
energy readily available. - Student, comm 70 20 Bedspce Museums, art galleries, libraries, One person
per 30m2 of the gross building floor area.
- Nurses home 70 20 Bedspce
The demand for hot water will vary Restaurants, One person per 1.0m2 of the
- Children's home 70 25 Bedspce
considerably between types of buildings, dining area.
governed by their occupants and the - Elderly sheltered 70 25 Bedroom
activities taking place. For example: - Elderly care home 90 25 Bedspace Bars, One person per 0.8m2 of the public
- Prison Inmate bar/seating area.
Office buildings will require small Hotels
quantities frequently and regularly
- Budget 115 35 Bedroom
throughout the ‘normal’ working day, and
availability at other times as and when • Travel Inn/ Lodge 115 35 Bedroom
occupant’s ‘overtime’ working hours • 4/5 Star Luxury 135 45 Bedroom
HWS distribution 60°C
demand. Offices & general work places
- with canteen 15 5 Person
A foctory with a production line will
- without canteen 10 5 Person Store
require sufficient hot water to meet the HWS secondary
Shops <65°C
demand at breaks in the shift when the circulation >50C
work force may all wish to wash hands - with canteen 15 5 Person
etc. - without canteen 10 5 Person
Factory
A sports povifion will need to be able to - with canteen 15 5 Person Hot water cold feed <20C
provide large quantities of hot water for
team’s showering needs over a short - without canteen 10 5 Person
period of time following games, whenever Schools
they occur. - Nursery 15 5 Pupil Figure 7 Hot water temperature protocol
- Primary 15 5 Pupill
• Secondary 15 5 Pupil
Selection off hot water • 6th form college 15 5 Pupil
When a conventional bulk hot water
vessel is used it is necessary to ensure
production • Boarding 114 25 Pupil
that the contents of the whole vessel
Hospitals
achieves the correct stored water
In the selection of the type of hot water - District General 200 50 Bed temperature as stratification can occur.
production, the time available for re- • Surgical ward 110 50 Bed To overcome this situation the storage
heating is an important consideration.
- Medical ward 110 50 Bed vessel should incorporate the following
If a high volume or rapid re-heat rate is - Paediatric ward 125 70 Bed features:
required then it would be necessary to - Geriatric ward 70 40 Bed a. Base inlet hot water cold feed supply
ensure that a sufficient energy capacity Sports changing
is available. If the energy capacity - Sports Hall 20 20 Person b. Top outlet hot water outlet flow
needed is not available then a greater • Swimming Pool 20 20 Person c. Convex ends to vessel
volume of water storage would have to
- Field Sports 35 35 Person
be provided to ensure hot water is d. Provide a ‘shunt’ pump to move the
available during the slower re-heat - All weather pitch 35 35 Person hot water from the top of the vessel
period. Places of assembly (exci. staff ) to the base to avoid stratification.
Hot water production and storage
- Art Gallery 2 1 Person
6
Plumbing Engineering Services Design Guide Hot and cold water supplies
demand. Once the daily usage is Therefore it can be seen that the stored activity that is likely to take place. In
determined then the more critical peak water is there to provide for a peak 1750 determining the pattern of usage, it is
demand can be assessed. litre draw -off occurring over any period important to differentiate between a
Traditionally hot water peak usage was from, say ten minutes upwards. maximum daily demand and an average
based on a two hour storage re-heat daily demand, so that the implications of
For consideration purposes 1750 litres
period and this has generally proved to equates to 35 baths, each using 50 litres
the system not meeting the buildings hot
water requirements can be recognised,
be a satisfactory benchmark for peak of 60°C stored hot water. Dependant on
demands for that period. and the maximum requirements
the bath usage ratio of either 1200, 2400,
designed for where necessary.
Table 6 schedules a compilation of or 4800 seconds frequency of use (see
figures currently recommended by the simultaneous demand data) the hot Measured quantities of hot water
water industry’s design codes, with
water stored could be used up after a 63 consumption should not stand alone as a
minute period. Alternatively 1750 litres sizing guide . The rate at which these
additional categories added as could provide for 73 persons having a amounts are drawn off must also be
considered useful. The recommended
storage volumes are based on a 65°C
shower , each lasting 5 minutes using 24 considered. To project the demand
storage temperature and a two hour re-
litres of 60°C of stored hot water ( mixed pattern over the operating period of the
with cold). Dependant on the shower building, an hour by hour analysis of
..
heat period, i e a bulk storage vessel .
usage rate of 900, 1800, or 2700 likely hot water usage should be made,
This data should be considered as
seconds frequency of use, the hot water taking into account the number of
representative of capacities, which have
not given rise to complaints of
stored could be used up after a 45 occupants, the type and level of activity
inadequacy. minute period. These two examples are and any other factors that may affect hot
based on a peak statistical usage which .
water demand The projected pattern of
would likely not reoccur during the demand should be recorded in the form
Ttoo hour re-heat -
remaining time of the two hour re heat of a histogram profile.
period.
Typical examples of daily demand in
-
The two hour re heat storage volume -
A ‘semi storage’ hot water generator various types of buildings are illustrated
figures can provide a guide to the peak requiring to meet the same demand for in Figures 8 and 9.
water volume used during a peak two baths would need to be capable of
hour usage period. The same hot water By establishing a hot water demand
providing, approximately a 3.3 litre per
output could also be achieved by the use histogram a representative peak demand
second flow rate of 65°C continuous hot volume can be established. Typically the
of low volume/rapid reheat ’semi-storage’ water output, assuming an initial stored
types of hot water generators, if the peak hour is between 15-20% of the
volume capacity of 500 litres.
energy input capacity is available . day’s total usage .
These potential peak demands could be
The ‘semi-storage’ type of hot water considered as being extreme examples.
When selecting a ‘semi-storage’ hot
heaters can meet shorter peak demand water production unit(s) it needs to be
However they clearly demonstrate the
periods i.e. 1 hour, or less, although demands capable of being put on hot
recognised that the small stored volume
detailed secure information about peak is there to meet the short period peak
water generation, when taking account of
period demands during periods of less the maximum simultaneous usage that is -
draw offs that occur in any water supply
that 1 hour are not sufficiently available, system. The shortest of these peak draw -
imposed on draw -off fittings by the
and therefore a design risk margin will be offs is the ‘maximum’ simultaneous
building occupants, and accordingly has
required. demand litre per second flow rate figure
to be considered for design purposes.
calculated from the sum of the draw off
The established two hour peak usage Whatever the building, the likely pattern ‘demand or ‘loading’ units used for pipe
1
7
Hot and cold water supplies Plumbing Engineering Services Design Guide
500
School
£
£
1
400
I 1 Service
Sa
•
300
I | Catering
§ 200
o
2 100
i
o
o
ELI
6 12
a 18 24
Time (hours) Time (hours)
100 150
Restaurant Office
I= 80
8
£
Sa 60
o 100
£
e
so 40
| 50
S' 20
o
0 6
L 12
mriM
-
18 24
2
6
D 12 18
I
24
Time (hours) Time ( hours)
Figure 9 Examples of daily demand patterns for commercial premises Reproduced from CIBSE Guide G: Public Health Engineering, by
permission of the Chartered Institution of Building Services Engineers.
sink, or bath, have a shower, and the additional transfer process and less
Vented or unvented
number of times the draw -off is used efficient operation when space heating is
during the peak demand period, i. e . not needed. generators
every 5, 10, or 20 minutes, or more The . Solar heating , when available and viable A vented hot water generator is supplied
‘ maximum simultaneous demand’ must
not be applied to periods greater than
is an excellent supplementary heat by a gravity hot water down feed and
source and effective in reducing annual expansion pipe and having an open vent
the period and frequency of ‘maximum
energy tariffs. pipe over the feed cistern/tank to provide
simultaneous demand.
Commonly used forms of hot water for pressure relief, in addition to
heating are:
Dwellings and small buildings: -
r
Hot water Electric, or gas combination (HWS &
Heating) boilers.
Option of
combined
generators Offices:
Electric, local or ‘point of use’ water
cold feed
and open
vent
heaters. Relief
The production of hot water can be valve
r
achieved by a varied number of energy Larger premises and sports facilities: Hot water ^
sources. Gas direct fired water heaters. cold feed Hot water
generator
1. Electric, generally with direct T
immersed elements Local or central plant
2. Gas, either direct, or indirect by a The adoption of local or central plant is
dedicated circulator Figure 10 Vented hot water generator
generally dependant on the type of
3. Low Temperature Hot Water (LTHW) building , where hot water is needed and Figure 11 Unvented hot water generator
boiler plant , dedicated or more likely the volume required. For toilet wash
forming part of the space heating basin ‘hand rinse ’ purposes only, where HWS distribution
plant relatively little hot water is required then Temperature
a local heater positioned adjacent to the relief valve
4 . Steam , when available from a central
draw -off fittings would be appropriate. -Mi
plant facility.
This may be considered particularly HWS generator
Energy forms, which provide a direct suitable for office and school toilets. The
means of heating hot water , i.e electric . advantages of this type of installation can
Expansion
vessel
and gas in particular, are the most be low installation, energy consumption,
effective in terms of efficiency because of and maintenance costs, plus alleviating
least loss of heat during the heat transfer the need for secondary circulation
process. Sharing hot water generation pipework and pump to maintain
with space heating plant can decrease distribution temperatures. Check valve Pressure
the energy efficiency through the relief valve
8
Plumbing Engineering Services Design Guide Hot and cold water supplies
expansion. These units generally are Secondary circulation and particularly suited for these type of units.
storage type units rather that semi-
storage units. As an open vessel the trace heating A number of different types of local
heaters are available. Most commonally
maximum pressure is the static head
from the cold water feed cistern/tank. Secondary circulation or trace heating are ‘unvented units’ supplied directly from
Individual vessels should be provided needs to be provided when the length of the incoming mains or from the main cold
with their own open vent. A pressure hot water pipework and the volume of water distribution system within the
and/or temperature relief valve can be water the pipework contains, becomes building. Usually a minimum inlet
considered in place of a separate open such that it would take an unreasonable pressure is required, often being 1.0 bar
vent subject to the vent being combined length of time to draw off the cool water. or above, subject to the manufactures
with the cold feed/expansion pipe, and The Water Regulations Guide instructions.
there being no means of closing off the recommends that un-circulated hot water The Water Regulations govern the
vent. distribution pipes should be kept as short
requirements for unvented water heaters.
as possible and if uninsulated not exceed
Heaters with a capacity of less than 15
Unvented hot water generators are the maximum length stated.
generally supplied from Utility Company’s litres are classed as being instantaneous
mains, or pumped distribution systems. Table 7 Water Regulations Guide and need no temperature or pressure
relief valves, or expansion valves or
Provision for expansion and Max, lengths of uninsulated pipes
pressure/temperature relief is provided vessels. Units above 15 litres capacity
by mechanical fittings to provide a safe
Pipe 0D Length (Seconds) require such devices.
system. Unvented units are commonly < 12 mm 20 m (11)
semi-storage types. The pressures that < 22 mm 12m (25)
they are subjected to are the operational < 28 mm 8m (26)
head of the ‘mains’ or ‘pumped ' system
inclusive of any ‘closed head’ situation.
> 28 mm 3m (>15)
Control of legionello
For unvented units with a capacity of 112 The ‘seconds’ column illustrates the
litres or less, the Building Regulations The means of controlling legionella
approximate length of time it would take
require that the unit is provided complete bacteria is determined by the Health &
to draw of the cool water based on the
with all it’s safety fittings. For larger Safety Approved Code of Guidance L8.
draw off rate of a wash basin tap with an
unvented units the ‘Designer’ is required 0.15 I/s flow rate. The Health & Safety
to specify the safety fittings in Figure 13 Design temperature and
Legionella Code L8 states a maximum associated risks (CIBSE TM13)
accordance with the Water Regulations. draw off period for hot water to reach its
correct temperature shall be 60 seconds.
Multiple hot water Insulating the pipes does not stop the hot
generators water cooling, it only slows down the
.
cooling rate Once the temperature has
100 - I
A
dropped below 50°C, then the Health & No viable
Legionella
Hot water flow distribution
Safety’s ‘60 seconds’ maximum length of
time criteria applies. The insulating of B
> pipes is desirable as it delays the cooling 80 -
Hot water rate of the hot water enabling it to be
generators in ‘useful’ for longer, and by that means 1 Legionella
parallel with
‘
=
saves energy and the associated costs. C will not
strictly balanced 60 -
pipework
connections in
length and
U HWS
Once it becomes necessary to provide
secondary circulation or trace heating,
. ,
multiply and
die in time
Legionella
will remain
Figure 12 Multiple hot water heaters Local heaters dormant
0
Where multiple hot water generators These generally comprise of small self
become necessary for capacity/output, contained electrically heated hot water Increasing multiplication of legionella
and/or standby/back up purposes care units individually placed near to the
must be taken to ensure that the position that hot water is required, and
interconnecting pipework configuration serve either a single draw off or a A. Steam humidification
provides a balanced use and flow number of draw off ’s which are adjacent B. LTHW heating
through the two of more hot water to each other. Gas heaters are available, C. Hot water storage
generators. but not commonally used due to the
D. Hot water taps outlets
E. Cold water storage, sprinklers
need to make provision for flues.The F. Spray humidification
purpose of such units provide hot water G. Mains cold water and air cooling coil
in a simple manner, in particular where condensate
the draw off is remote and only low
volumes of hot water is required, such as
for hand rinsing. Office toilet
accommodation and single showers are
9
Hot and cold water supplies Plumbing Engineering Services Design Guide
The Code identifies specific practical Graph 1 Temperature and duration of exposure, sufficient to cause burns in thin
guidance on how this is to be achieved in areas of skin
water supply systems. The key aims
being:
1. Maintain cold water below 25°C
2. Maintain stored hot water between
60-65°C
3. Maintain hot water distribution above
50°C, and preferably at 55°C
4. Insulate all cold and hot water
storage vessels and distribution
pipework
5. Minimise the length of un-circulated
and none trace heated hot water
pipes
6. Avoid supplies to little or unused
draw-off fittings
7. Maintain balanced use and flows
through multiple cold water
cisterns/tanks and hot water vessels .
See Figure 13.
NOTE:
For further details please see ‘legionella
section’, contained within this guide. Time in seconds
10
Plumbing Engineering Services Design Guide Hot and cold water supplies
11
Hot and cold water supplies Plumbing Engineering Services Design Guide
COMMENTS:
1 . The list of examples of applications shown above for each fluid category is not exhaustive, others will present themselves and require to be
matched to a Fluid Category, possibly by seeking guidance from the Water Regulations Advisory Scheme.
2. The Categories distinguish between domestic use, m eaing dwellings; and non-domestic uses, meaing commercial buildings.
3. The Fluid Categories define that the water within sinks, baths, basins and showers in domestic premises is a lesser Fluid Category risk , than
the water within sinks, baths, basins and showers in medical premises, ie hospitals.
Crown copyright 1999 with the permission of the Controller of Her Majesty's Stationery Office
12
Plumbing Engineering Services Design Guide Hot and cold water supplies
Simultaneous demand
The number of draw -off points that may
be used at any one time can be
estimated by the application of probability
theory.
The factors, which have to be taken into
account , are:
a. Capacity of appliance in litres
b. Draw -off flow rate in litres per second
c. Draw-off period in seconds, i.e. time
taken to fill appliance
d. Use frequency in seconds, i.e. time
between each use of the appliance.
All of these factors can vary .
The capacity of wash basins, sinks and
other appliances all vary in capacity.
Draw -off tap sizes and flow rates differ
between appliances. The frequency of
13
Hot and cold water supplies Plumbing Engineering Services Design Guide
14
Plumbing Engineering Services Design Guide Hot and cold water supplies
Ripe Loading Flow Assumed Length Pipe Velocity Pipe Fittings head loss (m/h) Total System Total Final
Ref units rate pipe dia. loss loss head head head pipe
E T SV IV BV DO Other loss loss available size
( 1/8) (m) ( mm/h) (m/s) ( mh) (mh) ( mh) (mh) ( mm)
1- 2 10 + tank .45 20 10 .15 1.3 .5 .2 .15 0.75 2.6 15.0 20
2-3 5 + tank .35 20 2 .09 1.1 .18 .00 .26 Less static 20
3-4 Tank .15 15 3 .17 1.0 .51 .01 .02 .16 .7 3.56 15
4-5 29 .56 25 2 .06 1.0 . 12 .07 .08 , 015 .07 .355 25
5-6 16 .42 25 3 .035 .75 .105 .155 25
6-7 12 .32 20 2 .07 .9 .14 .09 .065 .295 20
7-8 10 .3 20 4 .066 .85 .264 . 12 .065 .449 20
8-9 5 .2 20 2 .32 .65 .064 .02 .084 20
9- wc 1 .15 15 1 .16 1.0 .16 .04 .02 .16 .38 1,718 2.0 15
Fittings head loss (mh) Total head available (mh) and terminal outlets, against a range of
flow rates and sizes.
In metres head, for each pipe fitting and In metres head, being either the mains or
valve on the section of pipe being sized. pump pressure and/or the height of the
Loss of head through Tees should be
gravity feed cistern/tank. See Table 16. assumed to occur at the changes of
Total head loss (mh) direction only.
In metres head, being the total sum of Final pipe size (mm) For fittings not identified reference shall
the pipe head loss and the fittings head be made to the respective manufactures
In mm, nominal internal diameter,
loss. literature.
confirming the pipe size for that section
of pipe. Where the flow rate falls between the
System head loss (mh) stated figures then the proportional flow
In metres head, being the total sum of all rate difference between the higher and
the sections of pipe relevant to the Loss of head through fittings lower figure shall be equally applied to
source of head available. the higher and lower head loss figure.
Refer to Table 19 loss of head, in metres
through various pipeline fittings
15
Hot and cold water supplies Plumbing Engineering Services Design Guide
purposes.
Table 17 Pipework velocities Cavitation caused by velocity is not
Pipe material
considered an issue with water supply
Location Noise systems as velocities should always be
rating Metal: copper, stainless Plastic
NR steel, galvanised
(m/s) (m/s)
.
UPVC, ABS, CPV Pb
below the 7.0 to 10.0 metres/second
where velocity cavitation can occur.
Service duct, riser, shaft, plant room 50 2.0 2.5 Having determined the appropriate
Service enclosure, ceiling void 40 1.5 1.5
velocity for the location of the distribution
pipes, using the pipe sizing charts you
Circulation area, entrance corridor 35 1.5 1.5
can determine the pipe size by cross
Seating area, lecture/meeting room 30 1.25 1.25 reference to the design flow rate, and
Bedroom 25 1.0 1.0 record the pipe head loss per metre.
Theatre, cinema 20 0.75 0.75 From thereon the pipe sizing schedule
Recording studio <20 0.5 0.5 for the whole system can be completed.
Other factors than velocity need to be considered with regard to noise generated by water flows
in pipework . The pipe support and brackets required to secure the pipework sufficient to restrain
it and prevent contact with other elements. Where pipework passes through a hollow structure ie
wall or floor, then it needs to be separated or sleeved so as not to be in contact with the
structure, to avoid resonance, and resulting amplified noise to occur.
16
Plumbing Engineering Services Design Guide Hot and cold water supplies
Table 18a Heat emission from insulated pipes (40°C temperature difference)
Value of pipework insulation thermal conductivity W /mK
0.040 0.055 0.070
Thickness of pipework insulation ( mm)
12.5 19 25 38 12.5 19 25 38 12.5 19 25 38
10 9 7 6 4 12 10 6 7 14 12 10 9
15 11 9 8 6 14 12 10 9 16 14 12 11
20 12 10 9 7 16 13 12 10 19 16 14 12
25 14 11 10 8 19 15 13 11 22 18 16 14
32 17 13 12 9 22 18 5 12 26 22 19 15
40 19 15 13 10 24 20 17 13 29 24 21 17
50 23 18 15 12 30 23 20 16 34 28 24 19
65 27 21 18 14 35 28 23 18 42 33 28 22
75 31 24 20 15 40 31 26 20 48 38 32 25
Pipe Heat Flow Assumed Length Pipe Velocity Pipe Fittings head loss (m/h) Total System Total Final
Ref loss rate pipedia . loss loss head head head pipe
load E T SV IV BV DO Other loss loss available size
(W) (I/S) (m) (m/mh) ( m/s) (m/h) (m) (m) (m) ( m)
1-2 (flow) 400 .09 25 1 .0025 <.5 .0025 .002 .02 .0045 25
2-3 (flow) 200 .05 20 2 .003 <.5 .006 .001 .007 20
3-4 (flow) 200 .05 20 4 .003 <.5 .012 .001 .013 20
4-5 (flow) 200 .05 20 1 .003 <.5 .003 .002 .005 20
5-6 (flow) 200 .05 15 1 .02 <.5 .02 .001 .021 15
6-1 (return) 200 .05 15 7 .02 <.5 .14 .045 0185
, 15
7-1 ( return) 400 .09 15 3 .05 0.6 .15 .045 .02 .195 .264 15
17
Hot and cold water supplies Plumbing Engineering Services Design Guide
Hot water secondary The total heat loss from each section of which permit an accurate ‘low flow’
pipe is converted to a flow rate setting to be achieved and retained when
circulation necessary to replace the lost heat. the valve may be shut off and re-opened
Watts
during maintenance of the system. The
In order to maintain the correct
kg/s = use of ordinary isolation valves can
temperature of hot water within the hot 4.187 (she of water) x 1000 achieve a crude form of restricting the
water distribution system, provision of a
The pipework heat loss is that which is flow for balancing purposes, but these
‘return’ pipe to enable the water to be
emitted through the pipe wall and rarely remain effective, or return to their
circulated back to the hot water
insulation material. SeeTables18a and initial setting after being shut off.
generator is required.
18b for pipes with and without insulation. The over-riding purpose of the balancing
Hot water circulation can be achieved by valve is to maintain the correct
gravity or pump circulation means, A ‘Rule of Thumb’ method of sizing
pumped HWS secondary circuits is to temperature within the pipework
although in nearly all instances a
initially select a return pipe size two sizes distribution system to minimise the
pumped system is provided. potential for bacterial growth, in particular
lower than the flow. As a guide select
smaller sizes over larger pipe sizes, and legionella. The Health & Safety Approved
Code of Practice Guidance L8 should be
Secondary circulation maintain a check on the HWS return pipe
applied (see earlier).
velocities.
pipe sizing Pipe circuit balancing valves will be
The formal method of sizing the needed where the HWS return has a
secondary circulation pipework is to number of branches and loops to serve
calculate the heat loss from all of the the various parts of the circulation
‘flow’ and ‘return’ pipe circuits throughout system. These valves restrict the flow to
the system. Calculating the heat loss the circuits nearest the pump where
allows a comparable flow rate to be there is greater pump pressure, forcing
established, and thereafter the head loss the HWS return to circulate to the
throughout the system is determined, furthest circuit. Commonly the circuit
and the duty of the circulating pump. valves are a double regulating pattern
Table 19 Loss of head through pipe fittings (expressed in millimetres, ie 1mm = 0.001 m unless otherwise stated)
18
Plumbing Engineering Services Design Guide Hot and cold water supplies
Table 19 Loss of head through pipe fittings - continued (expressed in millimetres, ie 1mm = 0.001 m unless otherwise stated)
19
Hot and cold water supplies Plumbing Engineering Services Design Guide
20
Plumbing Engineering Services Design Guide Hot and cold water supplies
21
Hot and cold water supplies Plumbing Engineering Services Design Guide
22
Plumbing Engineering Services Design Guide Hot and cold water supplies
23
Hot and cold water supplies Plumbing Engineering Services Design Guide
24
Plumbing Engineering Services Design Guide Hot and cold water supplies
Pseudomonas bacteria that once in a Avoiding the above circumstances will building’s accommodation
water system can be difficult to eradicate. greatly reduce the likelihood of
If not completely destroyed the bacteria c. Under floor voids, unless part of the
pseudomonas bacteria becoming
can reappear and grow at a fast rate to building’s accommodation
prevalent within the water supply
form a biofilm within the system. installation. d. Outhouses, enclosures, sheds, and
Problems occur due to a greasy brown
Infected systems must be disinfected and
garages etc.
slime or biofilm that coats strainers,
pipework, tanks etc. creating corrosive flushed. Any excessive growth may e. Adjacent to ventilators, air bricks, or
conditions which can discolour thp water require repeated disinfecting and flushing anywhere subject to external drafts of
to effect a reduction. Ultra-violet water air.
and can exude a noxious smell.
treatment is an effective method of killing
If the above, and similar locations cannot
Pseudomonas Bacteria can grow more the widest range of micro-organisms.
be avoided then protection will need to
when it has access to a higher level of However both ultra-violet and disinfection
oxygen and temperatures between 20°C be provided by insulating the pipework
will only provide a temporary respite
and 40°C, although it can grow outside unless the causes are identified and and components, and possibly providing
this range if the water has a pH value of removed.
heating to the spaces that contain water
7-8.5. supply installations.
25
Hot and cold water supplies Plumbing Engineering Services Design Guide
Table 26 General pipe insulation can enter in to the building in its desired
location.
Pipe size ( mm) od Insulation material and thickness
Pipes laid below ground require to be of
Glass fibre Phenolic foam Nltrll rubber
a suitable material. The most commonally
0.040W/mK 0.018 W/mK 0.035W/mK used is polyethylene, certainly for sizes
15 25 15 13 up to 50mm ID (65mm MDPE OD).
22 25 15 19 The depth of pipes required to comply
25 32 20 25 with the Water Regulations is a minimum
32 32 20 32 of 750mm from ground level to the top of
40 32 20 32 the pipe barrel, and a maximum of
50 32 20 32 1350mm, unless in a duct. Where pipes
65 32 20 32 are located below a road the depth
75 32 20 32 should increase to 900mm and be
100 38 20 32 ducted. Where water pipes are laid in a
service strip close to other services, the
Where the insulation material is located in areas requiring fire protection in accordance with the National Joint Utilities guidance
Building Regulations then it shall have a ‘Class 0' classification. documents recommends that the depth
of the water service is at 900mm
throughout to coordinate with the depth
heating. This comprises of self regulating the respective manufactures of the other services, and enable
electrical heating elements in a tape requirements and recommendations services to cross each other. The
form, capable of being wrapped around should be fully adhered to. minimum distance between the water
pipework and componants By the. Pipework requires supporting throughout
pipework and other sevices is
selection of the appropriate type and recommended as being 350mm.
its length at regular and specific positions
rating of heating tape the water within The pipe trenches should be kept to the
to maintain its stability, avoid movement
pipework and componants can be kept which could result in noise or vibration, minimum width that is practicable and
above the freezing temperature. Trace retain the trench wall to minimise ground
whilst enabling sufficient movement for
heating is used in conjunction with loadings transfering onto the pipe. The
pipework expansion and contraction.
insulation and weathering protection . See Table 27. trench bottom requires to be firm, level
and to the correct depth. A bedding of
sand is appropraite having a minimum
General insulation Underground pipework depth of 50mm, to provide a suitable
Pipework and plant componants means of bedding the barrel and joints of
throughout the distribution system should
The Water Supply Company mains are the pipe. The trench back filling should
located below ground, and therefore the be of a suitable material such as
be provide to keep hot water hot and incoming mains connection to the
cold water cold. Without insulation a hot selected excavated or imported material,
building will also be below ground until it consolidated to resist subsequent
water distribution system would loose
heat wasting energy, requiring a larger
generating plant, and increasing the Table 27 Pipe supports - maximum spacing
opportunity for bacteria growth and Pipe size Ripe material - spacing of supports in metres
potentially failing to comply with the nominal id ( mm) Copper Stainless steel Polybutylene CPVC
Legionella Codes. The impact on the coid
Horizontal Vertical Horizontal Vertical Horizontal Vertical Horizontal Vertical
water system would be to unneccessarly
gain heat from the warmer ambiant 15 1.8 2.4 1.8 2.4 0.3 0.5 0.5 1.0
temperature and any adjacent heat 20 2.4 3.0 2.4 3.0 0.5 0.8 0.5 1.0
sources making the water less palatable 25 2.4 3.0 2.4 3.0 0.5 0.8 0.5 1.0
for drinking, and again increasing the 32 2.7 3.0 2.7 3.0 0.9 1.2 0.8 1.4
opportunity for bacteria growth and a 40 3.0 3.6 3.0 3.6 0.9 1.2 0.8 2.0
failure to comply to the Legionella Codes. 50 3.0 3.6 3.0 3.6 1.2 1.5 1.2 2.2
The insulation for cold water components 65 3.0 3.6 3.0 3.6 1.5 2.0 1.5 2.2
requires them to be vapour sealed to 75 3.6 4.5 3.6 4.5 1.8 2.2 1.8 2.2
prevent condensation forming on the
Intermediate supports will be required at changes of direction, branches, and connections to
cooler surfaces within the higher ambient plant. Polybutylene and CPVC pipe supports can benefit from being provided with a continuous
areas. tray, rigid bar or rail spanning between support brackets at centres similar to copper, with straps
Recommended types and thicknesses of to secure the pipe to the bar.
insulation are scheduled in Table 26.
Table 28 Thrust per bar internal pressure ( kN )
Pipework and plant supports Nominal internal End Radial thrust on bends of angle
Water supply pipework, plant and diameter of pipe thrust 90 deg 45 deg 22.5 deg 11.25 deg
components require to be adaquately 50 0.38 0.53 0.29 0.15 0.07
supported to be functional and prevent 75 0.72 1.02 0.55 0.28 0.15
noise, vibration and general movement, 100 1.17 1,66 0.9 0.46 0.24
which would become a nuisance and/or 1.76 2.49 1.35 0.69 0.35
125
lead to damage to itself and other
150 2.47 3.50 1.89 0.96 0.49
elements of the building.
The kN thrust figures stated are the force exerted by the pipe on it 's end or radial area.
For the support of plant and components,
26
Plumbing Engineering Services Design Guide Hot and cold water supplies
27
Hot and cold water supplies Plumbing Engineering Services Design Guide
28
Plumbing Engineering Services Design Guide Hot and cold water supplies
18
ii E 1 Plant by-pass
17
P r
"
I
1
5
16
1 19 1
m E3 : 7 j J
1 15 15 ! L
iirp_
1
Ring
main to
\ rr Raw
water in
service 1
14 13 12
1. Hand isolation valve 6. Non-return valve 11. Solenoid valve 16. Conductivity controller
2. Break tank for raw water 7. Pressure relief valve 12. Break tank for recirculation water 17. Conductivity meter
3. Low level float switch 8. Integrating water meter 13. Recirulation pump 18. Water condition alarm
5. Pump motor start 9. Rate of flow meter 14. Deioniser cylinder 19. 0.2p Particle filter
10. Two bed automatic deioniser 15. Line cell 20. Pressure regulating/relief valve
29
Hot and cold water supplies Plumbing Engineering Services Design Guide
When most salts are dissolved in water may be controlled by the solubility and different oxygen concentrations reaches
they form ions which are atoms or diffusion rate of dissolved gases that vary a maximum, however, where appreciable
groups of atoms carrying positive or appreciably with temperature. levels of chlorides are present
negative charges. The resulting solution (>200mg/iitre) , the corrosion rate
As the rate of corrosion of steel is partly
is called an electrolyte because of its continues to increase with increasing
determined by the availability of oxygen
ability to conduct an electrical current.
at the surface, it is found that this rate
oxygen availability.
Na2S04 2Na+ + S04 has a maximum in the range 75-85°C, Two indices have been developed to
a salt positive ion negative ion which is approximately 4 times that at predict whether a carbonate scale will be
ambient temperatures. deposited from a supply water of given
Some salts are much more soluble than composition. These are called the
others and their solubility in water often With other metals, for example zinc, the
Langelier and Ryznar indices
depends to a large extent on solution variation of corrosion rate with
respectively; a positive Langelier index or
temperature. temperature is related to the nature of
a Ryznar index of less than 6 indicating
the corrosion product. At temperatures
In practical terms, pH is used to measure that the water is scale forming.
that produce a continuous/adherent
the acidity or alkalinity of a solution. corrosion product, the corrosion rate is Since the deposition of a carbonate scale
Values range from 0-14, those less than low. However, when a granular, non- can stifle corrosion, it often follows that
7 being acid and those greater are adherent product is formed, the corrosion these waters are less corrosive than
alkaline. rate increases considerably. those that tend to dissolve calcium
Corrosion is electrochemical in nature carbonate. Their behaviour however,
Differences in surface temperature on the
and can occur by oxidation (dry depends greatly on the form in which the
same metal component can create areas scale is laid down, a discontinuous layer
corrosion) or wet corrosion. Most differing in potential, resulting in
corrosion problems in plumbing providing relatively little protective value.
increased corrosion.
applications are caused by wet corrosion When natural water runs over a metal
which requires the presence of an surface, it can take up traces of that
electrolyte to allow the passage of an
electric current and some agency to
Differential aeration metal, which are later deposited on
another metal. This may form a bimetallic
maintain a difference in potential. Many If part of a metal surface is shielded from couple and if the deposited metal is
corrosion processes also require the air, the natural oxide film can break cathodic to the substrate, rapid corrosion
presence of oxygen. Natural and supply down. Where the oxygen availability is will ensue. Typical examples are copper
waters contain dissolved salts that make low, these areas become anodic to those pipework upstream from galvanized
them into electrolytes and therefore areas to which there is greater supply. cisterns and run-off from copper roofs
capable of carrying an electric current. This results in localised corrosion, which into aluminium gutters. The high acidity
The factors which may cause and will can occur particularly in crevices and of rainfall in certain areas, due to the
affect the rate of corrosion are as follows: also underneath surface deposits, for dissolved sulphur and nitrogen oxide
example mill scale. This type of corrosion pollutants has generally resulted in
is called differential aeration. reduced service life of exposed metal
Solution potential surfaces.
If a metal is placed in an electrolyte,
corrosion in the form of a chemical
Dissolved salts
reaction may occur accompanied by the The influence on corrosion of salts Surface effects
passage of an electric current. That part dissolved in natural or supply waters is Certain surface films are cathodic to
of a metal system where current, i.e. determined both by their concentration steel and under wet conditions where
positive charges in the form of metal and more importantly, by the type of ion there are breaks in the film, the
ions, leaves and enters the solution is produced in solution. In general, a high underlying steel surface becomes the
called the anode while the resulting dissolved solids content would be anode and will corrode preferentially.
electrons (negative charges) migrate to expected to exacerbate corrosion, due to
an area of higher potential, the cathode, the increase in conductivity, if conditions
where they react with other ions or
,
favour it. Some ions, however, for Ion concentration
oxygen. example carbonates, can be protective
due to their scale forming ability on metal As discussed above, the solution
In the corrosion process it is always the surfaces. Other ions, in particular potential is affected by the concentration
anode that is dissolved. The difference in chloride and sulphate, are aggressive as of ions in the electrolyte. The higher the
potential between the anode and the they interfere with the development of concentration, the more cathodic the
cathode at equilibrium is termed the protective films and also allow passive metal becomes. If therefore, a metal
solution potential. This potential has films to be broken down more readily. surface is in contact with an electrolyte
different values for different metals and Both ions occur naturally in source that varies in concentration, those areas
conditions, e.g. temperature, electrolyte waters, with additional sources of of metal in contact with dilute solution will
concentration and the surface or chloride being fluxes, washing up liquids become anodic to those areas in contact
metallurgical condition of the metal, has (sometimes misguidedly used to quieten with the more concentrated solution and
a profound effect on corrosion. noisy boilers), and malfunctioning water corrosion will be accelerated.
softeners. Sulphate ions also support the
growth of anaerobic bacteria.
Temperature
Although in certain conditions the overall
In general, rates of chemical reaction rate of corrosion may not be increased,
and therefore corrosion, increase with a the attack may be more localised and
rise in temperature. However, some therefore corrosion pits tend to be
corrosion reactions, for example the deeper. In the absence of aggressive
corrosion of steel in aerated solution, ions, the corrosion rate of steel at
30
Plumbing Engineering Services Design Guide Hot and cold water supplies
31
Hot and cold water supplies Plumbing Engineering Services Design Guide
chlorides, which in the presence of mechanical damage to the metal surface significant quantities (Duralumin), are
moisture will cause corrosive attack. at that point and exacerbate corrosive less resistant to corrosion.
attack. This mechanism is responsible for
Soils are complex in nature and therefore The most commonly encountered form of
water hammer.
are extremely variable in corrosive aluminium corrosion is pitting but the rate
activity. The most widespread form of of propagation is very dependent on the
corrosion is due to sulphate reducing alloy composition and nature of the
bacteria. Other problems are caused by Stray current corrosion .
solution with which it is in contact While
acidic conditions due to natural Stray earth currents, in particular DC, many neutral or weakly alkaline solutions
constituents or contamination by can produce cathodic and anodic areas allow self -passivation, others particularly
industrial waste, for example ashes and where they enter and leave buried those containing chlorides or copper
clinker. pipelines or other metallic structures ions, cause rapid propagation of
Although not strictly corrosion, it is worth causing severe corrosion. corrosion pits in some alloys .
mentioning that other industrial wastes, Aluminium alloys may also suffer a
for example, tar, oils, can cause failures preferential attack at the boundaries
in buried plastic pipework due to Organic matter between the grain structure that is
environmental stress cracking. They may Organic matter, derived from their natural termed intercrystalline corrosion.
also attack protection on metal pipework, or industrial sources, may lower the pH Aluminium and its alloys have very good
thus exposing the underlying surfaces to and increase corrosion rates as well as resistance to atmospheric corrosion
corrosive attack . preventing scale deposition. Bacteria are providing the surfaces are regularly
also often present in organic matter and washed by rain etc. Where deposits of,
these may be responsible for fouling and for example acidic sulphates are allowed
Bacteria increased corrosive attack under both to build up on sheltered surfaces,
In the absence of oxygen, corrosion may aerobic and anaerobic conditions. moisture from condensation is sufficient
continue by the cathodic reduction of to give an increased rate of attack.
It can be seen from the forgoing that
sulphate, which is present in most soils corrosion phenomena are very complex In all environments, aluminium is very
and natural waters. This is facilitated by in nature and are affected by many sensitive to bimetallic corrosion. Contacts
anaerobic bacteria (called sulphate- factors. Most of these factors can have a with copper and copper alloys, and to a
reducing bacteria, disulpho-vibrio profound effect on corrosion rates and lesser extent, iron and iron alloys, should
disulphoricans) that are able to use highlight the difficulties in predicting be avoided.
cathodic hydrogen in their living process corrosion behaviour and time to first
and convert sulphate to sulphide. This maintenance or failure. However, many
type of corrosion is responsible for the
smell of ‘bad eggs’ (hydrogen sulphide)
techniques are now available for Cadmium
identifying, monitoring and controlling
sometimes observed when venting corrosion to acceptable limits. The main application of cadmium is as a
radiators. protective coating on steel. It is
particularly useful as a plated finish on
high strength steels where zinc finishes
Flow, erosion, impingement can heighten the risk of cracking due to
and cavitation Effects of corrosive hydrogen embrittlement. Its corrosion
behaviour is similar to zinc and although
Corrosion can be aggravated by the
nature of water flow across a metal
environments it is less protective to steel, unlike zinc, it
is stable in alkali solution.
surface. The overall rate will be controlled
both by the rate of reaction and how Corrosion can manifest itself in
quickly reactants and products can numerous ways, depending on the metal Cast iron
approach and leave the metal surface. or alloy and particular environment in
which it is in contact. It is convenient to Cast irons are ferrous alloys containing
These are termed chemical and diffusion
look back at the various metals likely to generally 2-4% carbon and frequently
control respectively. Flow may be have high silicon contents. A wide variety
stagnant, laminar or turbulent which will be encountered in plumbing applications
and the environments that can be of compositions are available and
affect the rates of diffusion.
detrimental to their service life. additions of silicon, chromium and nickel
Where the flow is turbulent, the can be used to improve corrosion
impingement of gas, liquid or solids or a Some of these metals are also used as resistance. Typical applications include
combination of any three can cause protective coatings and their performance boiler sections, pump housings and pipe
mechanical damage, which removes or together with that of the substrate is also fittings (malleable iron). Although
prevents formation of a protective film. If considered. corrosion rates are similar to those of
the metal or alloy is corrodible in that steel, above ground corrosion is not
environment, localised attack of the normally a problem due to the thick
surface will occur. Aluminium and sections used for cast iron components.
Cavitation is a particular type of attack aluminium alloys When in contact with some natural
that occurs when a metal surface is Although aluminium is a very reactive waters, particularly those that are slightly
exposed to a high velocity, low-pressure metal, it has a high resistance to acidic or contain chlorides (salt) , cast
liquid. corrosion because of the tenacious, inert iron may suffer a form of attack called
oxide film that forms on the surface. Pure graphitisation. The iron corrodes leaving
In areas where the pressure is weak, porous structure composed of
sufficiently low, pockets of vapour form, aluminium is generally stable in the pH
range 4.5-8.7 but outside this range, graphite and iron oxides. This can result
which may suddenly collapse when they in catastrophic failures in underground
pass to an area of higher pressure. The attack can be rapid. Aluminium alloys,
particularly those containing copper in pipes where soil or ground movement
shock generated is sufficient to cause causes large sections where
32
Plumbing Engineering Services Design Guide Hot and cold water supplies
graphitisation has occurred to crust corrosion are those drawn from wells and remain intact for approximately 3 months
without warning. springs (usually privately owned) which to fulfil its purpose,
Although not directly associated with
are often soft and contain dissolved
Problems, which have been generally
carbon dioxide. Such waters are called
corrosion, it is worthwhile mentioning a confined to cylinders not fully complying
cuprosolvent. Here the role of dissolved
common cause of premature failure in with BS1566 (for indirect) or BS699 ( for
oxygen is less significant and corrosion is
gas-fired sectional boilers. If hard- water directs), were found to arise in two ways
most marked when the water has been
scale is allowed to build up inside the from one cause. Poor insulation of the
heated.
cast iron sections, and flame connection point resulted in early
impingement occurs on the outside, Pitting corrosion of copper is divided into detachment of the anode, whereupon it
overheating can cause a change in the three categories: fell to the base of the cylinder, causing a
cast iron structure to a weaker massive build up of oxide sludge.
‘undercooled’ form. Subsequent thermal Type 1 Normally such oxide debris would form
stress can result in fracture and around the extremities of the anode and
consequent leakage from the boiler. Type 1 pitting is characterised by be carried away by the water flowing
broad/shallow pits. Temperature is a through the vessel, however, where
significant factor with corrosion more sludge built up, under-deposit corrosion
Copper and copper alloys likely to occur in cold and lukewarm of the base of the cylinder was initiated
water than in hot water. It is most usually due to differential oxygenation. Rapid
Copper and Its alloys comprise a associated with borehole waters or failure could occur. If failure didn’t occur
versatile range of materials, which are waters that have been treated by in this way, the absence of the anode
used in a wide variety of plumbing flocculation. Often the total hardness of from its proper position allowed corrosion
applications. the water is greater than 100mg/l and is by the mechanisms it was originally
usually greater than 150mg/l but installed to prevent.
Copper is used extensively for pipework corrosion can occur in soft waters. It is
and heat exchanges due to its excellent thought that in surface derived waters, Rosette corrosion is another form of
ductility and thermal conductivity. A wide the presence of extremely low levels of copper corrosion. The phenomenon is so
range of copper alloys are available and organics such as polyphenols acts to named because the corroded copper has
in addition to the aforementioned inhibit this form of attack. Type 1 pitting the characteristic appearance of petal
applications, they are used for valve and needs initiation and used to be caused shapes etched on to its surface. There
pump components, pipe fittings, etc. by carbon film in copper tube remaining are no reported instances of copper
Most problems occur when these after the drawing process. The modern other than that associated with cylinders
materials are in contact with water or use of abrasive cleaning of the tube being affected. Research into the causes
steam containing dissolved oxygen or minimises the problem. continues, but factors known to
carbon dioxide and/or acids or chlorides, contribute to its occurrence include
although corrosion can also result from Type 2 nitrate and the presence of an aluminium
contact with aggressive atmosphere e.g. anode. There is also evidence that
Type 2 pitting is characterised by rosette corrosion is favoured when a
flue gases or certain bacteria.
narrow/deep pits. It occurs in soft waters copper vessel fitted with an aluminium
These environments cause a breakdown at temperatures above 60°C. The anode has been allowed to stand full of
in the protective oxide film formed on the bicarbonate/sulphate ratio is often less water for an extended period.
surface by contact with oxygen and than 1 with the pH less that 7.6. In the
water, thus allowing corrosion to United Kingdom it is thought that the In some parts of the country, the
proceed. Not only will this eventually presence of manganese is contributory. concentration of nitrate has risen
result in failure of the component, but significantly over the last few years,
also dissolved copper can cause Type 3 probably due to the permeation of nitrate
accelerated corrosion if it is deposited on based fertilisers down to the aquifers
other metals that are more anodic. Type 3 pitting is characterised by pepper providing aU or part of the mains supply
pot holes under a crust. This form of water. However, it remains unproved that
corrosion remains a major area of this is the main factor responsible for the
Copper research. It is virtually unknown in apparent increase in rosette corrosion.
England but is prevalent in Scotland
Copper is used extensively in the form of where it is associated with moorland Changes to the design of cylinders to
tube for pipework and the manufacture of waters. The cause is uncertain however ; inhibit the formation of stable areas of
hot water cylinders. When in contact with it appears that the standard of tubing is colder water (less than 30°C) will prevent
natural waters corrosion can occur by a not important. Research is concentrating many early failures, whether they are due
variety of mechanisms. on finding methods of analysis for the to Type 1 pitting, or by elimination of the
detection of microscopic quantities of aluminium anode, rosette corrosion.
A major factor in the corrosion of copper organic acids, which it is thought, might Standards include a test to ensure that
is dissolved oxygen. The higher the be contributory. water in the base of the cylinder is
temperature of the water the less heated appropriately.
dissolved oxygen it can contain, Copper cylinders can be prone to pitting
consequently cold water is more attack, particularly in the base sections Specifiers and installers can also take
corrosive to copper than hot water. where near stagnant conditions exists in sensible steps to help themselves, by
Typically when copper is first exposed to crevices or underneath debris. In an installing only units correctly sized for the
a water, a significant increase in the attempt to control the problem, the job, so eliminating large volumes of
copper concentration will occur, however, incorporation of aluminium anodes, unused water from residing in the vessel.
within a short period of time the which corrode preferentially whilst a In regions of the country where pitting
corrosion rate will fall to an acceptable uniformly thick protective film builds up failure is known to be a problem, end
level due to the formation of protective on the surface of the copper, was users should be encouraged to
films or scales on a metal surface. included in a British Standard and soon periodically drain their cylinder
became commonplace. In most cases it completely. This might well be applied to
Waters given rise to the highest rates of was necessary only for the anode to cylinders filled and left in non-use
33
Hot and cold water supplies Plumbing Engineering Services Design Guide
situations, e.g., new unoccupied a brass and in the range 47-50% zinc is suffer attack by impingement or
properties. another single-phase alloy termed |3 cavitation. This may cause particular
brass. Alloys containing 39-47% zinc problems down stream from valves that
Compared with its alloys, copper
content, both phases are termed a + p or when properly open, cause a pressure
generally has a lower resistance to
duplex brasses. The latter alloys are drop sufficient to create air bubbles from
impingement attack in waters containing
more suitable for hot pressing or die- dissolved gasses and initiate attack. It is
oxygen and/or carbon dioxide. Where
casting small components. important therefore that valves are
dissolved gases are absent, for example
carefully positioned in plant so that
in closed heating systems, this type of An alloy has been developed having a
possible damage from this type of attack
attack is not a problem. Table 31 gives controlled composition so that it is
is minimised.
recommended maximum water velocities suitable for processing as a duplex brass
for copper pipework carrying fresh but heat treated to attain the
aerated water of pH not less than 7. dezincification resistance of inhibited
brass (see below). This material is Bronzes (gunmetals,
Table 31 Maximum recommended water
velocities for copper tube at
termed DZR (dezincification resistant) phosphor bronzes and
brass and fittings are marked by the
different temperatures
Water Research Centre recognised tin bronzes)
(metres/second)
symbol CR. It should be noted that Technically the term ‘bronze’ should refer
Temperature °C 10 SO 70 90 brazing alloys containing zinc can suffer to copper-tin alloys, but in practice a
Pipes that can from similar forms or attack to brasses. variety of copper alloys are termed
4.0 3.0 2.5 2.0
be replaced Brasses can suffer a form of selective bronzes, irrespective of whether they
Pipes that cannot corrosion called dezincification. Zinc is contain tin.
2.0 1.5 1.3 1.0
be replaced preferentially removed form the alloy This wide variation in composition makes
For short leaving a porous mass of copper having corrosion behaviour of a component
connections which little strength. Where the zinc corrosion difficult to predict unless the specific
are used products are not washed away, they may composition is known.
intermittently, form bulky hollow shells which readily
16.0 12.0 10.0 8.0 In general, copper-tin alloys have a good
eg taps block waterways. This is termed
‘meringue’ dezincification. In the single- resistance to corrosion when in contact
phase brasses the whole of the metal is with both water (natural and sea) and
Impingement attack has a distinctive steam and rarely suffer from the selective
appearance, the pits formed having a corroded either uniformly over the
surface or more commonly on the form of attack (dezincification) that brasses do.
water swept appearance, sometimes in
the shape of horseshoes and being free a ‘plug’. With duplex brasses the phase
from corrosion products. In closed which contains a higher proportion of
heating systems where the oxygen zinc is preferentially attacked. Aluminium bronze
content is low, this type of attack does In general the risk and/or rate of These materials generally have a high
occur. dezincification is increased by higher resistance to corrosion, impingement
Copper can fail by stress corrosion proportions of zinc in the alloy, high attack and cavitation erosion. They are
cracking ( the combination of constant temperature, high chloride content of the however, surprisingly prone to pitting
stress together with a specific corrodent, water, low pH, low temporary hardness, corrosion in natural waters and can suffer
(see brasses) and corrosion fatigue low water speed and the presence of selective corrosion analogous to
results from the conjoint action of surface deposits or crevices. dezincification.
fluctuating stresses, which may be Where leakage or breakage of a fitting
caused by expansion and contraction in has occurred, dezincification may be
restrained pipework, vibration of suspected if the defective areas have a
Cupro nickel alloys
equipment, poorly supported tubes, or dull, coppery appearance. Alloys containing copper and nickel have
pressure variations and a corrosive excellent resistance to corrosion and
environment. Brasses may be inhibited against
dezincificaiton by small additions of many environments, including those
Occasionally, corrosion can result in arsenic. Duplex brasses cannot be containing chlorides. They are more
copper calorifiers where large inhibited in this way and where there is a stable than brasses under flow
temperature differences exist. This may risk of dezincification, either DZR brass conditions, less susceptible to stress
be between a coil carrying steam, high or gunmetal must be used. corrosion and are used in heat
temperature water under pressure or exchanger applications.
immersion heater sheath and the Where brasses have a high degree of
calorifier shell. The large differences in internal stress, which may be induced
temperature are sufficient to generate a during manufacture, in particular those Lead
potential difference and cause containing ammonia or ammonium
compounds (in-organic or organic) can Lead and lead alloys have a good
preferential attack on the hotter surface. corrosion resistance due to the formation
This may be prevented by electrically cause failure by a mechanism called
stress corrosion cracking (season of insoluble adherent carbonate or
insulating the shell and heater.
cracking). The corrosive environment is sulphate corrosion products. These films
normally external and may result from an are protected and may be formed over a
ammonical compounds used as light wide range of pH values (3-11) in most
Brasses weight concrete foaming agents, in natural and treated waters. However, in
The common brasses consist of a range rubber lattices used as cement additives soft waters with a low carbon dioxide
of copper alloys containing from 10-50% or for bonding floor tiles, and from content, a less protective oxide film is
zinc and other minor alloying elements. fertilisers either as residues in aggregate formed which allows corrosion to
Alloys containing up to 39% zinc from a or airborne pollution. proceed slowly.
single-phase alloy with copper is termed In common with copper, brasses can Lead is generally resistant to
34
Plumbing Engineering Services Design Guide Hot and cold water supplies
atmospheric corrosion but may be common austenitic alloys contain 15-22% alkaline waters, calcium carbonate (lime
attacked by organic acids or free alkali. chromium, 6-11% nickel and 0.05-0.15% scale) can deposit on steel surfaces and
Run off from roofs bearing organic carbon and have the highest resistance provide a protective coating.
growths, acetic acid derived from wood to corrosion (grades 302, 304). The
Although carbon dioxide has no specific
and fresh cement, can all cause addition of molybdenum (2 -4%) confers influence on the corrosion of steel, it will
corrosive attack. even greater corrosion resistance (grade increase the corrosion rate by lowering
316). They are non-magnetic and not
In its pure form, lead has poor the pH and also preventing the formation
mechanical properties and without small hardenable unless heavily cold worked. of protective calcium carbonate films.
alloying additions, is susceptible to creep The main applications in plumbing
In the absence of oxygen, corrosion can
and fatigue failures induced by thermal services are for pipework, boiler flues, occur in waters where sulphate-reducing
movement. sinks and urinals. bacteria are active.
Stainless steels owe their high corrosion The effect of dissolved gases and
resistance to the presence of self -healing
Magnesium oxide films on the metal surface.
calcium carbonate in fresh waters has
already been discussed. Water may also
The only plumbing application in which However, certain environments may
contain a variety of other dissolved
magnesium is likely to be met is that of cause these films to break down and
material present in the supply or as a
cathodic protection. The greater negative allow corrosion rates comparable to
result of subsequent contamination. Ions
potential in relation to steel and those of mild steel. The most common
such as chloride and sulphate can
compared to zinc or aluminium makes environments to cause attack are those interfere with the development of
magnesium alloys efficient for protecting containing chlorides and in crevices or
protective films and lead too more
the interior of steel (either unprotected, underneath surface debris where the
localised attack whereas other ions such
painted or galvanised) water cisterns or absence of oxygen prevents repair of the
protective oxide film.
as calcium and bicarbonate have
the exterior of buried steel structures and inhibitive properties. Small concentrations
pipelines. Corrosion of stainless steels is often of organic matter can improve the
localised. The presence of chlorides can protective qualities of carbonate films;
cause rapid pitting, particularly at grain however, organic acids resulting from
Soft solders (tin alloys) boundaries and can initiate intergranular decomposition of vegetation can
Soft solders (i.e. tin alloyed with lead, attack and stress corrosion cracking. increase corrosion rates by lowering the
antimony, silver and/or copper) are pH. Where the pH is reduced to values
anodic to copper and therefore corrosion below 4 as a result of acid
of solder used in capillary joints could be Steels (low alloy) contamination, then the corrosion rate
expected. However, due to the nature of will progressively increase with a further
Low alloy steels, due to their ease of decrease in pH. Other surface
the protective film formed, corrosion fabrication and the range of mechanical
often occurs in waters of high contaminants such as oil, mill scale or
properties attainable by alloying deposits may not increase the overall
conductivity, for example those additions, are used in a wide variety of
containing chlorides. Most problems with rate of corrosion, but can localise the
plumbing applications. When compared attack causing pitting and pinhole
capillary joints may be attributed to the with other metals in most environments,
use of soldering fluxes which leave corrosion.
they are found to have a much lower
aggressive residues at, or adjacent to the corrosion resistance. Under certain Steel pipes are not normally suitable for
joint area. conditions, small additions of copper, use in wet soils unless protected against
chromium and nickel improve corrosion external corrosion.
resistance but the overall effect is often
Stainless steels small and variable.
The term ‘stainless steel’ covers a variety Steel can exhibit two entirely different
Zinc
of alloys which may be simply and types of corrosion behaviour depending Zinc is used almost exclusively in
conveniently divided into the following on the nature of the environment with plumbing applications as a protective
three categories: which it is in contact . In the passive state, coating on steel. It may be applied by a
for example when in contact with neutral variety of methods, which give widely
Martensitic stainless steels or alkaline natural water free from varying coating weights and consequent
bacteria and oxygen, the corrosion rate degrees of protection. Both zinc and zinc
These alloys generally contain 12-14%
is negligible. However, in the active state alloys have good resistance to corrosion
chromium and from 0.1-2 % carbon,
widely differing rates of corrosion, either under conditions of exterior exposure
which confers hardenability and controls
general or localised, can occur and when in contact with most natural
the mechanical properties. They are used
depending on the many factors that have waters. This resistance is due to the
for applications requiring high strength
and wear resistance combined with
been discussed earlier. protective layers of zinc oxide and
hydroxide, or other basic salts depending
considerable corrosion resistance. The most common cause of corrosion is on the nature of the environment, which
exposure to water containing dissolved
are formed on the metal surface.
Ferritic stainless steels oxygen. The rate of attack is greatest
when the water is soft and/or acidic and Under atmospheric conditions, the rate of
Alloys containing 16-18% chromium and the corrosion products often form bulky corrosion depends on the degree of
having a low carbon content are termed mounds in the surface called tubercles. pollution. Heavily polluted industrial areas
ferritic stainless steels. They are not These overlie areas where localised containing sulphur dioxide can increase
hardenable and are used for flue and attack is occurring and can seriously the rate of corrosion by a factor of up to
sink components. reduce the carrying capacity of pipes. In 10 as compared with rural areas. Where
severe cases, iron oxides can cause new zinc surfaces are stored under damp
Austenitic stainless steels contamination leading to complaints of conditions, an unsightly white corrosion
Often termed 18/8 stainless steels, the ‘red water’. In hard, neutral or slightly product may be formed. This is termed
35
Hot and cold water supplies Plumbing Engineering Services Design Guide
36
Plumbing Engineering Services Design Guide Hot and cold water supplies
5.0, an acid is present. If higher than 8.5, If the test sample contains rust particles, temperature drop of 5-8°C. This
the water is alkaline, either due to the they will be dissolved when the test is evaporation leaves behind both dissolved
presence of an alkaline treatment, e.g. carried out. The iron reading will then be solids that build up until deposition
caustic soda, or in some circumstances the dissolved iron plus the iron due to the occurs and aggressive ions, for example
due to alkali generated within the system particles. Care should be taken to ensure chlorides, which will exacerbate
naturally. that the suspended solids are corrosion. In addition the cooling water
representative of the overall system may become contaminated by
Conductivity conditions. atmospheric pollution resulting in acid
corrosion due to the reduced pH.
If the system water has a higher
conductivity than the supply water, this
Copper
indicates that the water has been treated
with an inhibitor or contaminated. The
A dissolved copper concentration of
0.2mg/l more in the system than in the
Corrosion control and
levels of concentration to be expected in supply water is significant. prevention
the other analyses can be estimated
from this comparison, e.g. a high External surfaces
conductivity is likely to be associated
with high levels on the other tests. Where aluminium components are A variety of methods are available for
present, an aluminium concentration of protecting pipework etc. When their
0.3mg/l or more in the system water than external surfaces are exposed to a
Chloride in the supply water indicates that some corrosive environment.
Chloride is naturally present in all supply corrosion has taken place. If the pH lies
waters. A high level may indicate the between 5.0 and 8.5, the aluminium Organic coatings such as paints, plastic
presence of residues from acid de- surfaces will be passive and further coatings or tape wrap systems may be
scaling or chloride based fluxes. It should applied to the metal surface which has
corrosion will not be occurring. Any given
be noted that the chloride concentration been prepared by grit blasting and/or the
concentration of aluminium is not a
problem in itself, but an increase over a application of a suitable primer. In
in a towns mains supply water is liable to
fluctuate, however, a level more than 25 period should be noted and would general the more severe the conditions
mg/I greater or 50% greater in the require corrective action. of service, the thicker and more resistant
system, is strongly suggestive of flux the coating needs to be. These types of
More significance should be attached to coatings can be very susceptible to
contamination. the aluminium concentration when an mechanical damage and this should be
aluminium heat exchanger is fitted. borne in mind during installation.
Sulphate Where aluminium radiators are
concerned, concentrations above 0.5 Both tanks and pipes can be repaired
Sulphate is naturally present in all supply and protected using either glass
waters. A low level (<10 mg/l) in the mg/I do not present any special problem,
provided there is no deterioration. reinforced plastic (GRP) or specially
system may indicate the presence of
formulated concrete linings.
sulphate reducing bacteria.
Metal coatings, for example zinc and
Hardness Steam boilers and aluminium, may be applied to steel
surfaces by hot dipping or spraying,
Towns mains supplies are categorised in water heaters which gives the thickest coating, diffusion
Table 22 or in the case of zinc, electro-deposition .
BS 2486: 1997 ‘Treatment of water for
Generally speaking, hard water is steam boilers and water heaters' gives These metals will corrode, albeit at a rate
present in 60% of the country (especially recommendations for the control of much slower than steel and therefore the
in the Eastern, Central and Southern waterside conditions of steam boilers and coating thickness required depends on
areas of England) and to varying water heaters and also for the the aggressiveness of the environment.
degrees in the rest of the United preparation of feed water for such plant. In severe cases, an additional paint
Kingdom and Northern Ireland. The water Categories covered are: coating may be applied.
for some northern cities is supplied from Another method of protecting
a. Hot water systems i.e. water above
naturally soft water reservoirs in Wales underground pipelines is that of cathodic
120°C (HTHW), water below 100°C
and the Lake District. protection. Two methods are available
(LTHW), water at 100-120°C inclusive
Most calcium salts form a scale when (MTHW) each of which produce a counter current
heated. Comparison with the system sufficiently large to neutralise the
water will indicate if scale has been
.
b Electrode boilers currents responsible for corrosion. The
formed. If a high level of hardness is c. Shell (fire tube) boilers operating at first uses a more electro-negative metal,
present in the system water after it has pressures up to 30 bar the most common being either
been heated, it may be because of water magnesium, aluminium or zinc, in the
d. Water tube boilers operating up to
loss and subsequent make-up . critical pressure
form of sacrificial anodes which are
connected electronically to the metal
Iron e. Once through boilers, including ‘coil’ requiring protection. The second uses an
and ‘hairpin’ types, operating up to impressed current from a generator in
As a heating system corrodes, iron will critical pressure. conjunction with auxiliary anodes of iron,
dissolve or form corrosion debris and steel, graphite, lead or platinised
hydrogen gas will be generated. The titanium.
amount of any debris present ( visible as Cooling waters
suspended solids) is a factor in Internal surfoces
determining the seriousness of a Cooling for air conditioning systems is
corrosion problem. In terms of dissolved most commonly achieved by evaporation All internal surfaces that store or carry
iron, an increase of 0.5mg/l over that in of water, normally 1 -1.5% of the water, for example pipes, tanks,
the supply water is significant, with an circulation rate being used to cause a calorifiers, heat exchangers, radiators
increase of more than 3mg/l very high. etc. may be subject to corrosive attack.
37
Hot and cold water supplies Plumbing Engineering Services Design Guide
There are many different possible joints and causing leaks. Where larger minimise corrosion. In addition to
approaches to preventing corrosion and systems suffer continuous water loses treatment for the prevention of corrosion,
it is of utmost importance that the correct due to the presence of leaks, it can be sludge and scale deposition also needs
method is chosen to suit each particular beneficial to use softened water for to be carefully controlled to maintain
situation. In most cases, proprietary make-up to reduce the need for frequent efficiently and steam purity, particularly
blends of chemicals are available which scale removal. as the trend in modern boilers is towards
fulfil some or all of the required a lower water content and higher heat
preventative treatment. Cooling waters transfer rates. In brief, the concentration
of solids in the boiler water may be
Other factors may also need to be Corrosion may be controlled by dosing controlled by the following methods
considered for example toxicity when the system with a suitable inhibitor. This depending on the quality of supply water :
treating wholesome waters or if there is a needs to be carried out continuously at a
risk of crossover between primary rate proportional to the bleed-off required i. Softening and filtration of the feed
heating and domestic supplies. to prevent scale deposition and water to remove dissolved and
excessive levels of aggressive ions suspended solids.
Both polyphosphates and sodium
silicates may be used as a non-toxic , building up. The treatment should also ii. Precipitation of hardness salts as a
tasteless, odourless and colourless include sludge conditioners to prevent mobile sludge in the boiler by
treatment for domestic waters. They both localised scale deposition and biocides to maintaining a controlled reserve of
prevent iron corrosion discolouring the control bacteria and algae (slime) growth. either carbonate or phosphate in
supply water (commonly known as ‘red In hard water areas, the cost of water solution in the boiler water. In
water’) and inhibit the deposition of scale and treatment chemicals can be high and addition, organic sludge conditioners
by forming a thin film on the metal therefore consideration should be given may be added to ensure that the
surfaces, which acts as a barrier. They to using a softened make-up supply. precipitated salts are non-adherent
are dosed either in liquid form using a Disposal of bleed-off water also needs to and mobile.
proportional dosing pump or as slowly be considered as some treatment iii. Maintaining the total dissolved solids
dissolving crystals from a suitable chemicals are toxic and cannot be below the maximum level applicable
dispenser. drained into local sewerage systems. to the particular boiler and operating
Storage tanks/cisterns may be protected conditions (usually below 3500mg/l)
internally using cathodic protection. Steam rising plant by ‘blowing down’. Blowdown may be
Sacrificial anodes, normally magnesium Steam boilers are treated by ensuring either intermittent or continuous.
for steel or aluminium for copper, are that the boiler water is alkaline at all iv. Cleaning the boiler when shut down.
connected to and suspended in the tank. times and by removing dissolved oxygen
While aluminium anodes in copper tanks to maintain a protective film of magnetite
only have to last for sufficient time to (magnetic iron oxide) on steel surfaces.
form a permanent protective film, In addition, treatment may also be
Cleaning and descaling of
magnesium anodes in steel tanks need necessary to prevent corrosion in boilers and associated plant
to be replaced when consumed. condensate lines, which is most
In newly installed systems, it is often
commonly caused by the presence of
Primary and secondary heating waters - necessary to remove internal
dissolved oxygen and carbon dioxide
chilled water systems gases.
contaminants, for example flux residues,
metal filings and other builder’s debris by
These systems, because they are Dissolved oxygen in boiler water may be flushing. Even if carried out in
essentially closed recirculating systems, removed by means of a physical de- accordance with recommended
may be treated with either oxygen aerator or oxygen scavenger, the procedures, it is unlikely that all will be
scavengers, which act by the removal of chemicals most commonly used being removed due to either their insolubility or
oxygen responsible for the corrosion catalysed sodium sulphite, certain the internal geometry of the system. This
process, or inhibitors which slow down selected tannins or hydrazine. highlights the need to adopt working
the corrosion reactions to acceptable Condensate corrosion may be controlled procedures that negate the need for
levels, sometimes in conjunction with pH by the addition of volatile amines which flushing, for example using non-
control. either neutralise the acidity caused by aggressive fluxes and cutting rather than
the presence of carbon dioxide, or form a sawing copper tubes.
Inhibitors need to be chosen carefully to protective film on the metal surfaces.
suit the system under consideration. In older systems, particularly where there
Some inhibitors may reduce corrosion in Caustic cracking, which used to be a has been water losses or air ingress;
one environment while increasing it in fairly common phenomenon particularly scale and sludge may have deposited,
another, while others only work in riveted boilers, can occur if which will affect the efficiency. In the
effectively in a certain concentration concentrations of sodium hydroxide worst case, particularly where low water
range, actually intensifying corrosion greater than 5% exist. This may be content boilers are used, overheating will
outside this range. Sulphate reducing prevented by either: lead to eventual failure of sections or
bacteria may be controlled by splitting of tubes.
i. maintaining the ratio of sodium nitrate
maintaining a specified level of biocide in If inspection indicates that de-scaling is
to total alkalinity (in terms of calcium
the system.
carbonate) at a minimum value of necessary, the nature of the deposits
With the current trend towards very low 0.32 at all times should be determined to ascertain the
content boilers, it is also advisable to use best method of removal.
ii. maintaining the ratio of sodium
sludge conditioners to prevent scale sulphate to caustic alkalinity (in terms Loose deposits may be removed
deposition inside boiler sections and manually or mechanically but hard
of calcium carbonate) at a minimum
tubes. These materials should be used value of 2.0 at all times. deposits will normally require chemical
with caution in older systems as they
removal. Table 32 indicates chemicals
may dislodge scale and corrosion In high-pressure boilers, the level of
that may be used to remove the most
products highlighting weaknesses at chloride ions needs to be limited to
38
Plumbing Engineering Services Design Guide Hot and cold water supplies
|
s
s
o
a.
To
%
5 I I
ti
'
i
1 i 5
£
t5
Citric adic X X
39
BLANK
Legionnaires' disease
Introduction
Systems ossocioted with outbreaks
Factors shown to increase susceptibility
Cold water storage systems and tanks
Continuous chlorination plant
Thorough testing of all outlets
Water softening and hot water storage system
Stagnant water positions - unoccupied
Domestic hot water calorifiers
Cooling towers
Humidifiers
Practical prevention and solutions
Summary
41
Legionnaires’ disease Plumbing Engineering Services Design Guide
42
Plumbing Engineering Services Design Guide Legionnaires’ disease
in water systems and how it survives in tank system. It has been determined Testing should be carried out using the
aerosols. Many of these issues have yet in the United Kingdom that no appropriate testing equipment and the
to be resolved but with existing chlorination or form of disinfection is Responsible Person should ensure that
knowledge a set of guidelines for the required for existing drinking water all members of his staff are trained to
control of Legionella in man-made water mains or outlets except for initial carry out this test efficiently.
systems have been set up. disinfection in the commissioning of a
new building or pipework. It is
important that when requests for
Outbreak control: duties of additional drinking water outlets are
the responsible person received, the maintenance staff
should check that connections are in
Continuous
The permanent duties of the responsible
person and the maintenance team need
fact made to drinking water mains
and that the outlets are labelled as
chlorination plant
to eliminate the recurrence of such. All new pipework should be
disinfected before being put into use. The continuous chlorination plant should
Legionnaires’ disease in buildings are
( In the National Health Service this is be located in a suitable position and this
summarised as follows:
recommended in HTM 2040). B.S. should be permanent. The use of
a. All cold water supplied (other than 6700 and other appropriate documents. chlorine gas is potentially hazardous so it
drinking water) and water storage is recommended that sodium
should be disinfected to ensure that hypochlorite solution be used for
water delivery to every cold water chlorination the Responsible Person
,
outlet in the building complies with should arrange for the inclusion in his
the requirements of the disinfection
control technique to be used.
Cold water storage Planned Preventive Maintenance system
of daily inspections of the chlorination
b. Ail cold water storage cisterns systems and tanks plant. The Responsible Person should
also order and obtain all spare parts,
(commonly known as tanks) should
be regularly inspected, maintained chemical etc . necessary to ensure that
It is intended that, when necessary, the equipment can be rapidly returned to
and disinfected in the manner
specified. modifications to pipe and storage service in the event of breakdown.
systems should take place so that only
c. Where water is distributed to water one unit for continuous disinfection need NOTE:
outlets at the recommended be installed. It should be noted that sodium hypochlorite
distribution temperatures i.e. 55-60°C solution will lose its strength if stored for a
a warning notice should be displayed Wherever possible the cold water storage long time, or in a warm place.
system and storage tanks should store
at each such outlet because there is
water at below 20°C. The Responsible
a risk of scalding at these
Person should eliminate the possibility of
temperatures.
d. All apparatus likely to produce
any conditions which produce abnormally
high temperature rises. Advice should be Thorough testing of
contaminated aerosols such as
humidifiers, cooling towers etc. should
sought on the method to be used to
control any temperature rise. all outlets
be scheduled and a detailed system
of cleaning and disinfecting by
Cold water storage systems and tanks
for wholesome water supply, shall be It is recommended that during one week
chlorination carried out at regular in each year, a thorough test of very hot
intervals. installed and maintained in a
workmanlike manner and, flushed, tested and cold water outlets, including all
e. The Responsible Person should and disinfected where necessary before thermostatic mixing valves etc should
ensure regular testing and inspection. bringing into use as required by The take place and a suitable log retained. In
All such testing should be recorded in Water Supply ( water fitting) Regulations the case of cold water outlets these
an agreed manner. 1999’. Part 2 Regulation 4(5) and should indicate between 1 -2mg/l chlorine
Schedule 2 Paragraph 13. strength within one minute of running the
f. In conjunction with other staff, such waste.
as administrators, production It is essential that all cold water storage
personnel, senior officers, cleaners systems and all storage tanks should be In the case of hot water outlets these
etc., a system should be initiated thoroughly cleaned out at least annually. should indicate temperatures of between
which ensures that any department, 50-60°C within one minute of running to
rooms and areas in the building, if left
The cold water storage system is waste. If connected to a dosing pump,
sometimes associated with pressurised 1-2mg/l chlorine strength should be
unoccupied for a week or more,
should be thoroughly tested before vessels and storage tanks, which should achieved. All thermostatic mixing valves,
bringing back into service. be disinfected as appropriate. All shower heads and spray taps etc. should
equipment should then be drained to be tested by first running hot water to
g. Special attention to items e and f waste and the system refilled. A waste without recording temperatures for
should be observed concerning continuous system of disinfection should a minimum of one minute, then running
shower equipment and spray taps. be constantly maintained. An official log cold to waste, when a chlorine strength
For drinking water - all drinking book should be maintained by the of between 1 -2mg/l chlorine strength
outlets in the buildings should have Responsible Person and the readings of should be achieved. Recording of test
been checked that they are disinfection effectiveness in the cold results should be carried out by the
connected to the drinking water water storage system recorded daily. At supervising engineer to the approved
mains and have been clearly labelled. least once a week the Maintenance schedule. Any outlet which fails these
All drinking water mains in the Team should examine and sign the log test conditions should be recorded and
building must be connected directly to book and in the event of the disinfection details submitted to the engineer who
the mains water to ensure that they level falling below the minimum effective must rectify the fault.
are not fed through any storage or levels take appropriate action.
43
Legionnaires’ disease Plumbing Engineering Services Design Guide
It is intended that in addition to the discrepancies and their effect on hot To make the calorifiers safe, one of
testing proposed above, more frequent water outlet temperatures. This schedule the following may be undertaken:
testing of selected outlets, both hot and should identify the remedial action
a. Attach a clear PVC hose pipe to
cold, should be carried out in a similar required to bring the system to the
the drain cock ensuring that the
manner. Chlorine levels, hot and cold approved standard and given to the
end of the hose is right in the
water temperatures should be tested Responsible Person for immediate
drain, (this is to prevent the
once weekly to maintain observation on action.
the current situation.
inhalation of infected aerosol),
Any showers found to be infrequently and drain off as much water as is
Recording of test results should be used should be taken out of use. required to make room for the
carried out by the supervising engineer disinfection solution to be added.
All shower positions in the building
to an approved schedule of outlets, This should be measured
should be regularly run to waste weekly.
which will be determined by a according to the amount of water
responsible body of people, and any Each shower fitting should be run for five in the system to achieve 50-
outlets which fail the test conditions minutes during which, in the first two 60mg/l dependent on the
should be recorded and brought to the minutes hot water should be passed, and requirements of the chemical
attention of the engineer. for the remaining time, cold chlorinated user. Other techniques such as
water. U.V., iron deposition and
irradiation should be dosed to the
This procedure should be the requirements of the
responsibility of a nominated person in
manufacturers Instructions.
Water softening and each department and a list of staff
nominated kept by the Administrator. b. Make sure the domestic hot water
hot water storage flow valve is closed (DHWF),
leave the remaining valves open,
i.e. the domestic hot water return
system Stagnant water valve (DHWR ), the cold water
supply make up valve (CWS). The
If the site contains only one main central
storage tank, this should be modified so
positions - primary heating source, flow and
return must be closed.
that one compartment, if possible, is
allocated to contain soft water only for
unoccupied Remove or disconnect any ‘over
temperature control stats’. Raise
the hot water supply system. the temperature of the water in
If necessary, existing pipework should be From time to time cases arise where the calorifier by turning on the
altered so that mains water is connected departments or individual rooms in the primary heat source so that a
directly to the water softening plant and building are left unoccupied for various temperature of 70°C is reached
then to the continuous chlorine injection reasons. It is essential that a policy be all over the casing of the
unit to provide the softened water with devised so that accommodation cannot calorifiers, then let the calorifier
chlorine to approximately 1-2mg/l at the be returned to general use until a full test stand for a minimum of 24 hours
outlets. The softened and chlorinated of hot and cold water outlets has been or longer if possible. This is to
water should be delivered to the carried out. enable the heat to penetrate
appropriate compartment of the central The engineer will be required to certify through the scale and sludge and
storage tank prior to distribution to that all hot and cold water outlets, kill of any Legionella. It will be
calorifiers. including thermostatical outlets, have noticed that the temperature will
been tested in the manner previously fall very slowly owing to the
The softened water storage
specified. lagging. Drain to waste, as before,
compartment should be cleaned and with the hose pipe inserted right
chlorinated to 50mg/l every year in the into the drain.
first week of April in a similar manner to
that specified for the raw water 4. Remove primary heating (coil(s) for
compartments. In addition, all associated
pipework, pumps and equipment which
Domestic hot water insurance requirements and
thoroughly mechanically clean out.
can be segregated from hot water
calorifiers etc. should also be similarly
calorifiers 5. Refix all heating coils etc. in the
calorifier and fill up with water. Make
chlorinated each year. sure the domestic hot water flow
Where Legionella pneumophila has been valve remains closed.
NOTE: identified, it is recommended that the
The water softener unit itself should not be calorifiers should be thoroughly cleansed 6. Reconnect the high limits stats and
subjected to chlorination. and the following guidelines should be turn the heat back on, the
followed: temperature control to be set at
approximately 60°C.
At each of the calorifiers the water 1. Isolate the calorifier from the system.
should be stored at a temperature high If more than one is involved, select 7. If it is proved that bacterial growth
enough to give a flow temperature of the one that is most infected. can still be found at the tap and
60°C and suitable thermometers shower outlets, then washers should
installed in flow and return pipework and 2. Do not disturb the other calorifiers i.e. be changed on the taps to a Water
aim for a maximum temperature putting them on or off line. Regulations Advisory Scheme
deviation of 5°C. 3. Drain and clean the calorifier to be approved type.
Where these conditions cannot be treated, refill with clean treated water
obtained, a schedule of calorifiers should and then decide which of the
be prepared, clearly indicating following techniques is to be applied.
44
Plumbing Engineering Services Design Guide Legionnaires’ disease
Humidifiers Summary
There are a number of different types of
humidifiers, i.e. steam, battery-spray, To minimise risk of Legionella infection:
spinning disc, and simple ‘pouring water 1
Practical prevention
and solutions
Wholesome water
Drinking fountains check mains supply
Vending machines Mains
supply/disinfection
Drinking water taps Mains supply -
label
45
BLANK
47
Heating Plumbing Engineering Services Design Guide
48
Plumbing Engineering Services Design Guide Heating
49
Heating Plumbing Engineering Services Design Guide
50mm Airspace
105mm Brick
Air change rates
In a building of normal construction there
will be air infiltration occurring at various
Resistances
Inner surface 0.12 m2K/W
Roofs
0.10m2K/W
points through the building structure (e.g.
Rsi window and door frames) and this has to
Outer surface Rso 0.06 0.04
Air space Ra 0.18 0.18 „ be allowed for in the heat loss
calculations. Actual infiltration rates may
0.013 0.15 0.050 . 0.18 . 0.105 vary considerably, depending upon the
R = 0.12 ^ + 0.06 = 3.36
*
0.16 011
Therefore U =
1
35
^
= 0.298 W/m2oC
0.84 age of the building , level of insulation and
exposure. Empirical values of air change
3.36 rates for various situations are given in
the HVCA/CIBSE/ loP Domestic Heating
Figure 1 V ’ value calculation Guide . The procedure for calculation is
straightforward - the volume of the room
is calculated ( V) and multiplied by the air
All new housing and conversions must temperature and variations in structural change rate (N), the specific heat of air
have an energy rating , calculated in thickness and/ or density. If considering ( 0.33 W /m3oC ) and the inside / outside
accordance with the Government’s the dynamic performance of a structure temperature difference .
Standard Assessment Procedure ( SAP) (normally in relation to heat gain
and which has to be declared for Building calculations) then it is necessary to take Modern buildings are increasingly being
Regulations approval. into account three factors in addition to constructed with higher standards of
the ‘U’ value: Surface Factor ( F), insulation and draught proofing and as a
For domestic dwellings , the Building can drop to
Regulations ( Section L1) details three -
Admittance Factor ( Y value) and result , the air change rate
considerably less than that required to
Decrement Factor ( f ).
methods of demonstrating that the adequately control moisture and odour
Regulations have been complied with in build- up. Under these circumstances,
respect to the building heat loss - the some form of mechanical extract and/or
Elemental method; Target U - value
Design temperatures supply ventilation should be considered.
method and Carbon index method. Full The temperature sensed by a body
details of the methods of calculation are The provision of mechanical extract from
depends upon the surrounding air
given in Section L1, together with domestic kitchens, bath/shower rooms
temperature and the mean radiant
example calculations . and some toilets is now mandatory under
temperature (MRT) of all the surrounding
the Building Regulations (reference
For other buildings, the Building surfaces - a similar level of comfort can
Approved Document F) and literature
Regulations ( Section 12) details three be achieved with a high air temperature
and low MRT, or with a lower air
from domestic fan manufacturers gives
methods of demonstrating that the guidance on requirements.
Regulations have been complied with in temperature and higher MRT.
respect to the building heat loss - the In commercial properties it is also
To only consider air temperature when necessary to take into account the
Elemental method; a Whole building carrying out heat loss calculations may
method and Carbon emissions number of occupants and ensure that an
give unsatisfactory results, so either adequate supply of fresh air is available.
calculation method. ‘environmental’ or ‘dry resultant ’ The recommended fresh air supply rate
The calculated heat flow rate based on temperatures are normally used, which
in offices, where there is minimal or no
the ‘U’ value is for steady -state conditions take into account both air and mean smoking , is 5-8 I/s per person.
and for the majority of situations, will give surface temperatures.
Installation of a fresh air ventilation
a perfectly adequate indication of the For normal situations, where air system may be required. Alternatively,
mean rate of heat loss from the structure. movement is low, the dry resultant the use of through- wall heat recovery
However, in reality the heat flow rate will temperature is used, and recommended ventilator units, could be considered.
vary in response to fluctuations in values for various situations are given in
internal temperature, external Wherever mechanical ventilation is used,
the CIBSE Guide , NHBC Guide and
50
Plumbing Engineering Services Design Guide Heating
51
Heating Plumbing Engineering Services Design Guide
52
Plumbing Engineering Services Design Guide Heating
53
Heating Plumbing Engineering Services Design Guide
The design of these appliances places In the average domestic situation, with a
well controlled system and with a low
Heat emitter
the air inlet and flue discharge in the
same pressure zone. The only ventilation
requirement may be for cooling purposes
capacity very high recovery cylinder (at
least 20kW heat transfer capacity) and hot
selection
water priority, the inclusion of an additional
54
Plumbing Engineering Services Design Guide Heating
55
Heating Plumbing Engineering Services Design Guide
82
& temperature, and they must be
connected top bottom opposite ends and
76 always with the return connection
downstream of the flow. Convectors and
67 69 71 hot water cylinders cannot be put on a
single pipe circuit. Mixing microbore and
71
62 66 68 smallbore is quite permissible , provided
the pipework and pump are correctly
sized.
Always connect a hot water cylinder
Figure 5 Single pipe circuit circulating temperatures °C primary return to the combined heating
and DHW return pipe downstream of the
last heating return connection, to avoid
bore ' . An option (usually for domestic connections must be top/bottom opposite
possible reverse circulation problems.
situations) is a ‘microbore’ system in ends (TBOE) . Although there is less
which the main flow and return from the pipework to install, a single - pipe system Correct pipe sizing is essential if
boiler , connect to manifolds from which must be carefully designed and it cannot problems of insufficient water flow to the
the radiators are individually connected be used with convectors, which must farthest radiators on the system are to be
by 8mm or 10mm pipes. Being flexible, have a pumped flow of water through avoided. Having determined the piping
the pipes can be ‘threaded’ between floor them to achieve the rated output . layout , the heating load on each section
joists etc. in much the same way as Since the water temperature around the can be calculated and the provisional
electrical cables, so avoiding having to pipe size can be determined from Table
pipe loop(s) will progressively drop as it
use fittings. Installation is simplified, but passes each radiator, the radiators 3, which is based on a flow rate
the system has to be very carefully
towards the end of the circuit will have to .
corresponding to an 11°C system
designed and a more powerful pump is temperature drop and also shows the
be larger than they would be for the
needed to circulate the water through the heat loss from uninsulated and insulated
small pipes as well as specially designed -
same output on a two pipe system, pipe .
where there would be little variation in
-
‘twin entry’ radiator valves.
flow temperature from one end of the For domestic systems it is generally
There are several variations for system to the other. unnecessary to carry out a detailed pipe
commercial installations, including sizing, with proportioning of mains
‘ ladder or ‘reverse return’ configurations.
A variation on the basic single pipe
1
losses, etc. , as one would do for a
system is the ‘ioop-in’ system whereby
commercial situation. However, it is a
the pipework loops in and out of a single good idea to carry out an accurate
two connection valve on each radiator -
Single pipe systems the valve incorporates a by-pass so that
pressure drop calculation, in order to
some of the water enters the radiator check the adequacy of the pipe sizing
With single pipe systems, water and check the pump duty.
circulates around one or more single whilst the remainder goes through the
pipe loops with the radiator flow and by - pass and is joined by the cooler water The procedure for this can be
return connections connected from the leaving the radiator - and the mixed summarised as follows:
same pipe loop, the return connection water leaves the valve through the
1. Total heating loads in each pipe
being downstream of the flow. Whilst second connection and passes to the
next radiator on the circuit. This gives a section and convert to flow rate in I/s
circulation is usually pump assisted, the ( same as kg/s). The following
circulation of water through each radiator more positive flow through each radiator.
conversion formula can be used:
is primarily by gravity, although it can be
aided by the use of diverter tees, and
56
Plumbing Engineering Services Design Guide Heating
57
Heating Plumbing Engineering Services Design Guide
58
Plumbing Engineering Services Design Guide Heating
adequate flow/pressure under periods of leakage are not positioned over any gate valves for ease of future
high demand/drought. electrical equipment. maintenance.
Water Regulations are very explicit in 7. Do not use softened water to fill a 20. Install temporary equipotential
their requirements to avoid wastage or system (or add washing-up liquid !!) bonds if breaking electrical
contamination of water supplies and - the high salt content can result in continuity of existing pipework, to
everyone who is involved with the design, serious corrosion problems. protect operatives and third parties.
specification, installation and
8. Only use the very minimum 21. Use non-dezincifiable fittings on
maintenance of domestic water systems
amounts of flux when making domestic water services.
must ensure that they comply with the
soldered joints and use a pre-
requirements of the various legislative
commissioning cleanser.
documents relating to the prevention of
Legionella. 9. If there is a risk of the installation By-pass connection
being left switched off during For boilers fitted with pump over-run
freezing conditions, use an anti- thermostats it is essential that there is
freeze as well as a corrosion always an open circuit for the water to be
proofer or provide frost protection pumped around. If all circuits can be
Piping installation controls. closed off by motorised or thermostatic
10. Always connect the DHW cylinder valves, a by -pass is required - use an
1. Avoid placing bends or other fittings primary return as the last automatic pressure operated by-pass
close to the inlet or outlet of pumps, connection on the return pipe to the valve to avoid loss of boiler operating
as this can cause cavitation under boiler, after any heating return efficiency. If the system has a three-port
certain conditions. If possible, aim connections to avoid reverse motorised control valve, or if there is
for a 450mm length of straight pipe circulation problems. some other permanently open circuit,
both sides of the pump. such as via a bathroom radiator ( without
11. Install pumps vertically, to self - hand- wheel valve), there is generally no
2. Fittings which offer a high purge of air, and with the shafts requirement for a by -pass Connection,
resistance to the flow of water can horizontal (not below) to reduce but check with boiler manufacturer.
give rise to noise generation and bearing load and wear. Fit valves
problems of inadequate flow. each side and do not position at
Generally, compression elbows and system low point.
end feed elbows have a far tighter 12.
radius than integral solder ring
elbows, and therefore offer a higher
If installing a combined cold feed
and open vent, in order to comply Controls
with British Standard
resistance to flow. Note that 5449:Pt1:1990 the boiler must be
microbore pipes are vulnerable to However well designed a system, its
fitted with a high limit safety ultimate efficiency will depend upon the
damage and blockage and there thermostat.
may also be noise problems due to method of control. The basic requirement
high water velocities at any 13. Do not install a new boiler or of any control system is to provide the
restrictions. equipment into an existing system correct amount of heat in the right place
without cleansing it thoroughly. at the required time, and to ensure that
3. Always consider requirements for Avoid fabricated or aluminium heat the boiler is switched off when there is no
venting and pre-commissioning exchangers if the system is not system demand for heat.
cleansing and maintenance, and chemically cleaned. Consider the
include adequate provision for The main components of a control
requirement for a strainer on the
drainage. At least two 15mm valved return to the boiler.
system will usually be a programmer to
full bore drain points should be enable selection of system operating
provided at low points in the 14. Use reflective radiator film over times; thermostats to control the space
system to enable it to be pipes which are immediately below and, where applicable, domestic hot
adequately flushed through, floor boards to avoid degradation of water storage temperature and motorised
positioning with regard to flushing floor covering. valve(s) to control the circulation of
paths, avoiding short circuiting. heating water to the different circuits (e.g.
15. Always fuse the control system at space heating and domestic hot water
4. Generally, the maximum safe depth 3A and mark the plug/connection heating).
for notching a floor joist is 0.15 x unit accordingly.
the joist depth, with a maximum Modern programmers are of the
16. The electrical supply to an electronic type (rather than electro-
width of 1.5 x the pipe width, and a immersion heater must be run
maximum of two pipes in a single mechanical) and either battery operated
directly from the distribution board, or mains operated with a battery reserve
notch. The maximum diameter for a and must not feed any other
hole drilled through a joist is 0.25 x (alkaline or rechargeable). Some are very
equipment. basic in operation, whilst others offer
the joist depth, with the centre line
between 0.25 and 0.4 of the joist 17. When an existing system cannot be three or more switching cycles a day,
depth down from the top. drained, a self cutting tee can be with separate times for heating and hot
used to provide a drain point. water plus separate programming for
5. Indicate on the floorboards with a each day of the week or weekdays and
felt marker pen the route of pipes 18. Use pipe clips that completely weekends. Such flexibility offers greater
under suspended floors. enclose the pipe and metal potential for energy saving, but
strapping for suspending pipes consideration of the occupants ability to
6. Ensure all high points are below floor joists.
adequately vented and that air vent operate the unit must be taken into
points, compression joists and any 19. Use good quality lever operated account.
other potential sources of water quarter turn ball valves rather than
59
Heating Plumbing Engineering Services Design Guide
60
Plumbing Engineering Services Design Guide Heating
.jMMMAMaa .
a . Oversite
b. Concrete slab
c. Insulation
d. Underfloor heating pipes
e. Floor screed
f. Final floor finish.
On some buildings, the insulation will be
fitted below the slab in which case the
pipes can be installed within the concrete
slab. See Figure 7 .
The above construction is used for both
ground bearing and suspended slabs.
The most common materials in use rapid corrosion of any steel components
today are : within the heating system can occur.
PEX : Cross linked Polyethylene Better insulation standards in our
PP :
buildings have meant that most floors are
Co - Polymer of Polypropylene
now insulated as standard. This means
PB: Polybutylene that for most buildings the installation of
the underfloor heating will be no more
All pipes should ideally incorporate a
difficult than any other form of heating.
diffusion barrier, which can be either
integral or applied to the outside of the The basic form of floor construction in
pipe as a coating. The purpose of the most buildings is solid concrete , floating
barrier is to reduce the amount of or suspended. There are many different
oxygen that can migrate through the pipe ways in which various underfloor heating
wall. Pipes without a diffusion barrier will manufacturers design their systems and
pass much higher rates of oxygen it is only possible to deal with some of Figure 8 Floating floors construction
thereby providing a highly oxygenated the standard methods of construction in
water circulation around the heating this publication.
system. If the heating system is not fully
The following are typical floor sections of
protected by a corrosion inhibitor then
the three most common types.
61
Heating Plumbing Engineering Services Design Guide
Design
considerations
The human foot is a highly effective
thermostat for the whole body. In the
colder areas of the world human kind
has been keen to ‘take the chill off the
floor ’ since ancient times. The techniques
used to achieve this range from the
simplest rugs and skins to the more
sophisticated hypocaust system of the
Greeks and Romans.
Research shows that a basic
temperature of 21°C on the floor surface
will give an ideal sensation of comfort.
International Standards indicate that the
comfortable range is between 19-26°C
Figure 9 Suspended floors and dependant upon the required air
temperature, floor heating systems
By using the above formula, the ‘U’ value should stay within this band
Suspended floor construction .
-.
of the un insulated slab can be Most areas are permitted with design
Typical floor make up: calculated Once this value is known the floor temperatures up to 29°C.
amount of insulation required to bring the Temperatures up to 35°C are acceptable
1. Timber joists or battening
floor up to the standard required can be for specific areas such as pool
2. Insulation between joists calculated. surrounds, changing rooms, bathrooms
3. Cross battens For an insulated slab the formula would and the first metre of space adjacent to
be; walls with high fabric losses. This may
4 . Heat emission plates fitted to occur where you have for Instance
cross battens 1 extensive floor to ceiling glazing where it
5. Underfloor heating pipes ^insulated
1 is necessary to offset as much as
6. Floor boarding Uslab
+ ^
insulation possible the cold down draught that
occurs.
Where:
7. Final floor finish. The sensitivity of the human foot will
Uinsulated = U value of an insulated perceive a temperature above 29°C as
This design is suitable for most types of slab W/m 2 K
joisted or battened floors. The cross ‘uncomfortable’ at normal room
battening fitted at 90° to the joists means Uslab = U value of un-insulated temperatures of 18-22°C and should be
that a consistent pipe centre can be slab W/m 2K avoided.
maintained irrespective of the joist = The thermal resistance of the Other limiting factors to the surface
centres. This particular system also ^insulation
insulation W/ m 2K temperature may be the particular floor
avoids any notching of the joists. covering and for some materials such as
The selection of a suitable insulation timer the maximum manufacturers
There are many variations on all the material will normally be made in
standard floor sections and there are temperature should be observed.
conjunction with the architect to ensure
systems available today which can be the material will meet the floor loading Modern well insulated buildings no
adapted in a variety of ways to meet the requirements in addition to the level of longer need high surface temperature in
building design. insulation required. order to provide sufficient output to meet
Insulation would be fitted to most floors the heat losses of a typical building.
For suspended floor slabs, the Average floor emissions of between 50
irrespective of the construction method calculations are more complex since an
and this would need to meet the and 75 watts per m2 will often be more
enclosed air space is introduced below than sufficient. Low temperature floor
requirements of the Building Regulations. the slab, which can often have a high systems provide inherent, passive self
The downward heat transmission can be infiltration rate. regulation. Floor temperatures generally
.
calculated in several ways For ground
need only be 3~5°K higher than room air.
bearing slabs the most common formulae It must be remembered that with
used is: underfloor heating a solid screed or Any rise in air temperature due to solar
concrete floor will have a higher mean gain or increased occupancy means the
P2 temperature than a floor constructed air will begin to approach the floor
^ — slab 0.05 + 1.65 x -
A
0.6 x -
A without underfloor heating. For this temperature. As this temperature
reason most floors will require a degree difference decreases the heat emission
Where: of insulation to be fitted to offset any from the floor reduces. This process is
downward losses. rapid and precise. Heat emission from
US|ab -
= U value of un insulated slab the floor will begin to decrease as soon
W /m 2K as air temperature rises. Given an air
P = External Perimeter of temperature of 20°C and a floor
Building m temperature of 23°C, heat emission from
the floor will decrease by about a third for
A = Total Area of Floor m2 each degree of temperature that the air
temperature rises. A three degree rise in
62
Plumbing Engineering Services Design Guide Heating
air temperature will thus be sufficient to the dry resultant temperature and is not All of these determine the total thermal
neutralise the system. Theoretically, this so affected by the rate of fabric loss. resistance above the pipe, which will
inherent self regulation makes it possible determine the drop in temperature
to design an underfloor heating system
This means that the floor radiant systems
lower dry resultant temperature can between the pipe and the surface of the
with no other form of room temperature floor.
safely be used for the calculation of heat
control.
losses. To achieve a set output from a floor
means that we can either vary the pitch
This difference can account for a
of the pipe and operate at a set water
reduction of 5-10% for most types of
buildings. temperature or we can fix the pipe pitch
Design criteria In addition, it is not necessary to allow
and operate at different water
temperatures.
any margins for height factors in
buildings when considering the use of Constant water temperature is
To evaluate comfort purely in terms of
radiant floor heating systems. sometimes introduced into the design by
temperature requires consideration of the
choice but more often is a function of
following: In order to prepare a design for a only ‘one’ water temperature being
1 . Wet Bulb temperature building it is necessary to calculate the available regardless of different floor
heat losses in an acceptable form. constructions. The main disadvantage of
2. Dry Bulb temperature
this approach will be encountered during
Many of the modern computer programs
3. Rate of air movement allow for the use of resultant
installation when the installer will have to
create different pipe pitches. Many
4. Mean radiant temperature. temperatures in conjunction with floor
projects - especially domestic ones -
radiant systems. These will give a more
There are various accepted methods for feature different floor structures with, for
accurate reflection of the steady state
the measurement of temperature heat losses.
example, the ground floor being concrete
including globe, equivalent, effective, and the upper storeys wooden
radiant, environmental, dry and wet bulb. Once the heat losses are known and suspended floors. Water temperature
tabulated then the underfloor heating required can differ by more than 15°C
The most commonly used measure of system can be designed. Since there is between the floors and such a
comfort for heating systems is the dry
an upper limit on the surface temperature temperature difference is difficult to meet
resultant temperature which in the the maximum output from the floor is using constant water temperature.
absence of high rates of convection can
restricted. Altering the pitch of pipes to meet
give accurate indications as to the level
requirements from area to area also
of comfort that can be anticipated. For general purposes, a figure of 11
presents potential future problems when
Watts/m2 K can be used to determine the
The dry resultant temperature is defined floor covering materials are replaced e.g.
maximum floor emission. Where K is the
as: switched from tiles to wall-to- wall carpet.
difference between surface and air
In such circumstances, the pipe pitch
_ t, + Tayi 0v temperature.
cannot be altered retrospectively and
^res 1 + V10 V For example: heat transfer may not be sufficient to
Where the internal rate of air movement Room area 10m2
achieve design temperatures.
v is less than 0.1m/s then the above If the pipe pitch is kept constant, it will
equation can be simplified as follows. Heat loss 540 Watts
result in varying water temperatures. This
Heat required 54 Watts/m2 method leads to easier design and
tres = 0.5taj + 0.5tr installation. It must be borne in mind that
where: Air temperature 20°C
there is always an upper limit to the
Floor temperature 26°C desirable water temperature and in
Ws = dry resultant temperature °C extreme cases different pipe pitches and
Output required 54/(26-20)
tai = inside air temperature °C = 9 Watts/m2K
loop configurations may need to be
= mean radiant temperature °C considered. Clearly there are an
tr In the above example, the heat required unlimited number of combinations of
The inside air temperature can be is within the design parameter of 11 construction methods and floor finishes,
assumed to be the dry bulb temperature Watts/m2K. each of which will give a different overall
with the mean radiant temperature as a thermal resistance.
calculation derived from the shape of the The calculation should be repeated for
room , it ’s area, surface emmisivity and each of the rooms or areas to determine The temperature drop across the pipe
temperature. whether there are any areas, which loops should be kept low i.e.
cannot be, heated within the permitted approximately 5-10°K in order to
The radiant temperature is significant to design limits of the maximum floor maintain even floor temperatures.
a feeling of comfort since it is the surface temperature.
exchange of radiation with our Different pipe sizes also require
surrounding that has the most effect on The water flow temperature required to equivalent adjustments to water
our perception of ‘thermal comfort’. achieve a given surface temperature is temperatures however this adjustment is
dependant upon the following: very small. The difference between a
With convective systems, the air 15mm and a 20mm pipe result in only a
temperature will always be higher than 1. Surface temperature required
2% increase in flow temperature for the
the dry resultant temperature and this 2. Type of floor construction 15mm pipe.
difference can be as much as 5°K in
buildings with high fabric losses such as 3. Depth of pipe below floor surface Three main types of loop configuration
glass walled structures. are used for underfloor heating. The
4. Floor covering.
construction techniques used for the
Conversely in floor radiant systems the building will effect selection of the most
air temperature will always be lower than
63
Heating Plumbing Engineering Services Design Guide
64
Plumbing Engineering Services Design Guide Heating
Water sensor f
, J I M
l ~* *~
£ Balancing valves
£ ^ Air sensors
65
BLANK
Resource efficient
Introduction
Energy efficiency
Water efficiency and conservation
Water conservation measures
67
Resource efficient design Plumbing Engineering Services Design Guide
always be taken. Draught sealing around succeeding 15 years, with the European
Introduction loft hatches is particularly important as
warm moisture-laden air from occupied
Union contributing 8%, the USA 7% and
Japan 6%.
Conservation has been described as the rooms can cause condensation in lofts.
Following an agreement reached
careful management and preservation of Pipework for heating must be insulated between the member states of the
natural resources and the environment. wherever it runs outside the heated living European Union, the United Kingdom is
Environmental issues such as climate space; e.g., under floors or in garages. committed to reducing its greenhouse
change, ozone layer destruction along Hot water systems should also be gas emissions to 12.5% below the 1990
with air and water pollution are having a insulated to minimise heat loss from level by 2010. The heating of buildings
greater impact on building designs than storage cylinders and primary circuits; accounts for around a third of all UK C02
in the past. For Building Services, heat output from them may contribute to emissions and is expected to contribute a
regulations are in place to help in the space heating requirements in the winter similar proportion of the necessary
design of space heating and hot and cold but in summer it is wasted and may reductions. Savings can be achieved
water services. The Institute of Plumbing make the building uncomfortably warm. from better insulation in new and existing
(loP) supports all initiatives that seek to buildings, more efficient heating and hot
reduce the use of energy and to rely water systems and electrical appliances.
where possible on renewable energy Professional responsibility
sources. This section of the Guide has
been compiled to give a broad view on The loP’s Code of Professional
Standards requires members to
The benefits of
aspects of installations where these
valuable resources can be saved. Some safeguard the environment, as does the energy efficiency
of these aspects are covered elsewhere Engineering Council’s Code of Practice
Energy efficiency produces benefits both
throughout the Guide, but this section Engineers and the Environment. As
for building occupants and for the
has greater detail to give the greenhouse gas emissions are one of
environment.
designer/installer a better understanding, the principal environmental concerns of
helping to achieve that all-important the present time, following the Code For the occupants of buildings, the
Resource Efficient Design. means that members must take all benefits are lower fuel bills and more
reasonable steps to pursue energy comfortable conditions. A well-insulated
efficiency in the work they undertake. building needs less heat to bring it up to
a comfortable temperature and cools
Aspects of heating system design and
down more slowly when the heating
Energy efficiency installation are subject to the legal
requirements relating to energy efficiency
system is turned off. And an efficient ,
well-controlled heating system uses less
set by the Building Regulations, which
fuel to produce a given amount of heat.
apply to all material alterations to heating
What energy systems, including those in existing
Both these attributes combine to reduce
the total amount of fuel needed and
efficiency means buildings. In many cases, the customer
relies on the installer for advice both on
hence the cost. Affordable heating is of
particular importance in the social
‘Energy efficiency’ is a measure of the compliance with the Regulations and on
housing sector, which increasingly caters
benefit obtained from the consumption of options for reducing environmental
a unit of energy. The energy efficiency of for households with low incomes.
impact. Professional responsibility must
a building depends upon how well it is Consequently, contractors working for
therefore rest on awareness of legislation
insulated and how well the heating is housing associations and local
and an appreciation of the wider factors
controlled, as well as the efficiency with authorities need to pay particular
contributing to energy efficiency.
which its heating and hot water systems attention to energy efficiency.
can convert fuel to heat. Energy efficiency contributes to reduced
The fabric of the building has an The environmental rationale environmental impact through the use of
important influence on the amount of less fuel and lower emissions of
The combustion of fossil fuels, such as atmospheric pollution. But it is also
energy required to keep it comfortable. If gas, oil and coal, is responsible for a important to remember the difference in
it is badly insulated, even the most large proportion of all carbon dioxide
efficient heating system will require a emissions between fuels, particularly the
(C02) emissions to the atmosphere. The high emissions associated with electricity
great deal of energy to keep it warm. concentration of C02 in the global
Although it may not always be possible to use. Electrical energy is already in a form
atmosphere has risen by about 30% that can be converted to heat with 100%
improve building fabric insulation, the since the start of the industrial revolution.
heating installer should always be aware efficiency and can operate motors, lights
In recent times, climatologists have and electronic circuits without further
of opportunities for improved insulation reached a consensus view that the
and bring them to the client's attention. conversion. But that versatility comes at
‘greenhouse effect’ arising from C02 and a price: electricity has been generated
Better insulation will improve comfort and other man-made gases in the
client satisfaction and may lead to from fuel consumed at power stations
atmosphere is likely to cause global with an average thermal efficiency of
opportunities for a more competitive warming and consequent changes on
quotation. around 40%. The energy used overall to
climates around the world. This has led provide 1kWh of delivered electricity is
Excessive ventilation, caused by air to agreements under the auspices of the therefore considerably greater at around
leakage through the building fabric, also United Nations Organisation to limit 2.5kWh. The total energy used to provide
contributes to unnecessary heat loss. It is further emissions of greenhouse gases. the supply is known as the ‘primary
essential to comply with requirements for Most notably, at the World Climate energy’, which takes account of the
ventilation and supply of combustion air Conference in Kyoto in 1997, it was energy overhead required for generation
to heating appliances and for the agreed that developed nations should and distribution. It should be noted that
ventilation of kitchens and bathrooms, achieve an overall reduction of 5.2% there are also energy overheads
but opportunities to reduce draughts relative to 1990 levels over the associated with the production, refining
around windows and doors should
68
Plumbing Engineering Services Design Guide Resource efficient design
and distribution of oil, gas and solid fuels, efficiency of the heating system, which operating and maintenance instructions.
although these are much smaller than for has the effect of reducing the relative The requirement for control of heating
electricity, typically around 5%. The disadvantage of electricity to some systems in dwellings may be met by
distinction between ‘delivered energy’ (as extent. zone controls, timing controls and boiler
metered and paid for by the consumer) interlock. The interlock requirement will
and primary energy is important when be satisfied if the boiler can only operate
considering environmental impact, which Building Regulations when either a space heating thermostat
arises from primary energy consumption. or a hot water cylinder thermostat is
Table 1 gives C02 emissions per unit of Part L of the Building Regulations (Part J calling for heat. In practice, this means
delivered energy for electricity and and Part F in the corresponding that thermostatic radiator valves alone
heating fuels in the UK. legislation for Scotland and Northern are not enough, and should be
Ireland, respectively) requires that supplemented by at least one room
‘reasonable provision shall be made for thermostat.
Table 1: C02 emission factors for the conservation of fuel and power’ in
delivered energy in the UK buildings. It specifically requires limiting The requirement for commissioning of
heat loss through the fabric of the heating systems was introduced for the
Fuel C02 emissions in kgC/kWti building, from hot water pipes and hot air first time in the year 2000 revision, and
Gas (mains) 0.053 ducts used for space heating, and from applies to both new and existing
LPG 0.068 hot water storage vessels. Other buildings. Responsibility for
Heating oil 0 074
, requirements of particular relevance to commissioning rests with the person
Solid fuels 0.079 - 0.106 heating installers are that space and carrying out the work and includes the
water heating systems should be energy recording of system settings and
Electricity 0.113
efficient and that building occupiers performance test results. A certificate
should be provided with sufficient must be made available to the client and
Fuel choice information to allow them to operate their the building control body; the certificate
heating and hot water services efficiently. issued under the Benchmark Code of
Space and water heating can be Practice for the Installation,
Part L was revised during 2001, with new
provided using a range of different fuels, Commissioning and Servicing of Central
requirements in force from April 2002
including electricity. Fuel price is heating systems is considered suitable
(Part L1 deals with dwellings, Part L2
generally the most important factor for for this purpose.
with other buildings).
consumers in making a choice of fuel.
Standard tariff electricity is generally very Under Part L, heating became a
expensive, at around 5 times the price of ‘controlled service’ from April 2002, and Table 3: Minimum SEDBUK boiler
gas in delivered energy terms. Heating for the first time the provisions applied to efficiencies to be used with
oil has varied considerably with the price ‘material alterations’ carried out to elemental U-values in Part L 1
of crude oil over the past 3 decades, from existing heating systems. So heating
being the most economical fuel at times installers must take account of the Central heating system fuel SEDBUK %
to considerably more expensive than gas Regulations not just in new buildings but Mains natural gas 78
at others. LPG is generally expensive also when renewing systems in existing LPG 80
and tends to follow oil price trends rather buildings: failure to do so will leave them Oil 852
than the price of natural gas. The relative exposed to action from aggrieved
For boilers for which SEDBUK is not available,
price of fuels for heating may be customers and Building Control
the appropriate seasonal efficiency may be
obtained from Table 12 in the Standard authorities. obtained from Table 4b of the SAP
Assessment Procedure ( SAP) , which is Approved Document L gives detailed For oil - fired combination boilers a SEDBUK
updated periodically: an abbreviated
practical guidance showing how the value of 82% , as calculated by the SAP 98
version is shown here in Table 2.
requirements may be met. In Part L1, for method, would be acceptable.
dwellings, three alternative ways of
Table 2: Typical fuel costs, including VAT
demonstrating compliance with the
insulation requirements are shown,
The Standard Assessment
but not standing charges
(SAP 2001 )
including a ‘Carbon Index Method’, in Procedure (SAP)
which the level of insulation required
Fuel pence per kWh A home energy rating is a measure of
depends on the choice of fuel and the
the energy efficiency of a dwelling,
Gas (mains) 1.4 heating system efficiency. A minimum
heating system efficiency is required for intended to give information on the
LPG (bulk) 3.1 relative energy efficiency of different
other cases, as shown in Table 3. Boilers
Heating oil 1.7 houses. SAP is the UK Government’s
should meet specified SEDBUK
Solid fuels 1.7 - 2.8 standard methodology for home energy
efficiencies, depending on type and fuel
Electricity (standard) 7.4 rating. The SAP rating is based upon
used, and there are minimum standards
Electricity (7 hour on-peak) 7.9 for cylinders and controls. For non-
running costs for space and water-
Electricity (7 hour off -peak) 3.0 heating, which are calculated taking
domestic buildings, there are also three
account of the form of the building, its
alternative ways of showing compliance,
Advice given by installers on the choice which are broadly analogous to those for
thermal insulation, which fuel is used and
of fuel for heating should be based on dwellings. The main difference is in the the performance of the heating system.
both relative costs and C02 emissions, calculation methods specified, which take SAP ratings are expressed on a range of
as an increasing proportion of clients are 1-120, the higher the better. They allow
account of the different building services
now concerned about environmental comparisons of energy efficiency to be
systems used.
impact. Table 1 (above) may be used to made, and can show the scope for
provide a comparison between Apart from boiler efficiency, the most improvements. The SAP process also
alternatives in terms of C02 emissions. relevant requirements for heating system delivers a carbon index, in the range
installers are those concerning controls, 0-10, to indicate carbon emissions. Using
Comparisons of both running cost and
C02 emissions must take account of the commissioning, and provision of energy ratings, designers, developers .
69
Resource efficient design Plumbing Engineering Services Design Guide
house-builders, and home owners can temporary, as it will be withdrawn when a and oil, can be seen on the Boiler
take energy efficiency factors into European directive on boiler energy Efficiency Database at
consideration both for new dwellings and labelling is introduced. www.boilers.org.uk.
when refurbishing existing ones. Energy
Minimum standards of efficiency for most
ratings can be used at the design stage Table 4: SEDBUK efficiency bands types of boiler are imposed by law, which
as a guide to energy efficiency and the in the UK is the Boiler ( Efficiency)
potential reduction of future fuel bills and Band SEDBUK range
Regulations 1993 (UK legislation
C02 production. The Building A 90% and above implementing the European Union Boiler
Regulations require that every new B 86%-90% Efficiency Directive).
dwelling be given a SAP energy rating, C 82%-86%
which must be displayed in the form of a 78%-82%
Boiler efficiency depends on the design
D
notice. of the boiler and the conditions under
E 74%-78%
which it operates. Boiler design features
The heating designer has an important F 70%-74% affecting efficiency include:
opportunity to influence the SAP rating G below 70%
and the carbon index through the choice a. Size (surface area) of heat exchanger
of fuel, boiler, hot water system, and
controls. When the carbon index is used Specifying efficient systems b. Water content of the heat exchanger
to show compliance with Part L of the c. the method of ignition, especially
How can purchasers specify efficient
Building Regulations, the performance of heating systems? To help them Central whether or not it relies on a
the heating system can contribute permanent pilot flame
Heating System Specifications (CHeSS)
significantly, leading to less stringent have been published under the Energy d. The type of burner control (on/off, gas
requirements for insulation. Efficiency Best Practice Programme as modulating or gas/air modulating)
General Information Leaflet 59. They
e. Whether or not the boiler is designed
have been written with assistance from
SEDBUK the relevant trade associations and the to operate in condensing mode
SEDBUK is an acronym for ‘Seasonal manufacturers of heating products. The f. Flue shape and length.
Efficiency of a Domestic Boiler in the specifications cover the efficiency -critical
components of domestic wet central
Operating conditions affecting boiler
UK'. The method used in SEDBUK was efficiency include:
developed under the Government’s heating systems (boilers, cylinders,
Energy Efficiency Best Practice controls), with an emphasis on ensuring a. The size (power rating) of the boiler
Programme with the co-operation of good levels of energy efficiency using in relation to the design heat load and
boiler manufacturers, and provides a well proven and cost-effective techniques radiator sizes
basis for fair comparison of different and products. At present (CHeSS in year
2000) there are four, summarised in b. The heating system controls
models. It was specifically designed to
provide efficiency values for use in SAP Table 5. It is intended that purchasers c. Flow and return water temperatures.
calculations, and has been used in SAP should refer to CHeSS when seeking
All three are at least in part within the
assessments since July 1999. quotations for installation work: as well as
calling for good or best practice this is an control of the designer. Installation and
SEDBUK is the average annual efficiency commissioning are also important to the
aid to making quotations comparable.
achieved in typical domestic conditions, realisation of the designer's intentions.
making reasonable assumptions about Regular servicing and maintenance are
pattern of usage, climate, control, and Table 5: CHeSS (2000) reference
also necessary to ensure that efficiency
other influences. It is calculated from the is sustained, particularly for oil fired
systems
results of standard laboratory tests boilers.
together with other important factors CHeSS Type of system
reference
such as boiler type, ignition arrangement,
internal store size, fuel used, and HR 1 Good practice; system with regular Condensing boilers
knowledge of the UK climate and typical (i.e. non-combi) boiler
The heat exchanger in a condensing
domestic usage patterns. SEDBUK HC1 Good practice; system with combi boiler is designed to extract maximum
figures for most boilers currently on sale boiler
heat from the flue gases. As a
can be seen on the website HR 2 Best practice; system with regular consequence of doing so, the
www.boilers.org.uk, which is updated ( i.e. non-combi) boiler temperature of the flue gases may fall
monthly. below the dew point, which causes water
HC2 Best practice; system with combi
For estimating annual fuel costs boiler vapour to condense on the surfaces of
SEDBUK is a better guide than the heat exchanger, a situation that is
laboratory test results alone. It can be deliberately avoided in other boilers. The
applied to most gas and oil domestic Boiler efficiency presence of condensation in large
boilers for which data is available from quantities means that the heat exchanger
tests conducted to the relevant European The efficiency of the boiler is the main must be made of corrosion-resistant
standards. The SEDBUK method is used factor affecting the energy efficiency of materials and that a drain must be
in SAP, which is described below. gas and oil-fired wet central heating provided to dispose of the liquid
systems. Guidance on boiler types condensate.
As a simple guide to boiler efficiency for (especially the relative advantages of
consumers, a scheme has been created Condensing boilers are always more
regular and combi boilers) and system efficient than non-condensing boilers,
with bands on an ‘A’ to ‘G’ scale, (see
design is given in Good Practice Guide
Table 4) The band may be used on which must be designed to operate with
284 Domestic central heating and hot
product literature and labels, though flue gas temperatures high enough to
water : systems with gas and oil- fired
there is no legal requirement for avoid the accumulation of condensate
boilers . Information on the efficiency of that would cause corrosion. Even the
manufacturers to do so. The scheme is both current and obsolete boilers, gas
70
Plumbing Engineering Services Design Guide Resource efficient design
least efficient condensing gas boiler is area to provide rapid warm-up, as poor extent to which the building is insulated.
about 3% more efficient than the best heat exchanger performance causes the Guidance for the insulation of pipes and
non-condensing boiler, and the difference boiler to be on for long periods at low ducts is given in Section 1.52 of
is typically about 13%. Condensing loads. Apart from providing poor service
Approved Document L1. Pipe work
boilers are most efficient when operating to the household, a slow response
located outside the insulated building
with low return water temperatures, reduces boiler efficiency and increases fabric should be insulated with a
which induce high levels of heat losses from the primary circuit. It is thickness, equal to the outside diameter
condensation. But they remain more also important to ensure that cylinders
of the pipe (up to a maximum of 40mm)
efficient than other boilers even while not have sufficient storage capacity; apart
with insulation material having a thermal
condensing. Although it is possible to from the inconvenience caused by lack of conductivity not exceeding 0.035 W /m.K.
increase the proportion of time boilers capacity, system energy efficiency will be Pipes connected to hot water storage
operate in condensing mode by installing impaired if the boiler has to be called
vessels, including the vent pipe and the
larger radiators and using lower flow and upon frequently to reheat the cylinder. primary flow and return to the heat
return temperature, it is neither
As a minimum, the designer should exchanger, should be similarly insulated
necessary nor to be recommended; field
always specify hot water cylinders that for at least 1 metre from their points of
trials have shown it to be not cost -
comply with BS 1566 or BS3198. ‘High connection. Additional insulation may be
effective. required to prevent freezing of pipes
performance’ cylinders, which have fast
From the installer's point of view, there recovery heat exchangers and are passing through unheated areas.
are two particular considerations to be usually also better insulated, are Guidance on suitable protection
taken into account when specifying recommended (see CHeSS (2000) notes measures is given in the BRE publication
condensing boilers: the provision of a 5, 6 and 7). ‘Medium duty’ cylinders Thermal insulation: avoiding risks.
drain for the condensate and the should always be avoided as they are
acceptability of ‘pluming’- the production usually badly insulated and have poor
of a visible cloud of water droplets - from heat exchanger performance, and do not Solar water heating
the flue. The condensate drain does not comply with Building Regulations.
normally cause a problem, although care Solar water heating panels are widely
must be taken to ensure that it can be used around the world to provide
kept clear. Pluming can be a real Controls for heating systems domestic hot water, particularly where
problem, however, when the flue sunshine is plentiful and fuel is relatively
discharges into an area close to The output required from a heating expensive. In the UK, the great majority
.
neighbouring property Pluming may be system varies considerably, particularly in of installed systems are in dwellings.
perceived as much less acceptable than response to external temperature. The efficiency of solar collector panels
the less visible and more buoyant Controls are needed to ensure that the depends on number of factors, including
combustion products from a non- system provides the appropriate output
the type of collector, the spectral
condensing boiler. Condensing boilers for all conditions, including those where response of the absorbing surface, the
are thought by some installers to be little or no additional heat is required. extent to which the panel is insulated and
more difficult to maintain and less Controls contribute significantly to the
the temperature difference between the
reliable but there is no reason why a efficient operation of a heating system, panel and the ambient air. Efficiency
condensing boiler should be different by allowing the desired temperatures to
declines sharply as panel temperature
from any other modern boiler in these be achieved in each room at the times increases above air temperature, and the
respects. There is little difference in required. The selection of appropriate surface finish of the collector is
complexity and the only additional controls also plays a key part in the important. Evacuated tube collectors are
maintenance task is to ensure that the overall running costs of a heating able to maintain their efficiency at high
condensate drain is clear. system. For example, upgrading controls
temperatures, although they may be no
on older heating systems can save up to
For gas installations, condensing boilers more efficient at low temperature rises.
15% on energy bills. The recommended
should be specified unless the additional minimum set of controls is given in Good A typical solar water heating installation
costs outweigh the benefits or where Practice Guide 302 Controls for domestic consists of one or more roof -mounted
there are serious difficulties with terminal heating and hot water systems. See also panels, a hot water storage cylinder and
siting, pluming or connection to a drain. General Information Leaflet 83 Domestic a means of transferring heat from the
For oil installations, condensing boilers boiler anti-cycling controls - an panels to the cylinder. Very simple
have less of an advantage over non- evaluation concerning claims made for systems, used where sunshine is
condensing types and until recently the boiler anti-cycling devices. abundant, rely on gravity circulation but
market for them has not been developed systems designed for a typical UK
to the same extent as for gas. climate require a pumped primary
Insulation circulation. BS5918 gives guidance for
the design and installation of such
Hot water cylinders Insulation is relevant to the heating systems. Some systems used in the UK
installer in two different contexts. Firstly, have separate storage cylinders for solar
Two points require consideration to as noted above, the extent to which the heated water, which can be kept at an
ensure the energy efficiency of hot water fabric of a building is insulated affects the intermediate temperature to maximise
storage cylinders. Firstly, they should be design heating load. Consequently, the amount of heat collected. Others rely
well insulated, as heat lost to their opportunities for improving insulation on an additional heating coil in the main
surroundings cannot contribute usefully should be explored before undertaking hot water cylinder, which is also heated
to space heating requirements when no heating system design - the cost of the by a central heating system or by an
heat is required in summer and may insulation may well be offset by electric immersion heater. The circulation
cause uncomfortably high temperatures. reductions in the cost of the heating pump is usually controlled by a
Insulation is especially important if the system, as well as energy cost savings differential temperature sensor, which
cylinder is located in an unheated space. throughout the life of the installation. causes the pump to operate whenever
Secondly, the heat exchangers in indirect Secondly, parts of the heating system the temperature of the collector exceeds
cylinders should have sufficient surface itself require insulation, regardless of the
71
Resource efficient design Plumbing Engineering Services Design Guide
the temperature of the stored water in appliance, in which a burner heats a to a low pressure circuit makes them the
the cylinder by a pre-set margin of thermal store. The water in the perfect choice for applications where the
2 or 3°C. thermal store is circulated to radiators operating pressures vary through a
to provide space heating, while a system. A typical example would be the
The energy content of the hot water heat exchanger is used to transfer use of a vented boiler system to heat
produced annually per unit area of solar mains pressure water. They are also
heat to incoming cold water at mains
water heating panel depends upon useful if there is a need to isolate
pressure to provide a supply of
several factors, including the collector domestic hot water. chemically treated water in one circuit
efficiency, storage volume and usage from separate systems. A plate heat
patterns. BS 5918 gives a method for b. Integrated thermal stores also provide exchanger allows the two systems to
sizing solar hot water systems for both space and water heating from
operate separately, while providing
individual houses, taking account of within a single appliance. However,
sufficient heat transfer for correct
climate, panel orientation and collector they differ from CPSUs in that a
operation.
performance. It shows that the optimum separate boiler is used to heat the
panel orientation is just West of South primary water.
but that there is little effect on output
Plate heat exchanger sizing
c. Hot -water-only thermal stores use
within 45° of the optimum. Optimum tilt When selecting plate heat exchangers,
thermal storage only for production of
for the UK is around 33° but there is little domestic hot water. As for the two they must be large enough to provide the
difference within ±15°, which includes types described above, the domestic
required rate of heat transfer, at the
most pitched roofs in the UK. A rule of hot water is provided by a heat desired temperatures, and must also be
thumb is that a house requires 2-4m2 of exchanger working at mains large enough to ensure that pressure
panel area, which will yield around a pressure. drops across the heat exchanger are not
1000kWh per year of heat and meet too high. Connection sizes will have an
around half of annual hot water Also, some models of combination boiler effect on pressure drops, however they
requirements. A set of European contain a small thermal store to are usually sized to suit the internal
Standards is currently under overcome the limitation on flow rates for arrangement of the plates. The
development. domestic hot water. relationship between power, flow rate
Thermal storage for larger buildings must and temperature rise of water flowing
An Energy Efficiency Best Practice
rely on purpose-designed storage through a plate heat exchanger can be
Programme report 1 on solar hot water
vessels with capacity and storage calculated from the equation:
systems in new housing was published in
June 2001. temperature optimised for the heat load. Power (kW) = 4.2 x Temperature
Other design parameters that must be change (°C) x Flow rate (I/s)
Solar panels are also well suited to considered are insulation of the storage
heating swimming pools. The low vessel, arrangements for dealing with Although the temperatures and flow rates
temperature required and the very large will be different on the primary side of the
expansion and the control strategy for
thermal capacity of the pool water makes heat exchanger to those on the
coupling the store to the rest of the
it possible to achieve relatively high secondary, the power will be the same
system.
collector efficiency using simple unglazed (energy out = energy in).
panels. Typical installations in the UK Thermal stores may contribute to
(covered by BS 6785) have a panel area improved energy efficiency by allowing Example
of around half of the pool surface area the installation of a smaller heat source To work out the basics for a heat exchanger
and produce an average temperature that can operate closer to its maximum required to feed a shower with hot water,
rise above ambient air temperature of load and hence with improved efficiency. we know the shower flow rate to be about 8
around 5°K provided the pool is covered However, heat losses from the energy litres per minute, the incoming mains water
at night or indoors. store need to be taken into account; if temperature to be 10°C, and the required
insulation is not of a very high standard, water temperature is 42°C:
then any gains in efficiency from the Power Out = 4.2 x ( 42 - 10) x (8/60)
Thermal storage sizing effect can be cancelled out. = 17.92kW = Power In
Energy storage may be used either to Assuming the temperature of the primary
cope with peak loads or to take
advantage of lower energy prices at
Plate heat exchanger water being used to provide the heat is
75°C, and we would like to aim for a
certain times of day. Heat is stored using A plate heat exchanger is a device used temperature drop of 10°C, we can work out
either solid cores or hot water vessels. to transfer heat from one liquid (or gas) the required flow rate by reversing the
The most common application of thermal flowing in one direction (primary) through previous equation:
storage is in dwellings, in which solid the heat exchanger to cold water flowing Power
core storage is charged with heat at off - the opposite direction (secondary). The Flow Rate =
( 4.2 x Temperature change)
peak rates for a 7 or 8 hour period. two sets of water are kept separate by
Guidance for the design of such systems numerous stainless steel plates through 17.92
is contained in the Electricity Council which the heat is conducted. Each ( 4.3 x (75 - 65))
(later the Electricity Association) waterway can operate typically up to 10
publication Design of mixed storage bar pressure, although models are = 0.42 I/s
heater/direct systems . available to take far higher pressures. A
typical plate heat exchanger measuring This is generally enough information
Gas fired systems relying on hot water only 20 x 7 x 12cm can transfer heat at required to select a heat exchanger,
storage vessels are also available for use over 100kW - enough to heat 45 litres however one may find that the flow rate
in dwellings. Three generic types are per minute of hot water from 12 -42°C. requirement or pressure drop on one
recognised: side of the heat exchanger is too high.
a. Combined primary storage units Isolation Increasing the size of the heat exchanger
(CPSU) provide both space and will allow reduced primary flow rates,
The ability of plate heat exchangers to with accordingly lower return
water heating from within a single
transfer heat from a high pressure circuit
72
Plumbing Engineering Services Design Guide Resource efficient design
temperatures. The only other alternative Air source heot pumps generating station is located in an urban
is to increase the size of the primary area and heat, which would otherwise
pump and/or pipework. The correct Air source heat pumps may be used to have gone to waste, is distributed to
balance has to be found between heat extract heat either from outside air or buildings nearby. A similar approach may
exchanger size and primary pump size. from ventilation exhaust air. When be adopted on a large campus site, such
outside air is used as a heat source, the as a hospital or industrial complex, which
Applications required to work with lower coefficient of performance declines as has a continuous need for both heat and
temperature differences across the heat the air temperature drops. There can also electric power. Smaller units are suitable
exchanger, such as using a heat be problems with icing of the heat for individual buildings, such as sports
exchanger to transfer heat from a boiler exchanger where the outside air is of centres or hotels. Large CHP systems
system at 75°C to a radiator circuit at high humidity, which is frequently the tend to be based on gas turbine
50°C will also require larger heat case in the UK. This requires periodic technology, while small units are more
exchangers. To size jobs accurately defrosting, which is often achieved by likely to use reciprocating engines.
requires access to various pump curves temporary reversals of the heat pump
and reduces the CoP. Because of those Micro CHP describes very small units
as well as heat exchanger software - designed to operate in an individual
both of which can be obtained from factors, air-to-air heat pumps have a
relatively low CoP (in the range of house or other small building, often
manufacturers and often free on the relying on a Stirling engine to drive the
Internet. On small output systems, under 2.0-2.5) when used for heating in a
typical UK climate. As CoP declines with generator. Fuel cells, which generate
10OkW, it may be far easier and more electricity directly from gas passed over
economical to choose a heat exchanger outside temperature, it is not economic to
size air-source heat pumps for the electrodes, are currently expensive but
that is slightly oversized, but off -the-shelf offer a promising long term alternative
and hence relatively cheap. coldest conditions, but to include some
supplementary heating by electrical form of generation. Micro CHP is
resistance coils. technically feasible and is currently
Limescole undergoing field tests in the UK and
The plates within the heat exchanger are Ground or water source elsewhere. However, there are problems
embossed with a corrugated pattern, beat pumps in matching short -term heat and
designed to maximise turbulence and electricity demand that could inhibit
heat transfer. Providing flow rates are Ground or water source heat pumps commercial exploitation. In particular, if
reasonable, the turbulent flow prevents extract heat from the ground, or from the unit were sized to replace a boiler,
scale deposits from sticking to the plates. bodies of water either at ambient there would be a significant surplus of
In addition, the slight flexing of the plates temperature or with temperature raised electricity that would need to be exported
during operation helps to break up any by the outflow of waste heat. They have and sold at a reasonable price.
deposits that do form. the advantage over air source heat Alternatively, if the unit were sized to
pumps in that their heat source has meet the base electrical load, the heat
Swimming pools much greater specific heat than air and, produced would not match the needs of
provided it has sufficient mass, varies the household and a separate boiler
Heating swimming pools poses additional much less with outside temperature. would still be required.
problems due to the levels of chlorides Small ground source heat pumps have a
and bromides often added to kill germs seasonal CoP of around 3.5 in a typical
and bacteria in the water. Chlorine and UK climate.
bromine both attack metals, including
copper, iron and steel. If a copper brazed
plate heat exchanger is used on treated
The CoP figures given above are for
electrically driven vapour compression Water efficiency
cycle heat pumps. Absorption cycle heat
water then the copper is open to attack
and may result in the failure of the heat pumps have a much lower CoP but have and conservation
exchanger. An alternative is to use Nickel the advantage that they can be powered
brazed plate heat exchangers that are far directly by gas. When used for heating, Water is a precious resource; it is
more resistant. the CoP obtainable in practice (of around required to sustain life and is used
1.4) still offers a considerable advantage extensively in modern lifestyles. Water is
over a boiler. Domestic sized absorption consumed in the sense that it is
heat pumps are currently being
Heat pumps evaluated in field trials in the
transformed from a drinking water to a
lower grade wastewater containing
Heat pumps are available in a number of Netherlands; they are compact enough to pollutants. This section examines
different forms and exploit different be considered as a replacement for a methods of water conservation within
sources of low grade heat, with the effect boiler, silent in operation and offer output and around domestic, commercial and
that they can produce significantly equivalent to that from a boiler of 140% industrial buildings.
greater energy output than is supplied to efficiency.
them by fuel or electricity input. The In the UK, water supplied by the public
Many heat pumps used for heating in supply main is abstracted from streams,
performance of a heat pump may be commercial buildings in the UK are
characterised by its coefficient of rivers, lakes and reservoirs, as well as
reversible and also provide cooling in groundwater from aquifers. These are fed
performance (CoP), which is the ratio of summer at no additional capital cost.
the heat output to the power input. by an average rainfall of 1000mm of
Although heat pumps clearly reduce water each year of which half returns to
requirements for delivered energy, they the atmosphere by evaporation and
should be considered in terms of primary
Micro CHP transpiration by plants. The hydrological
energy if an overall gain in energy Combined heat and power ( CHP) is the cycle is the process by which water
efficiency is to be established. For heat name given to systems designed to moves from the atmosphere to surface
pumps driven by electricity, a good CoP generate heat and electricity waters (by precipitation) and acquifers,
is required to overcome the primary simultaneously. This may be done on a and then into the sea.
energy ratio of the electricity. large scale, whereby an electricity
73
Resource efficient design Plumbing Engineering Services Design Guide
Water conservation has become in households has risen by 70% over the
increasingly important in the UK as last 30 years to around 140 litres/person
demand for water has increased and / day of which only about 2.5 litres is used
shortfalls in supply have occurred. Also, for drinking purposes. In order to match
public awareness of the scarcity of water these increases in demand new sources
in some areas of the UK and the of water have to be created. However, in
economic value of water has increased. recent years in the UK there have been
regular shortfalls in supply resulting in
The benefits of conserving water include :
178 drought orders being issued
1. Maintaining the availability of the between 1989 and 1991 . Building new
water supply during drought periods reservoirs is expensive and can have
2. Reduced pumping and treatment
significant effects on the environment . An
alternative new approach to the problem
costs (with associated energy savings)
is to reduce the demand for water .
3. Wastewater reduction
4. The protection of the environment
and the possible reduction in costs to Water supply in the UK
the consumer. In England and Wales, water abstracted
Throughout the world the use of water is to provide a public water supply is
provided by the ten regional water Figure 3 Typical household water use in
increasing. Since 1950 the use of water the UK
has more than tripled to about 4340km3 service companies and around
each year. In the UK, water consumption seventeen water companies as well as NOTE:
1. There is considerable variation in water-
use between household size, socio-
economic group and from region to region.
2. External use includes water used for
gardening and car washing.
74
Plumbing Engineering Services Design Guide Resource efficient design
75
Resource efficient design Plumbing Engineering Services Design Guide
addition, the Water Regulations Advisory WCs is now permitted. The reduced flush Approved Contractors
Scheme (WRAS) assesses compliance must be not more than two-thirds of the
of fittings with the Regulations. This maximum flush volume and clear The Regulations include the concept of
allows the selection of water fittings that operating instructions must be provided. Approved Contractors. This is a non-
will comply with the requirements and Also, alternatives to traditional external mandatory scheme whereby a contractor
minimise the possibility of contamination overflow arrangements for WC cisterns may choose to become a member of an
or waste of water. will be permitted. Approved Contractor Scheme. Such
schemes are administered by water
Backflow prevention authorities or other organisations
including the loP’s own scheme, that are
The Water Supply (Water An example of the application of appointed by DEFRA or National
Fittings) Regulations 1999 European Standards is the introduction Assembly for Wales. Some of the
of new backflow prevention requirements. notification requirements are waived for
The Secretary of State for the The Water Regulations reflect the Approved Contractors. An Approved
Environment, Transport and the Regions approach being adopted in draft Contractor will issue a certificate for the
(DETR, now DEFRA) used powers under European Standard EN1717. It is the work.
the Water Act to replace the individual responsibility of the system designer to
water companies’ Water Byelaws with select the backflow prevention device
Water Regulations. /Vote: The Water appropriate to the fluid risk (i.e. a
Supply ( Water Fittings) Regulations 1999 performance based approach). This
came into force in July 1999. They are
not retrospective, which means that they
allows for the introduction of new
methods to prevent backflow. The
Water conservation
do not apply to any fitting lawfully
installed with regard to the Byelaws
Regulations recognise risks associated
with five fluid categories.
measures
before July 1999. The Regulations apply
only to England and Wales. However, A number of water conservation
new Byelaws have been introduced in
Installation
measures have been identified that
Scotland that, subject to compliance with Installation issues are similar to those would be applicable in the UK, as well as
Scottish law, imposes similar covered previously in the Byelaws. other techniques that would require
requirements. Similar Regulations have Fittings should be installed as intended; further research to exploit there full
been introduced in Northern Ireland. i.e. the fitting should operate as required potential. The examination of water
by the Standards with which it is required conservation methods was based on
The efficient use of public water supplies
to comply. In addition, the Regulations various attributes such as:
and their prevention from contamination include requirements for not connecting
are crucial to the protection of public materials that might lead to
health as well as water resources. The
Regulations embrace this idea and
contamination through galvanic action or Types of conservation
leaching. They also include procedures
impact upon all water fittings, including for pressure testing and disinfecting measures
retrofitting and new construction within systems before they are used.
domestic, commercial and industrial To achieve water conservation, changes
plumbing systems. are required in the way water is used, by
Notifications altering the pattern of use, by the
Performance based requirements There are new notification requirements installation of efficient appliances or a
in the Regulations. The type of work that combination of the two. The simplest
Technically, the Regulations do not distinction that can be drawn between
is required to be notified includes the
introduce many changes to the extension of plumbing systems in non- measures is to divide them into those
requirements of the Byelaws that they domestic premises, where there is a that are:
replaced. The two main exceptions are material change of use of a building. In
(a) backflow prevention and (b) a. products which relate to items, such
addition, notifiable work includes as, WCs, taps and automatic car
requirements for water closets (WCs). appliances that consume high volumes of
The requirements of the Regulations are washes
water for discretionary uses, for example
based largely on performance standards, swimming pools. Where high water b. techniques, such as, using air to
rather than the prescriptive approach consumption fittings are to be installed, move waste products instead of water
adopted in the Byelaws. Compliance is and water pressure reduction
the water authority may consider
primarily based upon satisfying relevant metering the customer.
British and European Standards. c. services that cover water-use audits
Mechanisms are in place to update these and water-use labelling.
standards to reflect changes in Disagreement and disputes
Examples of these measures are given
technology and permit innovation. Water companies are still responsible for in the following sections.
enforcing the Regulations. In addition,
-
Water efficient WCs there is a procedure for resolving
disputes. Where a water authority will not
From 1 January 2001, the maximum endorse an application for a relaxation, Products
flush volume for newly installed WCs was or refuses consent following a
reduced to 6 litres. Such WCs must meet This includes all types of device that can
notification, or applies conditions to the be used to save water ranging from the
the requirements specified in DEFRA’s consent, the customer can appeal to
WC Suite Performance Specification. simple flow restrictor, through low- water-
DEFRA as to whether the action was use washing machines to fully recycling
WCs can be flushed using any reasonable.
mechanism that passes this performance automatic car washing equipment.
standard. Therefore, it will no longer be i. Flow restrictors are readily available
necessary to use a siphon. and can be fitted to many appliances,
The use of dual flush mechanisms for but their use has to be appropriate.
76
Plumbing Engineering Services Design Guide Resource efficient design
Where taps can be left on by careless not readily available in the UK but are ix. Automatic leak detectors are
users and where items are washed used in parts of France and the USA. becoming increasingly available in the
under running water they are a cheap To be used efficiently these cisterns UK. These devices are fitted into the
way of reducing water wastage. need to be matched to WC pans that incoming mains and close when a
However, a more effective, but more can use the higher velocity water leak is detected, preventing both the
expensive, solution would be to install effectively. Another type of water and waste of water and damage to
taps operated by proximity sensors. compressed air toilet, uses water to property. Some operate by sensing a
rinse the bowl and compressed air to high flow rate and others use
ii. The average amount of water used
evacuate the contents. This type is conductivity detectors to activate
for a conventional shower is
used in many types of buildings in the valves.
approximately 30 litres, whilst a bath
USA.
requires about 80 litres. It initially x. Automatic closure taps can produce
appears showering is more energy vi. Toilets that use no water for flushing water savings in commercial and
and water efficient, but the fact is that are available. The most common type public buildings where there is a risk
households with showers use them in the UK is the composting toilet. In of taps being left on accidentally.
more frequently than non-shower its domestic form this toilet is usually
xi. Presently, 85% of households
households use their baths. Also electrically powered heating the
pumped and multi-head showers are
possess a washing machine and 10%
waste material to enable composting
a dishwasher, consuming, in total,
not as efficient as conventional action to occur. The major problem
about 12% of domestic water. The
showers. Households whose water with this type of toilet is its size; the
ownership of these previously luxury
use is metered could use suitable smallest domestic model Is about
goods are increasing. Water
showering products as a method of twice the size of a conventional WC
Regulations govern the maximum
reducing total water consumption. suite. Large (greater than 15m3)
permissible volume of water used for
composting toilets do not usually
iii. Conventional showerheads can a wash; between 150 and 180 litre for
require the external input of energy
discharge water at between 0.3-0.5 a washing machine (depending on
for the process, as the aerobic
I/s. Low -flow showerheads can drum size) and about 196 litre for an
decomposition is sufficiently
reduce this to below 0.2 litre/sec average dishwasher. These levels are
exothermic to be self -sustaining.
depending on the supply pressure. above current consumption of about
Large composting toilets may be
Research conducted in the USA has 100 litre and 25 litre respectively).
environmentally acceptable as they
shown that the use of low-flow The Water Regulations maxima could
consume only a small volume of
showerheads can save approximately be brought in line with the water
water, require no drainage pipework
27 litre each day each person ( for a consumption of current production
and produce compost that can be
person who mainly showers rather models.
than takes baths). This equates to an used in the garden. However the
questions of adequate hand washing Other products include drip-proof taps
energy saving in hot water of 444kWh
(1.6 x 109 J) each person each year
facilities if there is no available water and drip feed irrigation systems.
supply and the safety of children
for water heated by gas (or 388kWh
for water heated by electricity). The
using toilets with open chutes needs Techniques
to be considered.
cheaper alternative to low -flow A technique is defined as the application
showerheads is to fit a flow restrictor vii. Urinal flushing cistern controllers of a collection of associated products
to the supply to an existing have been widely used in the UK for (e.g. a vacuum drainage system) ,
showerhead, although this may some time. Water Regulations state education or legislative policies, changes
increase the showering time. the maximum rate at which cisterns in cultural habits or the use of alternative
iv. WC cistern water displacement
may be filled. Since 1989 new fluids for various processes.
devices, called dams, which are cisterns are required to be refilled
only when the urinal is in use. There i. In most drainage systems in the
inserted into cisterns, are available to world water is used as the transport
reduce the volume of water flushed. are various methods of sensing use
and operation. Some use changes in medium. This is mainly due to
Although these are relatively historical reasons as most drainage
water pressure to identify operation of
inexpensive they can interfere with systems involved removal of waste
the correct and efficient operation of taps and therefore by association the
use of urinals. Others use passive into rivers. However, water is
the cistern. They do not fit easily into becoming increasingly valuable and
infra-red (PIR) detectors to detect
UK cisterns with a syphon flush in some circumstances it is very
movement of persons in the room,
mechanism because they are wasteful to use water of drinking
some sense the temperature of urine
designed primarily for use in cisterns quality to flush toilets and drains. An
in the urinal traps and many use
fitted with flap valves. If all the volume established alternative is the vacuum
of water in the cistern was necessary
various forms of proximity detector.
The essence of these devices is they drainage system. This uses air as the
to clear the WC pan, a reduced flush
all obviate the flushing of urinals main transport medium. Some
volume may not be effective and the systems also use special appliances
user will flush the cistern again and
when the premises are not being
used and are usually an improvement that use little water, such as, the
hence increase the use of water, vacuum WC and urinal.
instead of reducing it. over the use of the traditional ‘pet -
cock’ that has to be set to drip water ii. Education programmes to change the
v. WCs can be flushed with water using at the required rate into the cistern. public’s uses of water have been
compressed air assistance. Some used at various times in most
such cisterns use the pressure of the
viii. The use of an occupancy detector to
isolate the water supply to a developed countries of the world.
mains water supply to compress a Education of all ages is needed but
washroom when unoccupied is
volume of air above the stored water. education programmes in schools
When the water is released into the another application of PIR technology.
This can minimise the waste in urinal help produce a new generation with
bowl it has a much greater velocity an awareness of the problem.
flushing and that caused by taps
than from a conventional gravity
operated cistern. These products are being left on. iii. Metering of supplies is a technique
77
Resource efficient design Plumbing Engineering Services Design Guide
that has social, political and financial Economical products BRE has developed a water efficient
implications. Presently, the majority of To help in the selection of water specification for new housing which
domestic water used in the UK is economical products, water-use labelling meets the Water Regulations
charged on a tariff that was related to of appliances is being adopted in requirement and is given below.
the rateable value of a building. A Australia. It is analogous to fuel
BRE water efficiency specification:
charge based on the volume of water consumption figures for motor cars. A
consumed is an alternative to the rate prospective purchaser is able to compare i. WCs (6 litre)
method; this requires some form of the relative amounts of water that
ii. Dual flush WCs (6/4 litre) or (6/3 litre)
metering. Commercial and industrial .
different appliances use This scheme
buildings are generally metered. would require the testing of appliances to iii. Low volume baths
an agreed standard and would add to the
iv. Long pipe runs are to be avoided iv. Water butts ( for garden irrigation)
cost of the product. Currently, products
because water contained in them that are covered in the Australian v. Spray taps on handwash basins
may have to be run off before the
scheme include:
water reaches the desired vi. Reduced flowrate taps on handwash
temperature. The insulation of hot i. Shower heads basins
water pipes can reduce this problem.
ii. Taps vii. Water efficient dishwasher
It is common practice to run water
from hot taps to waste until it is up to iii. Flow restrictors viii. Water efficient washing machine
temperature and then add cold water.
iv. Dish washing machines ix. Water efficient showerhead.
If the initial cooler water was utilised
reductions could be achieved. Other v. Clothes washing machines Water metering
ways of reducing water wasted in Metering trials have been conducted in
vi. WCs
pipe runs would be to use point of twelve areas in England. These sites
use water heaters, and to use vii. Urinals cover a range of geographical areas and
unvented hot water systems which social groups; a total of approximately
viii. Domestic garden equipment.
operate on higher water pressures 56,570 households. A survey carried out
than traditional vented water heaters In the UK, the Bathroom Manufacturers by Ofwat indicated that there was a high
and can be used with smaller bore Association, represents many level of acceptance of water metering by
piping. sanitaryware manufacturers. 72% of those questioned. The installation
of water meters and their use for the
v. One of the most popular techniques Toilet rebate programmes
presently used for saving water is to Toilet rebate programmes have been
charging of water on a volume used
rather than on a flat rate basis could be
use rainwater for tasks where used to great effect in parts of the USA.
used to encourage water conservation.
drinking water would normally be They involve offering payments to users
The actual tariff system adopted for
.
used These include WC flushing, who exchange their existing WC for a
metered dwellings will affect the potential
garden and window box watering. low- water-use WC from a specified list.
water savings that can be achieved. The
Not only does this result in water savings
vi. Recycling of wastewater is possible relative contributions to the total water bill
but also increased WC and bathroom suit
but may give rise to problems. from standing charges and charges
sales and is an incentive to the industry.
Wastewater from sinks, baths and related to the volume of water used are
Experience in San Simeon, California,
basins may be used for irrigation important for creating financial incentives
USA has shown a 39% reduction in total
purposes but if it is used for WC for water conservation.
water-use after a toilet rebate scheme
flushing the cisterns mechanism may
had been implemented. This required the The majority of metered householders
suffer due to deposits of soap and
replacement of the existing 1198 WCs for (59%) in the study attempted to reduce
other contaminants. Other problems
low -water-user WCs (less than 7.2 litre). their water consumption by some means.
associated with recycling wastewater
A rebate scheme for gas-fired This was achieved by a number of
are storage, contamination and
condensing boilers is already operated in methods including:
separation from the existing drinkable
the UK by the Energy Savings Trust.
water supply. i. Less plant watering
Efficient landscaping
ii. Less toilet flushing
Services Efficient landscaping can reduce the
amount of water required for irrigation iii. Taking showers instead of baths
These are not product based but involve and the watering of plants. Presently the
knowledge that can be applied or iv. Using washing machines less
external use of water for gardening runs
utilised. at between 2% and 3% of total water
frequently
Audit consumption for domestic properties. v. Sharing baths, bath water, or
An audit of water using appliances, Many commercial and public buildings showers.
especially in large organisations, may have extensive landscaped areas. Low
Even though installation of meters may
reveal many areas where savings can be transpiration plants native to the
be costly in existing buildings, there are
made. Companies that offer these Mediterranean can be used for
ornamental gardening. Large areas are hidden benefits, such as detecting
services usually market devices such as existing leaks during installation.
WC dams, tap flow restrictors and are also given over to recreational uses,
Presently, many new buildings are
able to offer the audits at negligible cost such as golf courses. Efficient watering
automatically fitted with a water meter or
to the clients. In New York City, USA, the systems that monitor wind speed and air
provided with suitable connections for
use of a voluntary water audit in 5200 temperature can vary irrigation rates so
water is more fully utilised and
installation later, although trends show an
buildings has shown potential water increase in unmetered water
savings of 28 million litres per year. The evaporation is reduced.
consumption.
audit consisted of a leak and waste
inspection with free replacement of Evidence from the USA suggests that
showerheads, aerating taps and WC water savings from the installation of
cistern dams. water meters produced savings in the
78
Plumbing Engineering Services Design Guide Resource efficient design
79
BLANK
80
.
Piped gas services m
Wm
'
1
Natural gas 82
Conversion examples 85
Liquefied petroleum gas installations 85
Compressed air 91
Vacuum 98
81
Piped gas services Plumbing Engineering Services Design Guide
( Discharge in a straight horizontal copper tube with I .Ombar differential pressure between the ends, for gas of relative density 0.6 (air = 1 )
Natural gas copper tube to EN1057 - R250 Previous designation BS2871 Part 1 Table X 1971
82
Plumbing Engineering Services Design Guide Piped gas services
( Discharge in a straight horizontal steel pipe (to Table 2 , medium , of BS 1387: 1967) with I .Ombar differential pressure between the ends, for gas
of relative density 0.6 (air = 1))
Steel tube medium grade - BS 1387 General purpose tube to the quality assurance requirement of (ISO 9002/BS 5750 Part 2 )
Copper Tube to EN 1057- R250 half hard straight lengths and EN 1057- R220 Soft Coils .
Previous designation BS 2871 Part 1 Table ( Y ) 1971
(The effects of elbows, tees or bends inerted in a run of pipe [ expressed as the approximate additional lengths to be allowed] )
83
Piped gas services Plumbing Engineering Services Design Guide
*
1/2 22 2.5 8 1.8 6
15 15 2.5 8 2.0 6 4
Domestic properties
Normal gas usage would be satisfied by the following meter size:
Table 8a Meter characteristics
Model Capacity Standard Pressure loss Capacity Proving Meter
type per hour working pressure at capacity per revolution dial/circle connections
(ft3> ( m3) ( psi) ( mbar) ( w g) ( mbar ) ( ft3) ( dm3) ( ft3) (dm3)
U4/G2.5 141 4 0.7 50 <0.5 <1.22 .043 1.25 1 10 1" screwed
U6/G4 212 6 0.7 50 <0.5 <1.22 .071 2.0 1 10 to BS 746
Commercial properties
Usage will vary but the following Table would generally give a meter size to suit requirements:
Table 8b Meter characteristics
U16 U25 U40 U65 U100 11160
Capacity per
16m3 565ft3 25m3 833ft3 40m3 1412ft3 65m3 2296ft3 100m3 353ft3 160m3 5650ft3
hour
Std. working
75mbar I.Opsi 75mbar 1.Opsi 75mbar I.Opsi 75mbar I.Opsi 75mbar I.Opsi 75mbar 1.Opsi
Pressure
Mean pressure
1.22mbar 0.5"wg 1,62mbar 0.65' wg 1.22mbar 0.5"wg 2.36mbar 0.95"wg 1.32mbar 0.53"wg 2.91mbar 1.17"wg
loss
Capacity per
4dm3 0.142ft3 10dm3 0.353ft3 20dm3 0.714ft3 25dm3 1.0ft3 50dm3 2.0ft3 71.4dm3 2.5ft3
revolution
Proving circle
100dm3 1ft3 100dm3 10ft3 100dm3 10ft3 100dm3 10ft3 100dm3 10ft3 100dm3 10ft3
( 1 pulse =)
Standard 11/4~ screwed to 2" screwed to 2" screwed to 65mm flanged 80mm flanged 100mm flanged
connections BS746 BS746 BS746 BS4505.1 16/1 BS4505.1 16/1 BS4505.1 16/1
Shipping
9.43kg 20.75lb 16.40kg 36lb 28kg 61.51b 41.8kg 921b 70kg 1541b 75kg 1651b
weight
Standard working pressure is shown at 75mbar ( 1.0 psi) - meters can be supplied for higher working pressures.
Heat energy rates The gas discharge rate tables expressed (cv)
as m3/h, can be converted to energy
Wobbe No =
The rate at which gas is used and heat (Vsg )
produced in gas appliances may be input rates using one or more of the
expressed in several ways. The heat listed conversion calculations from 1 8 * Therefore if using natural gas with a cv
input rate can be calculated by and 9 for thermal efficiency. of 39.70 and a sg of 0.58
multiplying the gas rate in m3 or ft3 by It is essential however, that the heat (39.70)
the relevant calorific value (CV). The = = 52.12
output of appliances are kept reasonably (VO.58)
relevant cv may vary seasonally slightly constant and the gas quality maintained
from region to region. within close limits. The wobbe number WobbNo = 52.12
The current CV’s are generally will give an indication of the heat output
expressed as follows: from burners using any of the three
family gases. The wobbe number can be
a. cv Btu/ft3 = 1065.64 derived using the following formula:-
b. cv MJ/m3 = 39.70
84
Plumbing Engineering Services Design Guide Piped gas services
85
Piped gas services Plumbing Engineering Services Design Guide
Table 10 Liquid and vapour phase comparisons second person stationed outside the
area to supervise. The LPG supplier
Commercial butane Commercial propane
should be consulted if a leak is
Liquid phase suspected, particularly a leakage of
Relative density (to water) 0.57 0.51 liquid product. There is no acceptable
of liquid at 15.6°C percentage or degree of leakage with
Litres/tonne 1750 1960 LPG.
Kg/litre 0.57 0.51 LPG is normally odorised by the
Imperial gallons/ton 390 440 manufacture by the addition of an
Ib/imperial gallon 5.7 5.1 odorant such as ethyl mercaptan or
Vapour phase dimethyl sulphide which give LPG its
characteristic odour and enable leaks to
Relative density (to air) 2.0 1.5
at 15.6°C and 1015.9mbar
be detected by smell at concentrations
down to 0.4% of the gas in air (ie one-
Ratio of gas to liquid volume at 240 270 fifth of the lower limit of flammability).
15.6°C and 1015.9mbar
There are special applications where the
Boiling point at atmospheric pressure 2°C
- - 45°C LPG is not odorised, eg. where the
Vapour pressure (abs) ( max ) (bar) (psig) ( bar) ( psig) odorising material is harmful to a
20°C 2.5 40 9.0 130 process or does not serve any useful
50°C 7.0 100 19.6 283
purpose as a warning agent. In such
applications, extra precautions and
Limits of flammability at safety procedures must be taken in
atmospheric pressure
respect of marking storage vessels,
(% gas in air) 1.8 to 90 2.2 to 10 installing pipelines externally, inspections
Calorific values (gross) 121.8MJ/m3 93.1MJ/m3 daily, provision of automatic flammable
(net) 112.9MJ/m3 86.1MJ/m3 gas detectors etc.
Vessels are never completely filled with
General properties volumes of vapour/air mixtures and
possible hazard.
liquid, the maximum percentage fill
varying between 80-87% depending on
All personnel working with LPG should the vessel size. The space above the
LPG vapour is denser than air,
receive adequate initial and refresher liquid level allows for liquid expansion
commercial butane being about twice as
training as appropriate. The notes in this (due to temperature changes) and for a
heavy as air and commercial propane
Guide are not intended to cover all supply of compressed vapour for
about one and a half times as heavy as
aspects of LPG installations but are a drawing-off by the consumer. When the
air. Leakage of LPG will therefore flow to
guide to the extent of information pressure of the vapour in the space
low points, for example, along the ground
personnel engaged in small industrial, to the lowest level of the surroundings, above the liquid falls, the liquid boils to
commercial and domestic installations into basements or into drains without produce more vapour and restore the
would be expected to fully understand. pressure. The boiling point of propane is
water seals. If the air is still, any LPG
For reference and further information, the vapour will disperse slowly and could be around -45°C at atmospheric pressure.
Codes and Standards listed at the end of ignited a considerable distance from the The liquid takes heat (latent heat of
this Section should be consulted. The original leakage, the flame travelling back vapourisation) from the liquid itself, the
values of the physical characteristics of to the source of leakage. metal of the vessel in contact with the
the product have been ‘rounded’ to liquid and from the surrounding air. This
When LPG vapour is mixed with air in cooling effect may cause condensation
facilitate remembering; for exact values,
certain proportion, a lower flammable and even freezing of the water vapour in
refer to British Standards, LPGITA or the
mixture is formed. Within the range of the air local to a leakage. This effect
suppliers of the gas.
2% (lower limit) to 10% (upper limit) of may show as a ‘white frost’ at the point of
LPG is normally stored at ambient the vapour in air at atmospheric escape and make it easier to detect
temperature as a liquid in steel vessels pressure, there is a risk of explosion. leakage. Leaks can sometimes be seen
(or special lightweight alloy cylinders for Outside this range, any mixture is either as a ‘shimmering’ due to the refractive
touring caravans) under pressure. There too weak or too rich to propagate flame index of LPG.
are special applications where the liquid but it is important to understand that
is stored under refrigerated conditions at over-rich mixtures can become diluted LPG, particularly liquid product, can
a lower pressure but these applications with air and becomes hazardous. At cause severe frost burns ( for reasons
do not normally apply to the type of pressures higher than atmospheric, the similar to those outlined in the previous
projects being considered here. upper limit of flammability is increased paragraph) if brought into contact with
but the increase with pressure is not the skin. Goggles, gloves and protective
The liquid is colourless and is linear, eg. doubling the pressure does clothing should be worn if exposure to
approximately half the weight of an not double the upper limit of flammability. this hazard is likely to occur.
equivalent volume of water. If LPG is
spilled on water, it will float on the ON NO ACCOUNT SHOULD A NAKED A vessel which has contained LPG and
surface before vapourising. The liquid FLAME BE USED TO DETECT A LEAK is ‘ empty’ may still contain LPG in vapour
occupies about 1/250th of the volume form. In this state, the pressure in the
An explosimeter, properly calibrated for vessel is approximately atmospheric and
needed if the product was stored as a LPG, must be used for testing the
gas. It is more practical therefore, to if the outlet valve is left open or is
concentration of LPG vapour in the air. leaking, air can diffuse into the vessel
store and transport the product as a
LPG vapour is slightly anaesthetic and forming a flammable mixture and
liquid under pressure than as a gas. may cause suffocation if present in
However, a leakage of a small quantity of creating a risk of explosion. Alternatively,
sufficiently high concentrations. Extreme LPG may diffuse from the vessel to the
the liquid product can lead to large caution must be taken when testing tor atmosphere.
leaks and there should always be a
86
Plumbing Engineering Services Design Guide Piped gas services
LPG bulk tank location and The number of tanks in one group should oxygen or other toxic or hazardous
not exceed six, subject to the maximum substances (eg. chlorine) - distances
safety distances total capacity of a group given in Table between 6 and 45 metres are not
11. If more than one group is required, uncommon depending on the relative
This section covers LPG bulk storage then any tank in one group should be at sizes of the vessels - but specialist
installations at industrial, commercial and least 7.5 metres from any tank in another advice should always be obtained.
domestic consumers’ premises where the group unless a radiation wall is erected
LPG is stored in a tank or tanks larger No LPG storage tank should be installed
between the groups or adequate fixed
than 150 litres water capacity. For within the bunded enclosure of a tank
water spray systems are provided.
installations in refineries, bulk plants and containing a flammable liquid, liquid
large industrial plants, reference should Separation distances are intended to oxygen or any other hazardous or
be made to the publications issued by protect the LPG facilities from the cryogenic (producing low temperatures)
the Health and Safety Executive and the radiation effects of fires involving other substances. No LPG storage tank
LPGITA . facilities as well as to minimise the risk of should be located in any bund where
escaping LPG being ignited before being there is a permanent source of heat (eg.
Storage tanks should normally be dispersed or diluted. The distances steam mains) or within the bunded
installed above ground in the open air in given are minimum recommendations enclosure of a heated storage tank (eg.
a well ventilated position and should fuel oil tank).
and refer to the horizontal distance in
NOT be installed in basements or open
plan between the nearest point on the
pits. Tanks should not be installed one The vicinity of LPG storage tanks should
storage tank and the nearest point of a
above the other. Vertical cylindrical specified feature (eg. an adjacent storage
be free of pits and depressions which
storage tanks are commercially available might form gas pockets and affect the
tank, building, property line etc).
and although used extensively abroad, safety of the tanks. The ground beneath
vertical tank installations in the UK are Radiation walls or adequate fixed water storage tanks should be either
not commonplace and are generally drenching systems may be provided to compacted or concreted and should be
more expensive. However, a vertical enable separation distances for above sloped to;
tank may solve a problem on a restricted ground tanks to be reduced, but
a. Prevent the accumulation of any
site but the LPG supplier should be specialist advice should be obtained. If liquid, including rainwater and cooling
consulted at an early stage. separation distances are reduced. It may water applied under fire-fighting
be necessary to provide diversion walls conditions, beneath the tanks
Tanks may be installed underground but or kerbs (maximum height 500 mm) to
most LPG suppliers would prefer not to
ensure that the path of leaking gas from b. Ensure a flow of any liquid away from
put tanks underground mainly because tanks so that other vessels or
a storage site to a specified feature is not
such installations have to be accessed important areas are not affected.
less than that shown in Table 11.
for full internal visual examination and
ultrasonic or hydrostatic testing every 5 Conventional bunds (an enclosure LPG storage vessels should not be sited
years instead of every 10 years for an capable of retaining the total capacity, in locations known to be susceptible to
above ground tank. The cost of the plus 10% margin, of all the vessels within flooding eg. near rivers and streams
associated attendances may make the enclosure) around LPG storage tanks which could overflow their banks during
underground tank installations should NOT be used. abnormal weather conditions.
prohibitive. To prevent tampering and possible
No LPG storage tank should be installed
Storage tanks should be sited and nearer than: vandalism, storage tanks should be
located in accordance with Table 11. a. 6 metres to the bund wall of any tank
enclosed by an industrial type fence
Note that details for underground tanks which is at least 1.8 metres high and at a
containing a flammable liquid with a
have been omitted for clarity but details distance of not less than 1.5 metres from
flash point below 32°C
for these can be obtained from the the LPG tanks, unless it is a boundary
LGPITA. b. 6 metres from any tank containing a fence when the distances given in Table
* A fire wall may be used under certain
flammable liquid with a flash point 12 will apply.
between 32°C and 65°C
circumstances to reduce { to approximately Around the immediate vessel area,
half ) the minimum separation distances shown c. 3 metres from the top of the bund fences should have at least two non-self
above. For details see LPGITA publications. wall of any tank containing a locking gates, not adjacent to each other
flammable liquid. and preferably at diagonally opposite
corners of the fenced enclosure, opening
LPG storage tanks should be installed outwards to provide easy means of exit
well away from tanks containing liquid
in an emergency situation. It is
preferable that the padlocks fitted to
Table 11 Minimum recommended safety distances for LPG storage vessels these gates should suit the master key
Maximum water capacity system operated by most LPG suppliers
as this can prevent problems and delays
Maximum water Nominal Maximum Minimum separation distance during deliveries. The gates must be
capacity of any single LPG total water From building Between unlocked when the compound is
tank in a group capacity capacity of all boundary, tanks occupied.
tanks in a group property line
( whether built or The provision of a fence need not apply
not) or fixed to tanks of 9,000 litres water capacity or
source of ignition * less which are provided with a hinged,
( litres) (tonnes) ( litres) (metres) (metres) lockable cover to deny access to valves
and fittings. However, should it be
150 to 500 0.05 to 0.25 1,500 2.5 1.0
elected to erect a fence to prevent
>500 to 2,500 0.25 to 1.10 7,500 3.0 1.0 unauthorised interference, then the full
>2.500 to 9,000 1.10 to 4.00 27,000 7.5 1.0 provisions of the previous paragraph
>9,000 to 135,000 4.00 to 60.00 450,000 15.0 1.5 must be applied including the provision
87
Piped gas services Plumbing Engineering Services Design Guide
s
the road or hard standing for the tanker.
P c> Q Cb Cp Extended fill pipes are practicable but are
normally used as a last resort in difficult
—
r i m 111 r
for a bulk tanker vehicle may be required
under some site conditions. If the bulk
tanker vehicle has to negotiate difficult
bends or steep gradients, it is usually
5 advisable to arrange for the LPG supplier
to make a ‘dummy delivery’ before any
Vessel 1m work commences. Suppliers may charge
1 tonne Hedge Boundary fence more for the LPG if it is necessary to
(one side only) ( ranch type or similar ) send a helper with the driver for
deliveries to awkward sites.
Figure 2 Small bulk vessel at domestic premises Figure 1 shows the layout of a typical
small bulk vessel adjacent to a building
and Figure 2, a 1 tonne bulk vessel at
of two means of exit. Where there is background shall be fixed to the outside domestic premises.
surveillance at industrial premises, the of the compound surrounding wall or
site perimeter fence may suffice for fence or, if these have not been provided,
security. the notices shall be attached to the tank . Storage tanks and fittings
The size of the lettering shall be such Storage tanks are designed, fabricated
Where there is a possibility of
that notices can be clearly read at the and tested in accordance with British
mechanical damage to LPG storage and
safety distances applicable to the
associated equipment from vehicles (eg. Standards, AOTC Rules and other
installation and from points of access to recognised pressure vessel codes.
in goods delivery yards, near site roads
the storage site. Storage tanks are normally purchased or
etc.), suitable protection must be
provided by the use of crash barriers, Each storage tank shall be clearly and hired from the LPG supplier, who should
vehicle impact bollards or a non- boldly marked: assume responsibility for ensuring that
continuous wall not more than 500mm in the tanks, tank supports, protection
HIGHLY FLAMMABLE - BUTANE
height. against corrosion, testing and provision
(or PROPANE as appropriate) of tank fittings all comply with the rules
At least two NON SMOKING OR NAKED Long grass, weeds and combustible and regulations.
LIGHTS notices in red on white
material should be kept clear from an
88
Plumbing Engineering Services Design Guide Piped gas services
The pressure of the vapour within a bulk Table 12 Storage tank dimensions
storage vessel, under normal UK Approx. Continuous
Nominal Water Diameter Overall
weather conditions, can vary between 2 LPG capacity length overall off -take
and 9bar depending on the liquid product capacity height
temperature. On average, the vapour (kg) ( litres ) ( mm) ( mm) ( mm) ( m3/hr )
pressure is about 7bar when liquid
200 450 610 1675 900 2.26
product temperature is 15°C. Safety
pressure relief valves protect the vessel 600 1400 1000 1985 1310 5.66
against excessive pressure due to 1000 2250 1000 3042 1460 7.08
exposure to heat in adjacent facilities. 2000 4500 1220 4100 1685 10.19
7000 16000 1700 6782 3580* 28.30
A first stage regulator, mounted on the
1200 28000 2172 8600 3910* 39.62
tank at the vapour off -take, reduces the
varying high pressure to 0.75bar. A *including platform and guard rails
second stage regulator reduces the
intermediate pressure of 0.75bar down to appropriate to the operating conditions in
37mbar which is the industry standard service:
Overall length
propane operating pressure for domestic i. Pressure relief valve connected 1
appliances. directly to the vapour space
The second stage regulator incorporates ii. Drain or other means of removing the
safety features to protect the appliances liquid contents
against excessive pressure.
iii. A fixed maximum level device and
fi r>
Tanks are sized in accordance with three preferably also an independent
main criteria: contents gauge
Figure 3 Storage tank dimensions
Vapour offtake capacity iv. A pressure gauge connected to the
vapour space if the vessel is over
The tank must be able to boil-off liquid 5,000 litres water capacity
product faster than the vapour product is LPG storage in cylinders
being drawn-off when all the gas v. A suitable earthing connection if the
vessel is over 2,500 litres The basic principles detailed in previous
appliances are operating at maximum sections in respect of safety when
capacity. This rate of gas production is vi. A filling connection. handling and storing propane in tanks
known as the vapour offtake capacity of also apply to installations where the
the tank and is a function, amongst other It should be noted that some LPG
suppliers provide a combination valve for propane is stored in cylinders.
things, of the surface area of the tank;
the larger the tank the larger the offtake certain sizes of tanks which includes: For permanently piped domestic
capacity. It is normally quoted in cubic i. A threaded filling connection installations with a low offtake rating, eg.
metres per hour (m3/hr) or in kilograms incorporating a manual shut-off valve, single cooker, two 19kg propane
per hour (kg/hr). Sometimes two figures a spring loaded back check valve, a cylinders with a change-over regulator
are quoted; a figure for intermittent relief valve to prevent pressure build should be sufficient. Larger domestic
offtakes and a lower figure for continuous up between the back check valve and and small commercial and industrial
offtakes. the manual shut-off valve and a installations, with a higher offtake rating,
protective cap to prevent thread eg. central heating boilers and fires,
Storage capacity required damage and ingress of foreign bunsen burners in laboratories etc , may
matter. require four 47kg propane cylinders.
To ensure continuity and security of gas Each cylinder is fitted with a valve; the
supplies under adverse weather ii. A vapour off -take connection handwheel is turned anti-clockwise to
conditions, storage should be sufficient controlled by a diaphragm valve open and clockwise to close. An excess
for a minimum of six weeks gas supply at which can be fitted with a first stage pressure relief valve is also provided.
maximum use. (This allows for the tank regulator and pressure gauge. The four cylinders, at the container
being partially full, some of the gas being pressure of up to 9 bar, are connected to
iii. A fixed liquid level gauge
used and for three weeks adverse a change-over valve by means of pigtails
incorporating a replaceable control
weather conditions in the UK when it
valve. (see Figure 4) . The change-over valve
may not be possible for delivery vehicles incorporates a regulator to reduce the
to get to the site). The consequences of For a detailed specification of tank fittings pressure to 37 mbar for the supply to the
the gas supply failing during adverse and piping, consult the references at the appliances. The change-over valve
weather conditions, industrial action, etc end of this section. connects two cylinders to the pipework
should be considered (eg. hospitals, old system and, when these two cylinders
persons homes, etc) and additional Figure 3 and Table 12 show typical LPG
storage tank dimensions. For exact are empty, the valve automatically
storage provided if necessary. changes over to the two reserve
dimensions and a copy of a certified
drawing, consult the LPG supplier of the cylinders and indicates that these have
Location for tank tanks. been brought into use.
Tanks must be located in accordance For indoor applications, eg. portable
with the Codes of Practice and domestic cabinet heaters where the
Regulations. cylinder is contained in or close to the
Each tank should be provided with at unit, butane must be used.
least one each of the following fittings Manufacturers of LPG may have different
suitable for LPG service over the range sizes and ranges of sizes of cylinders.
of pressures and temperatures Table 13 gives details of the popular
89
Piped gas services Plumbing Engineering Services Design Guide
90
Plumbing Engineering Services Design Guide Piped gas services
2.3 8 8.70 1.181 0.835 0.682 0.590 0.528 0.457 0.409 0.373 0.323 0.289
2.3 10 12.20 2.751 1.945 1.588 1.375 1.230 1.065 0.953 0.870 0.753 0.673
2.6 15 15.90 5.334 3.772 3.080 2.667 2.385 2.066 1.848 1.686 1.460 1.306
2.6 20 21.40 11.211 7.927 6.472 5.605 5.013 4.342 3.883 3.545 3.070 2.746
3.2 25 27.00 20.046 14.174 11.573 10.023 8.964 7.763 6.944 6.339 5.489 4.910
3.2 32 35.70 40.298 28.495 23.266 20.149 18.022 15.607 13.959 12.743 11.036 9.871
General purpose tube to the Quality Assurance requirements of IS09002/BS5750 Part 2
91
Piped gas services Plumbing Engineering Services Design Guide
Table 16 Final temperature (°C) of adiabatic compression from free air at 1.013 bar Nowadays, air cooled compressors may
at 20°C (SI metric units ) have capacities up to 350dm3/s
Gauge pressure Single stage Two stage (750cfm), or be rated on continuous duty
( bar ) rc) rc) up to 14 bar (200psi). Air cooled
cylinders are finned and additional
3 164 85 cooling is provided by arranging for the
4 192 97 flywheel or a fan to direct a stream of air
5 218 106 onto the cylinder. Such compressors
6 240 116 should not be run in a confined space,
8 278 129 otherwise the high ambient temperature
10 310 141 will prevent adequate air cooling.
14 365 160 A common method of compressor
cooling is of course, to provide a water
Table 17 Effect of altitude on compressor volumetric efficiency (SI metric units ) jacket. There are a number of ways in
which such a jacket could be supplied
Altitude Barometer pressure Percentage relative
volumetric efficiency
with cooling water. It should however be
compared with sea level remembered that, although the colder the
water the more effective the inter or after
( m) (mbar) (4 bar) (7 bar)
cooler, cold water fed to the compressor
Sea level 1013 100.0 100.0 jackets can be harmful. This is because it
500 945 98.7 97.7 can cause water vapour in the
1000 894 97.0 95.2 compressed air to condense to the
1500 840 95.5 92.7 detriment of cylinder lubrication and also
2000 780 93.9 88.0 lead to possible corrosion.
2500 737 92.1 87.0
92
Plumbing Engineering Services Design Guide Piped gas services
93
Piped gas services Plumbing Engineering Services Design Guide
Example (SI metric units) distance above the drain trap outlet, oil Example 1
and scum floating on the water surface
How much moisture will separate out from ( which might foul up the trap) can be A machine requires 3m3; available pressure
air if the compressor inlet conditions are is 7 bar and the minimum suitable pressure
periodically drained off.
20°C and 70% relative humidity; the is 5.5 bar.
compressor delivers 1m3/sec of free air Apart from the receiver’s ability to cool
By using the formula to determine the
compressed to 7 bar to the system at 25°C. the air and hence deposit liquid (that is receiver capacity ;
Compressor takes in 1m3/sec why it is better to site the receiver where
the ambient temperature is low), it — = 2m3
From Graph 1, water taken in will be: performs two other functions. For some 1.5
0.16 x 70 = 0.0126kg/s applications, it is important that the
10 x 100 pressure pulses produced by a
Compression ratio at 7 bar = 7.91
reciprocating compressor be eliminated Exompie 2
as far as possible. The receiver therefore
(Table 19). acts as a pulsation damper. The receiver A machine requires 100 cu ft; available
pressure is 100psi and the minimum
Next, we must find the volume of air after also acts as a power storage vessel,
suitable pressure is 80psi.
compression. Since its volume is allowing intermittent high demands for
proportional to the absolute temperature compressed air to be met from a smaller By using the formula to determine the
and to compression set. receiver capacity;
1 Being a pressure vessel and thus subject 100 x 14.7
compression ratio x 1m3 = 73.5 cu ft
to regular inspection, a receiver is fitted 20
will occupy: with inspection covers and manholes.
These also allow any solid contaminent
1 (273 + 25) build-up to be removed. To comply with Layout
* = 0.128m3 Factory and Safety Acts, a receiver must
7.91 (273 + 20)
be fitted with an adequately sized safety Although in an ideal system , all cooling
From the graph, 10m3 of air at 250°C can valve and generally a pressure gauge is and condensing should be carried out
carry 0.24 kg of water also fitted. before the air leaves the receiver, this is
Therefore, 0.128m3 can carry : not very often achieved in practice. It is in
On small horizontal receivers generally fact impossible where aftercoolers are
supplied with the smaller industrial or
^
0.128 x = 0.00307 kg not fitted. The whole of the compressed
garage type compressor, automatic air mains therefore become additional
drainage may be more difficult . The drain cooling surfaces, the amount of
Therefore, the amount of water which will
separate out is: point is often in the centre of the dished condensing which takes place depending
end of the receiver or on the top. In each on the efficiency of moisture extraction
0.0126 - 0.00307 = 0.00953kg/s case, an internal dip pipe is fitted to allow before the air leaves the receiver and the
the air pressure to displace the collected temperature in the mains system itself .
liquid when the manual drain is opened.
Receivers An automatic trap can be used. It is useless to provide a compressed air
gun to blow out particles of swarf after a
Important as aftercoolers are, it would be It is also worthwhile considering the machining operation if, every time the
very unusual for all the water vapour in capacity of the receiver. This is usually operator used the gun, he squirts water
the air to condense at this point. Further sized on the actual output in 1 minute all over the finished job. Equally, it can be
cooling almost always takes place in the from the compressor, but where very expensive to pass this water
receiver as well as from the distribution consumption is high and fairly constant, through compressed air operated tools.
system. The water vapour, (and oil mist, the air is in the receiver for too short a
if the compressor is of the lubricated time to cool down very much. Where this Care must therefore be taken in the
type) condenses in the receiver and is so, the storage capacity is obviously layout of the mains so that adequate fall
collects at the bottom. On those low and it is better to size the receiver on is given to proper drainage points.
installations where the compression plant plant consumption rather than on The general layout of the building will
is small, an aftercooler may not be fitted, compression output. dictate the best positions for drain points
thus making the receiver the point at One compressor manufacturer but in general, the main should be given
which most condensed liquid will be recommends the following as a guide to a fall of not less than 1m in 100m in the
found. If these liquids are allowed to build receiver size: direction of air flow and the distance
up, carry-over into the mains system is between draining points should not
likely. There is also the possibility of Receiver capacity (m3) exceed 30m (100ft).
corrosion of the receiver itself. m3 of free air required It is a good idea to form a distribution
It is therefore, important to ensure that Allowable pressure drop (bar ) system as a ring main to help reduce
these collected liquids and solids pressure losses. It also makes the
(atmospheric dust, pipe scale, carbon, and also; alteration of extension of the existing
rust etc . ) are automatically removed as Receiver capacity (cu ft) system easier. Drainage points should be
they collect. As the trap and its protective provided by using equal tees and it
strainer will have to handle varying cu ft of free air required x 14.7psi assists in the separation of the water if
s
proportions of water, oil, emulsion, dirt, Allowable pressure drop (psi) these are arranged to change the
etc., regular cleaning is essential. direction of the flow as shown in Figure
If excessive amounts of oil are being 5. Whenever a branch line is taken off
carried over from the compressor, it the main, it should leave the top of it, so
generally indicates that maintenance of that any water in the main doesn’t fall
the compressor is required. If a manual straight into the plant and the bottom of
drain cock is fitted to the receiver a short the falling pipe should be drained as in
Figure 5.
94
Plumbing Engineering Services Design Guide Piped gas services
.
50
will cool the air down to a theoretical dew
point of 1 to 3°C ( 34 to 37°F) and thus -
bQx
2
10 - 4-
« ©- =
precipitate out the moisture. The system
is a straight mechanical refrigeration unit 32
©—S= 100
8
outgoing cold, dry air is used to pre-cool 4
95
Piped gas services Plumbing Engineering Services Design Guide
Ratio of
compression 1.5 1.99 2.97 3.96 4 , 95 5.94 6.92 7.91 8.9 10.87 12.85 14.82 18.77
Table 21 Formula for converting volume of compressed air to volume of free air
Air tools are usually rated in cfm of free air. Where ratings of other air equipment are not given in
terms of free air consumption, the following formulae may be used to convert .
q = Qi
P + 1.033
0=0
,
Q (P + 101325
, 101325 0 = 0,
P + 14.7 ,
1.033 14.7
q = Litres free air Q = Cubic metres free air Q = Cubic ft. of free air
q , = Litres compressed air ,
Q = Cubic metres ,
Q = Cubic ft. of compressed
p , = Compressed air compressed air air
pressure in kg/cm2 ,
P = Compressed air ,
P = Compressed air
pressure in pressure psig
Newtons/metre2
Weight and volume of pure air. Pure air at 32°F (0°C) and 14.7psi ( 101.325 Kn / m 2 absolute
.
(atmospheric pressure). Weight 0.08073 lb/ft 2 (1.29g/litre) Volume 12.381 ft 2Ab (772 litres/kg).
§. 70 /
Where K = 800 example, at 5.4 bar , with a temperature of /
L = length of pipe (m) 32.2°C (90°F), a compressed air system
would contain 7.419 litres of water in
£ 47
/
o
£ 24
/
Q = volume of free air passing vapour form every 8 hours. /
through the pipe (l/sec)
Ascertainment of peak capacities for
5
o
/ 4 8 12 16 20 24 28
R = ratio of compression compressed air systems is largely a Number of laboratories
matter of judgement. It is necessary to Average flow (2 or more labs)
d = internal pipe diameter (mm) = 2 outlets x 1 litre/sec x 150%
consider the probable use factors,
determined by the devices requiring = 2.8 litres/sec per laboratory
compressed air, the estimated number of
Example 2 people who will be drawing air from the
Determine the size of pipe needed to pass system and the pattern of air use, with
300 litres/sec free air with pressure drop of special attention paid to periods of high
not more than 300mbar in 125m of pipe load . For example , compressed air
run, air pressure is 9bar . demand in a two man laboratory may
-
96
Plumbing Engineering Services Design Guide Piped gas services
( in)
larger pipe
(mm)
1 1
.
10 15 *4
20
1
25 32 40
2
50 65
3
75
4
100
Approximate number of small pipe flows served by larger pipe
5
125
i
150
(ini
(mml
1
/8 6 1
1/4
8 2.1 1
3/e 10 4.5 2.1 1
1
/2 15 8 3.8 1.8 1
3/4 20 15 8 3.6 2 1
1 25 30 15 6.6 3.7 1.8 1
'
1A
11/2
32
40
60
90
25
40
13
20
7
10
3.6
5.5
2
2.9
1
1.5 1
2 50 165 75 35 20 10 5.5 2.7 1.9 1
21/2 65 255 120 55 30 16 8 4.3 2.9 1.6 1
3 75 440 210 100 55 27 15 7 5 2.7 1.7 1
4 100 870 400 190 100 55 30 15 10 5.3 3.4 2 1
5 125 1500 720 330 180 90 50 25 17 9 6 3.5 1.8 1
6 150 2400 1130 530 300 150 80 40 28 15 9 5.5 2.8 1.6 1
97
Piped gas services Plumbing Engineering Services Design Guide
Table 26 Volume of compressed air carried by medium grade steel pipes, of minimum bore, to BS 1387 at given velocities
Velocity Flow of air (litres/sec) through medium grade steel pipe to BS 1387, minimum bore
M/s 15mm 20mm 25mm 32mm 40mm 50mm | 65mm | 75mm | 100mm | 125mm 150mm 200mm
3.0 0.6 1.1 1.7 3.0 4.1 6.5 10.9 15.1 25.7 39.2 56.2 98.5
3.5 0.7 1.3 2.0 3.5 4.7 7.6 12.7 17.6 30.0 45.7 65.5 115.0
4.0 0.8 1.4 2.3 4.0 5.4 8.7 14.6 20.1 34.2 52.3 74.9 131.0
4.5 0.9 1.6 2.6 4.5 6.1 9.8 16.4 22.6 38.5 58.8 84.2 147.0
5.0 1.0 1.8 2.8 5.0 6.8 10.8 18.2 25.1 42.8 65.4 93.6 164.0
5.5 1.1 2.0 3.1 5.5 7.4 11.9 20.0 27.6 47.1 71.9 103.0 181.0
6.0 1.2 2.1 3.4 6.0 8.1 13.0 21.8 30,1 51.3 78.5 112.0 197.0
6.5 1.3 2.3 3.7 6.5 8.8 14.1 23.7 32.6 55.6 85.0 122.0 213.0
7.0 1.4 2.5 4.0 7.0 9.5 15.1 25.5 35.1 59.9 91.5 131.0 230.0
7.5 1.5 2.7 4.3 7.5 10.1 16.2 27.3 37.6 64.2 98.0 140.0 246.0
8.0 1.6 2.8 4.5 8.0 10.8 17.3 29.1 40.1 68.5 105.0 150.0 263.0
8.5 1.7 3.0 4.8 8.5 11.5 18.4 31.0 42.6 72.8 111.0 159.0 278.0
9.0 1.8 3.2 5.1 9.0 12.2 19.5 32.8 45.1 77.1 118.0 169.0 296.0
98
Plumbing Engineering Services Design Guide Piped gas services
pressure is 0 and the ultimate is 760 torr system will cut his maintenance work Theatre suction
or 30 inches of mercury. Also, considerably.
manufacturers of vacuum gauges The free air displaced in the theatre is
produce scales calibrated in both ways. naturally much higher than for general
This guide therefore uses 0 as ultimate Ward suction ward usage , and it is quite possible for
and 30in or 760 torr as atmosphere for
the surgeon and anaesthetist to require
The free air displacement required at the suction to be available at up to 80 litres
the remainder of this summary, bedside outlet varies of course, per minute in the theatre at any one time,
depending on the type of ward being and also at a pressure of 250 torr.
served. For instance, in the respiratory
The hospital system ward, suction is required for quick
Apart from the scientific and industrial removal of sputum etc, from the throat, X-ray bolus
and is not generally in use for long
fields , the main usage of vacuum is in
periods, whereas in the post-thoractomy This is a technique using the suction
the medical and medical research field
wards, the suction may be required for system to evacuate bags filled with
which covers five main areas: .
long periods of continuous duty granules that are placed in position
a . Ward suction Therefore the outlet displacements can around the limb to be X-rayed, and on
be anything from 1 litre per minute to an applying the suction, it is found that the
b. Theatre suction estimated maximum of 40 litres per -
limb will be held firmly in the pre set
c. X -ray bolus minute ( free air) at approximately 250 position. The free air displaced here is
torr. quite small once the initial evacuation
d. Dental suction
has taken place , and the degree of
e. Pathology and pharmacy laboratories . vacuum need not exceed 150 torr.
As any hospital engineer will confirm, the
provision of an efficient central vacuum
99
Piped gas services Plumbing Engineering Services Design Guide
100
Plumbing Engineering Services Design Guide Piped gas services
university chemistry block with up to 400 better than 10 torr. Nowadays, many major work has to be carried out before
laboratory places fitted with water jet contracts are split into mains services the trap is exposed.
pumps is not permissible by with the and then bench furniture and services
In senior and research laboratories, traps
Water Companies in most areas. separately. This is not a convenient
are not considered necessary because
arrangement for most services, but in
Even if the case is put that only a quarter this calibre of student using the vacuum
case of vacuum, it is not at all system would interpose his own trap on
of these outlets would be in use for say
satisfactory.
four hours per day, the possible water the bench top between the process being
consumption is going to be about 270m3 If, upon completion of the laboratory, only carried out and the bench valve, and this
per day. Due to this, the central vacuum 50 torr vacuum can be created at the trap would be charged with a suitable
pipeline system is here to stay for bench outlet, where is the fault ? The desiccant to neutralize the particular
sometime. vacuum pump, the main distribution vapour being pumped.
system , the bench pipe run or the bench
To overcome the water shortage, the The sizes of the main runs do, of course,
outlet ? Such a situation could involve up
obvious solution is to first look at a water depend upon the total number of outlets
to four different contractors, and to find a
recirculation system , but this has two to be served, and on the general layout
small leak in an already completed
main disadvantages. The ultimate of the building. If , for example, there is a
vacuum system can be a very tedious
vacuum obtainable is dependent upon tower block of laboratories four storeys
and expensive business.
the vapour pressure of water, and high, having 50 outlets on the first two
provided the water is maintained at an One should check that the specification floors, 10 on the third and 40 on the top
ambient temperature of 15°C, then a states quite clearly, the degree of floor, a suitable arrangement would be a
vacuum of 15 torr can be expected. vacuum at which the whole installation is 54mm diameter riser to the second floor
to undergo a pressure rise test, and also and 42mm extending to the top floor. This
However, the distribution pipes and tanks
the operating pressure at which the line riser must be suitably trapped at the
need to be internally treated and unless
will be maintained. base.
the recirculating water is filtered and
cooled, the temperature will rise, thus The first two floors would have 42mm
affecting the ultimate vacuum obtained, subsidiary mains reducing at the bench
ie. if the water temperature rose to 50°C, Bench outlets runs, the third floor would only require a
then the ultimate vacuum would be in the There are several good vacuum bench 28mm diameter floor run but the top floor
order of 100 torr as against the 15 torr at valves on the market in this country and would probably be best served by a
15°C. the types that give a good flow control 42mm main floor run.
It may be permissible to allow a minimum and easy replacement of working parts As with the hospital system , copper tube
number of water jet pump positions are preferred. For instance, never install with capillary fittings has been found
which could be reserved for pumping metal-to-metal cone-type vacuum cocks trouble-free in this pressure range, but
really corrosive vapours that would with a grease seal where hydrocarbon again, a rigid PVC line can be
otherwise be detrimental to the working vapours are present, because the maintained at better than 10 torr, but it is
mechanism of the central vacuum pump, vapours will quickly dissolve the grease essential to study the vapour content
and this compromise may be accepted if and a pressure rise will take place, likely to be pumped to make sure that the
it can be demonstrated that adequate causing the pumping unit to cycle at material chosen for the line will not be
protection is provided to prevent backflow frequent intervals. adversely affected by vapours pumped
in the water system. Most laboratories Valves having a stuffing-box shaft seal over.
will require a pressure at the bench are not considered suitable.
outlets at least as good as a water jet
pump, namely between 12 and 15 torr The push-in or bayonet type of outlet is Pumping units
absolute, and the speed of evacuation very practical provided that flow control is
found to be most suitable is about 6 litres not essential and is favoured on Vacuum pump manufacturers in this
per minute, which is a little faster than industrial projects. Its use in the teaching country whose pumps can achieve the
most water jet pumps. or research field is limited and its leak desired pressures are limited, and all
tightness in some cases is suspect. have merits of their own. The three most
The consultant or planning authority can essential points to look for in a vacuum
generally base laboratory requirements The sizing of the bench runs is not pump to serve laboratories are:
on these figures, but a close check difficult in this pressure range, and as a
should be made during discussion with guide, a 15mm copper line could serve a. That it will achieve and maintain the
the client and establish quite clearly what up to four outlets on a 4 metre bench, a pressure required
pressure is to be provided, and if a 22mm line would serve up to eight
b. That it is designed to discharge, or
pressure of better than 12 torr is wanted, outlets and a 28mm line up to 16 outlets. has facilities for dealing with corrosive
say for instance 1 torr, then the problems A 15mm line to each bench valve is
vapours pumped over
increase considerably, and these cases preferred, and if elementary work is
will be discussed later. being carried out or the laboratory is to c. That its noise will not give cause for
be used for a high density of students, complaint.
We are now at the stage where the then under-bench traps should be
pipelines and accessories should be It is not essential that a twin standby unit
incorporated at a convenient position in
discussed, having established that a is provided, although many modern
each bench run. These traps should be
standard system is wanted for normal colleges are favouring this arrangement.
designed to incorporate an isolation
filtration through buncher flasks and However, it must be decided whether the
valve and an air admittance facility to
possibly, some distillations etc, are to be prime mover is to be automatically
enable the trap to be emptied without controlled or manually operated.
carried out . If the system is to maintain a interference to the vacuum system. The
vacuum of 12 -15 torr, then the lines, laboratory steward would no doubt be The automatic unit is designed to provide
joints, isolation valves, traps and most responsible for emptying these traps, and a ‘vacuum on tap' service at all times of
important, the bench valves, must be it is most important that they are not the night and day, and is generally
proved free from vacuum leakage at installed in inaccessible positions where controlled by switches which operate
101
Piped gas services Plumbing Engineering Services Design Guide
from a vacuum bellows. Thus, the pump between their process and the bench Graph 4 Comparative vacuum scale
only runs when a pressure rise takes outlet which will preclude any liquids
place in the line. The differential between being accidentally pumped over and also Absolute vacuum
- -
the cutting in and cutting out pressure that the vapours being pumped will be Hg Torr
can be limited to about 5 torr if partially dried by the desiccant. If this mm ins
necessary. This type of controlled system simple precaution is taken, it will ensure 760 30 0
is ideal for laboratories or research areas that the small pump will not become 737 29 10
that have intermittent use , contaminated by carelessness; this will 711 28 50
686 27
add considerable life to the rotary pump. 660 26 100
The manually operated plant has to be
635 25
turned on when vacuum is required, and When providing these small systems with
this does mean that there is a time delay individual pumps, the biggest hazard is
{ which varies depending on pump speed to the working parts of the pump; for 560 22 200
and line capacity) in pumping out the example, if soluble organic acids are to
system. It also means that a lower be pumped, the oil film in the pump gives 508 20 252
pressure can eventually be achieved no protection at all to the working parts 460 300
18.12
provided that the line is leak tight. The and formic and acetic acids will cause
main advantage with this type of system, quite severe corrosion depending on the
as opposed to the automatic one is cost; number of outlets in use. The only way to 381 15 379
also the manually operated unit is most prevent such acids from entering the 360 14.12 400
suitable for large teaching laboratories pump is by the use of conical flasks on
where the vacuum service is only the bench tops, these containing sodium
260 10.25 500
required for a short period each day but hydroxide pellets mixed with indicating 254 10 516
because of the high percentage of bench soda lime.
valves in use simultaneously, there is no The question of explosion risk in small
real point in providing an automatic rotary pumps is sometimes raised, 160 6.25 600
pumping unit. In fact, if automatic gear is especially when ether-air mixture is
provided in such areas, there is 127 5 633
present, but the risk is very small
sometimes a risk that because of because the temperature at which
frequent cycling of the pumps, the 60 2.37 700
automatic ignition takes place would be
starters and switch gear could become
about 180°C which is at least twice the 0 0
overloaded. maximum running temperature of most
760
102
Plumbing Engineering Services Design Guide Piped gas services
As a crude example, a gramme of water air, which for 99% of the time, will not be
at , say 10 torr, will evolve about 100 litres the case.
Pump sizing for individual
of water vapour in the system , and other chamber work
vapours will have a similar or even
greater volumetric effect on the system. It Summary T = pump - down time (excavation time)
has been found that the best approach is F = pump - down factor from Graph 5 for
one based on discussion with the user, in Figure 5 is indicative of air which is fairly given pressure
order that the possible vapour content dry, and consideration must be taken of
can be considered, and this, coupled excess moisture that may be generated. S = pump speed (free air displacement )
with previous experience gained, should First establish usage and determine what V = system volume
enable a sensible sizing of the lines to be pressures and displacements are
possible. required. NOTE
Clarify these usages, ie. medical or .
V and S must be consistent units (ie litres
The suggestions already given for pipe
sizing may form a useful guide for those laboratory. .
and litres/min)
persons who have to design or install a To calculate the time taken to reach certain
Discuss the various types of outlets, the pressure in a given system with a given
.
piped vacuum system It must be siting of the pumps, the provision of an pump:
remembered however that there is no efficient exhaust system, and choose a
straightforward scale on pipe sizing for line material which is both leak - tight at T FxV
vacuum systems unless of course, the the desired pressure and one that is
system is only going to handle clean , dry functional in use.
103
Piped gas services Plumbing Engineering Services Design Guide
To calculate pump speed required to reach a Oxygen and vacuum are used
given pressure in a given time: extensively throughout most hospitals
References
FxV and are usually required in the following
S=
T areas: LP Gas Association
Codes of Proctke
1. In-patient departments
Example No. 1 - Installation and maintenance of
2. Operating suites bulk LPG at consumer's
Pump size required to excavate a chamber 3. Maternity departments premises.
of 60 litres to 1 torr in 3 minutes.
4. Accidents and emergency areas Pt. 1 - Design and installation.
„ FxV including out -patients.
Pump speed S - ~ Pt. 2 - Small bulk installations for
Vacuum and compressed air are required domestic premises.
From Graph 5, F = 7 in dental suites, and operating suites for Pt. 3 - Periodic inspection and testing.
7 x 60 patient ventilators and operating surgical
Hence, S = tools. No. 3 - Prevention and control of fire
3 involving LPG.
Nitrous oxide is required in operating
=140 litres/min No. 22 - LPG Piping systems - Design
suites, maternity units and accidents and
Therefore, pump with displacement of 140 emergency areas. In addition, N20/02 is and installation.
litres/min and ultimate vacuum better than 1 usually required in maternity delivery No. 24 - The use of LPG cylinders at
torr is required. rooms. residential premises.
Graph 5 enables pump-down time or
No. 25 - LPG Central storage and
pump size to be evaluated for any clean,
distribution systems for multiple
leak-tight rotary pumped system down to
consumers.
0.1 torr.
Due allowance made for change of pump
volumetric efficiency with reduction in
pressure but impedance of connecting
pipelines neglected.
For recommended plant layouts, consult
specialized manufacturers and for
medical vacuum, consult current Health
Technical Memorandum.
Medical gases
The term medical gases covers the
following:
1. Medical compressed air (oil and
moisture free)
2. Vacuum suction
3. Oxygen
4. Nitrous oxide
5. Nitrous oxide/oxygen mixture N20/02.
104
Design of sanitary pipework systems 106
Kitchen drainage 114
Laboratory drainage 115
Materials for above ground drainage systems 115
Inspection ond testing of discharge pipes 116
Methods of waste collection 117
Sanitary accommodation 117
The design of building drainage systems 123
Below ground drain renovation 132
Methods of renovation 132
Rainwater systems 134
Siphonic rainwater systems 149
Vacuum rainwater systems within buildings 152
Vacuum drainage systems 155
105
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Design basis
configurations in diagrammatic form .
The primary ventilated system
( previously known as the single stack
system) is shown in Figure 1 . Where any
WC
rt eye
Bath
106
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Discharge stack —
Air admittance valves
Ventilating stack
Lowest Air admittance valves may be used in
^
'
Lowest branch branch
either primary or secondary ventilated
Sink Wash basin systems, providing they are used within
0r= ==T==TJ1 R = 2 x I.D.
the application limits contained in the
approval document issued by a
wc Bath European Technical Approvals body,
==T]J) Preferable Alternative
such as the BBA and WIMLAS . These
Cleaning eye valves are available in a range of sizes,
arrangement arrangement and can be used to terminate stack vent
671/S>° max — pipes inside the building , and to prevent
Cross-connection as
Single Appliances an alternative to the Application L ( min)
siphonage problems for branch discharge
connection to the WC Single dwelling up to 3 storeys in height 450 mm pipes or individual appliances. The valves
branch (not preferred) Buildings up to 5 storeys in height 740mm open automatically on sensing negative
>n
Discharge stack — — Ventilating stack Buildings up to 20 storeys
Buildings over 20 storeys
1 storey
2 storey
air pressure within the system; thus
allowing air ingress only. They should not
Wash basins be used where positive pressure
Figure 5 Requirements at the base of ventilation is required, such as when the
Ventilating pipe = rffi Cleaning eye
primary ventilated discharge stacks stack connects to a septic tank,
intercepting trap, or where a sewer is
prone to surcharge.
Offsets
Cross-connection
671/2° max >- as an alternative to
the connection to
In large buildings, it is often be Termination of ventilation
necessary for the discharge stack to
Multiple Appliances LcJ
the WC branch (not
offset. Vent piping to relieve the offset pipes
preferred)
pressure fluctuation would be required At the top of a discharge stack, the vent
( see Figure 6) where systems are heavily pipe diameter should be equal to the
Figure 3 Secondary ventilated system
loaded, or serving more than three stack’s. However, on stacks serving 1 or
stories. The bore of the vent pipe should 2 storey housing, the vent pipe may be
be not less than half the bore of the reduced to 75mm diameter. Each pipe
Discharge stack — Ventilating stack discharge stack. Where offsets are should be fitted with a durable and
Ventilating pipe incorporated, the bends should have a secure domical cage, which is resistant
=3
: t
centreline radius of not less than 2 times
pipe bore, and no discharge branch
to bird nesting and movement by vermin .
Ventilation pipes should terminate
connection should be made to the offset outside the building, positioned where
Wash between the vent connection points. the emission of foul air does not cause a
basin Where offset venting is used, the stack nuisance. This is generally achieved, if
should still be sized as a primary the termination point is not less than
Cleaning ventilated system, unless vent 900mm above the top of any window or
zzJ connections to every storey are included.
671/2° max - - '
Icross-connection as natural ventilation opening if within a
an alternative to the
Offsets above the highest discharge horizontal distance of 3m. Consideration
Single Appliances connection to the WC connection to the stack do not require should also be made in relation to
branch (not preferred) venting or the use of large radius bends. adjacent roof structures likely to cause
Discharge stack — — Ventilating stack Figure 6 Offset venting
r Ventilating
pipe
Wash basin Discharge stack
Branch 67°
l/
Branch fT
l/ Ventilation stack to be :
Cross-connection half discharge stack !
67 V2° max > as an alternative to
the connection to
5)
the WC branch (not No connection to
Multiple Appliances preferred) stack in area
C\ indicated unless
vented
41
Extend to below if required
Direct connection to Connection to discharge branch
discharge stack (75mm branch or bigger )
107
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
wind based fluctuating pressure zones Waste traps Waste disposal units &
and mechanical ventilation inlets.
Every sanitary appliance should be macerators
provided with a trap, either as an integral
Branch discharge pipes serving waste
Stub stacks part of the appliance, or attached directly
disposal units and macerators should be
to the appliance outlet, or fitted in close connected to a discharge stack , stub
Stub stacks may be used as a method to proximity to the appliance . On showers,
connect discharge branches from ground stack, or direct to drain; not to a trapped
for ease of maintenance , a trap may be gully. Only tubular traps should be used,
floor appliances to drain. They are positioned up to 750mm from the outlet.
essentially a short vertical extension from and any bends should be swept (not the
An alternative method to a trap is to use
a 100mm drain, and there are limits on ‘knuckle ’ type). The minimum bore and
the height of branch connections, (see
-
a proprietary valve (see Figures 22 26). gradient of the discharge pipe should be
The purpose of the trap is to provide a
Figure 7). They can be used to connect non - mechanical barrier to prevent the
as recommended by the appliance
the discharge from a group of appliances manufacturer , but in any event not less
escape of foul air into the building , but in
in a bathroom and kitchen, but should be than given in Table 3 and 4 .
addition the water reservoir can act as a
limited to a cumulative load of 5 I/ s. They dilution feature and to intercept small
may be installed either internally or accidentally dropped objects.
outside the building, and should be Washing machines &
terminated with an access cap. If the There are essentially two types of trap;
dishwashers
stub stack is located inside the building , tubular, and bottle. Kitchen sinks and
and it is not possible to comply with the macerators should only be fitted with Branch discharge pipes serving washing
dimensional or flow limitations, then an .
tubular traps Kitchen sinks with two or machines and dishwashers should be
air admittance valve should be used three bowls may be provided with an connected as shown in Figure 8, 9 or 10 .
instead of an access cap. The length of outlet manifold and a single trap. There The minimum bore and gradient of the
the branch drain serving the stub stack should not be more than one trap on the discharge pipe should be as
should be limited as required for correct discharge pipework from any appliance. recommended by the appliance
drainage accessibility, and should be The minimum depth of trap seal for manufacturer, but in any event not less
connected to a drain, which is various applications is given in Table 2. than given in Table 3 and 4 .
adequately ventilated. Resealing traps and anti- vacuum traps
are available where self - siphonage may 25mm ( minimum ) ventilating pipe (to atmosphere )
Access cap above be a problem; some types are noisy in | do not connect to ventilation stack
spill over head i use. — Machine hose
Watertight connection
50mm
''?
I;
' Machine hose
— Air gap
108
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
1. Excluding the ‘connecting bend' fitted directly or close to the trap outlet.
2. If longer than 3m , this may result in noisy discharge, and there will be an increased risk of blockage.
3. Should ideally be as short as possible to limit deposition problems.
4. Swept bends should be used; not ‘knuckle’ bends.
5. For up to 7 people; longer slabs should have more than one outlet .
6. Includes small potato-peeling machines
7. Wash basins must not be fitted with outlet plugs.
109
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
n
u Branch ventilating pipe (if required)
See Table 3 i
50mm pipe to 50mm above spill-over
*
i
^— — level of WC , then reduce to 25mm (min).
l Discharge branch
V-
Appliance Discharge stack
trap Elevation
Discharge stack
b. Trap at 90° to discharge branch having
no vertical drop For maximum length, see Table 3 or 4
« -
Notes *
1. If WC branches are mounted vertically, the maximum drop from the centre of discharge branch must not exceed 1.5m.
Figure 11 Branch limitations for unventilated
2. When back to back WC arrangements are used, WC branches should not be opposing unless they are at 45° or use
branches where no vertical drop is proprietary fittings known to prevent crossflow.
permitted
Figure 14 Combined discharge branch fora group of kVC’s
Prevention of cross flow Prevention of cross flow Figure 15 Example of permitted stack
connection for small diameter
- small diameter pipes - large diameter pipes branch pipes
Opposed small diameter branch
discharge connections to stacks (without
swept entries) should be arranged so
To prevent the discharge from a large
branch ( e.g. WC) from affecting a smaller
opposed discharge branch connection,
m
that risk of the flow from one branch the latter should not be connected to the
affecting another branch is avoided See .
stack within a vertical height of 200mm i-
Figures 15 to 18 . below the larger branch, (see Figure 18). A
Connection
Where this cannot be achieved, a parallel also possible
branch can be used, ( see Figure 16), or in this area
a proprietary ‘Collar Boss ' could be used,
(see Figure 19).
110
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
111
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Where:
Qww = K V DU
^ Congested use, e.g. toilets
and/or showers open to the public 1.0
connect separately to drain (see Figure 5).
For 10 storeys, DU: 6.6 x 10 = 66
= Wastewater flow rate (I/s) Special use, e.g. laboratory 1.2 ^
K = 0.7, so QWW = 0.7 V66 = 5.71/s
K = Frequency of use
Qtot: 5.7 + 0.2 + 0.5 = 6.41/s
Table 7 Maximum capacity of PRIMARY
£DU = Sum of discharge units ventilated discharge stacks There are two options; a 150mm primary
Before the stack selection can be made, ventilated stack, or a 100mm secondary
any other continuous or fixed flow must Min. stack & vent I.D. Litres/sec ventilated stack and 50mm secondary
be added to the Qww value. The 75mm* 2.6 vent. Practical considerations would
following equation explains further; 100mm 5.2 dictate the best choice, for example a
12.4
proprietary fitting such as the collar boss
Qtot = QWW + Qc + Qp 150mm
(see Figure 19) is only available in the
Where: ’ No WC ’s allowed on 75mm stacks 100mm size.
Qtot = Total flowrate (I/s)
Table 8 Maximum capacity of
Qww = Wastewater flowrate (I/s) SECONDARY ventilated Self- sealing waste valves
Qc = Continuous flowrate (I/s) discharge stacks The recent introduction to the plumbing
Min, stack A vent I.D. Litres/sec market of waste valves to replace the
Qp = Pumped flowrate (l/s)
Stack & vent Vent water seal trap offers the installer an
75mm* 50mm 3.4
opportunity to reconsider his system
Once the Qtot value has been obtained, a design, often reducing the amount of
100mm 50mm 7.3
decision about the stack size, and pipework required, whilst still meeting the
150mm 50mm 18.3 mandatory requirement of Building
ventilation principle can be made by
referring to Table 7 and 8. The pipe sizes * No WC's allowed on 75 mm stacks Regulation ADH.1. These valves and
relate to the pipe bores which have their function are described in Figures 22
traditionally been used in the UK. The Example 1 to 26.
theoretical minimum bore for 50, 75, 100 Determine total design flowrate and stack As the name suggests, these valves
and 150 sizes is 44, 75, 96, and 146mm requirements for an 11-storey block of open to allow the flow of water from the
respectively. Both Table 4 and 5 are apartments. The each stack will serve one appliance, or to allow air to enter the
based on ‘swept entry’ equal branches, apartment per floor, comprising of pipework system in the case of negative
which are required in the UK. bathroom, en-suite shower room and fully pressure, then closes automatically when
fitted kitchen. the flow stops or the pipework system
DU per flat: pressure reaches eqilibrium with
Table 5 2 WC’s x 1.7 = 3.4 atmosphere.
Appliance DU (L/S) 2 wash basins x 0.3 = 0.6 This means that a system fitted with
1 bath - 1.3 valves in place of water seal traps would
Wash basin or bidet 0.3 1 shower = 0.4
0.4
be self -ventilating.
Shower without plug 1 kitchen sink = 1.3
Shower with plug 1.3 1 washing machine = 0.6 The valves are designed to open
Single urinal with cistern 0.4 1 dishwasher = 0.2 between 3 and 6mb and will remain
Slab urinal (per person) 0.2
7.8 sealed against 400+mb back pressure.
Assume a primary ventilated stack is
Bath 1.3 adequate; therefore the bottom storey must These valves are particularly useful for
Kitchen sink 1.3 connect separately to drain (see Figure 5). situations where water seals would be
Dishwasher ( household) 0.2 lost by evaporation - for example, holiday
Washing machine (6kg) 0.6
For 10 storeys, £DU: 7.8 x 10 = 78 homes, condensate drains from chillers
Washing machine ( 12kg) 1.2 K = 0.5, SO Qww = 0.5 V78 = 4.421/s and air conditioning units. (See
WC with 61 cistern 1.2 - 1.7 manufacturers' detailed instructions.)
Qc & Qp = zero, so Qtot = 4.421/s
WC with 7.51 cistern 1.4 - 1.8 The valves are available in 32mm (11/4")
From Table 7, a 100mm primary ventilated
WC with 91 cistern 1.6 - 2.0
stack has a limit of 5.21/s, so this size is
and 40mm (11/2") body size, together with
adequate. Secondary ventilation is not 871/2° knuckle elbow and running
The Water Regulations & Byelaws in the UK required. adaptor. Universal compression outlets
do not allow the use of 7.5 or 9 litre WC are used for making connections to either
flushing cisterns on new installations, the push fit BS 5254 or solvent weld BS
Example 2 5255 waste systems.
information is provided for use in connection
with existing systems. Determine total design flowrate and stack
requirements for an 11 -storey hotel. The
stack will serve two en-suite bathrooms on
each floor; there will be air conditioning
units on the roof with a peak discharge of
0.2L/S, and laundry equipment on the 5th
floor with a peak discharge of 0.5l/s.
112
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Standards
As these valves are not covered by
British Standards, it is important that they \
\
1 No 40mm
o V
i
valve
1 No 40mm
bent adaptor
Q Sink
1 No 40mm valve
Bath or shower 1 No 40mm straight adaptor
113
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
114
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
f. Boiling pans should be drained producing few problems on their own, but Types of materials
separately over removable tundishes which, if combined in a common branch
into trapped gullies. The trapped gully discharge pipe, may have a tendency to a. Cast iron
should be fitted with a solid hinged gel or produce an undesirable chemical
b. Copper
flap set flush with the floor and kept effect and therefore will need to be kept
closed when not in use. separate until sufficient dilution has c . Galvanised steel
occurred in the system.
d. ABS ( Acrylonitrile butadiene styrene)
As a general rule it is preferable for each
e. HDPE (High density polyethlene)
laboratory to have its own connection(s)
Laboratory to the main stack(s), and not to combine
wastes by continuous branch discharge
f. MUPVC (Modified unplasticized
polyvinyl chloride)
drainage pipes passing through a number of
laboratories. Obviously this will be easier
g. UPVC (Unplasticized polyvinyl
chloride)
where vertical stack layout has been
General adopted. For most practical purposes,
once the wastes discharge into a main
h. PP (Polypropylene)
115
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
116
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Table 10 Dwellings
Type of dwelling Appliances Number per dwelling Remarics
Dwellings on one level WC 1 for up to 5 persons Except for single persons accommodation,
e.g. bungalows & flats 2 for 6 or more where 1 WC is provided, the WC should be in
a separate compartment. Where 2 WC’s
are provided, 1 may be in the bathroom
Bath/shower 1
Wash basin 1
Sink 1
Dwellings on one or more levels WC 1 for up to 4 persons Except for single persons accommodation,
e.g. houses and maisonettes 2 for 5 or more where 1 WC is provided, the WC should be in
a separate compartment. Where 2 WC’s
are provided, 1 may be in the bathroom.
Bath/shower 1
Wash basin 1
Sink 1
NOTE 1 Where en-suite facilities are provided there should be additional provision of toilets for visitors & staff .
117
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
NOTE 1 Many persons using this type of accommodation may have disabilities therefore the layout of rooms, approaches and accesses should be
capable of being used by disabled persons .
Table 12 Residential homes and nursing homes for elderly people. Type of accommodation
Type of accommodation Appliances Number recommended Remarks
NOTE 1 Where en-suite facilities are provided, toilets for visitors and staff should also be provided .
NOTE 2 Attention is drawn to the Workplace ( health , Safety and Welfare) Regulations.
NOTE 3 Attention is drawn to the Department of Health and Social Security Local Authority Building Note No. 2 and the National Assistance
Regulations 1962.
Sitz baths with hand showers ( not fixed overhead) and/or shower units suitable for use by residents in wheelchairs or sani -chairs, may be suitable
alternatives. The number may vary in different parts of the country.
2
Where residential accommodation is provided for staff, sanitary appliances should be in accordance with table 11
118
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Table 13 Staff toilets in offices, shops, factories and other Table 14 Facilities for customers in shops and
non-domestic premises used as place of work shopping malls
Sanitary appliances for any group of staff Sales area of shop Appliances Male Female
Number of persons Number of WC's Number of washing 1000m2 to 2000m2 wc 1 2
at work stations Urinal 1 Nil
1 to 5 1 1 Wash basin 1 2
6 to 25 2 2 Toilet for disabled people 1
26 to 50 3 3 2001m2 to 4000m2 WC 1 4
51 to 75 4 4 Urinal 2 Nil
76 to 100 5 5 Wash basin 2 4
Above 100 One additional WC and washing station for Toilet for disabled people 1
every unit or fraction of a unit of 25 persons Greater than 4000m2 In proportion to the size of
Alternative scale of provision of sanitary appliances for use the net sales area
by male staff only
NOTE 1 This table of recommendation scale of provision for customers
Number of men at Number of WC’s Number of urinals applies to shops having a net sales area in excess of 1000m2
work
NOTE 2 In this table it has been assumed that the customers will be
1 to 15 1 1 50% male and 50% female. For different proportions the
16 to 30 2 1 accommodation levels will have to be adjusted proportionally.
31 to 45 2
NOTE 3 For shopping malls the sum of the floor areas of the shops
2
should be calculated and used with the above table.
46 to 60 3 2
61 to 75 3 3
76 to 90 4 3
92 to 100 4 4
Above 100 One additional WC for every unit or fraction of
a unit of 50 men provided at least an equal
number of additional urinals are provided.
NOTE 1 Where work activities result in the heavy soiling of hands and
forearms washing stations should be provided for staff as
follows:
1 per 10 people at work (or fraction of 10) up to 50 people
1 additional washing station for every further 20 people (or
fraction of 20)
NOTE 2 For facilities for disabled workers and visitors attention is
drawn to the building regulations
NOTE 3 Where sanitary conveniences provided for staff are also used
by the public the number of conveniences specified should be
increased by at least one, for each sex as necessary to
ensure that staff can use the facilities without undue delay
NOTE 4 In certain situations where security necessitates separate
provision for visitors, this should be sited in or adjacent to the
public area.
119
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Table 15 Schools
Type of school Appliances Number recommended Rematfcs
Special Fittings 1/10 of the number of pupils rounded up to the
next nearest whole number
WC only Girls: all fittings
Urinals and WC Boys: not more than 2/3 of fittings should
be urinals
Wash basin As for secondary school
Shower Although not required by statute, it is
suggested that sufficient showers should
be provided for physical education
Bucket/cleaner's At least one per floor
sink/slop hopper
Primary Fittings Aggregate of 1/10 of the number of pupils
under 5 years old and 1/20 of the number of
others. Not less than 4. Rounded up to the
nearest whole number
WC only Girls: All fittings
Urinal and WC Boys: not more than 2/3 of fittings should
be urinals
Wash basin As for secondary school
Shower Although not required by statute, it is
suggested that sufficient showers should
be provided for physical education
Bucket/cleaner's At least one per floor
sink/slop hopper
Secondary Fittings 1/20 of the number of pupils. Not less than 4.
Rounded up to the nearest whole number
WC only Girls: All fittings
Wash basin 1 in each washroom. At least
2 basins per 3 fittings
Shower As for primary school
Bucket/cleaner's
sink/slop hopper At least one per floor
Nursery and play WC 1 per 10 pupils (not less than 4)
Wash basins 1 perWC
Sink 1 per 40 pupils
Boarding WC 1 per 5 boarding pupils Where sanitary accommodation
for day pupils is accessible to
and suitable for the needs of
boarders, these requirements
may be reduced to such an
extent as may be approved in
each case.
Wash basin 1 per 3 pupils for the first 60 boarding pupils: 1 per 4 pupils for the next 40
boarding pupils; 1 for every additional 5 boarding pupils;
Bath 1 per 10 boarding pupils
Shower May be provided as alternative to not more
^
than 4 of the minimum number of baths
NOTE 1 For the purpose of this table ‘fittings' is the sum of WC's and urinals.
NOTE 2 Attention is drawn to the Workplace ( Health , Safety and Welfare) Regulations 1992.
NOTE 3 Attention is drawn to the need for facilities for the disposal of sanitary dressings.
NOTE 4 For educational establishments not mentioned above, advice should be sought for the Department of Education
NOTE 5 For Scotland attention is drawn to the School Premises (Scotland) Regulations 1967, 1973 and 1979
NOTE 6 For Northern Ireland attention is drawn to the statutory requirements of the Department of Education (Northern Ireland ).
NOTE 7 Attention is drawn to the Education (School Premises ) Regulations, 1981 an 1989, upon which this table is based
NOTE 8 Changing accommodation and showers should be provided for staff engaged in PE where pupils have achieved the age of 8 years.
NOTE 9 Medical accommodation should be provided centrally in all schools, to include a wash basin sited near to a WC. For boarding schools
attention is drawn to the Education (School Premises) Regulations 1981 and 1989.
NOTE 10 For toilets for disabled people attention is drawn to the Department of the Environment Design Note 18 1984 (12)
120
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Table 17 Hotels
Type of accommodation Appliances/facilities Number required Remarks
Hotel with en-suite En-suite 1 per residential guest bedroom Containing bath/shower, WC and wash basin
Accommodation Staff bathroom 1 per 9 residential staff
Bucket/cleaners' sink 1 per 30 bedrooms At least 1 on every floor
Hotels and guest houses WC 1 per 9 guests
without en-suite accommodation Wash basin 1 per bedroom
Bathroom 1 per 9 guests Containing:
Bath/shower, wash basin and additional WC
Bucket/cleaners' sink 1 per floor
Tourist hostels WC 1 per 9 guests
Wash basin 1 per bedroom or 1 for
every 9 guests in a dormitory
Bathroom 1 per 9 guests Containing bath/shower, wash basin and
additional WC
Bucket/cleaners' sink 1 per floor
NOTE 1 For staff toilets attention is drawn to the Workplace ( Health , Safety and Welfare) Regulations 1992.
NOTE 2 Attention is drawn to the necessity to provide facilities for the disposal of sanitary dressings.
NOTE 3 For provision of facilities associated with buildings used for public entertainment, restaurants and licensed bars see Tables 16, 18 and 19.
121
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
NOTE 1 In the absence of more reliable information it should be assumed that the customers will be 50% male and 50% female.
NOTE 2 Attention is drawn to the Workplace (Health , Safety and Welfare) Regulations 1992.
NOTE 3 Attention is drawn to the necessity to provide facilities for the disposal of sanitary dressings.
NOTE 4 For establishments with licensed bars see also Table 19.
NOTE 1 Occupancy should be calculated at the rate of 4 persons per 3m2 of effective drinking area ( EDA)
NOTE 2 In public houses a ratio of 75% male customers to 25% female customers may be assumed. In many other situations a ration of 50%
males and 50% females may be appropriate.
NOTE 3 For provision of toilets for employees and staff see table 13
NOTE 4 Public houses with restaurants should provide facilities as for licensed bars but restaurants should have additional separate toilets in
accordance with table 18.
NOTE 5 Public houses with public music , singing and dancing licences should be as for licensed bars. The licensed area for public music, singing
and dancing should be separated for calculation of occupancy and the provision of toilets should be in accordance with Table 16.
Tables 10- 20 are extracts from BS 6465 Part 1: 1994 reproduced with the kind permission of BSI under licence number 2002SK/0140.
122
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
The design of
building drainage
systems
The scope of this section is to provide
guidance for the design of foul and
surface water systems constructed in the
ground under and around buildings,
together with some general commentary
regarding larger drainage systems
beyond those directly associated with a
building development .
All drainage systems should be designed
to be as simple and direct as possible .
All vertical stacks should terminate with
long radius bends , and changes in
direction and gradient should be
minimised and as easy as practicable .
Access points should be provided only if
blockages could not be cleared without
them , and drain runs between access Figure 27 Rodding Point
points should be laid in straight lines,
both in the horizontal and vertical planes.
However, where it is unavoidable drains Table 21 Maximum spacing of access points
may be laid to slight curves in the Distance to From access From junction From From
horizontal plane, if these can still be fitting or branch inspection manhole
cleared of blockages. All changes in 1 2
gradient should be at an inspection ( m) (m ) ( m) ( m) ( m)
chamber or manhole. The drain soffit Start of external drain 12 12 22 45
should invariably be level, to facilitate Rodding eye 22 22 22 45 45
ventilation of the system, thus minimising Access fitting ( 1 ) min .
the problems associated with foul smells,
150mm x 100mm 12 22 22
gases and the creation of positive and or 159mm dia
negative pressures.
Access fitting ( 2) min. 22 45 45
Historically, installation required that all 225mm x 100mm
manhole branch inverts should be joined Inspection chamber 22 45 22 45 45
level with the horizontal centreline of the Manhole 22 45 45 45 90
main stream drain. However, this is not
1
adjustable top
Top hinged cover
(adjustable)
! rrS
.. I i
li A:
FFL ± ; FFL
•• • Gully &
•
body rr Siphonic bell trap
- Neoprene seal
\ \
\v/
Short make up -
piece
2 No. 45° bends
Tic 100 0
•:
CL drain
100 0 CL
‘ P’ trap
I
v _y/
100 0
u /\
«
CL drain
Traditional Waste Gully Rodding Point system gully
123
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
relevant to one-piece chamber branches drop. In hilly districts it is sometimes manufactured prior to the 1950’s.
or chamber bases that are factory necessary to use ramp drains.
This improvement in standards and
formed. Branches from individual gullies quality allow drain gradients to be
Under storm conditions, the bottom of
and sanitary appliances may be square, the sloping drain may become reduced whilst still maintaining an
but any branch that may run more than a
surcharged causing flood water to issue adequate velocity at the calculated depth
proportional depth of 0.3 (30% full)
from low level gullies and manholes. of flow.
should be connected into the main
stream with a 45 degree baron bend or Here again, flow restrictors and Discharges in branch drains are
3/4 slipper bend, plus a long radius bend temporary retention of flood water at the intermittent and normally start in the form
where necessary to minimise turbulence. top of the ramp/s plus the sealing of low of a short wave, close to the bottom of
level manholes can be used to prevent or the stack or appliance, such as from a
A relatively new development in the
reduce the surface flooding of low lying WC. As the wave travels down the
design of UK drainage systems is the areas, both for new and existing systems. branch drain, the initial vertical discharge
adoption of the ' Rodding Point System’, energy is lost and the depth of flow
which minimises the need for manholes flattens out, this attenuation occurs
or inspection chambers within a building. All drainage systems should be designed because at all normal gradients, the top
Figure 27 shows a ‘traditional’ UK design,
using an appropriate method. For small of the wave travels faster than the water
and the same system designed using the sites and individual buildings long hand in contact with the invert, thus leveling
rodding point principles. Both systems out the flow. Unless there is a continuous
calculations are invariably used.
comply with Building Regulations
However, larger drainage schemes may discharge of water to maintain the
(approved Document H) and BSEN 752 hydraulic depth of flow, it is not possible
be calculated using computer programs
Parts 1 -7, and are designed so that and cross checked by a few long hand to achieve a constant velocity. As the
every aspect of the system is roddable. It
calculations. numbers of discharges from branches
is imprtant when designing a rodding and buildings increase, so does the
point system to ensure that the maximum diversity of use. This, together with an
spacings of access points as given in the
Building Regulations ( Approved
Pipe gradients extended time of travel, creates the
average and peak dry weather flows
Document H) and BSEN 752 Parts 1-7 The maximum flow rate in a drain occurs found in the main public sewers.
are observed, and also that a roddable at a proportional depth of 82 to 83%. Any
gully is used. Table 21 shows the rise in water level above this figure will Table 22 which is taken from the
maximum spacing of access points. cause increased frictional resistance, a Approved Document H to the Building
Figure 28 shows a rodding point system hydraulic jump and a reduced flow rate, Regulations 2002 for England and Wales,
gully against a traditional UK waste gully, which will tend to maintain the full shows a very simple way of sizing a
which is not truly roddable. The rodding surcharge condition. scheme for small drainage systems,
point system gully, commonly known as a provided the maximum capacities are not
syphon bell gully is becoming more The maximum depth of flow for exceeded.
commonly available within the UK from stormwater in estate drainage generally
both European and British should not exceed 75%. This will allow Table 22 Recommended minimum
manufacturers. for changes in site development, the gradients for foul drains
ingress of ground water, and a margin to
All drainage systems should be designed allow the free ventilation of the system Peak Pipe Minimum Maximum
to flow at a constant velocity. Where this and spare capacity for infrequent peak flow size gradient capacity
cannot be achieved, the method of ( litres/sec) (mm) (1 in ...) ( litres/sec )
storms.
dealing with the problem will depend <1 75 1 :40 4.1
upon the capacity of the downstream Gradients and velocities should be kept 1 : 40
100 9.2
receiving sewer under flood conditions. low or reduced over the total length, and
this will tend to increase the drain sizes, >1 75 1 :80 2.8
Some sewers have spare capacity, in 100 1 :80 * 6.3
volume and transitional capacity/storage 150 1 :150« 15.0
which case a gradual rise or fall in the of the system. However, any continuous
system velocity is relatively unimportant. velocity should theoretically not be lower * Minimum of 1 WC
Some sewers surcharge under storm than 0.75m/s to maintain self cleansing. 5 Minimum of 5 WCs
conditions and where this situation There is no practical limit to maximum
occurs, the local authority may require velocity, but it is widely accepted that 3.6 Drainage systems should be designed to
the design and installation of flow metres/second should not be exceeded. provide constant or gradually changing
restrictors and temporary velocities at the design proportional
storage/retention of flood waters. The popular myth of a self cleansing
depth of flow. With the exception of
velocity in foul drains, was arbitrarily set
If it is not possible or economic to backdrops and ramps, all designs should
in the early Victorian era, when the
achieve sufficient storage of storm water avoid marked changes in velocity from
manufacturing standards and quality of
in the drain system, then suitable areas one section of drain to another.
materials was much lower than it is
for surface flooding, ( for surface water today. National standards of Branch drains carrying low volume
drainage only) such as car parks or flood workmanship and supervision had not intermittent flows from individual fittings
plains should be considered. For been established and much drainage and stacks should be laid to steeper
guidance on Sustainable Urban Drainage work was being done for the first time, gradients than main drains that carry the
Systems, refer to CIRIA guidelines. with limited and less accurate hand discharge from multiple stacks and
Wherever possible, steep drain gradients calculated hydraulic formula. buildings. The reasoning behind this
should be avoided. Most difficult site approach is extended as follows:
Modern drain pipes, manufactured from
conditions can be overcome with plastics, vitrified clay and spun iron are 1. Main surface water drains may be
backdrops, allow the horizontal drain to made in long straight lengths. All have laid at a gradient equal to their
flow at an acceptable velocity and the true and smooth bores, which provide a diameter in millimeters e.g. 100%
increased velocity down the backdrop considerable improvement by gradient = 300mm diameter drain
can be attenuated at the bottom of the comparison to their predecessors, laid at a gradient of 1:300.
124
Plumbing Engineering Services Design Guide Sanitary Plumbing and Drainage
125
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Example 1 Step 5
It is estimated that a new housing For other flows in a pipe laid at the gradient
development will produce daily peak foul found in Step ( 4ii) (e.g. 1:110).
sewage flow of 521/sec. Determine the pipe
a. Locate and read along the new O-curve
size and minimum gradient required to (e.g. 101/sec) to the intersection with the
carry this flow whilst ensuring that a
chosen S-curve
velocity of 0.76m/sec is achieved and that a
proportional depth of 0.75 is not exceeded. Read off:
Site conditions dictate that the maximum
grade available is 1:40 and the ground b. Proportional depth (e.g.0.28)
surface falls at 1:240. Confirm that a c. Velocity (e.g. 0.89).
satisfactory velocity is also achieved before
completion of the development when the
NOTES
flow is 10 l/sec. It is recommended that a value of K = 0.6 is
Assume Ks = 1.5mm used when designing stormwater drains and
K = 1.5 is used for foul drains.
Step 1 For a fuller account of the theory, more
Select a design chart by choosing: examples and a range of forty-four different
two colour charts, the reader is referred to the
a. A pipe roughness (e.g. Ks = 1 ,5mm) reference below. Graphs 1 to 5 have been
relevant to this application reproduced by permission of the authors and
publishers; Butler D and Pinkerton B. R.C.
b. A pipe diameter (e.g. D=250mm) which ‘Gravity flow pipe design charts' , Thomas
can carry the design flow (Q) . Q must Telford Limited 1987.
lie within the range of flows on the right
hand side of the chart.
Step 2
Sketch on the limiting factors:
a. Minimum self -cleansing velocity ( V) e.g.
0.76m/sec.
b. Maximum proportional depth of flow
(d/D) e.g. 0.75
c. Maximum available fall (e.g. 1:40)
d. Minimum available fall (e.g. 1:240).
This will define the allowable gradient
‘window’ (shown shaded in Graph 5) within
which all combinations of flow and gradient
satisfy the constraints listed above.
Step 3
Locate the actual design flow Q-curve (e.g.
52 l/sec) and verify that it passes through
the ‘window’. If it does not change the pipe
diameter and go to Step ( 1).
Step 4
Read along the Q-curve and:
a. Note the point where it leaves the
‘window’
b. Locate the gradient S-curve which
intersects it at this point (e.g. 1:110).
This value represents the minimum
gradient at which the pipe can be laid
whilst satisfying the velocity and
proportional depth constraints given in
Step (2).
Also read-off for this flow and grade:
c . Proportional depth (e.g. 0.75)
d. Velocity (e.g. 1.32m/sec).
126
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
127
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
128
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
129
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
130
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
131
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
132
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
I-
on open joints or in a section of slightly years, as tests beyond this period have
non- uniform pipe . not yet been carried out .
Once in place, the annular space However, from the research carried out
between the new liner and the drain has
on these resin materials where they have
to be sealed to prevent movement . This Resin grouting penetrates through been used to stabilise ground water , no
the drain’s cracks and into the deterioration has been found after
is carried out by pumping a weak cement surrounding concrete or soil
grout. periods of 20-30 years.
133
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
134
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Y
No Step 2: Return Period:
r
To selection category and determine return period Is return period know?
—
refer to Figure 34 and Table 24(a) (9) -
I
i Yes
No
Step 3: Is standard storm duration
of 2 minutes applicable?
Yes Y
Step 4: Is time of entry for roof in Yes
excess of 2 minutes?
or y
Is greater precision for
rate of rainfall required? Generally for building roof drainage. The storm
Yes duration coincides with the time of entry, which
No
V should not be in excess of 2 minutes.
Step 5: Rainfall:
Refer to Figure 34 and
Table 24(a)-(9) to
determine design rate of
-
and Table 24(a) (g)
*
To determine storm duration refer to Figure 34
rainfall.
Y
Step 6: Selection Route ‘A’ or ‘B’
depending on type of roof
drainage. ^
Route A
i Route B
Y
Step 13: Refer to gravity flow drain design charts for sizing
of underground drainage or horizontal pipework
135
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Example 1: Route A - flat roof Step 10A Example 2: Route B - valley gutter
A typical spec office block of approximate Select type of outlet Design and size roof drainage for a large
plan dimensions of 50m x 20m sited in For installation reasons a 100mm diameter warehouse with pitched roof and valley
Newcastle. The expected life of the building vertical grated type outlet Type 17B is gutters.
is 40 years and it has been decided to selected. The warehouse is to be located in Swindon
allow for a 60 years period.
Details of this outlet are to be found in and is to be designed for a 40 year building
The Architect has specified a flat roof, Table 25. life, with a high degree of confidence that
asphalt finish with a parapet around the the building will be protected from rainwater
perimeter of the roof. From this Table we can determine the for the duration of its life.
discharge rate in litres per second that the
Step 1: Life of building 40 years chosen outlet is capable of receiving at a The roof construction is to be steeply
given head. So calculating the number of pitched roof with valley gutters.
Step 2: Yes 60 years outlets required to drain the roof of the
building: Step 1
Step 3: Yes 2 min M5
Number of outlets = Life span of building: 40 years
Step 4: No Sensitive warehouse with steeply pitched
Total run-off in litres per second (from step 9) roof and valley gutter.
Step 5: Location of building - Newcastle litres per second discharge per outlet
Step 2
Design rate of rainfall An outlet has been chosen , having a head
of 30mm over the outlet. The roof is Return period. This is not known and has
By reference to the UK rainfall map. Figure
34, we can see that the site of our building protected with an asphalt upstand which is therefore to be determined. Refer to Table
(Newcastle) is adjacent to contour line D. capable of containing at least 60mm head 26.
over the outlet without risk of damage to Return period, T = ‘C’ factor x life of
We now refer to Table 24(d), from which we the building.
can determine that, for a 60 year return building
period with a 2 minute duration rainfall, the 41.66 Selecting category 3 from Table 26.
Therefore number of outlets = l/sec
required design intensity is 150mm per 2.92
hour. ‘C ’ factor is 4.5
Therefore 14 outlets required. Life of building is: 40 years
Step 6/7
Step 11A Therefore T = 4.5 x 40 years
In this example we have an upstand flat
roof with grated rainwater outlets. Therefore Flow rate per outlet is 2.92 litres per = 180 years.
we follow Route ‘A’ through the guide. second ( from Table 25)
Step 3
Step 8A Step 12
Is standard storm duration of 2 minutes
Determine area of roof and flow rate in To determine diameter of rainwater pipes. applicable?
litres per second from the roof. We are We have assumed for the purpose of this
assuming in this example that the area of exercise that there is one outlet per Step 4
roof to be drained is the same as the plan rainwater downpipe. No: storm duration (time of entry) is
area. i.e. no overhangs. Therefore flow down any one pipe is 2.92 required to be 1 minute.
Area of roof A = length x width litres per second.
Step 5
Therefore A = 50m x 20m By reference to Graph 8, it can be seen
that a 100mm diameter pipe flowing 1/5 full To determine the rainfall design intensity:
= 1000m2 (curve A ) is capable of receiving 4.2 litres
Referring to Figure 34, locating the building
per second and is therefore satisfactory. on the map of UK, Swindon lies on contour
Step 9A
F. This corresponds with Table 24( f) and
Total run off from roof in litres per second. Step 13
shows that, for a storm duration of 1 minute
Now from Step 5 we know that the design Horizontal pipework should be sized using with a return period of 180 years, the
intensity is 150mm/hr (0.15m/hr). underground gravity flow charts. design rainfall intensity is 275mm per hour
(0.275m/hr ).
So flow rate = Area x intensity When using high intensities for roof areas
the flow rates should only be carried Step 6/7
(in metres) through to the branch drains immediately
outside drainage system. Type of roof drainage
Therefore,
NOTE Steeply pitched roof with valley gutters,
flow rate = 1000m2 x 0.15m/hr
Flow rates for roof outlets should be follow Route ‘B’ ( trapezoidal Gutter) .
= 150m7hr or 41.66l/sec obtained from manufacturers, as these are
usually higher than the BS standard types Step 8B
listed due to their type of design and Plan area of roof and discharge to gutter.
construction.
Plan area of roof draining into each valley
gutter = 1000m2
Flow rate in litres per second to the gutter:
= area of roof x design rainfall intensity
(Step 3)
= 1000m2 x 0.275 m/hr
= 275m3/hr
136
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
275000
I/hour
Step 11B Design rote of rainfall for
3600 Size of rainwater outlet (and depth of box
= 76 I/s (run-off per second per length of receiver). Having selected a circular un-
varying storm durations and
gutter ) grated outlet refer to Table 28. return periods
Know criteria: The following tables should be used as
Step 9B
1. Flow rate per outlet follows:
Determine number of outlets and discharge = approximately 101/s
in litres per second per outlet: a. Read from Figure 34 the contour
2. Head of water cover outlet to be not reference for the site location.
Number of outlets provisionally determined more than yc or 29mm ( from Step 10) .
by potential stack location (one per outlet). The areas between contour lines on
Referring to Table 28, a 250mm diameter Figure 34 ( which correspond with
Therefore number selected: 8 outlet requires a head of water H of 45mm Tables 24(a)-(g) should not be read
Therefore flow rate per outlet over the outlet to receive a flow rate of as having a blanket coverage of
10.061/s. It is not possible to select a rainfall, but as two extreme rates of
total flow rate stanadard outlet . rainfall that coincide with the contour
number of outlets
A smaller outlet could be chosen by using a lines, having a constant graduation
76 box receiver to give a free discharge, as the from one contour to the other, e.g.
I/s
8 outlet would then be less than three Derby is situated mid-way between
quarters of the width of the sole of the contours E and F, therefore a
= 10 I/s
gutter. judgement must be made between
approximately (5 I/s from each length of Tables 24( e) and (f ).
gutter) Selecting a 150mm diameter outlet, the
head of water over the outlet, H, is 65mm. b. Now read off from the selected table
Step 10B 65 + 25mm = 90mm (minimum depth of the intensity in mm/hr against the
Determine size of gutter: box receiver) required storm duration and return
period.
Known criteria: Plan area of Box receiver would be made
up as follows:
1. Gutter sole to be suitable for foot traffic,
therefore minimum width of sole to be Width = Not less than the width of flow in
300mm. the gutter.
2. Drainage (Length of gutter 7.0 metres) Length = the length of the box for a flow of
(assuming equal outlet centres) . water from one direction should not be less
than (0.75 x depth of gutter) . If the flow of
Now refer to respective nomogram; in this water is from both directions, the length of
exercise we are using trapezoidal gutters the box should be (1.5 x depth of gutter)
with a 1.1 side slope. minimum.
Reading from gutter sizing nomogram, Step 12
Graph 9 where
Sizing of rainwater downpipes.
yc = 29mm (critical depth)
Refer to Graph 7.
yuf = 63mm (depth upstream of gutter
- high point of water ) Know criterion:
Freeboard must be added to yuf; this 1. Flow rate = 10 I/s
should be a minimum of 2/5ths of the A 150mm diameter rainwater downpipe
maximum depth of flow (yuf) subject to a flowing 1/5 full is capable of carrying 10
minimum of 25mm. litres per second.
Therefore freeboard = 25mm (minimum) When using high intensitites for roof areas
So, total depth of gutter is, yuf + freeboard the flow rates should only be carried
through to the branch drains immediately
= 63mm = 25mm outside the building.
= 88mm Design flow rates should be reassessed
Details of roof construction and weathering based on the sensitivity of the underground
might dictate that a greater overall depth of drainage system.
gutter is required.
For added safety overflow pipes or weirs
should be installed at either end of the
gutter as a minimum, preferably between
each pair of outlets.
For the gutter to discharge freely, the outlet
should be ungrated and of not less than
three quarters of the width of the gutter. It
may not be possible to select an outlet to
conform with this, therefore we must
alternatively construct a box receiver at the
outlet. Box receivers should be the width of
the gutter and the depth should not less
than H + 25mm, where H = head of water
over outlet.
137
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
138
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Table 24(b ) Rainfall amount 2mm in 2 minutes, occuring on Table 24( f ) Rainfall amount 4mm in 2 minutes, occuring on
average once in 5 years (2 min M5) average once in 5 years (2 min M5 )
Intensity (mm/hr ) Intensity ( mm/hr)
Duration Duration
( mins) 50mm 75mm 100mm 150mm 225mm ( mins) 50mm 75mm 100mm 150mm 225mm 275mm
1 1.75 7 35 325 4000 1 4 mths 17 mths 1.5 7 50 180
2 2 18 60 850 2 5 mths 8 mths 2 18 110 450
3 4.5 35 175 1800 3 5 mths 1.75 4 35 250 700
4 7 45 350 3000 4 6 mths 1.75 6 40 350 1000
5 8 60 750 4000 5 7 mths 2 7.5 50 650
10 45 450 2500 10 2 yrs 7.5 40 300 3500
Return period ( years) Return period ( years )
Table 24(c) Rainfall amount 2.5mm in 2 minutes, occuring on Table 24(g) Rainfall amount 4.5mm in 2 minutes, occuring on
average once in 5 years (2 min M5) average once in 5 years (2 min M5)
Intensity (mm/hr ) Intensity (mm/hr )
Duration Duration
(mins) 50mm 75mm 100mm 150mm 225mm (mins) 50mm 75mm 100mm 150mm 225mm 275mm 300mm
1 7 mths 3 8 90 1000 1 3 mths 5 mths 2 7 55 190 350
2 1.5 5 20 300 2500 2 3 mths 6 mths 2 7 55 190 750
3 2 7.5 40 500 3 4 mths 1 3 18 120 350 1100
4 3 15 60 800 4 6 mths 1.5 4.5 20 200 450 1600
5 4 20 100 1000 5 6 mths 2 5 38 250 650
10 15 150 700 10 1 yr 6 50 200 1800 1900
Return period (years) Return period ( years)
139
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Outlet type Table in Outlet Area drained at rainfall intensity of 75mm/ti at depth ol water above outlet:
BS416: 1973 size 5mm 10mm 15mm 20mm 25mm 30mm
(mm) ( m2) (m2) (m2) (m2) (m2) (m2)
17C 75 5.4 15 28 43 61 80
Square flat grating 17A 100 0.354 1.021 1.875 2.812 3.958 5.208
Circular flat grating 17B 50.65 0.093 0.250 0.479 0.750 1.062 1.396
Circular flat grating 17B 75, 90,100 0.200 0.562 1.040 1.604 2.187 2.920
D shaped flat grating 17C 65 0.108 0.292 0.562 0.875 1.208 1.604
D- shaped flat grating 17C 75 0.112 0.312 0.583 0.896 1.270 1.667
D- shaped flat grating 17C 90, 100 0.158 0.437 0.812 1.250 1.771 2.292
Circular flat grating 17D 50 0.093 0.250 0.479 0.750 1.062 1.396
Circular fiat grating 17D 75,100 0.148 0.417 0.771 1.187 1.667 2.187
Example
Roof size: 20 x 19.2 m = 384m2
(Refer to Graph 6)
Rainfall intensity = 75mm/hr
100% run off = 8 I/s
140
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
The gutter runs off full length (20m) of the Starting at the bottom right - hand side of the gutter length (10m) and drop into the
building and has one outlet at each end . chart select a gutter breadth ( B), say bottom left - hand section of the nomogram
Half of the water will discharge in each 200mm, follow vertically up the nomogram to the value of the depth ( yu) of 60m
.
direction; ie 4.0 I /s into 10m length of to the flow rate curve of 4.00 I/s. Read off previously established.
gutter. Select the appropriate nomogram for and note value of yu, 60mm . Follow right (horizontally) to the intercept
gutter profile required and range of sizes. Read across to the centre axis noting the with the yuf axis and read off the value at
.
depth (yc) at the outlet Of 32mm Continue yuf . Add freeboard to yuf.
to the left to the curve representing the
141
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Table 27 Flow rates, square/rectangular ungrated gutter outlets (litres per second)
Head of water
over outlet in mm Size of rainwater outlets in mm
H
75 x 75 100 x 75 100 x 100 150 x 100 150 x 150 200 x 150 200 x 200
5 0.14 0.16 0.19 0.23 0.28 0.33 0.37
10 0.40 0.46 0.53 0.66 0.79 0.92 1.05
15 0.73 0.85 0.97 1.21 1.45 1.69 1.94
20 1.12 1.30 1.49 1.86 2.24 2.61 2.98
25 1.56 1.82 2.08 2.60 3.13 3.65 4.17
30 2.05 2.40 2.74 3.42 4.11 4.79 5.48
35 2.59 3.02 3.45 4.31 5.18 6.04 6.90
40 2.96 3.69 4.22 5.27 6.32 7.38 8.43
45 3.14 4.19 5.03 6.29 7.55 8.80 10.06
50 3.31 4.42 5.89 7.37 8.84 10.31 11.79
55 3.48 4.64 6.18 8.50 10.20 11.90 13.60
60 3.63 4.84 6.45 9.68 11.62 13.56 15.49
65 3.78 5.04 6.72 10.08 13.10 15.28 17.47
142
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Table 28 Flow rates, circular ungrated gutter outlets (litres per second)
Head of water
over outlet in mm Size of rainwater outlets in mm
H
75 100 150 200 250
5 0.11 0.15 0.22 0.30 0.37
143
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
144
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
145
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
146
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
147
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
148
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
149
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
Example
If a system is designed on a building 500m
above sea level and the temperature of the
rainwater is taken as 10°C, then the
permitted negative pressure is 0.13 - 9.50
= -9.37m.
The maximum negative pressure must be
considered when selecting the working
pressure of pipework. Whilst the systems
operate well within the pressure range of
copper, steel and cast iron, care must be
taken when specifying plastics.
Manufacturers do not generally publish
negative ratings as pipes are normally used
for positive applications and therefore the
grade of material will have to be confirmed
with the manufacturer.
The ‘velocity break’ is where the full bore
system converts to a conventional gravity
system and is an integral part of the
design. The receiving pipe must be sized
to accept the flow rate (by gravity) that is
Figure 36 Typical storm Hows
discharging from the siphonic system. If
the velocity of the discharge is high then
it may be necessary to introduce an
system is correctly balanced. If the one third full when subjected to an initial collection chamber, to allow the
system has an imbalance then additional 40mm over its design head , velocity to be reduced before discharging
wavy/pulsating flow may occur more could have an increased carrying to the sewer via conventional sized drain
often resulting in a less effective capacity of up to 20%. This is due to the pipework. Typical velocity breaks are
discharge from the roof. Extensive pipe head of water over the outlet being the illustrated in Figures 37 and 38.
systems may take considerably longer to driving force in the system.
fill if not designed correctly. The positioning of the siphon or velocity
With a siphonic system the driving force break is important and it must be
The system will start to discharge under is the difference in height from the water maintained at all times or the calculations
‘siphonic conditions’ with water volumes level over the outlet to the ‘siphonic will be invalidated. If the siphon break is
-
of 50 60% and improve its discharge break’, normally at ground level. surcharged during a storm and the
capacity as water volumes approach Increasing this height by 40mm is working head increased there could be a
100% of the design rainfall intensity. insignificant and would typically result in significant effect upon the system.
an increased capacity of less than 1%. It Connecting directly from full bore
Roof outlets currently available tend to
will therefore often be necessary to rainwater pipework to full flowing drains
cater for nominal flows of 6 l/sec and
provide deeper gutters to store the extends the working head which
.
12 l/sec These flow rates are not fixed
additional rainfall above the design increases the negative pressure in the
and are dependent on the working head figure.
in the system and the head over the upper part of the system . If the negative
outlet . For exceptional storm intensities The design of the system must take into pressure exceeds the designed value the
such as found in Asia, outlets with a account the negative pressures that are possibility of cavitation increases and
capacity of up to 80 litres/ sec are created within the pipework . If the under extreme conditions the pipework
available. maximum permitted negative pressure is can implode. Conversely, connections to
exceeded there is a risk of cavitation and a surcharging drain will result in backing
It is important to ensure the free flow of collapse of plastic pipes. The maximum up in the rainwater pipework and cause
water to all sides of the outlets, on flat permitted negative pressure for a system the system to overload.
roofs they should be located at a
can be calculated as follows: The siphon break will not always be at
minimum distance of 0.5m from vertical
walls and not less than 1.5m from Vapour pressure - atmospheric pressure the bottom of the building as it only
needs to be at a height to generate the
intersecting walls or the end of a gutter. = permitted max. negative pressure required working head, ie to overcome
A check of the required free standing
Atmospheric pressure at different the system resistances. This may only be
head of water over the outlet is one or two storeys down the building.
elevations above sea level
necessary to achieve the maximum The system sections must be designed
discharge capacity as this can vary Elevation within a head loss balance of typically
between different manufcturers . above sea
level ( m )
0 500 1000 1500 2000 2500 400mm between each section to ensure
As with conventional design , it will be all outlets achieve their design flows
necessary to provide an overflow system pa/e (.g ) ( m) 10.09 9.50 8.95 8.45 7.95 7.45 within acceptable limits. A section in a
designed to function when the water system is the run of pipework from each
retained on the roof or in a gutter outlet to the velocity break. ( Figure 39.)
reaches an unacceptable level . This is Vapour pressure at different If this balance is not achieved the system
very important with a siphonic system as temperatures will not function effectively due to
unlike a conventional system there is Temperature 0 5 10 15 20 25 30 increased air entrainment , a reduced
practically no spare capacity above the °C discharge capacity and irregular flow. A
design flow. For example a gravity minimum design velocity of 1 m/s is
system typically running approximately Pa/ e( - 9) ( m) 0.06 0.09 0.13 0.17 0.22 0.32 0.43 required to enable the system to be self
150
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Pipework materials
At present the following materials are
being utilised for the installation of
siphonic systems:
Steel
Copper
Cast Iron
Polyethylene
When choosing the material to be used,
consideration should be given to the
following:
a. Will the material and jointing method
withstand the negative pressure that
the system has been designed to,
plus a safety margin.
b. Due to the reduction of vertical pipes
longer horizontal runs may be
required, provision should be made
to accommodate thermal expansion
Figure 37 Typical ground level velocity breaks and or contraction (in particular, with
the use of plastics).
Siphonic
System design
Siphonic Y Y
pipe
pipe Procedure
i. Calculate area of roof to be drained
Balcony discharging
Y Y less than 1 litre/sec (m 2 )
connects to
conventionally ii. Calculate the flow of rainwater to be
Gravity designed rainwater discharged (I/s)
downpipe
pipe
iii. Has client given any specific design
requirements, if not confirm basis of
Gravity Velocit
design
" 'i- Siphonic rainwater outlets iv. Note the head. Clearly identify the
Combined collection of
installed on different roof levels siphonic and conventional height from the roof outlet to the
rainwater outlets velocity break
v. Fix the position of the roof outlets
and hence the area drained, note the
Figure 38 Typical velocity breaks above ground individual discharges
151
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
152
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
system is suitable for a particular Systems with low volumes would require Vacuum pumps
building. the pumps to constantly be switching on
and off in response to valves opening. The vacuum pumps are required to
For instance it may be an acceptable risk generate the vacuum within the system.
to incorporate a vacuum system within Their second function is to act as a These should be arranged as duty, assist
an office development but not in an art holding tank prior to discharge to the and standby. Their duty cycle should be
gallery where the consequence of failure sewer/discharge system. This is rotated after each operation to yield even
is greater. Each building should be necessary as vacuum systems need to wear on the pumps. The pumps are
considered on it’s own merits and the be pumped to waste, it is not possible to connected via a header to the vacuum
pros and cons considered before any simply open a valve on the vessels and vessels and operate on pressure
system is selected for use. Even then the allow them to empty by gravity. Vacuum, switches to maintain the vacuum in the
designer should consider the form of the and therefore the operational status of system.
roof, a flat roof with internal parapet the system, must be maintained at all
gutters is less secure than a pitched roof times and the opening of a valve on a The vacuum pumps draw the air
with eaves gutter that would purely shed vessel would result in vacuum being lost. contained within the vessels above the
water over the side at times of failure. The provision of vacuum tanks gives the water surface to maintain a vacuum and
designer the opportunity to provide this needs to be expelled to outside.
Components attenuation within the system. This is Although relatively clean water is
where the allowable discharge to the contained in the vessels it may contain
Vacuum systems used for draining water sewer is less than the expected runoff leaf debris which over time will rot and
from roofs and other similar areas from the roofs. As local authority sewers cause odours. The discharge from the
incorporate similar items of equipment to become more congested the vacuum pumps should therefore be
foul drainage systems, including vacuum requirements for attenuating of discharge directed to discharge in a location so as
pumps, vacuum pipework, vacuum become more and more likely. Many not to cause nuisance. Location in
vessels, discharge pumps, actuators and projects within built up areas now require accordance with the building regulations
interface valves. some form of attenuation. The attenuated for vent pipes would be appropriate for
runoff is stored within the vessels whilst such a termination but it should be
Interface valves and actuators the discharge is arranged to release remembered that the discharge is forced
water to the sewer at a controlled rate, by the vacuum pumps and could be
The interface valves are located within
the excess being the volume required to moisture laden, so siting next to surfaces
the box receivers designed as part of the
be stored within the vessels. where it could readily condense such as
gutter system. It is important that some
metal cladding systems may cause
form of box receiver or sump is used in If the required attenuation storage is high staining.
order to ensure that the interface valve, a separate storage vessel should be
when called upon to function, will have a provided to receive the pumped Any moist air within the vent will have a
reasonable quantity of water to discharge from the vacuum vessel. tendency to condense and run to the
discharge. The system will, for lower bottom of the vent during times when the
rates of runoff, remove water from the Local authorities will need to be vacuum pumps are not operating. To
sumps intermittently as they fill up and consulted as to what their limits of remove condensation from the discharge
stop once the sumps are empty. The discharge are likely to be and what level line a small suction line is connected into
actuators which should be located of protection is required. This will be the discharge at its lowest point to suck
remotely from the interface valves in a specified as an allowable discharge in I/s the condensate back into the vessels by
position to aid maintenance, sense the and a return period critical storm to be opening a solenoid valve on the small
rise in water level within the sump/box protected against. The return period will bleed line before the vacuum pumps
receiver and open the interface valve for be given by the local authority and could operate.
a predetermined time, sufficient to be for example 10 years. The duration of
ensure the sump unit/receiver is emptied. the storm that gives the critical Discharge pumps
(maximum) volume of storage will then
have to be calculated. The actual stored Having been filled with the surface water
Vacuum pipework from the roofs, the discharge pumps
volume is dependent on the areas
The vacuum pipework consists of a drained, the limit set by the local empty the contents of the vessels ino the
network of pipes which are routed back authority and the allowable flow to the drainage system or sewer. Vacuum
to the main collecting vessels. These sewer. These calculations balance the pumps used for the discharge of water
pipes are constantly maintained at inflow with the outflow and give a from a vacuum must be designed
vacuum, the level of which is dependant resultant volume required to be stored specifically for this use. Conventional
on the lift required of the system. If a throughout the storm. If allowable pumps are designed to draw water under
system is required to lift rainwater discharges are relatively high then short flooded suction yielding a positive suction
through 2m vertically then the vacuum sharp flash storms can result in peak head. Pumps used on vacuum systems
the system generates must be in excess storage volumes whilst longer storms need to draw water from a vessel that is
of the 2m lift required. require peak storage when allowable at a negative head and raise its pressure
discharges are small. sufficient to overcome the negative head
Vacuum vessels plus any lift involved. It is important when
The calculations required for this type of specifying duties for systems that it is
The vacuum vessels within a surface analysis are complex and require input clear exactly what the pumps need to
water system serve two functions. Initially hydrographs for storm profiles relevant to achieve, to avoid confusion it is worth
they act as vacuum buffers that enable the location of the site and for the stating both the lift the pump is required
the system to function and for the duration of storms likely to yield the to perform as well as the negative head
vacuum pumps to operate. The buffer critical volume, usually between 30 the pumps are to overcome.
allows the vacuum pumps when called minutes and 2 hours duration. These are
upon to operate to do a reasonable most easily assessed using proprietary On start up of the discharge pumps they
amount of work replenishing the vacuum software. must overcome the maintained level of
in the buffers before they need to turn off. vacuum in the vessels. In order to allow
the pumps to discharge efficiently certain
153
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
154
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
155
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
flow of wastewater only or wastewater valve discharges. The reformed slug is so that it will operate as soon as there is
and air into the vacuum drainage system then propelled by the air admitted during sufficient vacuum available.
pipeline. the next discharge.
Typically, when operating a flush button,
Lift: Section of vacuum pipeline with an Once the interface valves have operated, pressurised water is introduced into the
increase in invert level in the direction of the discharge travels to the vacuum bowl through a water valve and a
flow. station, normally located at ground or flushing ring with holes to clean the bowl.
basement level. Air is discharged to Simultaneously the interface valve opens
Reforming Pocket: A low point in the and the pressure differential in the piping
atmosphere only from the vacuum
piping profile installed intentionally to forces the contents through the valve.
station. From the vacuum station, the
produce a controlled slug flow.
wastewater is pumped automatically to Before the interface valve closes, air is
Service Connection: The section of the building outfall connection, to drawn into the pipe. The flush water valve
vacuum pipeline connecting an individual discharge into the external drainage stays open for about two seconds to re-
interface unit to the vacuum main. system by gravity. establish the water pool in the bowl. The
typical water consumption for this timing
Slug: An isolated quantity of wastewater To design a reliable and economic
sequence would be 0.8-1.5 litre per
flowing full bore through the vacuum vacuum drainage system , it is necessary flush. Vacuum toilets may be re-flushed
pipeline. to generate sequentially high
in less than a quarter of the time taken
acceleration and self -cleansing velocities
Vacuum: Any pressure below for a conventional WC to refill, on
with the least amount of energy.
atmospheric. average, a vacuum toilet will take 3
NOTE: seconds to complete a flush cycle.
Vacuum Station: An installation A vacuum drainage system is NOT a reversed
comprising vacuum generator(s), a pressure system where all the water would be
means of discharge, and control accelerated simultaneously.
equipment and which may also Ejector unit
incorporate vacuum vessel/holding
Ejector units are used on small systems,
tank(s). Basic components which require approximately 40m3 of air
A vacuum drainage system may be an hour at peak flow. They have the
advantage of having a lower capital cost,
The vacuum transport considered as comprising four elements:
being small in physical size and with
process a. The automatic interface units ( AIU) fewer working parts than vacuum pumps,
b. The vacuum toilets and are easy to maintain and operate.
An understanding of the vacuum However, they are less power efficient
transport process is helpful to the system c. The pipework than a conventional vacuum station and,
designer. As long as no interface unit is therefore, are more expensive to run. The
operating, little wastewater transport d. The vacuum station.
control of this kind of vacuum station is
takes place. All wastewater remaining in similar to a conventional pumping station.
the vacuum pipework will drain, by Interlace units
These units can also receive discharges
gravity, into the reforming pockets when The valves that form the interface from gravity drainage systems directly
all upstream interface valves are closed. between the vacuum drainage lines and into the tank. However, wastewater
When an interface valve opens, the the appliances can be used directly with containing high levels of detergents may
differential pressure between the vacuum some appliances and with buffer volumes cause foaming problems.
in the system and atmosphere, forces the for others. When used with buffer
wastewater into the vacuum pipework. volumes, level sensors and controllers, Vacuum station
Whilst accelerating, the wastewater is the valves are termed interface units
transformed into foam and soon occupies ( AlUs) . Although AlUs are operated by A vacuum station has three functions:
only part of the vacuum pipe cross air, non-automatic units may use i. Generate vacuum
section so that the momentum transfer electricity to control their operation.
from air to water takes place largely ii. Receive and forward the wastewater
through the action of shear stresses. The They are of various sizes of interface and
magnitude of the propulsive forces starts valve up to about 100mm bore. The
larger valves are used in vacuum iii. Control and monitor the system.
to decline noticeably when the interface
valve closes but remain important as the sewerage systems. Although vacuum stations may be used
admitted air continues to expand. Typically a complete interface unit is with similar systems as the ejector unit,
Eventually, friction and gravity bring to composed of a buffer volume of varying they are used mainly for larger systems,
rest the wastewater at the low points of size, a sensor to sense the wastewater ie greater than 40m3 of air. They are
the pipework system; such as reforming level in the buffer volume, a controller large units with a higher capital cost but
pockets and at the bottom of pipeline which operates a pilot valve to open and typically are cheaper to run than ejectors.
lifts. close a vacuum supply line to the The machinery installed is similar to that
The vacuum drainage system transports interface valve. In many designs of of a conventional wastewater pumping
wastewater by means of atmospheric interface unit, level sensors and station or lift station, and consists of a
pressure acting against vacuum. controllers are combined into one device. collection tank, wastewater forwarding
pumps, vacuum pumps, controls and
When designing systems greater than Vacuum toilets alarms, and where required a standby
100m in length (from the valve to the generator.
vacuum station) , a series of reforming A vacuum toilet uses air instead of water
pockets must be used. These minimise to remove the contents of the bowl, and The vacuum receiver tank size and/or
the break -up of the wastewater slug and is a form of interface valve. Usually, it number of tanks depends on the number
reform that portion of the slug that includes a flushing rim and the toilet’s of appliances connected to the system
remains in the piping between interface controller may have a memory function and the expected frequency of discharge.
Each tank incorporates level switches
156
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
that control the discharge pumps Controls and conduction probes may need to be
automatically, vacuum regulator switches used.
which control the vacuum pumps and
System controls Level detectors, of some form, are fitted
level alarms which can be audible or
to all collection tanks. The signals from
connected to the building management The vacuum drainage system control the six common detectors control the
system. panel contains the main power switch discharge pumps and alarms as follows,
and the pump operating system which in accending order of height from the
Vacuum generating ond includes: magnetic starters, overload base of the tank:
forwarding pumps protection, control circuitry and hours run
meters for each vacuum and forwarding i. Earthing probe, or sensor float switch
Vacuum generating pumps pump. A data recorder may be built into or similar
Vacuum pumps of the liquid ring and this panel, as well as the collection tank ii. Both forwarding pumps stop
sliding vane types are both suitable for level control relays. Alarm and telemetry
use in vacuum drainage systems. Vane systems may also be included if required. iii. Lead forwarding pump start
type vacuum pumps are recommended iv. Assist forwarding pump start
for most projects since they are more Pump controls
efficient, ie they have a greater v. High level alarm
The controls should be designed so that ,
throughput of air and are less vi. High level cut -off - stop vacuum
where stand-by pumps and collection
temperature sensitive than similarly pumps.
powerful liquid ring pumps. tanks are installed, both the vacuum and
forwarding pumps alternate their use and
The maximum vacuum provided by a are interconnected and controlled to
liquid ring pump often will not exceed allow them to be used with either tank Vacuum gauges
-0.8 bar gauge , whilst the maximum automatically. The pump controls will
It is important that all vacuum gauges be
vacuum of a vane pump will typically be include logic controllers that will be specified to indicate gauge pressure and
closer to -1 bar gauge. This will affect connected to the various level and
have stainless steel bourdon tube and
the choice of pumps where vacuum vacuum sensors. The signal to start the
socket.
levels of a greater magnitude than the discharge comes from the high level
normal -0.5 to -0.7 bar gauge operating switch in the collection tank, the stop Vacuum gauges should be provided at
range will be required, or for projects at function is either controlled by a low level the following locations in positions that
high elevations where atmospheric switch or timer. For example, when the can be viewed easily :
pressure is lower. high level sensor indicates to the logic a. the side of the vacuum moisture
A vacuum switch attached to the control that water has risen to the high
removal tank (where fitted)
pipework and adjustable timer are used level, this sequence of operation will
commence: b. the collection tank
to control the vacuum pumps. A second
vacuum switch may control a low vacuum The controller will close automatic c . one gauge on each incoming vacuum
control alarm signal. These switches are valve in balance line, where fitted, main or header.
fitted with stainless steel bellows to and start the forwarding pump It is important that these gauges are
protect against corrosion from any gases
ii. If level does not fall within the pre-set located above the incoming pipes and in
evolving from the wastewater.
time, a second pump will be started a position that is easily viewed from the
or an alarm generated operating position of the isolation valves.
Forwarding pumps
iii. If level reaches the high level alarm
Forwarding pumps are required to sensor, then an alarm is given and
discharge the collected wastewater to the the vacuum system is shut down Combined vacuum generator
external gravity sewerage system. These
pumps are designed to operate with a iv. When the water level has fallen to a and forwarding pump
large pressure differential across them low level sensor or after a pre-set A combined vacuum generator and
with their inlets under vacuum. The size time period, the controller will stop forwarding pump or ‘vacuumarator’ is a
of the forwarding pump is a function of the forwarding pump( s) and open the screw vacuum pump with liquid ring seal
the following: design peak flow, volume to automatic balance line valve, if fitted. with a macerator for breaking up any
be discharged, and the permissible
In systems where only black water is solids passing through it. The macerator
discharge rate for the receiving sewer. being collected it is prudent to use the consists of one rotating knife fixed to the
To enable some forwarding pumps to second forwarding pump as a circulation shaft and one stationary knife fixed to the
work, a vacuum balance line may be pump. This circulates sewage within the suction chamber.
required down stream of the discharge collection tank and breaks up any solids The combined vacuum generator and
pump to reduce the pressure differences which may have formed on the surface of forwarding pump;
across the pump (a balance line is not the wastewater. This operation should be
required with an ejector system) . To programmed into the logic system as the a. generates vacuum
prevent loss of vacuum when the pump first step in the discharge cycle. b. macerates solids
is not discharging, a check valve is
required in the discharge pipework Collection tank level controls c . pumps wastewater in the same
downstream of the connection of the operation.
balance line. Level detectors are available in various
A combined vacuum generator and
forms, some are float switches, others
are fixed probes that may be conductive, forwarding pump can generate vacuum
inductive or capacitative. Where a lot of directly on the pipeline to an appliance
and discharge to a gravity system in the
condensate is being collected, for
example in supermarkets with chiller same operation. Vacuum tanks or
collecting tanks are not required
cabinets, the mineral content of the water
may affect the operation of the system normally. Combined vacuum generators
157
Sanitary plumbing and drainage Plumbing Engineering Services Design Guide
and forwarding pumps can be used for ail Generally, joints should be smooth and v. Required operational level of vacuum
size of systems. The size and number of protrusion free to ensure full flow
vi. Required vacuum generator capacity
combined vacuum generator and conditions.
forwarding pumps to be used depends vii. Required forwarding pump capacity, if
Not all rubber ring pipe joints are suitable
upon the required capacity. Combined utilised
for vacuum systems, the manufacturer
vacuum generators and forwarding
pumps have a small footprint compared
should supply a guarantee along with the viii. Required collecting tank capacity, if
test certification that the products are utilised
to conventional vacuum stations and can
appropriate for vacuum drainage
.
be located in small ducts A combined
applications. ix. Pipe sizes
vacuum generator and forwarding pump
x. Vacuum recovery time.
is more power efficient than an ejector
system, but a large number of combined
vacuum generator and forwarding pumps Design Pipework design
would be more expensive to purchase Vacuum systems are designed to
and run than a comparable vacuum Design requirements operate on two-phase air to liquid flows.
station based system. The system should be designed to The air in the pipework is not, as in a
accept discharges from all appliances conventional horizontal gravity system,
planned to be connected to the system. flowing above the wastewater but is
Check and isolation valves The designer should take into entrained into the wastewater where its
consideration any known possible future expansion propels the wastewater and
A check valve is installed in each vacuum lowers its bulk density. These factors
pump suction line to maintain the additions or modifications to the system
to avoid future installation and operating enable the wastewater to behave more
vacuum in the system. Check valves are like a gas than a liquid and in particular
also fitted on the discharge from a constraints.
flow uphill.
vacuum discharge pump, and often are
fitted on the service connection from an Design criteria The strength of thermoplastics is affected
appliance. In order to design a vacuum drainage by temperature. In industrial installations
system the following basic parameters where high wastewater temperatures are
Isolation valves are fitted to all forwarding anticipated, care must be taken in the
and vacuum pumps to allow their should be determined and obtained:
selection of pipe materials. Wastewater
removal without disrupting the system. i. Service life expectancy temperatures greater than 70°C should
Also they are fitted in strategic locations be notified to the designer, so that the
to enable sections of a system to be ii. Type of building
design can limit, by pipework design and
isolated for service. Isolation valves iii. Number of people the system is to buffer volume sizing, possible boiling due
should be suitable for vacuum use and serve to pressures lower than atmosphere.
may be of the eccentric plug type or
resilient face gate type and have a clean iv. Types, number and location of The pipes are installed in a near
opening of not less than the nominal appliances to be connected horizontal profile, without backfall
diameter of the pipe. Both check and v. Wastewater temperature range (high (0.2-0.5% fall) to a suitably located
isolation valves must be capable of temperature grey water discharges vertical pipe. Once the vertical pipe
withstanding 0.8 bar gauge vacuum, shall be specified concerning (stack) is installed, all horizontal pipes
when open, and a differential pressure of temperature, flow, batch volume and may be connected at each level in the
0.8 bar, when closed on a functioning frequency) building in the void between floor and
system. ceiling, subject to lift height restrictions.
vi. Ambient temperature range within All service connections from the interface
which the system shall operate units could either be lifted to the pipeline
Pipework vii. Minimum vacuum level required to in the ceiling above or dropped through
operate the interface units and the floor to the pipeline below. This
Usually stainless steel and thermoplastic makes installation one floor at a time
vacuum toilets
( ABS, HDPE, PVCu or MDPE) pipes are possible which is particularly valuable in
utilised for the construction of the viii. Air to water ratios required for the building refurbishment.
vacuum pipelines, the selection of interface units
pipeline material is dependent upon its Preferably, connections to horizontal
ix. Air consumption of vacuum toilets pipelines should be arrange so that the
location and the characteristics of the
waste water. All pipes used should be x. Permissible leakage factors. branch pipe enters from the top by way
suitable for vacuum, and the minimum of a Y-fitting. As a minimum it shall
The following parameters are required to connect into the top sector of the vacuum
pressure rating for thermoplastics should calculate the pipe sizes and system majn pipeline contained within the angle
be 10 bar but higher ratings shall be layout. They should be determined by the
used if the pipe has an initial ovality; if 0f ±60° about the vertical axis. Vertical lift
designer and equipment supplier for piping connecting to horizontal pipelines
progressive deformation or long term each system:
loss of strength due to high temperature should enter from the top by way of a Y-
is likely to occur. The velocities of water i. Total wastewater flow fitting. Precautions should be taken, eg
within the pipework and the resulting the use of a check valve suitable for
ii. Vacuum toilet flush frequency vacuum drainage, to prevent filling the
percussive effects at changes of direction
lead to the requirement for such pressure iii. Dynamic losses between the vacuum rise with wastewater by back surges.
rated pipe. Standard manufactured station and the furthest appliance on Horizontal piping connecting to vertical
fittings are used where available; Y each pipeline stacks should enter by way of single Y-
junctions for incoming branches should branches. Multiple connections should be
iv. Static losses between the vacuum at staggered levels where practical.
be 45° and reducers be concentric. station and the furthest appliance on
each pipeline
158
Plumbing Engineering Services Design Guide Sanitary plumbing and drainage
Moinfainabitity
System maintainability affects not only
maintenance costs but also availability.
The following aspects are the minimum
that should be addressed as part of
system design:
i. Fault finding procedures
ii. Access to all interface units, isolation
valves, cleaning eyes, check valves
and other items that need inspection
and/or service
iii. Procedures for removal of interface
units and their temporary effect on
system performance, if any
iv. Maintenance schedules for interface
units in relation to cycle frequency
and endurance
v. Estimated repair or replacement
times of interface units
vi. Maintenance schedule for vacuum
station equipment
vii. Procedures for removal or repair of
vacuum station equipment and their
temporary effects on system
performance, if any
viii. Estimated repair or replacement
times for vacuum station equipment
ix. Precaution routines if system
performance is temporarily lost or
reduced
x. Training of maintenance personnel
xi. Recommended stocking of spare
parts
xii. Estimated cost of maintenance per
year.
159
BLANK
160
Pumps and pumping
Definitions and descriptions 162
Pump types 164
Applications 165
Systems 165
Pump selection 166
Noise 166
Pump installation 166
A guide to sewage submersible pump selection 167
161
Pumps and pumping Plumbing Engineering Services Design Guide
162
Plumbing Engineering Services Design Guide Pumps and pumping
iv. Special care should be taken with Power Static delivery head
installations where two or more
pumps are fed from a common The total amount of energy required to The vertical distance between the
heater. drive a pump or a pumping set. centre-line of the pump and the free
surface of the discharged liquid.
v. Care should also be taken to avoid
places where gas pockets can occur.
See Figure 1 which illustrates good Power and efficiency
and bad practices in suction pipework work done
Static head
layout. Power of a pump =
time (seconds) The pressure exerted by a liquid at rest,
vi. When a by -pass is fitted to a pump to the surface, expressed in terms of
and this has to go back into the Newton x metres vertical head of the liquid.
suction line at some point, a check seconds
must be made to ensure that the
resultant temperature rises (at any force x total head Suction head (positive)
point) do not reduce the Net Positive seconds
This exists if the source of liquid is above
Suction Head available to a point the pump, a condition generally known
where cavitation occurs. _ kg x 9.81 x head
seconds as ‘flooded suction,’ and is the vertical
distance from the centre-line of the pump
up to the free surface of the liquid.
Efficiency 9.81 x litres x head
seconds
Efficiency of a pump is its ability to
perform with the least energy input. Pump power = 9.81 x l/sec x m Suction lift (negative)
This exists if the source of the liquid is
Nm below the pump and is the vertical
Watts
Friction head s distance from the centre-line of the pump
NOTE : up to the free surface of the liquid.
The head is necessary to overcome
resistance to motion in pipes and fittings. 1 kg/s = 1 l /sec
When a fluid (liquid or air) is sucked into
It is of great importance as it may 1 Newton = 1 kg x m/sec2 = force a pump, it is pushed in by the pressure
exceed the static head. of the atmosphere as a result of the
1 Newton = 1 kg x 9.81
pressure of the fluid in the pump being
The total pump head must include the reduced. The pressure of the
Gauge pressure measured pump head, plus all pipe and atmosphere and hence the depth from
fitting resistances plus the velocity head. which a pump will ‘suck’, varies with the
The intensity of pressure exerted by a
Total head = L + Lf + V2 MV 2 altitude above sea-level and with the
pump, recorded by gauge, calibrated
state of the weather (see definition of
above atmospheric pressure. The efficiency of a pump is the ratio of Atmospheric Pressure).
the input power to the brake power. The
brake power is the power absorbed by The suction lift for which a pump is listed
Net positive suction head the pump output. is, unless otherwise stated, the total
suction lift of which the pump is capable
(NPSH) _ output x 100 as the listed speed, assuming normal
Efficiency %
The method of specifying suction Input temperature at normal atmospheric
performance under critical suction pressure, deductions being made for
Input or power to be provided. high altitude and for high temperature
conditions including altitude, high
temperature and high vapour pressure _ output in kW and vapour pressure. The suction lift of a
Input in kW
and the limitations of the pump itself. Efficiency: % pump is also affected by the viscosity of
the liquid, but this should be covered by
Owing to the combined effectiveness of the manufacturers' ratings at stated
the pump and motor, overall efficiencies
NPSH available of about 50% are quite normal for
viscosities.
The absolute pressure of the liquid at the coupled sets. The effect of vapour pressure or
pump entry, less its vapour pressure at permissible suction lift is important,
the pumping temperature. It is an particularly with volatile liquids such as
expression of the installation conditions. Self-priming gasoline, aromatic solvents and most
liquids at elevated temperatures and
When a pump is operating under suction where suction lift is necessary, full details
lift (negative) conditions, self -priming is of the installation should preferably be
NPSH required the characteristic which enables the referred to the supplier for consideration.
The minimum absolute pressure pump to evacuate air from the suction
line, thus creating a vacuum which Where the suction conditions are liable
necessary at the pump entry to maintain to be critical it will be necessary to
the required flow without cavitation. allows the atmospheric pressure to push
the liquid through the suction pipe into calculate NPSH values to ensure correct
the pump. pump selection.
NOTE:
The NPSH required must always be less than
the NPSH available.
163
Pumps and pumping Plumbing Engineering Services Design Guide
a Ti
03 Q-
head
&
53
o
-
o
s
03
C
Jf /
1
_ X3 Flooded suction
Total suction lift S 03
head (positive)
3
|S
I
3 Friction head
suction
Velocity head
164
Plumbing Engineering Services Design Guide Pumps and pumping
Graphl Typical characteristic curves b. Capacity proportional to speed A. Can draw air through
Maximum generated c. Self -priming fittings whilst they might
not leak under pressure.
Peak efficiency. Pump
head, closed valve
position QH curve
should operate as near d. Suitable for viscous liquids ( reduced B. OK on cold systems
this point as possible speeds usually necessary for high
\ with low head
viscosities).
15
AJV. requirements. Modern
system higher head
greater than Hs only
boiler PD (3ft ft).
12 C. Worse than B. Greater
l \ S'
Applications chance of pumping over.
9 Efficiency 60|
; X
1
I
(
V
sz Boiler D
\ Pumped systems or a booster set will be x
1c 6 Power 50 4 required where any one or number of the
- H
45 S 3 following conditions prevail.
3 D. Best position. Energy dissipated through load.
°2
40 P
1. Where there is no piped public water Draw down in expansion pipe will be equal to F/R
1 supply and the only available water is between feed & suction of pump (pipework and
0 at or below ground level. boiler PD). Fittings/valves under pressure.
1 8 TO fir
Capacity (litres/sec) 2. Where the pressure from the public
supply main is insufficient to reach Figure 3 Pump positioning
the highest or most distant draw - off
At the point where the curve intersects point for the whole or part of the day.
the head ordinate, the generated head is 3. Where the available pressure is
at a maximum and corresponds to a no - sufficient for normal domestic and
flow condition. This is often referred to as culinary purposes but is too low for Feed and
the ‘ closed valve pressure ’ and a expansion cistern
other equipment or fittings to the
centrifugal pump should not be left building, e.g. hose reels, fire
operating in this condition for any length hydrants, wash down points, Vent
of time as it will rapidly over -heat due to pipe
showers, process equipment etc. Cold
the horse power at this point being feed
turned effectively into heat energy. 4 . Where the pressure is adequate for
ail the building’s requirements but the
The main characteristics of centrifugal Water Supply Undertaker is not
pumps can broadly be summarised as Pump
prepared to guarantee the pressure Flow
follows: in the foreseeable future . Boiler Heating
a. Capacity varies with head ( see Q/H system
curve) Return
b. Capacity proportional to pump speed Ideal position due to most of circuit being under
c. Head proportional to the square of Systems positive pressure to prevent ingress of air into the
system, causing subsequent damage. Pump over
the pump speed will not occur due to position of open vent and
cold feed making the neutral point on the same
d. Non-self -priming Packaged systems side of the pump.
-
e. Suitable for low viscosity liquids. Most pump manufacturers supply
Figure 4 ideal position
equipment that is prefabricated using all
the components necessary to provide a
Positive displacement system that is factory tested to a proven
supplied separately and the installer is
required to connect the pumps, vessels,
performance. Package systems reduce
Positive pumps usually consist of a the amount of site work and ensure that
valves and control equipment into an
casing containing gears, vanes, pistons, operational system .
lobes, screws, sliding- shoes etc . the arrangement of all components can
be adequately maintained . Although satisfactory systems can be
operating with minimum clearance, the
arranged, there are a number of
liquid being positively transferred from It is usual for package units to be
disadvantages. When properly costed, it
suction to discharge port. Due to fine positioned on a prepared base; only final
clearances involved, most positive connections to the suction and discharge is often found that this method of
providing a pumping system is expensive
pumps are self-priming and some will pipework and connection of the
and the responsibility for resolving
handle entrained gas or air. Neglecting -
electricity supply to the pre wired integral
problems is impossible to apportion
leakage , they deliver almost constant control panel is required on site.
between the pump manufacturer ,
capacity irrespective of variations in head
ancillary equipment supplier and the
so that the usual Q/H curve when drawn installer. There may also be over design
for a typical positive -displacement pump Unpackaged component of some systems due to the ‘ ad hoc’
is an almost vertical straight line. For this
reason it is not usual to provide Q/H systems selection of various components.
curves for positive pumps. It is sometimes necessary to design and
Their main characteristics are as follows: install separate items of pumping
equipment and controls to form a system
a. Capacity substantially independent of on site. The collection of items are all
head
165
Pumps and pumping Plumbing Engineering Services Design Guide
displacement pumps, the past few years connections are fitted to the suction and
Pump selection have seen a rapid growth in the number discharge flanges of the pump set to
of specialised designs available for minimise the possibility of vibrations
Between 90 and 95 per cent of the particular applications. It is therefore being transmitted to the structure
world’s pumping is carried out using advisable for pump manufacturers to be through the pipework and to prevent
centrifugal pumps and wherever the approached during the early stages of undue strain on the flanges.
conditions are suitable, a centrifugal installation layout and design for their
These simple precautions are normally
pump is normally the simplest and most recommendations.
sufficient to produce satisfactory results
economical type available. but where exceptionally quiet operation
For installations operating under flooded is essential for a very specialised
application it may be necessary to take
suction conditions, i.e. with a positive
suction head, or where large volumes of
water have to be moved at relatively low
Noise additional precautions and such cases
should be referred to companies who
heads, then the centrifugal pump is the specialise in noise suppression.
.
natural choice Many special types have Noise can be very simply defined as
been developed, including multi-stage unwanted sound. It is generally accepted
designs in which a number of impellers as an irritant which can affect our mental
and physical state and its effect can be
are assembled from a common shaft
with the pumped liquid being delivered to particularly significant in the relatively Pump installation
each impeller. Multi-stage pumps may be quiet environment of the office, domestic
of horizontal or vertical design, the latter and hospital buildings.
It is most important that pumps are
having the advantage of requiring Noise transmission associated with correctly installed and the following notes
appreciably less floor space. pumping systems falls into three main are intended as a general guide.
For water boosting services where categories, airborne noise, water borne
relatively small capacities are required at noise and noise transmitted through the
fairly high heads, vertical multi-stage actual structure of a building. Careful Location
centrifugal pumps have been developed. selection of equipment is most important
to ensure that noise generation is kept to The pump should be in an accessible
These have small diameter impellers location and there must be room for
having a low tip velocity, one of the an absolute minimum.
dismantling and maintenance. It is
factors contributing to the quiet operation Airborne noise is not normally a normally advisable to raise the pump
which is so often essential for this class particularly serious problem with above floor level so that it is more
of application, particularly in residential pumping equipment and its effects can accessible and can be easily drained.
premises and hospitals. Where viscous be minimised by careful siting of the
liquids are to be pumped or where self - plant room in relation to working or living
priming with good suction function areas and by the use of sound insulating Piping
performance is essential, a positive- materials on the walls and ceiling of the
displacement pump would be the first plant room. The size and suction of delivery pipes
choice. With some applications however, should be carefully calculated and
it is necessary for the pump to operate Water borne noise may be more of a should in any case not be smaller than
for periods with a completely dry suction problem as it carries through the the pump connections. For long runs of
and one specialised type, the sliding pipework to any part of the building and piping or when handling viscous liquid
shoe design, is capable of handling this the most effective way of dealing with it they should generally be larger than the
condition for reasonable periods without therefore is to prevent it at source as far pump connection. For other than very
harm. Such a dry suction condition could as possible, rather than to suppress it. simple runs, the actual pipe losses
arise with recirculation systems where Particular attention should be paid to should be calculated so as to check the
the suction source may be starved for pipe sizing and layout to keep water total head on the pump. It is quite
periods due to cyclical or abnormal velocities low and avoid turbulence and common for the friction head to exceed
operating conditions, with sump pumps pipework should be securely anchored to the static liquid.
emptying engine-room bilges aboard prevent vibration. Where risers pass
ship and similar duties. through floors they should not be grouted Piping should be accurately cut and fitted
in but supported by soft packing so that it can be bolted up to the pump
With the growing interest in pollution materials and where pipework is clipped branches without putting any strain on
control, there is an increasing interest in to walls, ceilings etc. pipe clips should the pump or pipe joints. Easy bends
pumps suitable for handling oily water preferably be insulated with rubber, felt should be used and sharp elbows and
without excessive emulsification so that or similar absorbent material. While it is tees avoided. Particular care must be
the liquid can be handled efficiently by generally considered that 1440rpm taken that all joints in the suction line are
conventional oil/water separators and the pumps are inherently quieter than absolutely tight to avoid loss of capacity
sliding-shoe design, for example, 2900rpm pumps, modern vertical multi- or difficulty in priming due to airleaks. In
operating at reduced speed, has proved stage pumps with small diameter the case of non-self priming centrifugal
very suitable for this application. impellers having a low top speed pumps, the suction pipe should slope up
Centrifugal pumps are generally operating at 2900rpm have proved to be towards the pump suction to avoid the
extremely quiet in operation. possibility of trapping air in the top of the
considered unsuitable as they churn the
suction piping.
liquid excessively and the oil/water Noise can be transmitted to the structure
separators are unable to handle the of the building through the foundations of
resultant emulsification. the pump and in certain instances it may
Although these notes on pump types be desirable to mount the pump sets on
have referred briefly to the main resilient mats or anti- vibration mountings
characteristics of centrifugal and positive in which case it is essential that flexible
166
Plumbing Engineering Services Design Guide Pumps and pumping
167
Pumps and pumping Plumbing Engineering Services Design Guide
Calculations
Most of the calculations related to pumps
have been covered in other parts of this
guide and they apply to submersibles
just the same. However viscosity and
solids content are of major importance to
our pump selection.
Heavy sludge may be some 3% solids in
suspension, this will increase the specific
gravity of the liquid and so must be
allowed for. Viscosity will vary depending
upon the nature of the liquid.
Domestic sewage is 1% approximately
solids. Use of a chopper or vortex
impeller type pump is your choice.
When pumping the solids (1-2%) through
horizontal pipework there is a need to
keep the liquid velocity to at least 1.5
metres per second or more, failure to do
so will allow the solids to settle out in the
pipe and may cause a blockage after a
period of time. Similarly to pump the
liquid vertically the velocity should be
increased to 2.5 metres per second,
failure to do so will result in solids falling
back down the pipe, with a blockage
shortly to follow.
The following question check list should
be answered before selecting a pumping
system:
1. What is the liquid to be pumped?
Sewage, storm water, dirty water.
2. What is the quantity to be pumped in
what time?
168
\
K
Fire protection
services
Principal causes of fires in buildings 170
Classification of fire risks 170
Residential/domestic fire sprinkler systems 170
Components 170
Pipework installation 171
Hose reel installations 174
Wet risers 175
Dry risers 176
Foam systems 177
Types of system 178
169
Fire protection services Plumbing Engineering Services Design Guide
170
Plumbing Engineering Services Design Guide Fire protection services
rating should be within the range of 79°C accordance with ISO 7- 1: 1982 and ISO
to 100°C. 65: 1981 and BS 21. Pipework
Sprinklers should be installed in
accordance with their approval listing
The nominal size of sprinklers should be
one of those shown in Table 2. installation
specification and supplier/
manufacturer’s instructions. Only new Pipework
equipment should be used. Any sprinkler Table 2 Sprinkler head orifice and pipe
head removed from a system should be thread sizes All pipework should be installed in the
discarded. Sprinkler heads should only same way as other water services, as
Nominal diameter Nominal pipe described in BS 6700.
be fitted by qualified installers. of orifice thread size
When using residential/domestic ( mm) ( inch) Pipes and fittings should either comply
with the appropriate standards of Table 3
sprinkler heads the system should be
capable of providing flow rates in
accordance with the manufacturer’s
10
15 and 20 *
1
/2
8
or for plastic and other pipe and fittings
suitable for residential and domestic
20 3/4
recommendations, based on the result of sprinkler systems, be installed in
the component performance test, or the accordance with the manufacturers’
flow rates required for conventional instructions and the approval and listing
sprinkler heads, see DD251. Valves and alarm devices requirements of an independent third
party certification body.
If conventional sprinkler heads are to be Valves and alarm devices suitable for
used the flow rate at the sprinkler head residential and domestic systems should
be installed in accordance with
should be not less than 60 l/min for single
head operation and 42 l/min for each of manufacturers’ instructions and should
Pipework support
two heads operating simultaneously in be manufactured to the appropriate Only metallic pipe fixings should be
domestic properties and for each of four British Standards, where applicable. used. Batons and lock type clips should
heads operating simultaneously in The sprinkler system should have: be fitted in close proximity to the
residential properties. sprinkler heads to ensure no movement
a. A backflow prevention valve to is allowed which may recoil heads into
Sprinklers should be positioned such that prevent mains water contamination. the ceiling or loft voids. Sprinkler system
they are not more than 4m apart nor are pipework should be supported at the
they more than 2m from any wall or b. A stop valve, of the full bore lever
type to isolate sprinkler pipework intervals given in Tables 4, 5, and 6.
partition. The distance between
sprinklers within a room should not be from mains water supply. The valve
less than 2m. DD251 recommends that should be locked in the open position
the maximum area protected by a single to prevent accidental interruption of Pipe sizing
sprinkler be 15m2. the water supply to the sprinkler (Hydraulic calculations)
system.
Sprinklers should be positioned so that: All pipework downstream of the alarm
c. And, where appropriate, a priority valve should be sized by hydraulic
a. They are in accordance with the demand valve.
manufacturer’s instructions identified calculation; calculation of pressure losses
in the approval listing. d. An alarm test valve: a test facility throughout the system.
should be provided at the end of the The difference in static pressure between
b. Their sensitivity and discharge hydraulically most remote range pipe
pattern are not adversely affected by two connected points in a sprinkler
on the system consisting of not less system is given by the following formula:
obstructions such as constructional than a 22mm nominal diameter pipe
beams or light fittings or other and quick acting test valve with an Static pressure difference, p = 0.1 h (bar)
sprinkler heads. outlet nozzle equivalent in size to the where h is the vertical distance between
c . The potential for a shielded fire to smallest sprinkler in the system. the two points (in m).
develop is taken into account. e. A drain and test valve should be fitted The pressure loss due to pipe friction
d. The heat sensitive elements are at the lowest point of the sprinkler should be calculated from the Hazen-
within 25 to 100mm below the ceiling pipework to allow testing and the Williams formula.
for ceiling mounted sprinklers. complete draining of the sprinkler 6.05 x 105
system , consisting of not less than a p= x L X a1 - 85
e. The heat sensitive elements are 22mm nominal diameter pipe and C185 x d4 07
within 100 to 150mm below the quick acting test valve with an outlet where p = pressure loss in pipe (bar)
ceiling for wall mounted sprinklers. nozzle equivalent in size to the
smallest sprinkler in the system. Q= flow rate through pipe
f. The whole of the floor area and the (litres/min)
walls from the floor up to 0.7m below f. An air bleed valve fitted to the highest
the ceiling are wetted when the point/s of the sprinkler system to d = mean bore of pipe (mm)
sprinklers are operated. allow the purging of air from the L = equivalent length of straight
system. pipe, bends and fittings (m)
NOTE concealed sprinklers may be
considered with the approval of the authority g. A water flow alarm for detecting water C = a constant for pipe material
having jurisdiction. flow into the system and sounding an (see Table 7)
alarm.
For flow rates of 60 l/min the following
The minimum operating pressure at any h. A mechanically driven alarm or an tables give the appropriate pressure
sprinkler should not be less than 0.5 bar. electrically operated flow switch losses per metre of pipe.
Sprinklers should be threaded suitable which, when triggered by the flow of
for use with fittings threaded in water in the sprinkler system, will
operate an audio- visual alarm.
171
Fire protection services Plumbing Engineering Services Design Guide
172
Plumbing Engineering Services Design Guide Fire protection services
Table 12 Copper - equivalent lengths of pipe for fittings ( in m of pipe) e. An inspection and routine checking
Fitting Nominal diameter ( mm) program for the system. The program
22 28
should include instructions on the
35 42 54
actions to be taken in respect of
Tee run 0.068 0.10 0.13 0.16 0.22 operation of the system, faults, etc.
Tee branch 1.00 1.40 1.80 2.30 3.10
f. A list of components used, identifying
90° capillary elbow 0.49 0.68 0.91 1.10 1.70 manufacturer’s name and parts
90° compression elbow 0.74 1.00 1.30 1.50 2.10 reference number.
g. A 24 hour emergency telephone
number which can be used to obtain
Table 13 Steel - equivalent lengths of pipe for fittings (in m of pipe)
assistance.
Fitting Nominal diameter ( mm)
h. A Log Book containing inspection,
20 25 32 40 50 65
checking and maintenance
90° screwed elbow 0.63 0.77 1.04 1.22 1.46 1.89 documents, detailing a regular
90° welded elbow 0.30 0.36 0.49 0.56 0.69 0.88 program to be undertaken by an
45° screwed elbow 0.34 0.40 0.55 0.66 0.76 1.02 approved contractor.
Standard screwed tee or cross 1.25 1.54 2.13 2.44 2.91 3.81 i. Essential information for the user e.g.
‘do not paint , cover or in any way
impede the operation of a sprinkler
Table 14 CPVC - equivalent lengths of pipe for fittings ( in m of pipe) head’.
Fitting Nominal diameter ( mm) It is recommended that a number of
20 25 32 40 50 65 80 spare sprinkler heads be left at the site
Tee run 0.30 0.30 0.30 0.30 0.30 0.60 0.60 of the installation to replace activated, or
Tee branch
damaged, sprinkler heads. Heads should
0.90 1.50 1.80 2.40 3.00 3.60 4.50
only be replaced by qualified installers.
90° elbow 2.10 2.10 2.40 2.70 3.30 3.60 3.90
45° elbow 0.30 0.30 0.60 0.60 0.60 0.90 1.20
Coupling 0.30 0.30 0.30 0.30 0.30 0.60 0.60 Logbook
A logbook should be handed over on
completion of the system commissioning.
Commissioning When all the commissioning tests have
been passed the installer should sign a This logbook should give details of:
On completion of the installation the Certificate to indicate that the system a. The date of inspection
pipework needs to be tested; leakage has been designed and installed
and hydraulic tests need to be carried following the guidance set out in DD251. b. Details of all tests conducted and
out. A small quantity of air should be left their results
in the system at the end of the purging c. Details of any remedial action taken
process. Documentation d. Confirmation or otherwise of the
With the pipework filled with water at the For new and extended systems all sprinkler systems operational status
normal working pressure for the system drawings and documents should bear:
any leaks should be found and repaired. e. Confirmation or otherwise of the
The water supply to the system should a. The address and location of the alarm systems operational status
then be isolated and the system should premises
f. Details of any recommendations or
be tested to a minimum of 1.5 times b. The name and address of the comments.
working pressure for one hour. If the installer
system fails to maintain pressure the leak
c. The name of the designer
should be found and corrected and this
test repeated.
Maintenance
d. The date of installation.
It is the property owner’s responsibility to
The sprinkler system should be tested to On completion of the installation, the ensure that a regular inspection and
ensure that at least the required flow rate installer should provide the following testing program is in place. The person
can be achieved at the required pressure information to the owner or occupier: carrying out the inspection should
at the alarm test valve. If this flow rate at
a. Details of the authorities consulted complete and sign the logbook
the required pressure cannot be
and any response to consultation. accordingly.
achieved, the system should not be
approved for use until the system has b. A general specification of the system The sprinkler system should be subject
been corrected and the test specified in and a statement of compliance with to an annual inspection and test by a
this clause has been passed. The the guidance given in DD251. qualified installer to ensure that the
installer and the designer should be sprinklers' heat sensing capacity and
responsible for correcting the system. c. A layout of the sprinklered premises their spray pattern is not impeded; the
showing the extent of the installation. minimum flow rates are achieved at the
The alarm (and/or repeaters) should be
d. Details of the water supplies which, if drain and test valve; the alarm is effective
heard in all habitable rooms in the
a town main, should include and that the system has not been
premises protected by sprinklers coupled
pressure/flow rate data at a specified modified, unless by a qualified
to the alarm device being tested. The
location for the commissioned designer/installer.
stated audibility should be achieved
when there is a water flow of not more installation, with the time and date of The person carrying out the inspection
than 60 litres/minute through the alarm the test. should test the system by visually
device under test. inspecting for leaks wherever possible.
173
Fire protection services Plumbing Engineering Services Design Guide
Should a leak be suspected the pipework the building usually on the columns or Discharge from jets
should be pressure tested to 1.5 times stanchions but care must be taken to
working pressure for 1 hour. The alarms ensure that they can be used safely in Quantity = Velocity x area
should be activated so that their .
the event of fire q = Cd x V x A x 1000
satisfactory operation can be audibly
verified. The sprinkler system should be Putting Cd = 0.96 - co-efficient of
flow tested for 1 minute at the drain and IVpes of hose reel discharge
test valve, or the highest test point of the H in m
installation pipework, to ensure that the There are two basic types of hose reel,
system flow rate requirements are met. fixed or swinging. The fixed type of reel d in mm
Stop valves should be exercised to should normally have its centre line at V in m/s = V2gH
ensure free movement. Where trace least 1.5m above the floor. A swinging
heating is installed, its effective operation type hose reel can be swung through q in litres/sec
should be checked. 180° and be mounted at any convenient
height, the average being 900mm to
1.05m above the floor.
Hose reels are normally fitted with 20mm
q = 0.96 x V2gH x - x - x 103
In office blocks especially the multi-storey Table 15 Height of jet (max ) in metres
type, the hose reels must be fitted inside Head on Diameter of orifice in millimetres
the actual office accommodation which jet in metres 3.2 6.3 9.5 12.7 16.8 19.0 25.4
as a general rule means that they are
3.0 2.67 2.86 2.93 2.97 2.99 3.00
fitted adjacent to the fire exit doors into
the lift or stair lobbies. This enables the 6.0 4.57 5.33 5.59 5.72 5.79 5.85 5.91
hose reel to be used without opening the 9.0 5.79 7.44 8.00 8.29 8.46 8.63 8.72
smoke stop doors thus preventing the 12.0 6.10 9.14 10.15 10.67 10.97 11.28 11.43
lobby from being filled with smoke. In
15.2 10.49 12.07 12.86 13.41 13.72 14.05
industrial premises, it is not always
possible to site hose reels adjacent to 18.3 11.43 13.72 14.84 15.54 15.83 16.50
the fire exits owing to the fact that the 21.3 12.19 16.15 18.29 19.51 20.42 21.34
width of the building would prevent the 24.4 12.19 16.15 18.29 19.51 20.42 21.34
hose from reaching a fire in the centre. In
27.4 17.07 19.81 21.34 22.25 23.47
these circumstances it is necessary to
position the hose reels in the centre of 30.4 17.68 21.03 23.86 24.08 25.60
174
Plumbing Engineering Services Design Guide Fire protection services
diameter with a 25mm by 20mm Special provision in respect addition, an electrical alarm bell is
reducing elbow at the bottom, the feed provided to run ail the time the pump is
pipe to the reel being 20mm diameter. of pump supplies running and thus provide a remote
warning of system operation.
Care should be exercised in positioning
— Hose reel
hose reels on drinking water systems
that a sufficient flow of water passes
along the pipework (oversized to meet 3
Riser
? Automatic 'On' and 'Off 7
Riser
Isolation valve
Site boundary
Isolating
also provided in the pump delivery line to
ensure that the pump continues to run all
the time there is a flow of water through
175
Fire protection services Plumbing Engineering Services Design Guide
176
Ptumbing Engineering Services Design Guide Fire protection services
177
Fire protection services Plumbing Engineering Services Design Guide
Foam inlets
Rooms which contain oil fired boilers, oil
storage tanks, oil filled electrical
equipment or other materials or
apparatus for which foam is a suitable
extinguishing medium may be fitted with
pourers so placed that a foam blanket
can be formed over the equipment and
floor of the room. Pipework from the
178
Steam and
condensate
9
Introduction 180
Steam tables 180
Design considerations 180
Steam and condensate traps 186
Steam separators 187
Strainers 187
Steam trap checking 187
Air venting 187
Reduction of heat losses 187
Allowance for expansion 188
Condensate return 189
Handling condensate 190
179
Steam and condensate Plumbing Engineering Services Design Guide
180
Plumbing Engineering Services Design Guide Steam and condensate
181
Steam and condensate Plumbing Engineering Services Design Guide
182
Plumbing Engineering Services Design Guide Steam and condensate
F
15mm
1/2" 3/4- r - 1/4" ,
20mm 25mm 32mm 40mm 50mm 65mm 80mm 100mm 125mm 150mm 175mm 200mm 225mm 250mm 300mm
w
r 21/2" 3" 4" 5" 6" 7" 8" 9" 10" 12"
0.00016 a 30.40 55.41 90.72 199.1 360.4 598.2 890.0 1275 1755 2329 3800
v 4.30 4.86 5.55 6.82 7.90 9.16 10.05 10.94 11.94 12.77 14.54
0.00020 a 16.18 34.32 62.77 103.0 225.6 407.0 662.0 1005 1437 1966 2623 4276
v 3.96 4.85 5.51 6.31 7.72 8.92 10.13 11.34 12.33 13.37 14.38 16.36
0.00025 a 10.84 17.92 38.19 69.31 113.2 249.9 450.3 Tsnr 1008 1678 2183 2904 4715
v 3.74 4.39 5.40 6.08 6.92 8.56 9.87 11.26 12.5 14.40 14.85 15.92 18.04
0.00030 a 11.95 19.31 41.83 75.85 124.1 271.2 491.9 804.5 1209 1733 2390 3172 5149
v 413 4.73 5.92 6.65 7.60 9.29 10.79 12.31 13.65 14.87 16.26 17.39 19.7
0.00035 a 6.86 12.44 20.59 43.76 80.24 130.0 285.3 519.2 845.3 1279 1823 2497 3346 5406
v 3.88 4.30 5.04 6.21 7.04 7.96 9.77 11.38 12.94 14.44 15.64 17.00 18.34 20.69
0.00045 a 3.62 7.94 14.56 23.39 50.75 92.68 150.9 333.2 604.6 979.7 1478 2118 2913 3884 6267
v 3.54 4.49 5.03 5.73 7.18 8.13 9.24 11.42 13.26 15.00 16.68 18.18 19.82 21.29 23.99
0.00055 a TB4 835 164 8 2612 5719 1031 V70l 3374 6747 1101 1663 2382 3281 4338 7057
v 3.96 5.09 5.59 6.49 8.08 9.10 10.46 12.78 14.78 16.85 18.22 20.44 22.32 23.78 27.01
0.00065 a 4.46 9.56 17.76 29.14 62.38 113.8 186.7 409.8 739.9 1207 1823 2595 3597 4781 7741
v 4.37 5.41 6.13 7.14 8.82 9.98 11.43 14 04 16.22 18.48 20.58 22.27 24.47 26.21 29.62
0.00075 a 4.87 10.57 19.31 31.72 68.04 124.1 203.2 445.9 804.5 1315 1977 2836 3908 5172 8367
v 4.77 5.98 6.67 7.77 9.62 10.88 12.44 15.28 17.64 20.13 22.32 24.34 26.59 28.35 32.02
0.00085 a 5.52 11.98 21.88 35.95 77.11 104.7 230.2 505.4 911.8 1490 2240 3215 4429 5861 9482
v 5.41 6.78 7.56 8.80 10.91 12.34 14.09 17.32 19.99 22.81 25.29 27.59 30.13 32.13 36.29
0.00100 a 1.96 5.84 1275 SIB 3515 8715 1481 2451 5351 5681 7575 2403 3383 4707 6228 75052
v 4.10 5 72 7.21 8.12 9.37 11.58 13.03 15.01 18.48 21.24 24.17 27 13 29.03 32.02 34.14 38.47
0.00125 a 2.10 6.26 13.57 24.96 40.72 87.57 159.8 261.8 577.9 1038 1699 2544 3634 5035 6655 10639
v 4.39 6.13 7.68 8.62 9.97 12.39 14.02 16.03 19.80 22.76 26.01 28.72 31.19 34,26 36.48 40.71
0.00150 a 2.39 7.35 15.17 28.04 45.97 98.84 179.3 295.1 652.8 1172 1908 2896 4091 5631 7493 11999
v 5.00 7.20 8.58 9.68 11.26 13.98 15.72 18.07 22.37 25.70 29.21 32.69 35.11 38.31 41.08 45.92
0.00175 a 2.48 7.51 16.30 29.61 49.34 103.4 188.8 311.1 686.5 1270 2017 3046 4291 5921 7852 13087
v 5.19 7.36 9.22 10.23 12.08 14.63 16.56 19.05 23.52 27.85 30.88 34.39 36.83 40.28 43.04 50.08
0.0020 a 2.84 8.58 18.63 33.83 56.39 118.2 215.8 355.5 784.6 1451. 2305 3482 4904 6767 8974 14956
v 5.94 8.40 10.54 11.68 M.81 16.72 18.93 21.77 26 88 31.82 35.28 39.31 42.09 46.04 49.19 57.24
0.0025 a 3.16 9.48 20.75 37.25 61.30 132.0 240.5 391.3 881.7 1556 2546 3819 5422 7544 10090 16503
v 6.61 9.29 11.74 12.86 15.01 18.67 21.09 23.96 30.21 34,12 38.97 43.11 46.53 51.33 55.31 63.16
0.0030 a 3.44 10.34 22.5 40.45 66.66 143.4 262.0 429.8 942.4 1701 2767 4183 6068 8275 11033 18021
v 7.20 10.13 12.73 13.97 16.33 20.29 22.98 26.32 32.29 37.30 42.36 47 22 52.08 56.30 60.48 68.97
0.0040 a 4.17 12.50 26.97 48.55 80.91 173.1 313.8 514.9 1128 2040 3330 5051 7208 9905 13240 21625
v 8.73 12.25 15.26 16.77 19.82 24.49 27.52 31.53 38.65 44.73 50.97 57.02 61.86 67.39 72.58 82.76
0.0050 a 47T 7442 3B1B 54l2 9015 i5S! 554 578.6 1275 2305 W 1757 8189 11278 14858 24469
v 9.86 13.83 17,20 18.97 20.10 27.74 31.05 35.43 43.68 50.54 57 05 64.76 70.28 76.73 81.45 93.64
0.0060 a 5.25 15.69 35.80 60.31 99.05 215.8 392.3 6473 1412 2550 4148 6277 9072 12406 16476 26970
v 10.99 15.37 20.26 20.83 24.26 30.53 34.41 39.63 48.38 55.92 63.50 70.86 77.86 84.40 9032 103.21
0.0080 a 6.08 18.34 39.23 70.12 116.2 251.5 456.0 750 3 1648 2976 4879 7355 10543 14417 19173 31384
v 12.72 17.97 22.20 24.22 28.46 35.58 40.00 45.95 56.46 65.26 74.69 83.03 90.48 98.09 105.1 120.1
0.0100 a 6.86 20.64 44.13 79.44 130.4 283.9 514.9 845.9 1863 3334 5492 8336 11867 16280 21576 35307
V 14.36 20.22 24.97 27.44 31.94 40.16 45.16 51.80 63.83 73.11 84.07 94.11 101.8 110.8 118.28 135.1
0.0125 a TBs '
2210 4718 800 1401 3021 5471 9079 1983 3589 5867
'
8844 2697 17426 23074 37785
v 15.38 21.75 26.75 27.98 34.31 42.74 48.00 55.22 67.94 78.70 89.81 99.84 109.0 118.5 126.5 144.6
0.0150 a 8.27 25.00 53.33 95.62 157.2 342.0 620.6 1020 2230 4045 6620 10022 4251 19584 25974 42616
v 17.31 24.49 30.18 33.03 38.50 48.38 54.43 62.46 76.40 88.70 101.3 113 1 22.3 133.2 142.4 163.09
0.0175 a 8.58 26.39 55.78 100.4 165.6 360.4 665.1 1073 2360 4291 6994 10512 5017 20595 27461 44194
v 17.95 25.85 31.56 34.68 40.65 50.99 58.34 65.70 80.52 94.09 107.1 118.7 128.9 140.1 150.5 169.1
0.020 a 9.80 30.16 63.75 114.7 189.3 411.9 760.1 1226 2697 4904 7993 12014 7163 23538 31384 50508
v 20.51 29.55 36.07 39.62 46.36 58.27 66.67 75.01 92 41 107.5 122.3 135.6 147.3 160.1 172.0 193.3
0.025 a 10.99 33.48 7073 127.3 209.8 4597 834.6 1367 2970 5422 8817 13296 9332 26357 34750 56581
v 23.00 32.80 40.02 43.97 51.39 65.03 73.20 83.70 101.7 118.9 135.0 150.1 65.9 179.3 190.5 216.5
0.030 a 12.00 36.78 77.23 137.9 229.9 501.1 919.4 1480 3264 5884 9792 14481 20917 28595 37697 62522
v 25.11 36.03 43 70 47.63 56.31 70.89 80.64 90.62 111.8 129.0 149.9 163.5 179.5 194.5 206.6 239.3
0 040 a 14.46 44.13 93.17 169.2 279.5 600.7 1093 1790 3923 7110 11622 17457 25254 34571 45604 75026
v 30.26 43.23 52.72 58.44 68.46 84.98 95.87 109.6 134.4 155.9 177.9 197.2 216.7 235.2 250.0 287.1
0.050 a 16.43 49.53 104.4 191.2 313.8 676.7 1231 2020 4413 8042 13044 19370 23441 39229 51489 85324
v 34.38 48.52 59.08 66.04 76.86 95.73 108.0 123.7~ 151.2 176.3 199.7 218.7 244.1 266.9 282.3 326.5
0.06 a 1844 5215 1157 !
210 3431 755! 1373 233T 4855 1827 14368 21282 31384 43152 57373
v 37.96 51.88 65.47 72.81 84.06 106.1 120.4 136.6 166.3 193.5 219.9 240.2 269.3 293.6 314.5
0.08 a 21.08 62.28 134.8 245.2 402.1 872.8 1594 2599 5688 10249 16672 24518 36532
v 44.11 61.02 76.28 86.69 98.49 123.5 139.8 159.1 194.9 224.7 255.2 276.8 313.5
0.10 a 24.03 70.12 152.0 277.0 456 0 980.7 1804 2942 6424 11524 18879 27461
v 50.29 68.70 86.01 95.67 111.7 138.7 158.2 180.1 220.1 252.7 289.0 310.0
0.12 a 25.99 77.48 167.7 306.5 500.2 1079 1986 3236 7110 12700 20841
v 54.39 75.91 94.90 105.9 122.5 152.6 174.2 198.1 243.6 278.5 319.0
0.15 a 28.50 84.13 183.9 334.2 551.7 1195 2161 3494 7769
v 59.64 82.42 104.1 115.4 135.1 169.0 189.5 213.9 266 2
0.20 a 34.32 102.0 220.7 402.1 662.0 1427 2599 4217 9317
v 71.82 99.93 124.9 138.9 162.1 201.9 228.0 258.2 319.2
0.25 a 37.72 112.7 245.2 447.9 735.5 1565 2876 4668
v 78.94 110.4 138.7 154.7 180.1 221.4 252.3 285.8
0.30 a 41.37 122.7 266.6 487.3 804.5 1710 3126 5057
v 86.58 120.2 150.9 168.3 197.0 241.9 274.2 309.6
0.35 a 43.34 128.7 283.2 514.9 841.0 1802 3261
v 90.70 126.1 160.2 177.8 206.0 254.9 286.0
0.40 a 49.93 147.1 323.6 588.4 961.1 2059 3727
v 104.5 144.1 183.1 203.2 235.4 291.3 326.9
0.45 a 50.31 150.0 326.6 600.2 979.7 2083
v 105.3 146.9 184.8 207.3 239.9 294.7
050 a 55.90 166.7 362.9 666.9 1089 2314
v 117.0 163.3 205.3 230.3 266.7 327.4
0.6 a 62.28 185.3 402.1 735.5 1201
v 130.3 181.5 227.5 254.0 294.1
0.7 a 63.07 188.8 407.6 750.9
v 132.0 185.0 230.6 259.3
0.8 a 72.08 215.8 465.8 858.1
v 150.8 211.4 263.6 296.4
0.9 a 73.28 218.4 476.6
« 153.3 214.0 269.7
a = kg/h capacity v = m/s velocity with a volume of 1 m3/kg
183
Steam and condensate Plumbing Engineering Services Design Guide
kg/h
Pressure Velocity
( bar ) ( m/s) 15mm 20mm 25mm 32mm 40mm 50mm 65mm 80mm 100mm 125mm 150mm
0.4 15 7 14 24 37 52 99 145 213 394 648 917
25 10 25 40 62 92 162 265 384 675 972 1457
40 17 35 64 102 142 265 403 576 1037 1670 2303
0.7 15 7 16 25 40 59 109 166 250 431 680 1006
25 12 25 45 72 100 182 287 430 716 1145 1575
40 18 37 68 106 167 298 428 630 1108 1712 2417
1.0 15 8 17 29 43 65 112 182 260 470 694 1020
25 12 26 48 72 100 193 300 445 730 1160 1660
40 19 39 71 112 172 311 465 640 1150 1800 2500
2.0 15 12 25 45 70 100 162 280 410 715 1125 1580
25 19 43 70 112 162 295 428 656 1215 1755 2520
40 30 64 115 178 275 475 745 1010 1895 2925 4175
3.0 15 16 37 60 93 127 245 385 535 925 1505 2040
25 26 56 100 152 225 425 632 910 1580 2480 3440
40 41 87 157 250 357 595 1025 1460 2540 4050 5940
4.0 15 19 42 70 108 156 281 432 635 1166 1685 2460
25 30 63 115 180 270 450 742 1080 1980 2925 4225
40 49 116 197 295 456 796 1247 1825 3120 4940 7050
5.0 15 22 49 87 128 187 352 526 770 1295 2105 2835
25 36 61 135 211 308 548 885 1265 2110 3540 5150
40 59 131 225 338 495 855 1350 1890 3510 5400 7870
6.0 15 26 59 105 153 225 425 632 925 1555 2525 3400
25 43 97 162 253 370 658 1065 1520 2530 4250 6175
40 71 157 270 405 595 1025 1620 2270 4210 6475 9445
7.0 15 29 63 110 165 260 445 705 952 1815 2765 3990
25 49 114 190 288 450 785 1205 1750 3025 4815 6900
40 76 117 303 455 690 1210 1865 2520 4585 7560 10880
8.0 15 32 70 126 190 285 475 800 1125 1990 3025 4540
25 54 122 205 320 465 810 1260 1870 3240 5220 7120
40 84 192 327 510 730 1370 2065 3120 5135 8395 12470
10.0 15 41 95 155 250 372 626 1012 1465 2495 3995 5860
25 66 145 257 405 562 990 1530 2205 3825 6295 8995
40 104 216 408 615 910 1635 2545 3600 6230 9880 14390
14.0 15 50 121 205 310 465 810 1270 1870 3220 5215 7390
25 85 195 331 520 740 1375 2080 3120 5200 8500 12560
40 126 305 555 825 1210 2195 3425 4735 8510 13050 18630
184
Plumbing Engineering Services Design Guide Steam and condensate
kg/h
Pa mbar
per m per m 15mm 20mm 25mm 32mm 40mm 50mm 65mm 80mm 100mm
185
Steam and condensate Plumbing Engineering Services Design Guide
Thermodynamic traps
( Figure 7 )
Some traps rely on the fact that when
condensate at near steam temperature is
reduced in pressure at an orifice, flash
steam is produced. The most common
trap of this type is the thermodynamic
trap which uses the increased velocity of
the flash steam to close a disc against a
seat. The trap opens on a cyclic
186
Plumbing Engineering Services Design Guide Steam and condensate
187
Steam and condensate Plumbing Engineering Services Design Guide
Table 7 Expansion of steel pipes ‘cold stressing’ as it is alternatively Horse shoe or lyre loop
Final Expansion
known. Expansion in long lengths of
temperature per 30 m pipework can be taken up by non- The horse shoe or lyre loop is commonly
( °C ) ( mm ) mechanical means by the use of loops in used . It has a tendency for the ends of
the pipework. the loop to straighten slightly but this
66 19 does not cause any misalignment of the
93 29 connecting flanges.
121 41 Full loop Expansion loops can be fabricated from
177 61
The full loop is achieved by one complete straight lengths of pipes and bends, long
204 74
turn of the pipe, the ends being flanged radius bends should be used, as short
232 84
for incorporation into the pipework radius bends restrict flexibility.
260 97
system, the downstream side passes
Expansion (mm) = below the upstream side and should be
1.25 x 10'5 x °C (diff ) x 1000/m fitted horizontally or a trapping set would Sliding joint
External installations require
be required to drain the build up of - Sliding joint expansion devices take up
condensate that would occur.
weatherproofing as the heat losses of little space, however unless they are
water saturated insulation, can be up to This type of loop has a tendency to rigidly anchored they can develop
50 times greater than from the same unwind and can exert a force on the problems of separating, any
pipework in still air conditions. connecting flanges. misalignment in pipework will cause the
sleeve to bend, the joints also need
regular maintenance, care should be
taken in their use.
Allowance for
expansion M
Allowance for expansion within the steam
distribution system is required to give the
LLA
necessary flexibility, as the system heats
up to ensure no undue stresses are set
up. Table 7 shows the approximate
expansion of steel pipework installed at a
IS
temperature of 16°C, through a range of
Figure 8 The full loop Figure 10 Sliding joint
heat -up temperatures.
The distribution pipework where possible Figure 9 The horse or lyre loop Figure 11 Bellows joint
should be installed in reasonable lengths
with sufficient bends, ie. changes of
direction to allow the expansion to be
taken up ‘freely’ .
Where ‘free’ movement is not possible
other means of achieving the flexibility
should be incorporated into the system.
Where practicable the expansion of the
steam pipework and any expansion
devices incorporated into it should be
reduced by the inclusion of ‘cold draw’ or
188
Plumbing Engineering Services Design Guide Steam and condensate
Table 8 Flow of water in steel pipes ( kg / h ) steam pressures up to 10 bar. Above this
Tube 0.3 0.5 0.6 0.8 1.0 1.4 pressure range, some additional capacity
diameter in the condense lines may however be
( mm ) ( 30Pa ) ( 50 Pa ) ( 60 Pa ) ( 80Pa ) ( lOOPa ) (140Pa ) desirable.
15 95 130 140 160 180 220 The flow rates and pressure drops given
20 220 290 320 370 420 500 in Tables 5 and 8 may be found
25 410 540 600 690 790 940 convenient for pipe sizing condensate
32 890 1180 1300 1500 1700 2040 lines.
40 1360 1790 2000 2290 2590 3100
50 2630 3450 3810 4390 4990 6000
Example 3
65 5350 6950 7730 8900 10150 12100
80 8320 10900 12000 13800 15650 18700 A plant having a normal running load of
10OOkg/h and a starting load of 2000kg/h is
100 17000 22200 24500 28200 31900 38000
to be adopted for condensate line sizing.
Starting load ie running load x 2 Assuming a steam trap is fitted not more
Approx, frictional resistance (mbar per m of travel) than 3m from the condensate receiver tank,
Heavy grade steel tube determine a suitable diameter of pipe for
the condensate pipeline .
Expansion (mm) = 1.25 x 10"5 x 30 x Referring to Table 8, it will be seen that a
Bellows (260 - 16) x 1000 32mm pipe can handle 2040kg/h at a
pressure drop of 1.40KPa ( mbar ) per metre
Bellows type devices are also in line - = 1.25 x 30 x 2.44 of travel.
fittings but unlike the ‘sliding joint’ type = 91.5mm
require no packings, however pressure The heat emission from bare horizontal The overall pressure drop is therefore
within the fitting can extend them, pipes with ambient temperatures between 1.40 x 3 = 4.20mbar and this small amount
adequate anchoring and guiding is 10°C and 21°C in still air conditions are of back pressure would be acceptable. If,
essential. shown in Table 8. on the other hand, the condensate has to
travel over a distance of say 500m, then
the back pressure will be 500 x 1.4
= 700mbar and allowing for additional
resistance, would impose a total back
Articulated bellows
Articulated bellows are capable of
Condensate return pressure in the region of 800mbar, to which
must be added the back pressure caused
by any lift in a line.
absorbing the axial movement in the
pipework and some of the lateral and Design of the condensate return system Condensate should run away from the
angular displacement and have a is important. It should not impose any trap by gravity but there are occasions
number of advantages over other undue back pressure on the steam traps when it is necessary to ‘lift’ it. This is
devices particularly at changes of in the system. achieved by the pressure available at the
direction. Anchoring and guiding are The system should be adequately sized trap outlet and therefore, no steam trap
important with this type of device. to carry maximum flow and be arranged will actually ‘lift’ the condensate.
Heavy quality steel pipes have a linear with a fail to overcome the system It is handy to remember in initial design
coefficient of expansion of 1.25 x 10'5oC resistance and flow under gravity that for each 0.11mbar (11 KPa) pressure
per unit length. Table 7 gives the conditions. at the trap, the condensate can be lifted
expansion in steel pipes . It is however rarely possible to return all 1 metre, it should be remembered when
the condensate produced in the selecting steam traps that water hammer
distribution system all the way back to and attendant noise with the risk of
Example 2 the boiler hotwell by gravity, some lifting mechanical damage are inevitable when
will almost certainly be required. lifting condensate ,
Assume a steam main 30 metres long has
a temperature rise from 16°C to 260°C. It is therefore usual to direct the Pumped condensate return pipe lines
Calculate the linear expansion to be taken condensate to collecting receivers from are generally flooded when running,
up by an expansion unit. which it can be pumped back to the these pipelines often follow the routing of
boilerhouse. the steam mains. Care should be taken
Figure 12 Articulated arrangement not to connect the pipework from the
At start up the plant is cold. Steam will traps draining the steam main to the
condense rapidly and the steam flooded pumped condensate returns.
consumption may be two or three times Introducing condensate at higher
the normal running rate. Under these pressure and temperature into flooded
conditions, the condensate pipework will
be required to pass two or three times
condensate pipework will cause re -
evaporation where some of the
the normal condensate rate. As the plant
warms up, so the amount of condensate
-
condensate will flash off into steam
again, these steam bubbles will soon
reduces to the running load. collapse in the cooler condensate
Experience has shown that pipes sized causing severe water hammer.
for the above conditions will have an
adequate capacity to handle the normal
running conditions. For this kind of
exercise the start-up load should be
taken as not less than twice the running
load. This provision will be sufficient for
189
Steam and condensate Plumbing Engineering Services Design Guide
Handling
condensate
The receivers that collect condensate are
usually at lower level than the boiler
‘Hotwell’ back at the boilerhouse, it will
therefore be necessary to pump the
condensate to higher levels than the
collection receivers.
There are generally two accepted types
of pump for condensate, one is positive
displacement and the other uses
electronically operated pumps.
190
Pipework expansion
Consideration for design and installation
Calculation of expansion ond contraction
Controlled pipework movement
Pipework expansion Plumbing Engineering Services Design Guide
All pipework will expand and contract The change in length of pipework, for
longitudinally and around the both expansion and contraction, due to From Formula 1
circumference when subjected to temperature variation can be calculated Al = I x a x At
temperature variations. using the following formula:
= 15 x 16.9 x10 6 x (80 - 20)
'
192
Plumbing Engineering Services Design Guide Pipework expansion
f.
flexibility to prevent the connection
shearing.
Ensure that expanding pipework will
not clash with structures.
a SOa
Anchor
M Expansion
Z /J '
\
, Expansion
193
Pipework expansion Plumbing Engineering Services Design Guide
The following points should be noted Supports and pipe guides For guides nearest the bellows, the
when using expansion bellows or clearances between the outside pipe and
compensators: The purpose of a support is to transfer inside guide walls should not be greater
the load of the pipe and the contents than 1.6mm for pipe diameter up to
a. Axial type bellows must not be used
where the pipe is hung or suspended within the pipe safely to a structure The . 100mm and not greater than 3.2mm for
pipe support should reduce deflection of larger pipes. For the guides along the
freely. The pipe supports must guide
the pipe and allow only axial bending of the pipe. pipe run, maximum clearances of 3.2mm
and 6.4mm respectively should be used.
movement along the entire length of The purpose of a pipe guide is to control
the pipe. the direction in which a pipe will move
when it expands. A pipe guide is any
b. It is essential to ensure that the pipe Guides nearest
is guided carefully on each side of form of constraint which allows the pipe
the bellows. The guides must allow true axial movement along its length but the bellows
prevents offset movement whether
only axial movement onto the The function of guides closest to the
bellows. horizontal or vertical. Pipe guides can ,
however, be designed to also provide a bellows is to ensure true axial movement
c. It is essential to ensure that the pipe .
support facility Some typical pipe guides on to the bellows. This can be achieved
is guided carefully at the necessary are indicated in Figures 7 to 11. by using a tubular type guide (as Figure
intervals along the whole pipe run. 10) of such length that the necessary
clearances to permit axial movement do
d. Only the bellows unit should be not allow appreciable offset movement.
installed between two pipe anchors . Generally a tubular guide having a length
e. The line between two anchors should to diameter ratio of 6:1 will be adequate.
be straight, in plan and in elevation,
with no sets or bends.
Clearance
3 Tubular guides are generally only fitted to
small pipes. For larger sizes (50mm and
f. Pipe anchors must be of adequate
L over), proprietary straps and roller guides
strength. are normally employed. Straps and roller
guides are short and individually cannot
g. Bellows must be stretched by half the Figure 7 Strap-type guide control angular movement of the pipe. To
total expansion movement ( cold- ensure alignment of the pipe onto the
draw). This does not apply to special bellows, an additional set of guides is
-
applications or ‘pre cold drawn' units . required as follows.
h. Screwed end units must be held firm Clearance \ — Strap ]
when installing to prevent twisting of
the bellows .
Anchor
Correct guides
Anchor No guides
194
Plumbing Engineering Services Design Guide Pipework expansion
mb *
Anchor
*
Anchor Anchor
—F-
* Guide at necessary
intervals
195
Pipework expansion Plumbing Engineering Services Design Guide
This resistance acts against the direction Pipework system under test conditions vi. The pipe between bellows and
of movement e.g. it can act either way, anchors is frequently in compression
depending on whether the pipe is Thrust due to internal pressure on bellow and unless the pipe is guided
warming up or cooling down. = test pressure x effective area carefully, and runs accurately in a
straight line from anchor to anchor,
Should the above figures give = 830 x 103 x 0.023N the pipe may bow out sideways. This
unacceptably high forces consideration
could be given to using special PTFE = 19090N pushing outwards on anchors will pull the bellows with it and may
Force due to bellows stiffness (bellows cause failure.
support pads which gives figures as low
as 0.02. stretched in cold-draw position) vii. Never use axial bellows in pipework
= 6700N pulling inwards on anchors
systems incorporating suspended
hanger supports or any other support
Example 2 Frictional resistance systems which can readily swing.
The following example illustrates the = NIL as pipe only moves under
calculation to determine the force imposed viii. Confirmation should always be
temperature effect obtained from the bellows
on an anchor under normal working and
test conditions on a pipework installation Total thrust on anchor manufacturer regarding any special
indicated in Figure 19, which incorporates requirements they may have
= 19090 - 6700 regarding the position of anchors and
axial type bellows.
= 12390N pushing outwards on guides.
The designer must obtain the relevant data anchors.
from the bellows manufacturer.
It can be seen in this instance that the
Pipe weight = 22kg/m greatest force acting on the anchor is under
Water weight = 19.5kg/m normal working conditions, this however is
Lagging weight = 6kg/m not always the case.
Effective area of bellows = 0.023m2
Thrust to compress or extend bellows
through full movement = 6700N The following important points should be
from manufacturer’s data (Newtons) considered when installing bellows:
Coefficient of friction between i. When a fitting such as a bend, valve
pipe and supports = 0.3 or distance piece is installed into a
System working pressure = 550kPa pipe and subjected to internal
(550 x 103Pa) pressure. The fitting will act just like a
System test pressure = 830kPa pipe itself, holding the internal
Length of pipe = 42.5 pressure, but not pushing or pulling
on the pipe.
Pipework system under ii When an axial bellows is fitted into a
normal working conditions pipe and subjected to internal
pressure, it reacts to the internal
Thrust due to internal pressure on bellows pressure by trying to open out
= working pressure x effective area lengthways. An outward pressure is
therefore exerted by the bellows.
= 550 x 103 x 0.023N
iii. When a pipe restrained by an anchor
= 12650N pushing outwards on anchors at one end, but otherwise free to
Force due to bellows stiffness (bellows move longitudinally, is subjected to
compressed in working platform) heat , it will expand away from the
= 6700N pushing outwards on anchors.
anchor position, exerting an outward
force away from the anchor.
Frictional resistance to pipe movement over
its supports: iv. When a pipe anchored at two points
and provided with a bellows between
= coefficient of friction x (total weight of the anchor points is subjected to
pipe + water + lagging) heat, pressure is exerted by both
= 0.3 x [(22 x 42.5) + (19.5 x 42.5) pipework sections towards the
+ (6 x 42.5)]kg bellows. Meanwhile the pressurised
bellows is exerting pressure outwards
= Converted to Newtons (1kg = 9.807N) towards the two anchor points .
= 0.3 x [(22 x 42.5 + (19.5 x 42.5)
v. When the pipe gets hot, it expands
+ (6 x 42.5)] x 9.807N
towards the bellows and tries to
= approximately 6000N against the compress it. Meanwhile, the
direction of movement, eg. pushing pressurised bellows is trying to open
outwards on anchors. out lengthways. The expanding pipe
Total Thrust on Anchor therefore has to overcome this
pressure force as well as the stiffness
= 12650 + 6700 + 6000 of the bellows and the friction of the
= 25350N (Newtons) pushing outwards pipe supports. Hence the need for
on anchors. firm anchors at each end of the pipe
run, and careful guiding not only on
each side of the bellows but also
along the pipe run.
196
197
Mechanical ventilation Plumbing Engineering Services Design Guide
198
Plumbing Engineering Services Design Guide Mechanical ventilation
Fresh air -
Pre heating of the air can be achieved by
a water heating coil, an electric heater \
199
Mechanical ventilation Plumbing Engineering Services Design Guide
If the supply air is not pre- heated an Table 2 Ductwork fitting K factors ( Velocity pressure loss factors ) .
additional 7.563kW will need to be added to Percentages for branches are based on the change in air velocity of the air stream
the room heat loss of 3.7kW. under consideration.
Discharge air temperature ( Ts ) to Circular ducts Rectangular ducts
provide 3.7kW heating within room
Fitting K Fitting K
Q = q x 1.2 x 1.01 x At
3.7 = 0 . 2 4 x 1 . 2 x 1 . 0 1 x (Ts -
2 1)
Bends 90 °
( Radius to inside edge of bend)
’
Bends 90° radius /2 x D
(Radius to inside edge of bend)
3.7
Ts = 0.24 x 1.2 x 1.01 + 21 '
Radius A x D
Radius 1 x D
0.34
0.24
Height/ width ratio
0.2 0.48
= 33.72°C Radius 11/5 xD 0.23 0.4 0.37
Duct heater output 0.6 0.28
Q = 0.24 x 1.2 x 1.01 x [33.72 -
( 5)]
-
0.8 0.25
= 11.26kW 1.0 0.23
Conical branch with VD Shoe branch with Vc. VD
airflow to branch ( Vc to VB) . airflow to branch ( Vc to VB) .
Use velocity pressure in VB vB Use velocity pressure in VB
I VB
Effect of mechanical 50%
60%
3.0
2.0
50%
60%
2.5
1.7
ventilation on 70%
80%
1.5
1.2
70%
80%
1.3
0.8
heat producing 90%
Conical branch with through
1.0 90%
Shoe branch with through
0.7
Vc. V0 Vc. VD
appliances airflow (Vp to VD).
Use velocity pressure in VD
airflow ( Vq to VD).
Use velocity pressure in VD
VB VB
It is essential to ensure that any extract 50% 0.09 50% 1.0
system installed does not cause spillage 60% 0.06 60% 0.45
of flue gases from open flued boilers, 70% 0.03 70% 0.3
fires, cooking appliances, etc. 80% 0 80% 0.1
The Building Regulations stipulate that 90% 0 90% 0.07
an internal room provided with extract Conical branch with airflow Vc. VD Shoe branch with airflow Vc. VD
ventilation alone must not contain open from branch ( VB to VD). from branch ( VB to VD) .
flued appliances. If mechanical supply air Use velocity pressure in vD VB Use velocity pressure in vD VB
ventilation is provided to such a room, it
must be electrically interlocked with the 50% 0.5 50% 0.5
extract fan(s) and provided with an 60% 0.52 60% 0.52
interlocked supply air flow proving switch 70% 0.53 70% 0.53
to ensure: 80% 0.54 80% 0.54
1. The supply air system is activated 90% 0.55 90% 0.55
whenever the extract system is Conical branch with through Vc. VD Shoe branch with through Vc. VD
operating. airflow ( Vq to VD). airflow (Vq to VD).
Use velocity pressure in VD VB Use velocity pressure in V0 VB
2. The extract fan(s) will not be activated
until supply airflow has been proved. 50% 0.09 50% 0.09
3. The open flued appliances will not 60% 0.06 60% 0.06
operate until supply airflow has been 70% 0.03 70% 0.03
proved. 80% 0 80% 0
90% 0 90% 0
4. The extract fan(s) and open flued
appliances will immediately shut Concentric reducer Concentric reducer
( Use velocity pressure ( Use velocity pressure
down should the supply airflow at reduction ) at reduction)
proving switch determine that the
supply air system has failed. 30° Angle 0.02 30° Angle 0.02
45° Angle 0.04 45° Angle 0.04
The Building Regulations also stipulate Aerofoil damper 0.2 Aerofoil damper 0.2
that a mechanical extract system must
not be installed in any room containing a
solid fuel burning appliance. Flexible spiral reinforced duct Length ( mm)
0.05 x
Diameter ( mm)
Open flued appliances must be able to
operate correctly whether or not the
fan(s) is (are) running where natural
ventilation and mechanical extract
ventilation are provided to the same
room space.
200
Plumbing Engineering Services Design Guide Mechanical ventilation
201
Mechanical ventilation Plumbing Engineering Services Design Guide
Graph 2: Relationship between rectangular and circular ducts (equal volume flow rate and unit pressure drop)
202
Plumbing Engineering Services Design Guide Mechanical ventilation
extent, on the type of duct material and would be the index run (eg: the run with there is a difference between ‘sound
method of construction. the highest pressure loss). power’ and ‘sound pressure’ noise levels.
Graph 1 provides the relationship It is usual practice when selecting a fan Attenuators (silencers) can be installed
between airflow, unit pressure drop and to add a percentage (between 10 and within the ductwork to reduce the
air velocity through straight circular 20%) to the required airflow for ductwork airborne noise transmission from a fan.
ductwork, typical for use in small leakage. Advice regarding attenuator selection
ductwork systems constructed from should be sought from the fan
PVCu or steel. manufacturers or a specialist.
The rectangular equivalent of the circular
duct section used can be determined
from Graph 2. Noise control
Pressure loss through ductwork fittings
can be calculated by multiplying the Consideration must be given to ensure
Fan types
fitting K factor listed by Table 2, with the that vibration and airborne noise
air velocity pressure in the duct. generated by a fan will not cause There are four main types of fans used in
damage or a nuisance. ventilation systems:
Formula 6 Vibration transmission can be reduced by 1. Centrifugal
providing a sound isolating material
The air velocity pressure can be 2. Axial Flow
between the fan, support structure and
calculated using the formula:
connecting ductwork. 3. Mixed Flow
Pv = 1/2 x ip x v2 This can take the form of : 4. Propeller.
Where Pv = The Velocity Pressure in 1. Proprietary anti-vibration mountings These four types of fans are further
Pascals (Pa)
constructed from neoprene, metal or divided into various types, primarily
<p = The density of air in kg/m3 plastic springs or similar associated with the type of fan blades
v = The air velocity in m/s which they contain.
2. Neoprene or similar inserts between
For general ventilation systems the the fan and fixings Generally the type of fan selected will be
density of air can be taken as 1.2kg/m3. 3. Flexible ductwork connections to the
governed by the fan duty required
Therefore the formula can be simplified (airflow and pressure), and the type of
fan unit.
to: application. The following general
2 It should be ensured that the fan and characteristics of each fan type should
Pv = 0.6 x v ductwork system are not fixed to, or in be noted:
The velocity pressure against velocity is close proximity of any materials which
tabulated in Table 3. could readily flex and vibrate.
Pressure loss through grilles, air Airborne noise can be reduced, in the
Centrifugal fans
terminals and louvres should be obtained first instance, by selecting a fan which a. High airflow
from the manufacturer. has a low sound power level. Tabulated
sound power levels In decibels (dB) b. High pressure
The individual pressure loss through against frequency (Hz) can be obtained
each element of the ductwork system c. Main sound power generation in
from the fan manufacturer. It should be lower frequencies, which are more
has to be added together to arrive at the noted that the published figures can take
required fan pressure. Where branches readily controlled by attenuation
various forms and it is therefore
are provided within the system, it is necessary to ensure that like for like
necessary to determine which route comparisons are made. Also note that
203
Mechanical ventilation Plumbing Engineering Services Design Guide
Propeller fan
a. High airflow
b. Low pressure
c . Low cost
d. Low efficiency
e. Can be noisy.
204
jjT
Designing for
the disabled
Introduction
Approaches to buildings
Inside buildings
WC compartments in public buildings
Washbasin fittings
WC levels in private facilities
Facilities for private use and nursing homes
Advanced WC cubicle design for wheelchair disabled 213
Central heating for the disabled
Designing for the disabled Plumbing Engineering Services Design Guide
206
Plumbing Engineering Services Design Guide Designing for the disabled
207
Designing for the disabled Plumbing Engineering Services Design Guide
S
*
750 Basin Light switch or pull Hand rinse basin
IT
) cord for light
position Where practical, this should be placed so
8 — Horizontal handrail that it is usable whilst seated on the WC
CNJ
S1
'
WC
Handle-
fi has to transfer back into the chair before
washing their hands and so fouls the
o
m
s o chair’s arm rests and wheel runs used for
o
Door to propulsion. The basin should be at a
Pull rail — height of 750mm.
swing out
Fixed vert cal rail
Do not install shallow basins with
w pedestals. Vanity units can be suitable for
2000 minimum
wheelchair users with built into the wall
types most useful and practicable. It is
* possible to get an adjustable height
Hinged support
rail
basin, such as the ‘Zoom’ basin, or items
Dimensions in mm which tip at the front, such as the ‘Ifo
tilting’ wash basin.
It is poor practice to design the flushing deforms and moves when sat on must
The door must be unlockable from the operating device/handle behind the not be used as it could cause accidents
outside in the event of emergency and disabled person. during transfer operations. Also accidents
assistance needed by an attendant , can occur during use, resulting in
If users are likely to be too severely personal injuries, including cuts which
handicapped to be able to clean result in the disabled person having
Support rails themselves, an installation of a pressure ulcers.
50mm minimum diameter support rails
proprietary WC /bidet (closomat or medic - A raised seat should be adjusted
ioo type of unit) should be considered.
should be provided on all sidewalls These have a warm douche and warm carefully to fit the WC securely and the
adjacent to the WC with a hinged air for drying. These units need a user or a helper should check frequently
horizontal rail of 300mm minimum length relaxation from the Water Company and that the fittings are secure.
on the exposed side. If the design is for Building Control before installation.
208
Plumbing Engineering Services Design Guide Designing for the disabled
Mixer fittings with swivel arms can be Most raised seats can be removed for
Restricted space moved to the side to leave the sink bowl normal use of the WC by able bodied
In a building whose size makes it area free. and for cleaning.
impractical for a unisex compartment to
Taps can be wall-mounted, which Check that the seat fittings are easy to
be installed, the recommended minimum clean.
necessitates reaching forward, set into
dimensions should be not less than the basin or into the surround. Controls
2000mm by 1500mm. This can result in a can be fitted to the front of a vanity unit
Some users may require carefully
limited manoeuvring space, however positioned grabrails or a WC support
to allow remote control of the tap outlets.
lateral transfer can be accommodated. frame to help them transfer on and off
High-necked fittings provide more space the seat.
when hand- washing and can facilitate A padded WC seat may be of help to
Additional facilities cleaning.
those with sensitive skins and those
Where there is already a unisex toilet In a domestic facility, choose taps which prone to pressure sores. Regular dusting
compartment and wheelchair users are suitable for the individual, carefully with talcum powder helps to prevent the
require additional toilet accommodation it assessing the action required to operate seat from becoming hot and sticky. A
is recommended that a WC compartment each type. raised seat with one cut-out side may be
2000mm by 1500mm minimum suitable for a person with a stiff hip.
Long-handled lever taps require less
dimensions be installed. power to operate but need a wider arc of A person with two stiff lower limbs or
movement than short-handled levers. extremely weak upper limbs may be
helped by a self -lifting seat or angled
Macerating WC boxes and Pressure handles vary in the pressure
seat fixed to a frame support. Both
needed and must be held in position to should be adjusted carefully to the
WC pans operate. The springs must be reduced in
individual and are suitable for those with
These electrical mechanical units cannot tension for the disabled. poor balance.
dispose of sanitary towels or Mixer taps may be dangerous if heat
incontinence towels and must not be sensation is impaired or if the person is
fitted to WC pans used by the disabled confused. Selection of raised
community, unless strict disposal
management control is imposed.
Foot -operated pressure pads may be toilet seats
useful for some with upper limb
diabilities, but they require good balance The seat should preferably be fixed to
to use. They are not suitable for the WC pan by brackets: in certain
WC facilities for wheelchair users. situations removable seats are useful,
ambulant disabled Knee-action valves are available for
however seats that are not securely fixed
can be dangerous.
Supplementary facilities for ambulant those who cannot manage taps and
disabled should be provided in large these can be operated from wheelchairs. The method of fixing should be easy to
carry out.
buildings as for the wheelchair disabled Tap turners are a cheaper alternative to
users. fitting new taps for general home use and The fixing brackets should not damage
can be useful when away from home. the WC Pan.
Basin plugs with short chains tangle The seat height must be assessed for
least and may be easier for the disabled each individual and a seat should be
Washbasin fittings user to reach than the longer type. supplied which, when placed on the WC
pan, provides this height. Some disabled
Central column fitting plugs can be people require a seat height of between
Taps may be paired, with cross- tops, operated with a push and pull movement. 475-550mm.
levers, short (or long), quarter turn Control knobs are easier to handle than
a chain but are smaller than most tap A convex seat rim is more comfortable
levers, single lever mixer types or than a concave one.
electronic taps. handles which cause arthritic disabled
people severe problems. The surface finish of the seat should not
Electronically operated taps are operated adhere to the skin even after prolonged
by the user placing their hands under the sitting.
spout which activates a remote sensor.
The remote sensor should be adjusted to To allow easy access for personal
suit the application. Combined mixer,
separate hot tap, bidets and all other hot
WC levels in cleansing the aperture length should
preferably be 300mm.
water application temperatures should be
set at not more than 35°C by the use of
private facilities
a thermostatic valve to maintain an even
safe temperature to prevent scalding. Considerations
Some disabled people are not sufficiently
sensitive to temperature to realise when The required overall height should be
the water is too hot and for such checked for the individual user.
applications, the advice should be sought The comfort of the seat for the individual
from the disabled person’s medical user should be checked.
professional as to the maximum
temperature the mixed water should be Wooden seats may be preferred for
set to. comfort by some users and may be more
stable than plastic seats for some types
of transfer.
209
Designing for the disabled Plumbing Engineering Services Design Guide
210
Plumbing Engineering Services Design Guide Designing for the disabled
make getting in easier but provides Check that the person is not likely to house.
insufficient support when getting out . suffer dizziness when changing from
The disabled person or assisting helper
The bathroom floor should be checked horizontal to vertical.
must have sufficient arm movement and
carefully for suitability if a special bath is strength to operate a mechanical device
being considered. effectively.
Baths with built-in seats
Fitting a non-slip mat in the bath and Some lifting devices are simple to use.
teaching the person to turn on their The small square bath is designed to fit They are portable and can be used by
hands and knees after draining the bath into a bathroom with limited space. It can community nurses to bath patients at
water may enable them to get out without be used as a shower area by a seated home. They are unsuitable for those with
further aids. person. This bath is made from cast poor balance; devices with rigid seats are
acrylic sheet and has a slip-resistant safer.
A combination of bathrails, bathboard, finish. A seat is built -in and handgrips are
bath seat and non-slip mat may assist fitted on each side. If the device is operated electrically, a
many people who have difficulty getting suitable power point will be required
into and out of the bath. outside the bathroom. Those involved in
It is recommended that quarter turn lever Bath inserts using the device must be made fully
aware of the safety factors recommended
taps may be the most suitable. A rigid insert may be more suitable than by the manufacturer.
Ensure water pressure is reduced for a bath board combined with bath seat if
safety. the person has great difficulty in getting Before a floor-fixed device is installed the
out of an ordinary bath or lacks balance floor should be checked for suitability.
Corner taps may be practical for some or co-ordination. Periodically, the user or helper should
but if fitted on the outer side, may check the device for stability.
impede getting into and out of the bath. A bath board is useful for those with
They are unsuitable if a plastic insert is difficulty getting over the side of the bath, Portable patient lifters can be used in the
bathroom provided adequate
used. including those with lower limb
disabilities, balance or co-ordination manoeuvring space is available and
The tap closest to the bath edge must be problems or stiff joints. The person sits there is space under the bath for the legs
the cold tap to help the blind and for the on the board, feet outside the bath, of the hoist. Alternatively, a base plate
safety of children. can be floor- fixed at the side or end of
slides backwards on the board, turns to
A walk-in bath may suit those who are swing the legs over into the bath and the bath and hoist mast fitted into it.
liable to fall or are afraid of falling. It is slides to the middle of the board. An electrically-operated hoist can be
particularly practical for institutional use A non-slip bath should always be used used in the bathroom; the ceiling joists
and may prevent the attendants hurting where available. must be inspected and their structural
their backs. strength confirmed to ensure that they
Those who lack limb strength or have are adequate to carry the tracking. Slings
The bath can be used as a sit -in bath or poor balance may prefer to sit on the used must allow the water to drain and it
as a shower cubicle. The user must be bath and use an over-bath shower. The
able to sit in the normal position. A water is recommended that a spare set be
curtain will need to hang outside the bath supplied to allow for drying.
thermostat must be fitted to the taps. so suitable flooring is required with a
The sensation of rising water may be drain gully in the floor.
frightening to some elderly or confused A seat is useful for a person who is Showering
people. unable to sit in the bottom of a bath Showers must be thermostatically
An adjustable height bath is intended for because of balance, mobility or lower controlled with maximum hot water outlet
use in hospital or in residential limb problems; strong arms are needed temperature of 35°C. Seek medical
accommodation. It saves the attendant to lower to the seat and onto the bottom advice for each user’s needs.
from unnecessary bending and may help of the bath. The seat can be used alone
prevent back strain. or in conjunction with a bath board. A Discussion should be given to the choice
bath rail may be necessary. The user can between an over-bath shower and
An ambulant person can step into the shower cubicle. Showering does not
sit on the seat to bath or shower if he is
bath at its lowest level and be raised to a unable to lower themselves into the always overcome all problems of
convenient height for the helper bathing bottom of the bath. disabled bathers. Some, particularly the
him. elderly disabled, dislike showers and
Some makes have mesh or slatted seats prefer a strip-wash.
A person who is unable to get into or out
for water drainage. Only a seat which
of the bath unaided should be hoisted hangs from the bath rims or stands on Grants may be available for part of the
using the particular model the bath was the bottom of the bath is suitable in an cost of installing a shower from
designed to accommodate. acrylic bath. Environmental Health Departments ( for
A tilting bath may reduce the need for private housing) or the Local Authority
assistance and increase the ( for council housing).
independence of some people confined Bath lifts If new downstairs facilities are essential,
to a wheelchair. consider the site of the shower with the
Some bath lifts can be operated
A wheelchair user should check that he independently by the bather, others are WC and washbasin, allowing sufficient
can transfer easily into and out of the assistant -operated. space for a wheelchair and a helper as
tilting bath, using a transfer board if necessary.
necessary. Installing a lifting device may be more
cost -effective than fitting a special bath Heating, lighting and ventilation of the
If the user cannot close the door and or shower. Some are suitable for shower areas should be as detailed
operate the controls of the tilting bath a installing in small bathrooms and most previously and the installation of an
helper must be available to do so. can be re-sited if the person leaves the emergency call system is essential.
211
Designing for the disabled Plumbing Engineering Services Design Guide
Shower trays designed for the disabled are available. Grabrails will be necessary. however design the drainage system to
do not have a step-over ledge. Check the For a wheelchair user, the seat height
accommodate these items when the
model and install a grabrail for safety by disposal units are not functioning.
must be the same as the wheelchair
the entrance. A non-slip sloping floor
seat. The user can sit facing forwards or All changes of direction must be
area is much safer than a shower tray backwards on the bidet as convenient. designed with long radius easy bends
and it is essential for wheelchair use,
The hot water requirements must be as and sufficient access points, readily
though it is more expensive to install.
for ‘Showering’ section previously. available in practical positions for use by
Sloping floors must be non-slip. Non-slip maintenance personnel.
mats are dangerous in such areas.
Ensure that drainage gradients are not
Adhesive safety treads can be used. Urinals minimum but generous for self cleansing
It may be difficult to install a sloping floor Specially adapted wheelchairs, cushions velocity of the solids from the drain.
area in an upstairs bathroom. or seat cushions may help those using Before using dual water capacity flushing
urinals. Generally the wheelchair user will units, calculate the volume and discharge
The shower curtain or door should be
not be able to use wall hung or slab rates required to keep the drainage
easy for the disabled user to manage.
urinals. system from the toilet areas used by the
Some magnetic door catches on cubicles
disabled community clean of soiled
require considerable dexterity. A shower
items.
curtain must hang inside the shower unit
which reduces the area that can be Grabrails
used. Grabrails are fitted in the bathroom to
provide support to the disabled user
Joints
The shower mixing valve should have
maximum temperature pre-set at 35°C when washing at the basin, getting into Ensure all joints are sealed with non-
and thermostatically controlled. This is and out of the bath and on and off the setting ceramic sealants.
especially important for those with WC. They should be positioned so that
sensory problems when the temperature the washbasin, toilet roll holder or towel
must be pre-set lower to suit their rail are never used for support through Hot water and heating
medical needs. An anti-scald shut off habit or emergency.
device must be provided as an essential Rails should be positioned to suit the Scope
component. individual. Standard layouts and NHS Estates Guidance Note DN4 gives
An instantaneous electric heater must combination may not be satisfactory. information for all health care and
contain an anti-scald device to cope with Walls and partition walls must be of personal social services premises,
variations in water pressure. There sufficient structural strength to support Registered Homes Act 1984 and non-
should be a visual method of checking the load exerted on the rail. registered premises such as sheltered
the water temperature for those with Reinforcement may be necessary. accommodation. All commercial activity
sensory problems. The unit must be to private or public homes and domestic
temperature pre-set to suit the user’s Installation should be carried out by a facilities within requirements for all
medical needs. The temperature leaving qualified person. patients, residents and visitors.
the shower-head must not exceed 35°C. Grabrails fitted in a bathroom or WC
The controls must be easy to operate must have an anti-slip finish. Requirement
and within safe reach of the user or Hinged grabrails should be checked All responsible persons including design
helper. It is recommended that the regularly to ensure that the hinge is in staff, supervisors and contractors/
shower be used for hairwashing and good working order. installers under the Health and Safety at
conveniently sited for this application. Work (etc.) Act 1974 have a ‘duty of care’
A shower head fitted to a flexible tube and should be able to demonstrate that
with wall-mountings at alternative heights Disposal of incontinence and they are providing a safe environment.
or a shower head with a sliding bracket This requirement is equally applicable to
on a wall-mounted tube are
sanitary towels new and existing premises.
recommended in preference to a fixed For reasons of hygiene and to prohibit Only where a resident or patient or user
spray position. The installaiton of these the spread of disease by contamination, is under adequate continuous
types of showers must be in compliance macerators or incinerators should be supervision may the use of low surface
with the Water Regulations, with regard installed instead of bins. Maintenance temperature radiators not be warranted.
to backflow. personnel must be protected against However what is adequate for one user
A tray for soap and sponges should be contracting diseases; incinerators are may not be adequate for all. It is
accessible to the user. threfore preferable. The use of recommended for safety reasons that the
macerators is only acceptable providing whole installation works comply to the
Floor drain gratings should be flush with maintenance personnel are given training Guidance Note DN4.
the floor. The grating material should be and protection against AIDS and other
nickel bronze or stainless steel. related diseases. Seek advice from Safe hot water temperature
Health and Safety at Work Commission.
Hot water distribution temperature will be
Bidets in excess of 50°C for the control of
Legionella. See the appropriate section
A bidet is recommended for independent
Drainage for details.
personal cleansing. The installation must If no disposal unit is made available, the Safe hot water temperature must not
conform to the Water Regulations. incontinence and sanitary towels will be exceed 35°C. All outlets must be
The seat height of the bidet must be placed into the WC Pan for disposal as thermostatically controlled and blended
suitable for the disabled ambulant no other facility is provided. This is not to temperatures below 35°C to
person; special models with a higher seat good practice. The designer should accommodate the user’s medical needs.
212
Plumbing Engineering Services Design Guide Designing for the disabled
Space heating
Living environment them easily. The controls must be so
situated to ensure that the user could not
Special consideration may be required be injured from the hot surfaces in the
Domestic hot water systems must not be
with regard to the design internal boiler. Boilers with sharp edges must be
used for space heating, towel rails, bed
temperature. This is particularly important avoided.
pan racks, etc.
for those users who do not move
frequently and would therefore require a
warmer environment. Each installation
must be considered individually to
Solid fuel
Advaaced WC determine the required temperature for
the user. In some instances, higher than
It is recommended that where possible,
solid fuel boilers should not be provided
cubicle desiga for standard design ventilation rates will be
required, these could be provided either
for disabled users. They must only be
considered when the user would be
capable of transferring fuel, removing
wheelchair disabled by natural ventilation, ie openable
windows or mechanical ventilation. In ashes, lighting and stoking the fire. The
those instances, the additional heat load associated dangers of this type of boiler
This uses the recommended guidelines must be included within the design of the must not be overlooked, particularly the
for the size of the WC compartment and heating system. necessity of the user coming into close
facilities. The WC compartment is contact with flames, heat and hot fuel
The standard design heating flow and and ashes. Where solid fuel boilers are
illuminated by an automatic light return temperatures of around 82°C and
incorporating an infra red device which used it is recommended that the fuel
71°C has to be used with convectors or feed should be hopper fed requiring the
switches ‘on’ when a disabled person low surface temperature radiators. If
enters the room and only switches ‘off ’ minimum of attention. The bunker itself
water temperatures are decreased it is may require special consideration to
after the person has left the room. imperative that heat output from the ensure that the fuel can be readily
The tap and hand dryer are operated by emitters are corrected. It will also be racked to the outlet; it may be necessary
automatic sensors. The sanitary fittings necessary to conceal or guard pipework to raise the bunker to provide adequate
are placed within easy reach of the to protect the user from the possibility of access. Consideration should be given to
disabled person whilst they are seated burns. providing a method of ash removal direct
on the WC Pan. All bare radiators and pipework and to outside so that it is not necessary for
Support rails of the standard size are controls within areas of use by disabled the user to carry hot ashes through the
placed in the positions shown in Figure and elderly persons must be screen premises.
4. The whole cubicle has a fail safe guarded to comply with Statutory
mechanism. requirements, low surface temperature
radiators being the exception. Gas/oil fired
Facilities should not be institutional
looking. They should be well designed The system should be designed to These are generally more reliable,
with good quality products and user ensure that all air and hydrogen dispels require less attention and are easier to
friendly. The designer should use a naturally through the open vent to avoid operate than solid fuel boilers. The
wheelchair to gain experience for the the necessity to vent radiators. Correct ignition system should be of the fully
user’s needs. Everyone is unique and a pipework gradients are therefore automatic self -igniting type to avoid the
person. essential. necessity of re-lighting the pilot in the
event of failure. If this cannot be provided
than a pilot having piezo or electronic
ignition should be used. Pilots requiring
manual ignition by flame should be
avoided. The fuel can be oil, natural or
liquid petroleum gas. If banks of liquid
petroleum gas bottles are provided
having standby or changeover provision ,
the valving arrangement must be readily
213
Designing for the disabled Plumbing Engineering Services Design Guide
214
#
^ 9 1
w. 4
Y\
t i 1111
Introduction 216
Pool shells 216
Filtration 218
Heating 219
Treatment 220
215
Domestic swimming pools Plumbing Engineering Services Design Guide
216
Plumbing Engineering Services Design Guide Domestic swimming pools
house air heating ductwork and water made of wood or even steel as difficulties the shell should be installed
pipes and in this case the strength of the developments progressed galvanised very quickly. There is, once again, a size
pool shell is of paramount importance. metal and basic fibreglass were used but and shape limitation.
today there are many composite ‘plastic’
The method of constructing shells can All the above comments apply to the
also vary. In commercial installations one wall panels of high quality available.
freeboard pool whether commercial or
These are held in the vertical plane by
method is a poured floor and shuttered domestic. The deck level pool with the
braces usually known as ‘A’ frames.
walls with both thickness and reinforcing water over flowing into a perimeter
according to the design. This is also These frames are set in concrete for
channel is usually built of reinforced
strength and support . Generally speaking
suitable for smaller pools but the cost of concrete rather than a traditional liner.
the shuttering can be a high. Cavity block this type of liner construction gives a
Once again there are products that are
constant panel depth of approximately 1
wall containing reinforced concrete tied the exception to this but they are few in
to a poured floor is a method widely used
metre. The floor profile can then be
graded from the bottom of the wall into number. It would be technically possible
in the domestic market and for smaller to have a prefabricated fibreglass pool in
commercial pools. In this case the two either a hopper or wedge shape.
this type but the practicality of it would be
block walls act as shuttering for the Blockwork can also be used for liner pool in doubt .
poured concrete in between once again walls; depending on the depth of the wall
both thickness and reinforcing according One common factor in relation to the
either hollow agricultural type or ordinary
to the design. The blockwork is quicker blocks can be used. However this type of proper installation of all pool shells is the
and cheaper to construct but due to the question of ground water. If the ground
wall has to have sand and cement
water pressure builds up the shell of the
block size is limited to gentle curves and rendering to provide a smooth finish,
therefore shape. pool will be at risk unless the pressure is
which will not puncture the liner material.
relieved. Battleships were made of steel,
Sprayed concrete , either Shotcrete or However the use of hollow blocks that
weighed thousands of tons and floated. If
Gunite depending on the aggregate size can be reinforced can give greater wall
and therefore water depths and this the pressure is greater than the water
is applied by spraying it under pressure and the weight of the concrete or
onto the pre-assembled reinforcement
leads to gentle constant slope floors. The
fibreglass shell it could lift or float the
frame. The constituents of the concrete sand used on the walls and floor should
be sharp sand as this gives a greater shell. In concrete pools not only should a
mixing at the nozzle of the spray gun. hydrostatic relief valve be fitted in the
This method of application results in a longevity. It is also good practice, with
block walls without reinforcement, to lowest point but also the drainage under
much lighter shell but one with a greater and around the structure should be such
degree of flexibility in shape. have a ring beam of concrete at the top
that the water can easily gravitate to the
of the wall, which is reinforced and runs
Stainless steel pools are structurally deepest point and if necessary operate
the length of the perimeter, to give added
designed to retain the weight of the water strength. the relief valve. Liner pools with their
in the same manner as the concrete porous base do not have hydrostatic
pool. Some products have supporting Again because of the construction of the relief valves because that water would
frames and others have reinforcing built walls liner pool have limitations in shape. permeate through the liner floor. Again
into them. They are considerably lighter Fibreglass pools were usually small one- the surround drainage should be
than the concrete type of shell and are piece shells or if larger were in two designed to take water away from the
structure as the liner will lift off the base
usually restricted to the deck level type of pieces. The fibreglass was not
pool as the surround channel adds to the particularly thick and the general and float and a floating liner is not
strength. In some cases stainless steel conducive to swimming. This, in extreme
principle on installation was to bed them
can be the finish and in others vinyl. soundly and then back fill between the cases, could mean the installation of a
Angular shapes are favoured rather than pumping chamber and float operated
shell and the dig with a lean-mix of
free form. concrete, which would give some
pump to take away the ground water. The
fibreglass shell should be protected in
Liner pools have a shell that is radically strength to the structure. Additionally
most, but not all, of these pools were of
the same way as the concrete pool. It is
different . To start with the water tightness therefore important to assess the ground
constant depth.
is achieved by a vinyl container (the water situation, and consider the winter
liner). The structure is non-reinforced and In the last few years there has been a months, before the installation is started
the floor of the pool is porous. The resurgence of this type of pool but with so that all necessary precautions can be
porosity of the floor is to allow ground better construction techniques used. The included in the specification.
water to permeate through it should the shells are made of good marine
ground water pressure become greater Although a discussion on the relative
fibreglass, with timber incorporated to
than the weight of the water in the pool merits of the many pool finishes is not
provide structural support, and are
at which time the flexibility of the liner included here, the internal finish of the
designed to hold water in or out of the
allows movement to prevent collapse. pool does have a bearing on the
ground. They are now usually factory
The liner is supported by a structure, selection of pool shell construction
fitted with flow control fittings and
method. The appearance and feel of the
which is not meant to have any great pipework to ease plant installation. They
finished pool is important to the users,
strength in relation to the ground and also come in quite a range of sizes. This
water, but is there to give shape to the in itself is one of the problems with this especially in the domestic market.
pool and to keep the liner in place. For type of shell. The larger they are the The different methods of construction
this reason, this liner system is not heavier and more difficult they are to described earlier indicate that there is an
generally used for large commercial transport and to get into the site. They obvious cost difference between concrete
installations however there are some are moved with the use of low loader pools and liner pools. Whether there is
products which are similar and due to lorries, large cranes and even an appreciable difference between liner
their more robust design have structural helicopters. Once the excavation is pools and fibreglass pools will depend on
strength. completed the pool is lowered onto the the problems on site related to access
The supporting structure can be drainage bed on the floor of the hole, and general transportation. The actual
constructed of a variety of materials. leveled and the backfilling carried out. costs will also depend on a number of
Years ago one would see liner walls Consequently despite the logistical factors, which vary from design to design
217
Domestic swimming pools Plumbing Engineering Services Design Guide
Figure 1 Schematic domestic swimming pool layout of family pool with large step area for small toddlers
and from project to project, consequently media produce a finer filtration the
it is very difficult to be precise. One must Filtration operational problems are such that they
are rarely if ever used.
bear in mind that the surround work,
filtration, heating etc are going to be the In a swimming pool the filtration system The water in the sand filter should pass
same regardless of the shell construction is there to remove, as far as possible the uniformly through the surface area and it
and that there will be some variation in suspended inorganic matter from the is the relation of the speed of the water
the cost of internal finish. water. This is done in all pools by a and the surface area that give the
pump(s) sucking the water from the pool filtration rate in m3/m 2/per hour.
tank, blowing it through a filter medium
Internal finishes and thereafter back into the pool tank. Low rate filtration up to 10m3/m 2 /per hour
The filter medium can be a fine powder is rarely if ever used these days . Medium
The liner and fiberglass pool have their rate from 1 1 - 3 0 m 3/m2/per hour is
finish as an integral part of the system. It called diatomaceous earth or a material
widely used in commercial pools and is
is only the concrete structure that is tiled similar to cartridge paper but these days
graded silica sand is mainly used . Sand recommended by PWTAG and SPATA .
either with ceramic or vitreous glass High rate from 31 - 50m3/m 2 /per hour is
mosaics. The large commercial pool is provides a particulate removal down to
10 microns and although the other two the preferred rate for the domestic
nearly always tiled with large ceramic tiles. market although it is true to say that this
218
Plumbing Engineering Services Design Guide Domestic swimming pools
219
Domestic swimming pools Plumbing Engineering Services Design Guide
Treatment
Pool water needs to be treated to remove
the organic mater, bacteria etc, which
enters the water on bathers and is
generally blown or taken into it. There are
several options but chlorine is the most
widely used. However ozone and ultra-
violet are also to be considered.
Not only should a 'disinfectant ' be applied
but also water balance has to take into
account of the pH, the total alkalinity, the
calcium hardness and the total dissolved
solids.
220
4
"
Introduction 222
General 222
Metal pipes and services 222
Plastic pipes and services 225
Size of bonding conductors 225
221
Electrical earthing and bonding of building services Plumbing Engineering Services Design Guide
Bonding to be as
near as possible
Consumer to point of entry
Earthing into customer's
unit bar premises - on
customer's side of
gas meter
within 600mm of
same and onto
/ hard metal pipes
before any tee-joints
Meter
10mm2 minimum
fU Gas
meter
LI
Intake
terminal
earthing /
unit terminal /
Customer's metallic water
and gas pipes and other
metallic services (except
telephone) to be bonded
16mm2 minimum
222
Plumbing Engineering Services Design Guide Electrical earthing and bonding of building services
— 1 Ceiling
a
Metal Pull cord switch [ ] Luminaire
pipe
i . Outside zones
Zone 2 Zone 3
Zone 1
I Shaver
unit
3.0m
IgJ
Zone 2
. 0 Zone 3 2.25m
NOTES:
1. The protective
conductors of all
power and lighting
s~\ points within the
zones must be
supplementary
bonded to all
extraneous-
m conductive- parts
ff
Metal waste be used as
0.6m 2.4m supplementary
> > bonding
conduct m s
* Zone 1. If the space is accessible without the use of a tool.
Spaces under the bath, accessible only with the use of a tool are outside the zones.
Ceiling
Plastic Pull cord switch
pipe
t,
Outside zones
Zone 2 Zone 3
i Shaver
3.0m Zone 1 Zone 2 Zone 3 2.25m
3=5 NOTES:
1. The protective
conductors of all
power and lighting
points within the
zones must be
P 0 <
I
supplementary
bonded to all
extraneous-
conductive-parts
in the zones,
Zone 0 UUJS Plastic pipes including metal
^
Plastic waste waste, water and
central heating
pipes, and metal
baths and metal
shower basins.
2. Circuit protective
conductors may
Plastic waste be used as
0.6m 2.4m supplementary
< + > bonding
conductors.
* Zone 1. If the space is accessible without the use of a tool.
Spaces under the bath, accessible only with the use of a tool are outside the zones.
223
Plumbing Engineering Services Design Guide Electrical earthing and bonding of building services
section or insert at that point or there is a b. Metal central heating pipes and air Earthing and bonding
meter, the connection must be made to conditioning systems
the consumers’ hard metal pipework and
c. Accessible metal structural parts of
damps and labels
before any branch pipework. Where
the building (metallic door architraves, Earthing and bonding conductors must
practicable the connection should be
metal handrails, window frames and be connected to metal pipes with clamps
made within 600mm of the meter outlet
similar parts are not considered to be to BS 951 ( Specification for clamps for
union or at the point of entry to the
extraneous-conductive-parts unless earthing and bonding purposes ) . A
building, if the meter is external.
they are connected to metallic permanent label also to BS 951 with the
structural parts of the building) words.
Supplementary equipotential d. Metal baths and metallic shower
basins. SAFETY ELECTRICAL CONNECTION - DO NOT REMOVE
bonding in locations of
The supplementary equipotential bonding
increased shock risk - metal may be provided in close proximity to the shall be permanently fixed in a visible
pipework location. position at or near the point of
A typical installation is shown in Figure 2. connection of:
Supplementary equipotential bonding is
required only in locations of increased a. Every main and supplementary
shock risk such as those as in Part 6 of bonding conductor
the Wiring Regulations (471-08-01). In Supplementary bonding in c. Every earthing conductor to an earth
domestic premises the locations
identified as having increased shock
other locations - metal electrode
risks are rooms containing a bath or pipework d. At the main earthing terminal (where
shower (bathrooms) and around the terminal is not part of the main
There is no specific requirement in the switchgear)
swimming pools.
Wiring Regulations to supplementary
In a bathroom or shower room, local bond the following: e. Plastic pipes and services.
supplementary equipotential bonding is
a. Kitchen pipes, sinks or draining
required to be provided, connecting
boards
together the terminals of protective
conductors of each circuit supplying b. Metallic pipes and wash handbasins
Class 1 and Class 2 equipment in zones in domestic locations other than
1, 2 or 3 and extraneous-conductive- bathrooms.
parts in these zones including the
following: NOTE
Metal waste pipes in contact with earth should
a. Metal pipes supplying services and be main bonded back to the main earthing
metallic waste pipes (eg water, gas) terminal.
224
Plumbing Engineering Services Design Guide Electrical earthing and bonding of building services
Supplementary bonding of
plastic pipe installations
Supplementary bonding is not required to
metallic parts supplied by plastic pipes
such as metal hot and cold water taps
supplied from plastic pipes or a metal
bath not connected to extraneous -
conductive-parts such as structural
steelwork and where the hot and cold
water pipes and the waste are plastic.
Supplementary bonding in a bathroom or
shower room will still be required
between the protective conductors of
circuits supplying Class 1 and Class 2
equipment in the zones, eg heaters,
showers and luminaires, see Figure 3.
Figure 4 Requirements for bonding in domestic situations (not intended to be used as a design
for a plumbing installation).
Plastic pipe central
heating systems
Where metallic radiators are supplied by
Size of bonding
plastic pipes, there is no requirement to
supplementary bond the metallic radiator conductors
including any radiator in the bathroom,
unless the radiator incorporates an Where bonding is required, the minimum
electric fan. size of copper conductor is given below:
It is common practice to use plastic pipe Main bonding 10mm2 PME supplies
works for the generality of a plumbing conductor
installation, and use copper pipe just for
visible parts of the pipe runs. There is no Earthing 16mm2 for PME
need to supplementary bond such visible conductor supplies
metal parts of pipework as are supplied Supplementary 4mm2 where
by plastic pipes. bonding mechanical protection
conductor is not provided.
The size of main earthing, main
equipotential and supplementary bonding
conductors when insulated are given in
Tables 2, 3 and 4 .
225
Electrical earthing and bonding of building services Plumbing Engineering Services Design Guide
Table 2 Main earthing and main equipotential bonding conductor sizes (copper
equivalent) for TN-S and TN-C-S supplies
Phase conductor or
neutral conductor of ( mmz) 6 6 10 16 25 35 50 70
PME supplies
Earthing conductor
not buried or buried
protected against corrosion (mm2) 6 6 10 16 16 16 25 25
and mechanical damage
see notes
Main equipotential
bonding conductor (mm2) 6 6 6 10 10 10 16 16
see notes
Main equipotential
bonding conductor ( mm2) 10 10 10 10 10 10 16 25
for PME supplies
(TN -C-S)
1. Protective conductors (including earthing and bonding conductors) of 10mm2 cross -sectional
area or less shall be copper.
2. Regional electricity companies may require a minimum of earthing conductor at the origin of
the supply of 16mm2 copper or greater for TN-S and TN-C-S supplies.
3. Buried earthing conductors must be at least:
25mm2 copper if not protected against mechanical damage or corrosion
50mm2 steel if not protected against mechanical damage or corrosion
16mm2 coated steel if not protected against mechanical damage but protected against
corrosion.
4. Regional electricity companies should be consulted when in doubt .
1. If one of the extraneous-conductive-parts is connected to an exposed-conductive -part, the bond must be no smaller than that required for
bonds between exposed -conductive-parts - columns 3 or 4.
Table 4 Copper earthing conductor cross -sectional areas (csa) for TT supplies for earth fault loop impedances not less than
1 ohm (Q )
Buried Not Buried
Unprotected Protected against Protected against Unprotected Protected against Protected against
corrosion corrosion and corrosion corrosion and
mechanical damage mechanical damage
226
227
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
& Codes of Practice BS EN 1213 : Building valves - Copper alloy stop valves for
potable water in buildings General technical specifications.
BS EN 1254 : Copper and copper alloys - Plumbing fittings.
Some of the BS ENs listed below were still to be published at
the time of writing this guide. On publication these BS ENs will BS EN 1254 •1 : Fittings with ends for capillary solder.
often completely or partially replace a British Standard, which
BS EN 1254 - 2 : Fittings with compression ends for copper
will then be withdrawn or revised as appropriate. The exact title tube.
and possibly the number of parts may vary slightly when new
BS ENs are actually published. BS EN 1254 - 3 : Fittings with compression ends for plastic
pipes.
Users are advised to check the current status of these
documents before using them. BSI have an excellent web site -
BS EN 1254 4 : Fittings combining other end connections
where on line checks can instantly be made. with capillary or compression ends.
www.bsi-global.com BS EN 1254 - 5 : Fittings with short ends for capillary brazing
to copper tubes.
Hot and cold water supplies -
BS EN 1452 Plastic piping systems for water supply - PVC -U.
BS EN 1452 - 1 : General.
Design
BS EN 1452 - 2 : Pipes.
BS EN 805 : Water supply - Requirements for systems and
components outside buildings. BS EN 1452 - 3 : Fittings.
BS EN 806 : Specification for installations inside buildings BS EN 1452 - 4 : Valves and ancillary equipment.
conveying water for human consumption. BS EN 1452 - 5 : Fitness for purpose of the system.
-
BS EN 806 1 : General. -
BS EN 1452 6 : Recommended practice for installation.
BS EN 806 - 2 : Design. BS EN 1452 - 7 : Assessment of conformity.
-
BS EN 806 3 : Pipe sizing. BS EN 1508 : Water supply - Requirements for systems &
BS EN 806 - 4 : Installation. components for the storage of water.
BS 699 : Specification for copper direct cylinders for domestic BS 6282 : Devices with moving parts for the prevention of
purposes. contamination of water by backflow.
228
Plumbing Engineering Services Design Guide Standards, codes and miscellaneous data
229
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
-
BS EN 1254 3 : Fittings with compression ends for plastic Sanitary plumbing and drainage
pipes.
Design
-
BS EN 1254 4 : Fittings combining other end connections
with capillary or compression ends. BS EN 752 : Drain and sewer systems outside buildings.
BS 1387 : Specification for screwed and socketed steel tubes
and tubulars and for plain steel tubes suitable for welding or for
-
BS EN 752 1 : Generalities and definitions.
BS EN 752 - 2 : Performance requirements.
screwing to BS 21 pipe threads.
BS EN 752 - 3 : Planning.
BS 1552 : Specification for open bottomed taper plug valves for
1st, 2nd and 3rd family gases up to 200mbar. -
BS EN 752 4 : Hydraulic design and environmental
BS 3016 : Specification for pressure regulators and automatic
considerations.
change-over devices for liquefied petroleum gases. -
BS EN 752 5 : Rehabilitation.
BS 3212 : Specification for flexible rubber tubing, rubber hose BS EN 752 - 6: Pumping installations.
and rubber hose assemblies for use in LPG vapour phase and
BS EN 752 - 7 : Maintenance and operations.
LPG/air installations.
BS EN 858 : Installations for separation of light liquids (oil &
BS 3554 : Specification for gas governors.
petrol).
BS 3554 - 1 : Independent governors for inlet pressures up to
25mbar. -
BS EN 858 1 : Principles of deign, performance, testing,
marking and quality control.
BS 3554 - 2 : Independent governors for inlet pressures up to
BS EN 1085 : Wastewater treatment - vocabulary.
350mbar.
BS EN 1091 : Vacuum sewerage systems outside buildings.
BS 3601 : Specification for carbon steel pipes and tubes with
specified room temperature properties for pressure purposes. BS EN 12109 : Vacuum Drainage in Buildings.
BS 3604 : Steel pipes and tubes for pressure purposes - BS EN 1295 : Structural design of buried pipelines under
Ferritic alloy steel with specified elevated temperature various conditions of loadings - General requirements.
properties.
BS EN 1610 : Construction and testing of drains and sewers.
-
BS 3604 1 : Specification for seamless and electric resistance
BS EN 1671 : Pressure sewer systems outside buildings.
welded tubes.
BS EN 1825 Part 2 : Installations for separation of grease.
-
BS 3604 2 : Specification for longitudinally arc welded tubes.
BS 6297 : Code of Practice for design and installation of small
BS 3605 : Austenitic stainless steel pipes and tubes for
pressure purposes. sewage treatment works.
BS 6465 : Sanitary installations.
-
BS 3605 1 : Specification for seamless tubes.
BS 3605 • 2 : Specification for longitudinally welded tube. -
BS 6465 1 : Code of practice for scale of provision, selection
and installation of sanitary appliances.
BS 4089 : Specification for metallic hose assemblies for liquid
petroleum gases and liquefied natural gas. -
BS 6465 2 : Code of practice for space requirements for
sanitary appliances.
BS 4161 : Gas meters.
BS EN 12056 - Gravity drainage systems inside buildings.
BS 4161 - 8 : Specification for electronic volume correctors.
BS EN 12056 •1 : General performance requirements.
BS 4250 : Specification for commercial butane and commercial
propane. -
BS EN 12056 2 : Sanitary pipework, layout and calculation.
BS EN 12056 - 3 : Roof drainage, layout and calculation.
BS 7281 : Specification for polyethylene pipes for the supply of
gaseous fuels. -
BS EN 12056 4 : Wastewater lifting plants, layout and
BS 7336 : Specification for polyethylene fusion fittings with calculation.
integral heating elements(s) for use with polyethylene pipes for -
BS EN 12056 5 : Installation and testing, instructions for
the conveyance of gaseous fuels. operation and use.
BS 7838 : Specification for corrugated stainless steel semi-rigid BS EN 12566 : Small wastewater treatment plants less than
pipe and associated fittings for low pressure gas pipework of up 50pt.
to 28mm.
Materials
BS 65 : Specification for vitrified clay pipes, fittings and ducts,
also flexible mechanical joints for use solely with surface water
pipes and fittings.
BS EN 124 : Gully tops and manhole tops for vehicular &
pedestrian areas - Design requirements, type testing, marking,
quality control.
BS EN 274 : Sanitary tapware - Waste fittings for basins,
bidets & baths. General technical specification.
BS EN 295 : Specification for vitrified clay pipes and fittings
and pipe joints for drains and sewers.
230
Plumbing Engineering Services Design Guide Standards, codes and miscellaneous data
231
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
232
Plumbing Engineering Services Design Guide Standards, codes and miscellaneous data
Fire protection services BS 3604 : Steel pipes and tubes for pressure purposes -
Ferritic alloy steel with specified elevated temperature
Design properties.
BS 5306 : Fire extinguishing installations and equipment on BS 3604 - 1 : Specification for seamless and electric resistance
premises. welded tubes.
-
BS 5306 0 : Guide for the selection of installed systems and BS 3604 • 2 : Specification for longitudinally arc welded tubes.
other fire equipment.
BS 3605 : Austenitic stainless steel pipes and tubes for
BS 5306 - 1 : Hydrant systems, hose reels and foam inlets. pressure purposes.
BS 5306 - 2 : Specification for sprinkler systems. BS 3605 - 1 : Specification for seamless tubes.
BS 5306 - 3 : Maintenance of portable fire extinguishers - BS 3605 - 2 : Specification for longitudinally welded tube.
Code of practice.
EN 671 : Fixed fire fighting systems - Hose systems.
-
BS 5306 4 : Specification for carbon dioxide systems.
BS EN 671 •1 : Hose reels with semi-rigid hose.
BS 5306 - 5.1 : Halon systems - Specification for halon 1301
total flooding systems. -
BS EN 671 2 : Hose systems with lay-flat hose.
BS EN 671 •3 : Maintenance of hose reels with semi-rigid
systems.
-
BS 5306 5.2 : Halon systems - Halon 1211 total flooding
hose and hose systems with-lay flat hose.
BS 750 : Specification for underground fire hydrants and
-
BS 5306 6.1 : Foam systems - Specification for low
surface box frames and covers.
expansion foam systems.
BS 1635 : Graphic symbols and abbreviations for fire protection
BS 5306 - 6.2 : Foam systems - Specification for medium and
drawings.
high expansion foam systems.
BS 3169 : Specification for first aid reel hoses for fire brigade
-
BS 5306 8 : Selection and installation of portable fire purposes.
extinguishers - Code of practice.
BS 3251 : Specification - Indicator plates for fire hydrants and
BS 5588 : Fire precautions in the design, construction and use
of buildings.
emergency water supplies.
BS 5041 : Fire hydrant systems equipment .
-
BS 5588 0 : Guide to fire safety codes of practice for
particular premises/applications. -
BS 5041 1 : Specification for landing valves for wet risers.
BS 5588 •1 : Code of practice for residential buildings. BS 5041 • 2 : Specification for landing valves for dry risers.
-
BS 5588 4 : Code of practice for smoke control using -
BS 5041 3 : Specification for inlet breechings for dry riser
pressure differentials. inlets.
-
BS 5588 5 : Code of practice for firefighting stairs and lifts. BS 5041 - 4 : Specification for boxes for landing valves for dry
risers.
BS 5588 - 6 : Code of practice for places of assembly.
BS 5588 - 7 : Code of practice for the incorporation of atria in -
BS 5041 5 : Specification for boxes for foam inlets and dry
riser inlets.
buildings.
BS 5588 •8 : Code of practice for means of escape for
disabled people.
-
BS 5588 9 : Code of practice for ventilation and air
conditioning of buildings.
-
BS 5588 10 : Code of practice for shopping complexes.
BS 5588 - 11 : Code of practice for shops, offices, industrial,
storage and other similar buildings.
Materials
BS 336 : Specification for fire hose couplings and ancillary
equipment.
BS EN 1254 : Copper and copper alloys - Plumbing fittings.
BS EN 1254 •1 : Fittings with ends for capillary solder.
BS EN 1254 • 2 : Fittings with compression ends for copper
tube.
-
BS EN 1254 4 : Fittings combining other end connections
with capillary or compression ends.
BS 1387 : Specification for screwed and socketed steel tubes
and tubulars and for plain steel tubes suitable for welding or for
screwing to BS 21 pipe threads.
BS 3601 : Specification for carbon steel pipes and tubes with
specified room temperature properties for pressure purposes.
233
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
Pipework Expansion
BS 4618 - 3.1 : Recommendations for the presentation of
plastic design data - Thermal properties - Linear thermal
expansion.
BS 6129 - 1 : Code of practice for the selection and application
of bellows expansion joints for use in pressure systems -
Metallic bellows expansion joints.
BS EN 26801 : Rubber or plastic hoses - Determination of
volumetric expansion.
Mechanical Ventilation
BS 5720 : Code of practice for mechanical ventilation and air
conditioning in buildings.
pr EN 13141 - 7 : Ventilation for buildings - Performance
testing of components/products for residential ventilation -
Part 7: Performance testing of a mechanical supply and
exhaust ventilation units (including heat recovery) for
mechanical ventilation systems intended for single family
dwellings.
234
Plumbing Engineering Services Design Guide Standards, codes and miscellaneous data
235
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
Pressure Pressure
Head in metres kN/m2 or kPa mbar & bar Head in metres kN/m2 or kPa mbar & bar
1 9.81 98 mbar 18.36 180 1.80 bar
1.02 10 100 mbar 19 186.33 1.86 bar
2 19.61 196 mbar 19.38 190 1.90 bar
2.04 20 200 mbar 20 196.13 1.96 bar
3 29.42 294 mbar 20.40 200 2.00 bar
3.06 30 300 mbar 25 245.17 2.45 bar
4 39.23 392 mbar 25.49 250 2.50 bar
4.08 40 400 mbar 30 294.20 2.94 bar
5 49.03 490 mbar 30.59 300 3.00 bar
5.10 50 500 mbar 35 343.23 3.43 bar
6 58.84 588 mbar 35.69 350 3.50 bar
6.12 60 600 mbar 40 392.27 3.92 bar
7 68.65 686 mbar 40.79 400 4.00 bar
7.14 70 700 mbar 45 441.30 4.41 bar
8 78.45 785 mbar 45.89 450 4.50 bar
8.16 80 800 mbar 50 490.33 4.90 bar
9 88.26 883 mbar 50.99 500 5.00 bar
9.16 90 900 mbar 60 588.40 5.88 bar
10 98.07 981 mbar 61.18 600 6.00 bar
10.20 100 1.00 bar 70 686.47 6.86 bar
11 107.87 1.08 bar 71.38 700 7.00 bar
11.22 110 1.10 bar 80 784.53 7.85 bar
12 117.68 1.18 bar 81.58 800 8.00 bar
12.24 120 1.20 bar 90 882.60 8.83 bar
13 127.49 1.27 bar 91.77 900 9.00 bar
13.26 130 1.30 bar 100 980.66 9.81 bar
14 137.29 1.37 bar 101.97 1 MN/m2 10.00 bar
14.28 140 1.42 bar 200 1.96 MN/m2 19.61 bar
15 147.10 1.47 bar 203.94 2MN/m2 20.00 bar
15.30 150 1.50 bar 300 2.94 MN/m2 29.42 bar
16 156.91 1.57 bar 305.92 3 MN/m2 30.00 bar
16.32 160 1.60 bar 400 3.92 MN/m2 39.23 bar
17 166.71 1.67 bar 407.89 4 MN/m2 40.00 bar
17.34 170 1.70 bar 500 4.90 MN/m2 49.03 bar
18 176.52 1.77 bar 509.86 5 MN/m2 50.00 bar
The use of various units to describe pressure is creating some confusion and the increasing use of the Pascal ( Pa) in lieu of the N/m2 or the Bar may
lead eventually to it becoming the most commonly used unit of pressure. This guide does not use the Pascal as a unit of pressure but generally refers
2 2 and the symbol has
to the SI unit for pressure, which is the N/m .
2 However , as 1 Pa is equal to IN/ m it presents no difficulty in relating Pa to N/ m
been added to the table above to enable the user to more fully understand its function.
236
Plumbing Engineering Services Design Guide Standards, codes and miscellaneous data
Hydrostatic tables
Table 3 Atmospheric pressure at sea level
SI Metric units
1 Litre of water weighs 1 kilogram
1 Cubic meter of water equals 1000 litres
Head of water in meters x 9810 = pressure in N/m2
Head of water in meters x9.81 = pressure in kN/m2
Pressure in kN/m2 x 0.120 = Head of water in meters
1 Bar equals 1000 mbar = 105N/m2 = 10Pa
1 millibar ( mbar) = 100N/M2 =100Pa
Imperial units
1 Gallon of water weighs 10 pounds
1 Gallon of water equals 0.16 Cubic feet
6.25 Gallons of water equals 1 Cubic foot
Head of water in feet x 62.5 = pressure in lbf/ft2
Head of water in feet x 0.434 = pressure in lbf/in2
Pressure in lbf/in2 x 2.3 = Head of water in ft
237
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
238
Plumbing Engineering Services Design Guide Standards, codes and miscellaneous data
Spacing of pipes Table 7 Minimum Distance allowable between centre lines of screwed steel and
copper pipes
The accompanying table gives the Minimum distance between furring (F), (mm)
Minimum Norn.
allowable minimum distances between
(a) two pipes, (b) pipe and wall and (c)
distance pipe 38 | 41 | 48 | 51 | 54 j 64 | 70 | 79 l 95 | 114 | 127 | 152
from wall size Nominal pipe size ( mm)
pipe and furring for two pipes with (K )
standard malleable or cast iron screwed 15 | 20 l 25 | 32 | 40 | 50 | 66 80 | 100 | 125 | 150 | 200
fittings. (mm) ( mm) Distance between pipes (mm)
216 200 323 238 241 248 251 257 267 276 289 305 321 356
The table has been developed on the
168 150 187 191 194 200 203 210 219 229 241 260 273
basis of the following analysis: between
two pipes of differing diameter there will 146 125 165 168 171 178 181 187 197 206 219 235
be two values for the minimum distance 124 100 140 143 146 152 156 165 171 181 197
which will allow free turning of an elbow 98 90 117 120 124 130 133 140 149 159
or tee. The value used will depend upon 86 65 101 108 111 117 120 127 133
which pipe is installed first. 73 50 92 95 98 101 108 114
In order that there will be no confusion 60 40 79 83 86 92 95
as to which pipe should be installed first, 54 32 76 79 83 89
the condition giving the greater distance 48 25 73 76 79
between pipes will be considered. It is 41 20 70 73
fairly obvious that turning the fitting on 38 15 67
the larger pipe will require the large
space between pipes for clearance,
therefore less space will be required if Maximum spacing of pipe supports
the larger pipe is installed first. Table 8 Hot and cold water pipes and gas pipes
It is evident that the minimum distance
Type of Piping Size of pipe Spacing for Spacing for
for the wall will be that distance which
Horizontal Vertical
will allow turning of a fitting on the pipe. ( mm) (m) ( m)
This will be the distance K shown in the
first column of the table. Lead All sizes 0.6* 0.9
Copper 12 1.2 1.8
The minimum distance from furring (light gauge) and 15- 28 1.8 2.4
(dimension F in the table) will not be less Stainless steel 35- 42 2.4 3.0
than 6mm larger than the radius of
insulated pipe, because furring is 54 2.7 3.0
constructed after pipes have been 76- 133 3.0 3.6
installed. 159 3.6 4.2
Steel to BS 1387 10-15 1.8 2.4
It should be noted that, for pipes smaller and Copper 20-25 2.4 3.0
than 25mm, the distance for insulation is (heavy gauge)
larger than that required for turning 32 2.7 3.0
fittings. Therefore, on such small pipes, 40-50 3.0 3.6
only the allowance for insulation has 65-80 3.6 4.5
been considered in the table. 100-125 4.0 4.5
150 4.5 5.4
Example Grey or 50 1.8 1.8
ductile iron 75- 100 2.7 2.7
Find the minimum space required for
32mm and 100mm pipes of the smaller 150 3.6 3.6
pipe is located near the wall. ' For pipes conveying hot water and where it is essential to avoid air locks (e.g . primary
circulation pipes), continuous support is recommended.
Sohitioi
The table shows, under 32mm and Table 9 Soil and waste pipes ' At least one fixing must be provided for each unit length
opposite 100mm pipes, that 152mm is the Type of piping Size of pipe Spacing for Spacing for
minimum distance between 100mm and horizontal vertical
32mm pipes. (mm) (m) (m)
To the left of 32mm in the second column Cast iron’ All sizes 2.0 3.0
of the table, find 54mm as the minimum Copper as for water pipes
distance from the wall of the smaller pipe.
Steel to BS 1387 as for water pipes
The distance from the furring of the larger Lead (single tacks) Up to 50 0.6
pipe is found (above 100mm) to be 95mm. 50 and over 0.9
The total space is thus Lead (double tacks) All sizes 1.2
152 + 54 + 95 = 301mm uPVC 32-40 0.5 1.2
In the same manner it can be shown that 50 0.6 1.2
the total space if the pipes were reversed 75-100 0.9 1.8
would be 152 + 124 + 51 = 327mm, 150 1.2 1.8
so it would be advisable to locate the ABS 32-40 0.5 1.2
smaller pipe near the wall or column. 50 0.7 1.2
Polypropylene 32-40 0.5 1.2
50 0.7 1.2
239
Standards, codes and miscellaneous data Plumbing Engineering Services Design Guide
Pipe or duct Cold Natural Electricity Telecom- Hot water Ventilation Drainage Oil Flammable Compressed
conveying water gas munications and steam and air gases and air
conditioning liquids
Hot water & steam A O A A F C C L 0
Ventilation & air
Conditioning F L A A F C C L O
Cold water O A A F F C C c O
Electricity C F M B B C C L 0
Telecommunications C F M B B C C L 0
Natural Gas C F F C L AC C L G
Drainage D D A A D D D L D
Oil C J A A B B C O 0
Flammable gases &
Liquid C L L L L L L O L
Compressed air 0 G 0 A O O C O L
It is on occasions necessary to run different services to the same position to operate equipment connected directly to a number of services, eg.
Motor -driven pumps, thermostatic valves, electrically operated gas valves, etc. The above precautions should be taken in each instance as far as
practicable.
O. No precautions necessary. G. Not to be run in such a position as would cause any escape of
A. Not to be run adjacent to. air to circulate a gas leakage, or to make the leakage become
B. Not to be exposed to temperature or leakage from. more dangerous.
C. Not to be exposed to leakage from. J. Not to be run where an escape of gas could cause risk of
D. Not to be exposed to effluent from. ignition in presence of oil .
F. Shall not be prevented by spacing, insulation or other means L. Not to be run in same duct.
from coming into contact with. M. Not to be run adjacent to without further precautions.
Miscellaneous data
Table 11 Multiples and sub-multiples of units
x factor Prefix Symbol
1,000,000,000,000 1012 Tera T
1,000,000,000 109 Giga G
1,000,000 106 Mega M
1,000 103 Kilo k
100 102 Hecto h
10 101 Deca da
1
0.1
°
10 Basic unit
10-1 Deci d
0.01 10 1 Centi
‘
c
0.001 10 3 Milli
'
m
0.000 0001 10 6 Micro
'
p
240
thelnstitute
of Plumbing