TVR™ Ultra

A cutting-edge solution for different


applications
Index
Index

Outdoor Unit Lineup 380V 4 Controller Lineup 43

Outdoor Unit Lineup 220V 5 BACnet® Gateway 57

Indoor Unit Lineup 6 LonWorks® Gateway 58

Wide Application Range 7 Modbus® Gateway 59

High Efficiency 7 Hotel Key Card Interface Modules 60

High Reliability 9 Diagnosis Software 61

Easy Installation and Service 12 VRF AHU Control Box 62

Specifications 220V 14 Heat Recovery Ventilator 63

Specifications 380V 21 DC Series Specifications 64

Wide Application Range 29 Branch Joints 65

Comfort and Efficiency 29 Outdoor Branch Joints 66

Indoor Branch Joints 67

3
Outdoor Unit Lineup
380V

HP 8 10 12 14 16 18 20 22 24 26 28 30 32
Outdoor Unit Lineup

Appearance

(with single fan) (with single fan) (with dual fans) (with dual fans)
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96

4
Outdoor Unit Lineup
220V

HP 8 10 12 14 16 18 20 22 24 26 28

Outdoor Unit Lineup


Appearance

(with single fan) (with single fan) (with dual fans) (with dual fans)
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
96

5
Indoor Unit Lineup

kW 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 20.0 25.0 28.0 40.0* 45.0* 56.0*
Indoor Unit Lineup

Btu/h x 1000 5 7 9 12 15 19 24 27 30 34 38 42 48 55 68 85 96 136 154 191

One-way Cassette

Two-way Cassette

Compact
Four-way Cassette

Four-way Cassette

Medium Static
Pressure Duct

High Static
Pressure Duct

Fresh Air Processing


Unit

Wall Mounted
Unit

Ceiling / Floor Unit

Floor Standing Unit

Console

6
Wide Application Range
Wide Capacity Range

Starting at 8HP, capacity increases in 2HP increments up to 96HP,


which is the world’s largest single-system VRF capacity.

380V, 50-60 Hz 220V, 50-60 Hz

Outdoor Unit
8/10/12 HP 14/16 HP 18/20/22 HP 24/26/28/30/32 HP 8/10/12 HP 14/16 HP 18/20/22 HP 24/26/28/30/32 HP
(single fan) (single fan) (dual fan) (dual fan) (single fan) (single fan) (dual fan) (dual fan)

16-64 HP 66-96 HP 16-56 HP 58-64 HP 86-96 HP

High Efficiency
Extended compressor speed from 15rpm to
140rpm

1 Vapor injection technology


Improves heating.

2 Improved compressor design


Better overall.

3 Release Valve improvement


Noise reduction & better performance.

4 Non-contact oil membrane


Reduces friction and improves reliability.

5 Advanced bearing design for high speed running


Broader frequency range

6 Improved compressor design


Better overall performance.

7 New BLDC motor


Better efficiency, especially at part load.

8 High pressure chamber structure


Better lubrication, lower noise level and higher stability.

9 Better oil management


New oil circulation, positive displacement gear oil pump and
dynamic oil balance

7
Optimized Heat Exchanger Electricity Demand Setting
24-32HP units use a high efficiency 3-row G-shape heat Through the integration of EMS, for projects with temporary
exchanger with a heat exchange area 1.5 compared to the 22HP electrical supply restrictions, TVR Ultra can be adjusted to work
unit. between 40-100% of its capacity.

A super-sized 750mm diameter fan is used for a higher heat


exchange.

100%
Outdoor Unit

90%

80%

70%

60%

50%

40%

Energy Management System (EMS)


Effective
Refrigerant temperature management Capacity

Refrigerant temperature is automatically adjusted according to


both outdoor temperature and room demand to maximize space
Refrigerant Variable Temp.
comfort and energy efficiency.
Temperature Fixed Temp.

Capacity is controlled by the inverter compressor and variable


refrigerant temperature in order to achieve the highest seasonal
efficiency.
SEER EER Variable Temp.
EER Fixed Temp.
Seasonal energy efficiency can be increased by 30%.
15°c 20°c 25°c 30°c 35°c Outdoor Temp.
1°c 2°c 3°c 4°c 5°c Room temp. - Setpoint

8
Extended Operational Range High Reliability
During summer, with temperatures of up to 54°C, the TVR Ultra Electrical connections protection
series unit will continue in the cooling mode.
During winter, with temperatures as low as -23°C, the TVR Ultra Special internal protection circuitry is designed to protect the
series unit will continue in the heating mode. system from any wrong connection between live and neutral wiring.

-5°C(23°F) 54°C(129°F)

Outdoor Unit
COOLING MODE

-25°C(-13°F) 24°C(75°F)

HEATING MODE

Extended piping length Advanced Oil Control


Extended piping length capability offers the designer or the Four stages of oil control technology ensures that all the
installer additional flexibility for design and Installation. compressor oil is constantly maintained at a safe level.
Total piping length
1,000m

2 High efficiency
oil separator
Longest actual piping length 200m

4 Balance controlled
by smart procedure
between IDU~IDU 30m
90m

1 Unique oil
separation 3 Balance between
in compressor compressors in
one outdoor unit

*The most extended length after the 1st piping branch is 40m as standard, same
which may be extended to 90m under certain conditions.

Refrigerant Cooling PCB (Printed Circuit Board)


Double U-shape refrigerant piping decreases PCB’s temperature
and enhances reliability.

Compared to a single U-shaped refrigerant pipe, the PCB


temperature is 5°C lower.

Compared to an air cooling method, the PCB temperature is


10°C lower.

9
Automatic Duty Cycling Real-time refrigerant amount monitoring

Duty cycling regulates the operating time of the outdoor units in The temperature and pressure of refrigerant can be real-time
a multiple-unit system, as well as that of the compressors in each monitored by the outdoor unit. TVR Ultra outdoor unit can
unit, which action significantly extends all compressor unit lifespan. detect excessive or insufficient amounts of refrigerant to ensure
consistent performance.
Unit Operation Priority

1st Cycle 1 2 3 Detects excessive Detects normal Detects insufficient


refrigerant refrigerant refrigerant
Outdoor Unit

2nd Cycle 3 1 2

3rd Cycle 2 3 1

110% 90%

R410A
Double Backup
Compressor backup and Unit backup.
Allows time for maintenance or repair duties while comfort remains Flexible Pipe Connection and Rotatory PCB
warranted.
360° pipe / power wire / communication wire connection for the
ODU. The bottom layer can be easily reached through the rotatory
upper PCB, for easier maintenance.
Compressor Backup Module Backup

One compressor fails, another one One ODU fails, another one will
will operate up to 4 days operate up to 4 days

Running State Stand-by State Fault or Shutdown

Simple Triple Configurations


Triple (local/remote/network) configuration for simplified
Integrated design of electrical components installation, commissioning and servicing.

The integrated design will simplify all electrical wiring and make it Field local configuration achieves quick and easy on-site
much more reliable. settings, simplifies installation and commissioning.

10
Outdoor Unit
Load
Advanced “silent” technology
Sound Off
4 night silent modes, 3 silent modes and 4 super silent modes Level
selections, provide more freedom and convenience to match the Judgment time Low-noise operation time
6hrs 10hrs
customer needs.
Max. 15dB(A) reduction

6:00 12:00 14:00 18:00 20:00 0:00 6:00


Highest Start End
outdoor temp.

Night Silent Mode and Super Silent Mode


Silent Mode Fan Speed and Compressor
Fan Speed is Limited Frequency are Limited

Five Priority Mode Settings Auto Addressing

Five (5) priority mode settings, provide more freedom and New TVR Ultra saves installation time with outdoor units
convenience to match the customer needs. automatically addressing up to 64 indoor units.

8 7 6 5

Auto Priority Cooling Priority 1 2 3 4

63

VIP/Vote Priority Heating Only Cooling Only

11
Easy Installation and Service Automatic Refrigerant Charging/Recycling
Function*
High External Static Pressure
Automatic refrigerant charging and recycling make installation and
service easier and more efficient.
External static pressure (ESP) reaches 60Pa.
Outdoor Unit

*This function is available as a customization option

12 m

Optional Multifunctional Small PCB

An optional multifunctional small PCB can be installed on the


unit’s side columns, enabling installation and service engineers to
Non-polarized Communication Wiring*
activate Auto-commissioning or check the operating status without
removing the front panel. It can also perform automatic data
Only one chain of 2-core non-polarized shielded communication
backup of the last 30 minutes’ operating record.
wiring is required for indoor and outdoor unit communication.

Q P Q P Q P Q P

Q P

*In installations where relatively strong electromagnetic fields are present, 3-core
shielded wiring should be used in order to prevent interference.

12
Anti-corrosion Protection

Outdoor units are given anti-corrosion treatment for non-extreme


conditions as standard and can also be customized with heavy anti-
corrosion treatment on main components for surface protection
against corrosive air, acid rain and saline air (for installations in
coastal regions) to extend overall useful life. The integrity of the
anti-corrosion treatment is ensured by exposing major components
and parts to salt spray testing, moisture and heating testing and
light aging testing.

Outdoor Unit
Fan motor
Standard products:
72h of neutral salt mist

Heavy anti-corrosion products:


240h of neutral salt mist Heat exchanger aluminum foil
Standard products:
72h of neutral salt mist

Heavy anti-corrosion products:


1000h of neutral salt mist
140h of acid salt mist

Painted sheet metal


Standard products:
500h of neutral salt mist Heat exchanger copper pipe
1000h of moisture and heating test Standard products:
500h of light aging test 24h of neutral salt mist

Heavy anti-corrosion products: Heavy anti-corrosion products:


1000h of neutral salt mist 120h of neutral salt mist
2000h of moisture and heating test
720h of light aging test

Screws / bolts / gaskets Electric control box case


Standard products: Standard products:
300h of neutral salt mist 96h of neutral salt mist

Heavy anti-corrosion products: Heavy anti-corrosion products:


720h of neutral salt mist 240h of neutral salt mist

13
Specifications 220V

Capacity HP 8 10  14 16

Model 4TVH0086E8000AA 4TVH0096E8000AA 79+($$ 4TVH0140E8000AA 79+($$


V/Ph/Hz
kW    40.0 
Capacity
kBtu/h 86.0  114.3  
Outdoor Unit

Cooling¹ Power Input kW 4.80    


EER kW/kW  4.91  4.60 4.38
IEER kW/kW  9.09   
kW    40.0 
Capacity
Heating² kBtu/h 86.0  114.3  
Power Input kW     
COP kW/kW     4.68
Connectable Indoor Unit Max.Quantity 13 16   
Compressors Quantity 1
Refrigerant (R-410a) Factory Charge kg 11 13
Pipe Liquid Pipe mm ĭ ĭ ĭ ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ ĭ ĭ ĭ
Airflow Rate m³/h 11000 14000
Sound Pressure Level຾ dB(A)   60 60 61
Net Dimensions (WxHxD) mm îî îî
Packed Dimensions (WxHxD) mm îî îî
Net Weight kg  
Gross Weight kg  311

Capacity HP 18     

Model 79+($$ 79+($$ 79+($$ 79+($$ 79+($$ 79+($$


V/Ph/Hz
kW      
Capacity
kBtu/h  191.1    
Cooling¹ Power Input kW  13.66   19.11 
EER kW/kW  4.10  4.04  
IEER kW/kW 8.01     
kW      
Capacity
Heating² kBtu/h  191.1    
Power Input kW   14.61   
COP kW/kW  4.46  4.43 4.68 3.88
Connectable Indoor Unit Max.Quantity  33 36 39 43 46
Compressors Quantity 
Refrigerant (R-410a) Factory Charge kg  
Pipe Liquid Pipe mm ĭ ĭ ĭ ĭ ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ ĭ ĭ ĭ ĭ
Airflow Rate m³/h  
Sound Pressure Level຾ dB(A)  63 63 64 64 64
Net Dimensions (WxHxD) mm îî îî
Packed Dimensions (WxHxD) mm îî îî
Net Weight kg 366 438
Gross Weight kg 386 461

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

14
Specifications 220V

Capacity HP   

Model 79+($$ 79+($$ 79+($$


Combination +3+3 +3+3 +3+3
V/Ph/Hz
kW   
Capacity

Outdoor Unit
Cooling¹ kBtu/h   
Power Input kW   
EER kW/kW   
kW/kW   
Capacity
Heating² kW   
Power Input kBtu/h   
COP kW   
Connectable Indoor Unit Max.Quantity   
Compressors Quantity   
Refrigerant (R-410a) Factory Charge kg   
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h   
Sound Pressure Level຾ dB(A)   
Net Dimensions (WxHxD) mm îî î îî  îî
Packed Dimensions (WxHxD) mm îî î îî  îî
Net Weight kg [ 
Gross Weight kg [ 

Capacity HP   40

Model 79+($$ 79+($$ 79+($$


Combination +3+3 +3+3 +3+3
V/Ph/Hz
kW   
Capacity
Cooling¹ kBtu/h   
Power Input kW   
EER kW/kW   
kW/kW   
Capacity
Heating² kW   
Power Input kBtu/h   
COP kW 4.40 4.40 
Connectable Indoor Unit Max.Quantity   
Compressors Quantity 4 4 
Refrigerant (R-410a) Factory Charge kg   
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h   
Sound Pressure Level຾ dB(A)   
Net Dimensions (WxHxD) mm îî î îî  îî
Packed Dimensions (WxHxD) mm îî î îî  îî
Net Weight kg [ 
Gross Weight kg  

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

15
Specifications 220V

Capacity HP 42 44 46 48 50

Model 4TVH0401E8000AA 4TVH0420E8000AA 4TVH0438E8000AA 4TVH0459E8000AA 4TVH0478E8000AA


Combination 14HP+28HP 16HP+28HP 22HP+24HP 22HP+26HP 22HP+28HP
V/Ph/Hz
kW 118.5 123.5 128.5 134.5 140.0
Capacity
Outdoor Unit

Cooling¹ kBtu/h 404.3 421.4 438.4 458.9 477.7


Power Input kW 32.13 33.71 31.77 34.30 38.62
EER kW/kW 3.69 3.66 4.04 3.92 3.63
kW/kW 118.5 123.5 128.5 134.5 140.0
Capacity
Heating² kBtu/h 404.3 421.4 438.4 458.9 477.7
Power Input kW 28.71 29.85 29.73 31.99 34.84
COP 4.13 4.14 4.32 4.20 4.02
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 3 4
Refrigerant (R-410a) Factory Charge kg 39000 42000

Pipe Liquid Pipe mm 34 38


Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h ĭ
Sound Pressure Level຾ dB(A) 66
Net Dimensions (WxHxD) mm (1340×1635×825)+(1730×1830×850)
Packed Dimensions (WxHxD) mm (1405×1805×910)+(1800×2000×910)
Net Weight kg 284+438 366+438
Gross Weight kg 311+461 386+461

Capacity HP 52 54 56

Model 4TVH0498E8000AA 4TVH0517E8000AA 4TVH0535E8000AA


Combination 26HP+26HP 26HP+28HP 28HP+28HP
V/Ph/Hz
kW 146.0 151.5 157.0
Capacity
Cooling¹ kBtu/h 498.2 516.9 535.7
Power Input kW 38.22 42.54 46.87
EER kW/kW 3.82 3.56 3.35
kW/kW 146.0 151.5 157.0
Capacity
kBtu/h 498.2 516.9 535.7
Heating²
Power Input kW 34.76 37.61 40.46
COP 4.20 4.03 3.88
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 50000
Refrigerant (R-410a) Factory Charge kg 4
Pipe Liquid Pipe mm 42
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h ĭ ĭ
Sound Pressure Level຾ dB(A) 66
Net Dimensions (WxHxD) mm (1730×1830×850)×2
Packed Dimensions (WxHxD) mm (1800×2000×910)×2
Net Weight kg 438×2
Gross Weight kg 461×2

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

16
Specifications 220V

Capacity HP   

Model 79+($$ 79+($$ 79+($$


Combination +3+3+3 +3+3+3 +3+3+3
V/Ph/Hz
kW   
Capacity

Outdoor Unit
Cooling¹ kBtu/h   
Power Input kW   
EER kW/kW   
kW/kW   
Capacity
Heating² kW   
Power Input kBtu/h   
COP kW   
Connectable Indoor Unit Max.Quantity 
Compressors Quantity 4 
Refrigerant (R-410a) Factory Charge kg   
Pipe Liquid Pipe mm ĭ ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ ĭ
Airflow Rate m³/h   
Sound Pressure Level຾ dB(A) 
Net Dimensions (WxHxD) mm îî î îî îî  îî 

Packed Dimensions (WxHxD) mm îî î îî îî  îî 


îî

Net Weight kg î 


Gross Weight kg î 

Capacity HP   

Model 79+($$ 79+($$ 79+($$


Combination +3+3+3 +3+3+3 +3+3+3
V/Ph/Hz
kW   
Capacity
Cooling¹ kBtu/h   
Power Input kW   
EER kW/kW   
kW/kW   
Capacity
Heating² kW   
Power Input kBtu/h   
COP kW   4.04
Connectable Indoor Unit Max.Quantity 
Compressors Quantity 
Refrigerant (R-410a) Factory Charge kg   
Pipe Liquid Pipe mm ĭ ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ ĭ
Airflow Rate m³/h   
Sound Pressure Level຾ dB(A)   
Net Dimensions (WxHxD) mm îî î îî îî  îî î
Packed Dimensions (WxHxD) mm îî î îî îî  îî î
Net Weight kg  î
Gross Weight kg  î

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

17
Specifications 220V

Capacity HP 70 72 74 76 78

Model 4TVH0672E8000AA 4TVH0689E8000AA 4TVH0706E8000AA 4TVH0727E8000AA 4TVH0746E8000AA


Combination 14HP+28HP+28HP 16HP+28HP+28HP 22HP+24HP+28HP 22HP+26HP+28HP 22HP+28HP+28HP
V/Ph/Hz
kW 197.0 202.0 207.0 213.0 218.5
Capacity
Outdoor Unit

Cooling¹ kBtu/h 672.2 689.2 706.3 726.8 745.5


Power Input kW 55.56 57.14 55.20 57.73 62.05
EER kW/kW 3.55 3.54 3.75 3.69 3.52
kW/kW 197.0 202.0 207.0 213.0 218.5
Capacity
Heating² kBtu/h 672.2 689.2 706.3 726.8 745.5
Power Input kW 48.94 50.08 49.96 52.22 55.07
COP 4.03 4.03 4.14 4.08 3.97
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 5 6
Refrigerant (R-410a) Factory Charge kg 64000 64000 67000 67000 67000

Pipe Liquid Pipe mm 55 55 59 59 59


Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h ĭ
Sound Pressure Level຾ dB(A) 67 67 68 68 68
Net Dimensions (WxHxD) mm (1340×1635×825)+(1730×1830×850)×2
Packed Dimensions (WxHxD) mm (1405×1805×910)+(1800×2000×910)×2
Net Weight kg 284+438×2 284+438×2 366+438×2 366+438×2 366+438×2
Gross Weight kg 311+461×2 311+461×2 311+461×2 311+461×2 311+461×2

Capacity HP 80 82 84

Model 4TVH0766E8000AA 4TVH0785E8000AA 4TVH0804E8000AA


Combination 26HP+26HP+28HP 26HP+28HP+28HP 28HP+28HP+28HP
V/Ph/Hz
kW 224.5 320.0 235.5
Capacity
kBtu/h 766.0 784.8 803.5
Cooling¹
Power Input kW 61.65 65.98 70.30
EER kW/kW 3.64 3.49 3.35
kW/kW 224.5 230.0 235.5
Capacity
kBtu/h 776.0 784.8 803.5
Heating²
Power Input kW 54.99 57.84 60.70
COP 4.08 3.98 3.88
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 6
Refrigerant (R-410a) Factory Charge kg 63
Pipe Liquid Pipe mm 42
Connzections³ Gas Pipe mm ĭ ĭ ĭ
Airflow Rate m³/h ĭ ĭ ĭ
Sound Pressure Level຾ dB(A) 68
Net Dimensions (WxHxD) mm (1730×1830×850)×3
Packed Dimensions (WxHxD) mm (1800×2000×910)×3
Net Weight kg 438×3
Gross Weight kg 461×3

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

18
Specifications 220V

Capacity HP   

Model 79+($$ 79+($$ 79+($$


Combination +3+3 +3+3 +3+3
V/Ph/Hz
kW   
Capacity

Outdoor Unit
Cooling¹ kBtu/h   
Power Input kW   
EER kW/kW   4.04
kW/kW   
Capacity
Heating² kW   
Power Input kBtu/h   
COP kW   
Connectable Indoor Unit Max.Quantity   
Compressors Quantity   
Refrigerant (R-410a) Factory Charge kg   
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h   
Sound Pressure Level຾ dB(A)   
Net Dimensions (WxHxD) mm îî î îî [
Packed Dimensions (WxHxD) mm îî î [[ [
Net Weight kg [ [
Gross Weight kg [ [

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

19
Outdoor Unit

20
Specifications 380V

Capacity HP  10  14

Model 79+(($$ 4TVH0096EE000AA 79+(($$ 4TVH0140EE000AA


V/Ph/Hz
kW    40.0
Capacity
Cooling¹ kBtu/h   114.3 

Outdoor Unit
Power Input kW  6.3  9.9
EER kW/kW    
kW    40.0
Capacity
kBtu/h   114.3 
Heating²
Power Input kW 4.6  6.6 
COP kW/kW    
Connectable Indoor Unit Max.Quantity 13 16  
Compressors Quantity 1
Refrigerant (R-410a) Factory Charge kg 11 13
Pipe Liquid Pipe mm ĭ ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ ĭ
Airflow Rate m³/h 11000 13000
Sound Pressure Level຾ dB(A)  60
Net Dimensions (WxHxD) mm îî îî
Packed Dimensions (WxHxD) mm îî îî
Net Weight kg  
Gross Weight kg  304

Capacity HP 16   

Model 79+(($$ 79+(($$ 79+(($$ 79+(($$


V/Ph/Hz
kW    
Capacity
Cooling¹ kBtu/h   191.1 
Power Input kW    
EER kW/kW  4.00  
kW    
Capacity
kBtu/h   191.1 
Heating²
Power Input kW  10.6  
COP kW/kW 4.60  4.40 4.10
Connectable Indoor Unit Max.Quantity   33 36
Compressors Quantity 1 
Refrigerant (R-410a) Factory Charge kg 13 
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 13000 
Sound Pressure Level຾ dB(A) 61  63
Net Dimensions (WxHxD) mm îî îî
Packed Dimensions (WxHxD) mm îî
Net Weight kg  
Gross Weight kg 304 

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

21
Specifications 380V

Capacity HP 24 26 28

Model 4TVH0229EE000AA 4TVH0249EE000AA 4TVH0268EE000AA


V/Ph/Hz
kW 67.0 73.0 78.5
Capacity
Cooling¹ kBtu/h 228.6 249.1 267.8
Outdoor Unit

Power Input kW 18.1 20.9 24.2


EER kW/kW 3.70 3.49 3.25
kW 67.0 73.0 78.5
Capacity
kBtu/h 228.6 249.1 267.8
Heating²
Power Input kW 14.9 17.6 20.7
COP kW/kW 4.50 4.15 3.80
Connectable Indoor Unit Max.Quantity 39 43 46
Compressors Quantity 2
Refrigerant (R-410a) Factory Charge kg 22
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 25000
Sound Pressure Level຾ dB(A) 64
Net Dimensions (WxHxD) mm 1730×1830×850
Packed Dimensions (WxHxD) mm 1800×2000×910
Net Weight kg 430
Gross Weight kg 453

Capacity HP 30 32

Model 4TVH0290EE000AA 4TVH0307ZZEE000AA


V/Ph/Hz
kW 85.0 90.0
Capacity
Cooling¹ kBtu/h 290.0 307.1
Power Input kW 27.4 31.0
EER kW/kW 3.10 2.90
kW 85.0 90.0
Capacity
kBtu/h 290.0 307.1
Heating²
Power Input kW 23.0 25.7
COP kW/kW 3.70 3.50
Connectable Indoor Unit Max.Quantity 50 53
Compressors Quantity 2
Refrigerant (R-410a) Factory Charge kg 25
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h 24000
Sound Pressure Level຾ dB(A) 64
Net Dimensions (WxHxD) mm 1730×1830×850
Packed Dimensions (WxHxD) mm 1800×2000×910
Net Weight kg 475
Gross Weight kg 507

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

22
Specifications 380V

Capacity HP 34 36  40

Model 4TVH0324EE000AA 4TVH0346EE000AA 4TVH0363EE000AA 79+(($$


Combination Type 12HP+22HP 14HP+22HP 16HP+22HP +3+3
V/Ph/Hz
kW 95.0 101.5 106.5 112.0
Capacity

Outdoor Unit
Cooling¹ kBtu/h 324.1 346.3 363.4 
Power Input kW 27.1  30.4 32.9

EER kW/kW 3.51 3.59 3.51 3.41


kW 95.0 101.5 106.5 112.0
Capacity
kBtu/h 324.1 346.3 363.4 
Heating² kW 21.6 23.5 27.2
Power Input 

COP kW/kW 4.40 4.32 4.30 4.11


Connectable Indoor Unit Max.Quantity 56 59 63 64
Compressors Quantity 3
Refrigerant (R-410a) Factory Charge kg 11+17 13+17 11+22
Liquid Pipe mm ĭ ĭ
Pipe Connections³
Gas Pipe mm ĭ ĭ
Airflow Rate m³/h  30000 36000
Sound Pressure Level຾ dB(A) 65
(990×1635×790)+ (990×1635×790)+
Net Dimensions (WxHxD) mm îî  îî
îî îî

îî  îî 
Packed Dimensions (WxHxD) mm îî î
îî îî
Net Weight kg   277
Gross Weight kg   304

Capacity HP 42 44 46 

Model 4TVH0401EE000AA 4TVH0420EE000AA 79+(($$ 4TVH0459EE000AA


Combination Type 20HP+22HP 22HP+22HP 22HP+24HP 22HP+26HP
V/Ph/Hz
kW 117.5 123.0  134.5
Capacity
kBtu/h 400.9 419.7  
Cooling¹
Power Input kW 33.5 36.7 36.5 39.3
EER kW/kW 3.51 3.52 3.52 3.43
kW 117.5   134.5
Capacity
kBtu/h 400.9   
Heating²
Power Input kW 27.7 29.9 29.9 32.6

COP kW/kW 4.24 4.30 4.30 4.13


Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 4
Refrigerant (R-410a) Factory Charge kg 17x2 17+22
Liquid Pipe mm ĭ
Pipe Connections³
Gas Pipe mm ĭ
Airflow Rate m³/h 34000 42000
Sound Pressure Level຾ dB(A) 66
Net Dimensions (WxHxD) mm îî î îî  îî
Packed Dimensions (WxHxD) mm îî î îî  îî
Net Weight kg [ 
Gross Weight kg [ 

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

23
Specifications 380V

Capacity HP 50 52 54 56

Model 79+(($$ 79+(($$ 4TVH0517EE000AA 79+(($$


Combination Type +3+3 26HP+26HP +3+3 +3+3
V/Ph/Hz
kW 140.0 146.0 151.5 157.0
Capacity
Outdoor Unit

Cooling¹ kBtu/h 477.7   


Power Input kW 42.5  45.1 

EER kW/kW    


kW 140.0 146.0 151.5 157.0
Capacity
kBtu/h 477.7   
Heating² kW
Power Input    

COP kW/kW  4.15  


Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 4
Refrigerant (R-410a) Factory Charge kg 17+22 22x2
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 42000 50000
Sound Pressure Level຾ dB(A) 66
îî 
Net Dimensions (WxHxD) mm îî î
îî

îî 
Packed Dimensions (WxHxD) mm îî î
îî
Net Weight kg  [
Gross Weight kg  [

Capacity HP  60 62 64

Model 79+(($$ 4TVH0575EE000AA 79+(($$ 4TVH0614EE000AA


Combination Type +3+3 +3+3 +3+3 +3+3
V/Ph/Hz
kW   175.0 
Capacity
kBtu/h    614.2
Cooling¹
Power Input kW 51.6 55.2  62.1
EER kW/kW    
kW   175.0 
Capacity
kBtu/h    614.2
Heating²
Power Input kW  46.4  51.4

COP kW/kW    


Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 4
Refrigerant (R-410a) Factory Charge kg 22+25 25x2
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h  42000
Sound Pressure Level຾ dB(A) 66
Net Dimensions (WxHxD) mm îî î
Packed Dimensions (WxHxD) mm îî î
Net Weight kg  475x2
Gross Weight kg  507x2

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

24
Specifications 380V

Capacity HP 66 68 70 72

Model 4TVH0631EE000AA 4TVH0650EE000AA 4TVH0672EE000AA 4TVH0689EE000AA


Combination Type 12HP+22HP+32HP 14HP+22HP+32HP 16HP+22HP+32HP 12HP+28HP+32HP
V/Ph/Hz
kW 185.0 191.5 196.5 202.0
Capacity

Outdoor Unit
kBtu/h 631.2 653.4 670.5 689.2
Cooling¹
Power Input kW 58.1 59.3 61.4 63.9
EER kW/kW 3.18 3.23 3.20 3.16
kW 185.0 191.5 196.5 202.0
Capacity
kBtu/h 631.2 653.4 670.5 689.2
Heating²
Power Input kW 47.3 49.2 50.5 52.9
COP kW/kW 3.91 3.89 3.89 3.82
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 5
Refrigerant (R-410a) Factory Charge kg 11+17+25 13+17+25 11+22+25
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 52000 54000 60000
Sound Pressure Level຾ dB(A) 67
(990×1635×790)+ (990×1635×790)+
Net Dimensions (WxHxD) mm (1340×1635×825)+ (1340×1635×850)+(1340×1635×825)
+(1730×1830×850) (1730×1830×850) ×2
(1730×1830×850)
(1090×1805×860)+ (1090×1805×860)+
Packed Dimensions (WxHxD) mm (1405×1805×910)+ (1405×1805×910)×2+(1800×2000×910) (1800×2000×910)×2
(1800×2000×910)
Net Weight kg 227+348+475 277+348+475 227+430+475
Gross Weight kg 242+368+507 304+368+507 242+453+507

Capacity HP 74 76 78 80

Model 4TVH0706EE000AA 4TVH0727EE000AA 4TVH0746EE000AA 4TVH0766EE000AA


Combination Type 20HP+22HP+32HP 22HP+22HP+32HP 22HP+24HP+32HP 22HP+26HP+32HP
V/Ph/Hz
kW 207.5 213.0 218.5 224.5
Capacity
kBtu/h 708.0 726.8 745.5 766.0
Cooling¹
Power Input kW 64.5 67.8 67.5 70.3
EER kW/kW 3.22 3.14 3.24 3.19
kW 207.5 213.0 218.5 224.5
Capacity
kBtu/h 708.0 726.8 745.5 766.0
Heating²
Power Input kW 53.4 55.7 55.6 58.3
COP kW/kW 3.88 3.82 3.93 3.85
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 6
Refrigerant (R-410a) Factory Charge kg 7x2+25 17+22+25
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h 58000 66000
Sound Pressure Level຾ dB(A) 68
Net Dimensions (WxHxD) mm (1340×1635×825)×2+(1730×1830×850) (1340×1635×825)+(1730×1830×850)×2
Packed Dimensions (WxHxD) mm (1405×1805×910)×2+(1800×2000×910) (1405×1805×910)+(1800×2000×910)×2
Net Weight kg 348x2+475 348+430+475
Gross Weight kg 368x2+507 368+453+507

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

25
Specifications 380V

Capacity HP 82 84 86 88

Model 4TVH0785EE000AA 4TVH0804EE000AA 4TVH0824EE000AA 4TVH0843EE000AA


Combination Type 22HP+28HP+32HP 26HP+26HP+32HP 26HP+28HP+32HP 28HP+28HP+32HP
V/Ph/Hz
kW 230.0 236.0 241.5 247.0
Capacity
Outdoor Unit

kBtu/h 784.8 805.2 824.0 842.8


Cooling¹
Power Input kW 73.5 72.8 76.1 79.3

EER kW/kW 3.13 3.24 3.17 3.11


kW 230.0 236.0 241.5 247.0
Capacity
kBtu/h 784.8 805.2 824.0 842.8
Heating²
Power Input kW 61.4 60.9 64.0 67.0

COP kW/kW 3.75 3.87 3.78 3.68


Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 6
Refrigerant (R-410a) Factory Charge kg 17+22+25 22x2+25
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 66000 74000
Sound Pressure Level຾ dB(A) 68
(1340×1635×825)+
Net Dimensions (WxHxD) mm (1730×1830×850)×3
(1730×1830×850)×2

(1405×1805×910)+
Packed Dimensions (WxHxD) mm (1800×2000×910)×3
(1800×2000×910)×2
Net Weight kg 348+430+475 430x2+475
Gross Weight kg 368+453+507 453x2+507

Capacity HP 90 92 94 96

Model 4TVH0865EE000AA 4TVH0882EE000AA 4TVH0904EE000AA 4TVH0921EE000AA


Combination Type 28HP+30HP+32HP 28HP+32HP+32HP 30HP+32HP+32HP 32HP+32HP+32HP
V/Ph/Hz
kW 253.5 258.5 265.0 270.0
Capacity
kBtu/h 864.9 882.0 904.2 921.2
Cooling¹
Power Input kW 82.6 86.2 89.5 93.1
EER kW/kW 3.07 3.00 2.96 2.90
kW 253.5 258.5 265.0 270.0
Capacity
kBtu/h 864.9 882.0 904.2 921.2
Heating²
Power Input kW 69.3 72.1 74.4 77.1
COP kW/kW 3.66 3.59 3.56 3.50
Connectable Indoor Unit Max.Quantity 64
Compressors Quantity 6
Refrigerant (R-410a) Factory Charge kg 22+25x2 25+25x2
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h 73000 72000
Sound Pressure Level຾ dB(A) 68
Net Dimensions (WxHxD) mm (1730×1830×850)×3
Packed Dimensions (WxHxD) mm (1800×2000×910)×3
Net Weight kg 348x2 348+430
Gross Weight kg 348x2 368+453

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

26
TVR Ultra-S
Specifications 380V
TVR Ultra-S brings the best value for money to the Trane VRF portfolio.
All features, indoor units and controls are the same as TVR Ultra,
but the modules are independent, not allowing combination.

Outdoor Unit
Capacity HP 8 10 12

Model 4TVH0086FE000AA 4TVH0096FE000AA 4TVH0115FE000AA


V/Ph/Hz
kW 25.2 28 33.5
Capacity
Cooling¹ kBtu/h 86 95.5 114.3
Power Input kW 5.5 6.7 8.9
EER kW/kW 4.7 4.34 3.95
kW 25.2 28 33.5
Capacity
kBtu/h 86 95.5 114.3
Heating²
Power Input kW 4.8 5.5 7.6
COP kW/kW 5.3 5.21 4.58
Connectable Indoor Unit Max.Quantity 13 16 20
Compressors Quantity 1
Refrigerant (R-410a) Factory Charge kg 11
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 11000
Sound Pressure Level຾ dB(A) 58 58 60
Net Dimensions (WxHxD) mm 990x1635x790
Packed Dimensions (WxHxD) mm 1090x1805x860
Net Weight kg 227
Gross Weight kg 242

Capacity HP 14 16 18

Model 4TVH0140FE000AA 4TVH0155FE000AA 4TVH0170FE000AA


V/Ph/Hz
kW 40 45 50
Capacity
Cooling¹ kBtu/h 136.5 153.5 170.6
Power Input kW 11 12.9 14.7
EER kW/kW 3.77 3.61 3.71
kW 40 45 50
Capacity
kBtu/h 136.5 153.5 170.6
Heating²
Power Input kW 9.3 10.7 12.2
COP kW/kW 4.39 4.28 4.36
Connectable Indoor Unit Max.Quantity 23 26 29
Compressors Quantity 1
Refrigerant (R-410a) Factory Charge kg 13
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h 13000
Sound Pressure Level຾ dB(A) 60 61 62
Net Dimensions (WxHxD) mm 1340×1635×850
Packed Dimensions (WxHxD) mm 1405×1805×910
Net Weight kg 227 395
Gross Weight kg 304 322

27
TVR Ultra-S
Specifications 380V
TVR Ultra-S brings the best value for money to the Trane VRF portfolio.
All features, indoor units and controls are the same as TVR Ultra,
but the modules are independent, not allowing combination.
Outdoor Unit

Capacity HP 20 22

Model 79+)($$ 4TVH0210FE000AA


V/Ph/Hz
kW 56 61.5
Capacity
Cooling¹ kBtu/h  
Power Input kW 16 20.2
EER kW/kW 3.5 3.05
kW 56 61.5
Capacity
kBtu/h  
Heating²
Power Input kW  17.6
COP kW/kW 4.05 3.5
Connectable Indoor Unit Max.Quantity 33 36
Compressors Quantity 2
Refrigerant (R-410a) Factory Charge kg 17
Pipe Liquid Pipe mm ĭ
Connections³ Gas Pipe mm ĭ
Airflow Rate m³/h 17000
Sound Pressure Level຾ dB(A) 63
Net Dimensions (WxHxD) mm îî
Packed Dimensions (WxHxD) mm îî
Net Weight kg 344
Gross Weight kg 364

Capacity HP 24 26  30 32

Model 79+)($$ 79+)($$ 79+)($$ 79+)($$ 4TVH0307FE000AA


V/Ph/Hz
kW 67 73   
Capacity
Cooling¹ kBtu/h     307.1
Power Input kW 21.6 21.6   32.1
EER kW/kW 3.1 3.4 3.15 3 
kW 67 73   
Capacity
kBtu/h     307.1
Heating²
Power Input kW    24.3 26.5
COP kW/kW 4 4.05 3.6 3.5 3.4
Connectable Indoor Unit Max.Quantity  43 46 50 53
Compressors Quantity 2
Refrigerant (R-410a) Factory Charge kg 22 25
Pipe Liquid Pipe mm ĭ ĭ
Connections³ Gas Pipe mm ĭ ĭ
Airflow Rate m³/h 25000 24000
Sound Pressure Level຾ dB(A) 64
Net Dimensions (WxHxD) mm îî
Packed Dimensions (WxHxD) mm îî
Net Weight kg 407  475
Gross Weight kg 430 452 507

28
Indoor Units Constant Level of Indoor Air Temperature

Based on thermal load, the DC Inverter fan motor adjusts the air
Wide Application Range flow to create less temperature fluctuation, and provide the desired
Wide Range of Indoor Units space comfort.

With 11 types and more than 100 models, TVR Ultra indoor units
meet varied customer requirements in a wide range of locations
Fluctuation of Room Temperature
including shopping malls, hospitals, office buildings, hotels and
airports. Temp

Time

DC Motor
AC Motor

5-step Swing Louver


The 5-step swing louver directs the airflow to the desired airflow

Indoor Unit
angle. This function is available through the unit controller.

Comfort and Efficiency


High Efficiency DC Fan Motor
1
The power consumption of DC fan motor can be reduced greatly in
comparison to the corresponding AC type. 2
3
Step
4
Swing 5

Static Pressure 20 Steps Control (Ducted Unit)


Quiet Operation Depending on the installation, the medium static pressure and high
static pressure ducted units can control the static pressure using up
The low sound operation of the DC fan motor and optimized fan to 10 steps and 20 steps respectively, providing suitable comfort
blades guarantees smooth air discharge while providing a quiet for any environment.
living environment.

Constant airflow discharge

20 steps static pressure control

29
High-lift Drain Pump

A drain pump with a 750mm or 500mm pump head is fitted as


standard or optional, simplifying installation of the drain piping.

7-Speed Fan Control


7 indoor fan speeds provide control flexibility to meet the needs of
different indoor conditions.

Fresh Air Intake

On selected models, a reserved outside air intake port allows


outdoor air to be introduced directly into the unit, avoiding the
Indoor Unit

need for a separate ventilation system.

Flexible Installation

For Medium Static Pressure Duct Units, to provide the flexibility


to adapt to different installation situations, the air inlet may be
positioned either on the underside or the rear of the unit.

Air intake Air intake


from rear from below

Ceiling

Floor Units can be installed either on the ceiling or on the floor,


providing flexibility to accommodate a wide range of room designs.
For Wall Mounted Units, the refrigerant outlet direction can be left,
right or rear as the installation situation requires. A new fixing plate
design accelerates installation and provides extra stability.

Rear

Left Right

Floor installation Ceiling installation

30
One-way Cassette
Fresh air intake (4.5-7.1kW models).

One-way air discharge, ideal for corner locations.

Drain pump with 750mm pump head fitted as standard.

Optional wireless remote Optional wired


controller controller

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVE0005EF000AA 4TVE0007EF000AA 4TVE0009EF000AA 4TVE0012EF000AA

kW 1.8 2.2 2.8 3.6


Capacity
Cooling¹ kBtu/h 6.1 7.5 9.6 12.3
Power Input kW 25 25 30 30
kW/kW 2.2 2.6 3.2 4.0
Capacity
Heating² kBtu/h 7.5 8.9 10.9 13.6
Power Input W 25 25 30 30
Air Flow Rate 3 m³/h 380/355/330/300/286/263/240 460/440/410/380/355/330/300
Sound Pressure Level຾ dB(A) 30/28/27/26/25/24/22 37/36/35/34/32/31/30 38/37/35/34/32/31/30

Indoor Unit
Net dimensions 5 (WxHxD) mm 1054×153×425
Main Body Packed dimensions (WxHxD) mm 1155×245×490
Net/Gross weight kg 11.8/15.3 12.3/15.8
Net dimensions (W×H×D) mm 1180×25×465
Panel
Packed dimensions (W×H×D) mm 1232×107×517
Net/Gross weight kg 3.5/5.2
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVE0015EF000AA 4TVE0018EF000AA 4TVE0024EF000AA

kW 4.5 5.6 7.1


Capacity
Cooling¹ kBtu/h 15.4 19.1 24.2
Power Input kW 40 48 60
kW/kW 5.0 6.3 8.0
Capacity
Heating² kBtu/h 17.1 21.5 27.3
Power Input W 40 48 60
Air Flow Rate 3 m³/h 693/662/638/600/556/510/476 792/763/728/688/643/589/549 933/873/815/749/689/637/592
Sound Pressure Level຾ dB(A) 39/37/36/35/34/32/31 41/39/38/37/36/35/33 43/41/40/39/37/36/35
Net dimensions 5 (WxHxD) mm 1275×189×450
Main Body Packed dimensions (WxHxD) mm 1370×295×505
Net/Gross weight kg 16.1/20.4 16.4/20.7 17.6/22.4
Net dimensions (W×H×D) mm 1350×25×505
Panel
Packed dimensions (W×H×D) mm 1410×95×560
Net/Gross weight kg 4/5.4
Liquid/Gas pipe mm ɎɎ ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

31
Two-way Cassette
Fresh air intake.

Two-way air discharge, perfect for limited ceiling space applications.

Drain pump with 750mm pump head fitted as standard.

Optional wireless remote Optional wired


controller controller

RM12D RM05B WDC-86E/KD WDC-120G/WK

Model 4TVG0007EF000AA 4TVG0009EF000AA 4TVG0012EF000AA

kW 2.2 2.8 3.6


Capacity
Cooling¹ kBtu/h 7.5 9.6 12.3
Power Input kW 35 40 40
kW/kW 2.6 3.2 4.0
Capacity
Heating² kBtu/h 8.9 10.9 13.6
Power Input W 35 40 40
Air Flow Rate 3 m³/h 654/612/571/530/488/449/410 725/679/641/591/554/509/458
Sound Pressure Level຾ dB(A) 33/31/30/29/27/25/24 35/33/32/30/29/27/25
Net dimensions 5 (WxHxD) mm 1172×299×591
Indoor Unit

Main Body Packed dimensions (WxHxD) mm 1355×400×675


Net/Gross weight kg 33.5/42.0
Net dimensions (W×H×D) mm 1430×53×680
Panel
Packed dimensions (W×H×D) mm 1525×130×765
Net/Gross weight kg 10.5/15
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVG0015EF000AA 4TVG0018EF000AA 4TVG0024EF000AA

kW 4.5 5.6 7.1


Capacity
Cooling¹ kBtu/h 15.4 19.1 24.2
Power Input kW 50 69 98
kW/kW 5.0 6.3 8.0
Capacity
Heating² kBtu/h 17.1 21.5 27.3
Power Input W 50 69 98
Air Flow Rate 3 m³/h 850/792/731/670/631/592/550 980/925/855/800/755/702/670 1200/1115/1068/1000/921/808/770
Sound Pressure Level຾ dB(A) 37/36/35/34/32/31/30 39/37/36/35/33/31/30 44/42/41/40/38/36/34
Net dimensions 5 (WxHxD) mm 1172×299×591
Main Body Packed dimensions (WxHxD) mm 1355×400×675
Net/Gross weight kg 35/43.5
Net dimensions (W×H×D) mm 1430×53×680
Panel
Packed dimensions (W×H×D) mm 1525×130×765
Net/Gross weight kg 10.5/15
Liquid/Gas pipe mm ɎɎ ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

32
Compact Four-way Cassette
360° airflow allows for even, wide-range cooling and heating.

Drain pump with 500mm pump head fitted as standard.

Optional wireless remote Optional wired


controller controller

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVB0007EF000AA 4TVB0009EF000AA 4TVB0012EF000AA 4TVB0015EF000AA

kW 2.2 2.8 3.6 4.5


Capacity
Cooling¹ kBtu/h 7.5 9.6 12.3 15.4
Power Input kW 35 35 40 50
kW/kW 2.4 3.2 4.0 5.0
Capacity
Heating² kBtu/h 8.2 10.9 13.6 17.1
Power Input W 35 35 40 50
Air Flow Rate 3 m³/h 414/380/345/313/288/268/238 521/485/450/409/380/350/314
Sound Pressure Level຾ dB(A) 35/34/34/33/28/27/26 41/39/37/35/32/31/29
Net dimensions 5 (WxHxD) mm 630×260×570
Main Body Packed dimensions (WxHxD) mm 700×330×660

Indoor Unit
Net/Gross weight kg 18/23.5 19.2/24.7
Net dimensions (W×H×D) mm 647×50×647
Panel
Packed dimensions (W×H×D) mm 715×123×715
Net/Gross weight kg 2.5/4.5
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ
Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

Notes:
Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

33
Four-way Cassette
Fresh air intake

Four-way airflow, allows wide-angle, equal distribution of cooling


and heating.

Drain pump with 750mm pump head fitted as standard.


Optional wireless remote Optional wired
controller controller
Brand-new, elegant panel with four independently controlled
louvers.

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVC0009EF000AA 4TVC0012EF000AA 4TVC0015EF000AA 4TVC0018EF000AA 4TVC0024EF000AA

kW 2.8 3.6 4.5 5.6 7.1


Capacity
Cooling¹ kBtu/h 9.6 12.3 15.4 19.1 24.2
Power Input kW 25 25 31 31 46
kW/kW 3.2 4.0 5.0 6.3 8.0
Capacity
Heating² kBtu/h 10.9 13.6 17.1 21.5 27.3
Power Input W 25 25 31 31 46
1200/1132/1065/
Air Flow Rate 3 m³/h 982/935/877/832/788/732/677 1029/957/899/857/801/756/704
996/920/866/748

Sound Pressure Level຾ dB(A) 42/40/38/37/35/34/32 43/41/39/38/36/35/34 45/43/41/39/37/35/34


Indoor Unit

Net dimensions 5 (WxHxD) mm 840×230×840


Main Body Packed dimensions (WxHxD) mm 955×260×955
Net/Gross weight kg 21.3/25.8 23.2/27.6
Net dimensions (W×H×D) mm 950×54.5×950
Panel Packed dimensions (W×H×D) mm 1035×90×1035
Net/Gross weight kg 5/8
Liquid/Gas pipe mm ɎɎ ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVC0027EF000AA 4TVC0030EF000AA 4TVC0034EF000AA 4TVC0038EF000AA 4TVC0048EF000AA

kW 8.0 9.0 10.0 11.2 14.0


Capacity
Cooling¹ kBtu/h 27.3 30.7 34.1 38.2 47.8
Power Input kW 48 75 75 75 94
kW/kW 9.0 10.0 11.0 12.5 16.0
Capacity
Heating² kBtu/h 30.7 34.1 37.5 42.7 54.6
Power Input W 48 75 75 75 94
1800/1650/1500/1300/
Air Flow Rate 3 m³/h 1264/1195/1117/1055/975/893/811 1600/1530/1380/1250 1700/1600/1440/1250/
1250/1200/1150
/1200/1150/1100 1200/1150/1100
Sound Pressure Level຾ dB(A) 46/44/42/40/38/36/35 43/42/40/38/37/35/34 45/44/42/41/40/39/37
Net dimensions 5 (WxHxD) mm 840×230×840 840×300×840
Main Body Packed dimensions (WxHxD) mm 955×260×955 955×330×955
Net/Gross weight kg 23.2/27.6 28.4/33.8 30.7/35.8
Net dimensions (W×H×D) mm 950×54.5×950
Panel Packed dimensions (W×H×D) mm 1035×90×1035
Net/Gross weight kg 5/8
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

34
Medium Static Pressure Duct
Fresh air intake.

6-step static pressure control on 2.2kW to 7.1kW models and 10-step static
pressure control on 8kW to 14kW units (requires latest generation wired Optional wireless remote
controller
Optional wired
controller
controllers).
Drain pump with 750mm pump head fitted as standard.
Flexible installation for the air inlet may be positioned either on the
underside or the rear of the unit. TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVD0007EF000AA 4TVD0009EF000AA 4TVD0012EF000AA

kW 2.2 2.8 3.6


Capacity
Cooling¹ kBtu/h 7.5 9.6 12.3
Power Input W 40 40 45
kW 2.6 3.2 4.0
Capacity
Heating² kBtu/h 8.2 10.9 13.6
Power Input W 40 40 45
Air Flow Rate 3 m³/h 520/480/440/400/360/330/300 580/540/500/460/430/400/370
Sound Pressure Level຾ dB(A) 32/31/29/28/26/25/23 33/32/31/30/28/27/25
Net dimensions 5 (WxHxD) mm 780×210×500
Unit Packed dimensions (WxHxD) mm 870×285×525
Net/Gross weight kg 18/21
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Indoor Unit
Model 4TVD0015EF000AA 4TVD0018EF000AA 4TVD0024EF000AA

kW 4.5 5.6 7.1


Capacity
Cooling¹ kBtu/h 15.4 19.1 24.2
Power Input W 92 92 98
kW 5.0 6.3 8.0
Capacity
Heating² kBtu/h 17.1 21.5 27.3
Power Input W 92 92 98
Air Flow Rate 3 m³/h 800/740/680/620/540/480/400 830/760/720/680/640/600/560 1000/960/900/840/780/720/680
Sound Pressure Level຾ dB(A) 36/34/32/31/29/27/25 36/34/33/32/30/29/28 37/35/33/32/30/29/28
Net dimensions 5 (WxHxD) mm 1000×210×500 1220×210×500
Unit Packed dimensions (WxHxD) mm 1115×285×525 1335×285×525
Net/Gross weight kg 21.5/25 27.5/31.5
Liquid/Gas pipe mm ɎɎ ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVD0027EF000AA 4TVD0030EF000AA 4TVD0038EF000AA 4TVD0048EF000AA

kW 8.0 9.0 11.2 14.0


Capacity
Cooling¹ kBtu/h 27.3 30.7 38.2 47.8
Power Input W 110 120 200 250
kW 9.0 10.0 12.5 15.5
Capacity
Heating² kBtu/h 30.7 34.1 42.7 52.9
Power Input W 110 120 200 250
1500/1430/1360/1290/ 1960/1860/1760/1660/
Air Flow Rate 3 m³/h 1260/1180/1100/1020/940/860/780
1210/1140/1080 1560/1460/1360

Sound Pressure Level຾ dB(A) 37/35/34/33/31/29/28 39/38/38/37/35/34/33 41/39/38/37/36/35/33


Net dimensions 5 (WxHxD) mm 1230×270×775
Unit
Packed dimensions (WxHxD) mm 1355×350×795
Net/Gross weight kg 36.5/44.5 37/45 46.5/55.5
Pipe connections Liquid/Gas pipe mm ɎɎ
Drain pipe mm 2'Ɏ

Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
4. All specifications are measured at standard external static pressure.

35
High Static Pressure Duct
External static pressure up to 400Pa facilitates extensive duct and
grille network.

20-step static pressure control on all models (requires latest Optional wireless remote Optional wired
generation wired controllers). controller controller

A double-skin drainage pan provides double protection for ceilings


(models 7.1 to 16.0 kW).
TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVA0024EF000AA 4TVA0027EF000AA 4TVA0030EF000AA

kW 7.1 8.0 9.0


Capacity
Cooling¹ kBtu/h 24.2 27.3 30.7
Power Input W 180 180 220
kW 8.0 9.0 10.0
Capacity
Heating² kBtu/h 27.3 30.7 34.1
Power Input W 180 180 220
Air Flow Rate 3 m³/h 1360/1327/1293/1260/1227/1193/1160 1360/1327/1293/1260/1227/1193/1160 1420/1373/1327/1280/1233/1187/1140
Sound Pressure Level຾ dB(A) 42/41/40/40/39/39/38 45/44/43/42/41/40/39
Net dimensions 5 (WxHxD) mm 965x423x690
Unit Packed dimensions (WxHxD) mm 1090×440×768
Net/Gross weight kg 41/47 51/57
Liquid/Gas pipe mm ɎɎ
Pipe connections
Indoor Unit

Drain pipe mm 2'Ɏ

Model 4TVA0038EF000AA 4TVA0048EF000AA 4TVA0055EF000AA

kW 11.2 14.0 16.0


Capacity
Cooling¹ kBtu/h 38.2 47.8 54.6
Power Input W 380 420 700
kW 12.5 16.0 17.0
Capacity
Heating² kBtu/h 42.7 54.6 58.0
Power Input W 380 420 700
Air Flow Rate 3 m³/h 1870/1783/1697/1610/1523/1437/1350 2240/2133/2027/1920/1813/1707/1600 2660/2530/2400/2270/2140/2010/1880
Sound Pressure Level຾ dB(A) 48/47/46/45/43/42/41 45/44/43/42/41/40/40 46/45/44/43/42/41/40
Net dimensions 5 (WxHxD) mm 965x423x690 1322x423x691
Unit Packed dimensions (WxHxD) mm 1090×440×768 1335×285×525
Net/Gross weight kg 51/57 68/76
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVA0068EF000AA 4TVA0085EF000AA 4TVA0095EF000AA 4TVA0192EF000AA

kW 20.0 25.0 28.0 56.0


Capacity
Cooling¹ kBtu/h 68.2 85.3 95.5 191.1
Power Input W 990 1200 1200 2272
kW 22.5 26.0 31.5 63.0
Capacity
Heating² kBtu/h 76.8 88.7 107.5 215.0
Power Input W 990 1200 1200 2272
Air Flow Rate 3 m³/h 4330/4230/4130/4030/3930/3830/3730 7400/7000/6600/6200/5800/5400/5000
Sound Pressure Level຾ dB(A) 51/50/50/49/49/48/47 4356/4120/3885/3649/3414/3178/2943
Net dimensions 5 (WxHxD) mm 1454x515x931 2005×929×670
Unit Packed dimensions (WxHxD) mm 1509×550×990 2095×964×800
Net/Gross weight kg 130/142 218/248
Liquid/Gas pipe mm ɎɎ ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ 2'Ɏ

Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
4. All specifications are measured at standard external static pressure.

36
Fresh Air Processing Unit
100% fresh air processing unit, both fresh air filtration and
heating/cooling can be achieved in a single system.

External static pressure up to 400Pa facilitates extensive duct and


grille network.
Optional wireless remote Optional wired
20-step static pressure control on all models (requires latest controller controller

generation wired controllers).

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVF0042EF000AA 4TVF0048EF000AA

kW 12.5 14.0
Capacity
Cooling¹ kBtu/h 42.6 47.8
Power Input W 480 480
kW 10.5 12.0
Capacity
Heating² kBtu/h 36.0 41.1
Power Input W 480 480
Air Flow Rate 3 m³/h 2000/1917/1833/1750/1667/1583/1500
Sound Pressure Level຾ dB(A) 48/47/46/45/44/43/42
Net dimensions 5 (WxHxD) mm 1322x423x691
Unit Packed dimensions (WxHxD) mm 1436×450×768

Indoor Unit
Net/Gross weight kg 68/76
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVF0068EF000AA 4TVF0085EF000AA 4TVF0095EF000AA

kW 20.0 25.0 28.0


Capacity
Cooling¹ kBtu/h 68.2 85.3 95.5
Power Input W 850 850 850
kW 12.8 16.0 18.0
Capacity
Heating² kBtu/h 43.7 54.6 61.4
Power Input W 850 850 850
Air Flow Rate 3 m³/h 3000/2833/2667/2500/2333/2167/2000
Sound Pressure Level຾ dB(A) 50/49/48/47/46/44/43
Net dimensions (WxHxD)
5 mm 1454x515x931
Unit Packed dimensions (WxHxD) mm 1509×550×990
Net/Gross weight kg 130/142
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
4. All specifications are measured at standard external static pressure.
5. The Fresh Air Processing Unit can be used either independently or in conjunction with other types of indoor unit. If used independently, the total
capacity of the Fresh Air Processing Units must be between 50% and 100% of that of the outdoor units. If used in conjunction with other types of
indoor unit, the total capacity of the indoor units and Fresh Air Processing Units must be between 50% and 100% of that of the outdoor units and the
total capacity of the Fresh Air Processing Units must not exceed 30% of that of the outdoor units.

37
Wall Mounted Unit
Three interchangeable panels allow units to blend easily with any
interior decoration, perfect for rooms with no false ceilings or free
floor space. Optional wireless remote Optional wired
controller controller

Refrigerant outlet direction can be left, right or rear as the


installation situation requires.
TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVW0007EF000AA 4TVW0009EF000AA

kW 2.2 2.8
Capacity
Cooling¹ kBtu/h 7.5 9.6
Power Input W 28 28
kW 2.4 3.2
Capacity
Heating² kBtu/h 8.2 10.9
Power Input W 28 28
Air Flow Rate 3 m³/h 422/411/402/393/380/368/356 417/402/386/370/353/338/316
Sound Pressure Level຾ dB(A) 31/30/30/30/29/29/29 31/30/30/30/29/29/29
Net dimensions 5 (WxHxD) mm 835×280×203
Unit Packed dimensions (WxHxD) mm 935×385×320
Net/Gross weight kg 8.4/12.1 9.5/13.1
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ
Indoor Unit

Model 4TVW0012EF000AA 4TVW0015EF000AA 4TVW0018EF000AA

kW 3.6 4.5 5.6


Capacity
Cooling¹ kBtu/h 12.3 15.4 19.1
Power Input W 30 40 45
kW 4.0 5.0 6.3
Capacity
Heating² kBtu/h 13.6 17.1 21.5
Power Input W 30 40 45
Air Flow Rate 3 m³/h 656/628/591/573/544/515/488 594/563/535/507/478/450/424 747/713/685/648/613/578/547
Sound Pressure Level຾ dB(A) 33/32/32/31/31/30/30 35/34/33/33/32/31/31 38/37/36/36/35/34/34
Net dimensions 5 (WxHxD) mm 990×315×223
Unit Packed dimensions (WxHxD) mm 1085×420×335
Net/Gross weight kg 11.4/15.5 12.8/16.9
Liquid/Gas pipe mm ɎɎ ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Model 4TVW0024EF000AA 4TVW0027EF000AA 4TVW0030EF000AA

kW 7.1 8.0 9.0


Capacity
Cooling¹ kBtu/h 24.2 27.3 30.7
Power Input W 55 55 82
kW 8.0 9.0 10.0
Capacity
Heating² kBtu/h 27.3 30.7 34.1
Power Input W 55 55 82
Air Flow Rate 3 m³/h 1195/1130/1065/1005/940/875/809 1195/1130/1065/1005/940/875/809 1421/1300/1125/1067/1005/934/867
Sound Pressure Level຾ dB(A) 44/43/42/39/38/37/36 44/43/42/39/38/37/36 48/46/45/43/41/40/38
Net dimensions 5 (WxHxD) mm 1194×343×262
Unit Packed dimensions (WxHxD) mm 1290×375×460
Net/Gross weight kg 17.0/22.4
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'Ɏ

Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

38
Ceiling / Floor
Can be installed either on the ceiling or floor.

Compact and clean design

Low noise level

Optional wireless remote Optional wired


controller controller

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVX0012EF000AA 4TVX0015EF000AA 4TVX0018EF000AA 4TVX0024EF000AA

kW 3.6 4.5 5.6 7.1


Capacity
Cooling¹ kBtu/h 12.3 15.4 19.1 24.2
Power Input W 49 115 115 115
kW 4.0 5.0 6.3 8.0
Capacity
Heating² kBtu/h 13.6 17.1 21.5 27.3
Power Input W 49 115 115 115
650/620/595/570/
Air Flow Rate 3 m³/h 800/750/700/650/600/550/500
550/525/500

Indoor Unit
Sound Pressure Level຾ dB(A) 36/35/34/33/32/31/30 43/42/41/41/39/38/38
Net dimensions 5 (WxHxD) mm 990×660×203
Unit
Packed dimensions (WxHxD) mm 1089×744×296
Net/Gross weight kg 27/33 28/34
Pipe connections Liquid/Gas pipe mm ɎɎ ɎɎ
Drain pipe mm 2'Ɏ

Model 4TVX0027EF000AA 4TVX0030EF000AA 4TVX0038EF000AA 4TVX0048EF000AA

kW 8.0 9.0 11.2 14.0


Capacity
Cooling¹ kBtu/h 27.2 30.7 38.2 47.8
Power Input W 130 130 180 180
kW 9.0 10.0 12.5 15.0
Capacity
Heating² kBtu/h 30.7 34.1 42.7 51.2
Power Input W 130 130 180 180
Air Flow Rate 3 m³/h 1200/1100/1000/900/840/780/700 1980/1940/1900/1860/1810/1770/1730
Sound Pressure Level຾ dB(A) 45/44/43/43/42/41/40 47/46/45/45/44/43/42
Net dimensions 5 (WxHxD) mm 1280×660×203 1670×680×244
Unit
Packed dimensions (WxHxD) mm 1379×744×296 1915×760×330
Net/Gross weight kg 35/41 48/58
Pipe connections Liquid/Gas pipe mm ɎɎ
Drain pipe mm 2'Ɏ

Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

39
Floor Standing Unit (Concealed)
Designed to be concealed in walls with only the suction and
discharge grills visible.

Optional wireless remote Optional wired


controller controller

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVS0007EF000AA 4TVS0009EF000AA

kW 2.2 2.8
Capacity
Cooling¹ kBtu/h 7.5 9.6
Power Input W 40 45
kW 2.4 3.2
Capacity
Heating² kBtu/h 8.2 10.9
Power Input W 40 45
Air Flow Rate 3 m³/h 530/504/478/456/439/418/400 569/540/515/485/462/443/421
Sound Pressure Level຾ dB(A) 36/35/34/33/31/30/29 36/35/34/33/31/30/29
Net dimensions 5 (WxHxD) mm 840×545×212
Unit Packed dimensions (WxHxD) mm 925×639×305
Net/Gross weight kg 21/25.5
Liquid/Gas pipe mm ɎɎ
Indoor Unit

Pipe connections
Drain pipe mm ĭ

Model 4TVS0012EF000AA 4TVS0015EF000AA

kW 3.6 4.5
Capacity
Cooling¹ kBtu/h 12.3 15.4
Power Input W 55 60
kW 4.0 5.0
Capacity
Heating² kBtu/h 13.6 17.1
Power Input W 55 60
Air Flow Rate 3 m³/h 624/591/557/522/473/420/375 660/625/583/542/501/475/440
Sound Pressure Level຾ dB(A) 37/36/35/34/32/31/30 37/36/35/34/32/31/30
Net dimensions (WxHxD)
5 mm 1036×639×305
Unit Packed dimensions (WxHxD) mm 1125×639×305
Net/Gross weight kg 25.5/30.5
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm ĭ

Model 4TVS0018EF000AA 4TVS0024EF000AA 4TVS0027EF000AA

kW 5.6 7.1 8.0


Capacity
Cooling¹ kBtu/h 19.1 24.2 27.3
Power Input W 88 110 130
kW 6.3 8.0 9.0
Capacity
Heating² kBtu/h 21.5 27.3 30.7
Power Input W 88 110 130
Air Flow Rate 3 m³/h 1150/1094/1028/970/925/886/830 1380/1290/1205/1100/1033/955/870 1380/1290/1205/1100/1033/955/870
Sound Pressure Level຾ dB(A) 41/39/37/35/33/32/31 44/42/40/39/37/35/33 44/42/40/39/37/35/33
Net dimensions 5 (WxHxD) mm 1340×545×212
Unit Packed dimensions (WxHxD) mm 1425×639×305
Net/Gross weight kg 30.5/35.5 32/37
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm ĭ

Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
4.All specifications are measured at 10Pa external static pressure.

40
Floor Standing Unit (Exposed)
The front air intake and underside air intake offer an alternative
depending on the application.
Optional wireless remote Optional wired
controller controller

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G


4TVN0007EF000AA 4TVN0009EF000AA
Model
4TVU0007EF000AA 4TVU0009EF000AA
kW 2.2 2.8
Capacity
Cooling¹ kBtu/h 7.5 9.6
Power Input W 40 45
kW 2.4 3.2
Capacity
Heating² kBtu/h 8.2 10.9
Power Input W 40 45
Air Flow Rate 3 m³/h 530/504/478/456/439/418/400 569/540/515/485/462/443/421
Sound Pressure Level຾ dB(A) 36/35/34/33/31/30/29 36/35/34/33/31/30/29
mm(F4) 1000×596×225
Net dimensions (WxHxD)
5
mm(F5) 1000×677×220
mm(F4) 1089×683×312
Unit Packed dimensions (WxHxD)
mm(F5) 1182×683×312
kg(F4) 28/33
Net/Gross weight
kg(F5) 28/35
Liquid/Gas pipe mm ɎɎ
Pipe connections

Indoor Unit
Drain pipe mm ĭ

4TVN0012EF000AA 4TVN0015EF000AA
Model
4TVU0012EF000AA 4TVU0015EF000AA
kW 3.6 4.5
Capacity
Cooling¹ kBtu/h 12.3 15.4
Power Input W 55 60
kW 4.0 5.0
Capacity
Heating² kBtu/h 13.6 17.1
Power Input W 55 60
Air Flow Rate 3 m³/h 624/591/557/522/473/420/375 660/625/583/542/501/475/440
Sound Pressure Level຾ dB(A) 37/36/35/34/32/31/30 37/36/35/34/32/31/30
mm(F4) 1200×596×225
Net dimensions 5 (WxHxD)
mm(F5) 1200×677×220
mm(F4) 1289×683×312
Packed dimensions (WxHxD)
mm(F5) 1382×683×312
Unit kg(F4) 33/38.6
Net/Gross weight
kg(F5) 33/40.7
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm ĭ

4TVN0018EF000AA 4TVN0024EF000AA 4TVN0027EF000AA


Model
4TVU0018EF000AA 4TVU0024EF000AA 4TVU0027EF000AA
kW 5.6 7.1 8.0
Capacity
Cooling¹ kBtu/h 19.1 24.2 27.3
Power Input W 88 110 130
kW 6.3 8.0 9.0
Capacity
Heating² kBtu/h 21.5 27.3 30.7
Power Input W 88 110 130
Air Flow Rate 3 m³/h 1150/1094/1028/970/925/886/830 1380/1290/1205/1100/1033/955/870 1380/1290/1205/1100/1033/955/870
Sound Pressure Level຾ dB(A) 41/39/37/35/33/32/31 44/42/40/39/37/35/33 44/42/40/39/37/35/33
mm(F4) 1500×596×225
Net dimensions 5 (WxHxD)
mm(F5)
mm(F4) 1500×677×220
Unit Packed dimensions (WxHxD)
mm(F5) 1589×683×312
kg(F4) 40/46 1682×683×312
Net/Gross weight
kg(F5) 40.0/48.6 40/46
Pipe connections Liquid/Gas pipe mm ɎɎ 41.5/49.5
Drain pipe mm ĭ
Notes:
1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level di erence.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level di erence.
3.Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.

41
Console
Combination of four air inlets and two air outlets ensures that
cooling and heating are distributed in all directions.

Optional wireless remote Optional wired


controller controller

TCONTRMUT12D TCONTRMUT05B TCONTKJRUT86ED TCONTKJRUT120G

Model 4TVJ0007EF000AA 4TVJ0009EF000AA 4TVJ0012EF000AA 4TVJ0015EF000AA

kW 2.2 2.8 3.6 4.5


Capacity
Cooling¹ kBtu/h 7.5 9.6 12.3 15.4
Power Input W 20 25 25 35
kW/kW 2.6 3.2 4.0 5.0
Capacity
Heating² kBtu/h 8.9 10.9 13.4 17.1
Power Input W 20 25 25 35

430/401/374/345/ 660/614/561/512/
Air Flow Rate 3 m³/h 510/482/456/430/355/286/229
302/268/229 478/436/400
Indoor Unit

Sound Pressure Level຾ dB(A) 38/36/34/32/28/27/26 39/37/35/33/31/29/27 42/41/40/39/37/36/36


Net dimensions 5 (WxHxD) mm 700×600×210
Unit
Packed dimensions (WxHxD) mm 810×710×305
Net/Gross weight kg 14/19 15/20
Liquid/Gas pipe mm ɎɎ
Pipe connections
Drain pipe mm 2'ĭ

Notes:
1.Indoor temperature
Indoor temperature 27°C
27°C DB,
DB, 19°C
19°C WB;
WB; outdoor
outdoor temperature
temperature 35°C
35°C DB;
DB; equivalent
equivalent refrigerant
refrigerant piping
piping length
length 7.5m
7.5m with
with zero
zero level
level difference.
difference.
2.Indoor temperature20°C
Indoor temperature 20°CDB;DB;outdoor
outdoor temperature
temperature 7°C
7°C DB,DB, 6°C
6°C WB;
WB; equivalent
equivalent refrigerant
refrigerant piping
piping length
length 7.5m
7.5m with
with zerolevel
zero leveldifference.
difference.
3.Sound pressure
Sound pressure level
level is is measured1.4m
measured 1.4mbelow
belowthe
theunit
unitinina semi-anechoic
a semi-anechoicchamber.
chamber.

42
Controller Lineup
Wireless Remote
Centralized Controllers Data converter Network Control System BMS Gateways Accessories
Wired Controllers

TCONTCCM180A TCONTCCM15B Hotel Key Card


TCONTWEBBAC01
Interface Module
TCONTRMUT05B

TCONTNAM05A

TCONTRMUT12D
TCONTNAM05B

TCONTCCM270A TCONTWEBBAC01 TCONTCCM20 Infrared Sensor


Controller

+
TCONTNAM09A

TCONTCNTSUT

TCONTKJRUT86ED TCONTCCM270A Diagnosis software


TCONTCCM18E

TCONTKJRUT120G
+
TCONTCNTSUT

TCONTDIAGS

Indoor Unit

43
Wireless Remote Controllers

TCONTRMUT05B TCONTRMUT12D

MODEL

On / Off
Mode selection
Temperature setting
7-speed fan control (0.5°C or 1°C steps) (0.5°C or 1°C steps)
Auto swing
5-step swing louver
Address setting
Follow me
Eco mode
Night silent mode
Display shut-off
Daily timer
Keyboard lock
Background light
Dimensions (H×W×D) (mm) 150x65x20 170x48x20
Batteries 1.5V (LR03/AAA) × 2
Control Solutions

44
Temperature Setting Follow Me

The temperature setpoint can be adjusted in 0.5°C or 1.0°C steps. The follow me function works in the following way when it is
This feature allows for a precise control, resulting in a comfortable active. The indoor unit responds to the temperature sensor built-in
environment. into the wireless remote controller instead of using the indoor
unit’s sensor. In this way, the temperature measurement is more
accurate and precise.

7-Speed Fan Control


The indoor unit’s DC fan is equipped with a 7-speed motor,
providing the flexibility to meet the airflow requirement for any
condition.

Eco Mode

In Eco mode the system will attempt to reduce the energy


consumption, while keeping a comfortable indoor environment.

Display Shut-off

Control Solutions
The indoor unit display can be turned off at night creating a
cozier environment.

5-step Swing Louver

The 5-step swing louver directs the airflow to the desired airflow
angle. This function is available through the unit controller.

1
2
3
Step
4
Swing 5

45
Wired Controllers

Model TCONTKJRUT86ED TCONTKJRUT12DG

MODEL

On / Off
Mode selection
Temperature setting (0.5°C or 1°C steps) (0.5°C or 1°C steps)
Dual temperature setpoints
7-speed fan control
Auto swing
5-step swing louver
Address setting
Follow me
Eco mode
Room temperature display
°F/°C display
Keyboard lock
Background light
Daily timer
Weekly schedule timer
Auto restart
2 permission levels
Control Solutions

Bi-directional communication
Group control
Main or secondary controller setting
Display shut-off
Night silent mode
Remote signal receiver
Clean filter reminder
Override function
Daylight time saving
Clock display
Dot matrix display
Error check function
System query
System setup
Dimensions (WxHxD) (mm) 86x86x18 86x86x18
Power supply 18V DC 18V DC

46
Group Control Override Function
The wired controllers are capable of controlling up to 16 indoor When the override function is enabled, it postpones a system
units using the same setpoint. scheduled shutdown by 1 or 2 hours.

D1D2 D1D2 D1D2 D1D2

24°C OVERRIDE

ON OFF
X1X2

Indoor Units Up to 16

Dual Temperature Set Points

Main or Secondary Controller Setting One setpoint for cooling and another for heating mode can be
set up using the dual setpoint function. When the unit mode is
A single indoor unit could receive operating instructions by 2 changed, the setpoint has been already defined for the user’s
different controllers. The indoor unit will respond to the latest convenience.
command received. When a command is sent by one of the
controllers, the other controller is automatically adjusted showing
the same information in the display.

X1X2 X1X2 17°C 30°C

Indoor Units
Main Secondary

One Indoor Unit

D1D2 D1D2 D1D2 D1D2


Weekly Schedule
The weekly schedule timer allows users to set multiple schedules
X1X2 X1X2 each with its own operating mode, temperature settings and fan
Indoor Units Up to 16 speeds.

Control Solutions
Two or more Indoor Units

Two Permission Levels


WEEKLY SCHDULE
Having two levels of permission ensures that only the administrator
has access to advanced functions and the users are only allowed SU MO TU WE TH FR SA
to control basic functions avoiding a possible operating system OFF HEAT COOL FAN
misuse.

Bi-directional Communication
ADMIN
The wired controller can query the system operating parameters
thanks to the new bi-directional communication functionality. In
addition, settings including static pressure, cold draft prevention
and temperature compensation can be configured in the wired
controller.

USER Bi-directional Bi-directional

47
Centralized Controllers

TCONTCCM180A TCONTCCM270A

MODEL

Max. number of indoor units


Max. number of refrigerant systems 8 48
Touch screen (6.2-inch) (10.1-inch)
On / Off
Mode selection
Temperature setting (0.5°C or 1°C steps) (0.5°C steps)
7-speed fan control
Auto swing
5-step swing louver
Room temperature display
Outdoor unit Eco mode setting
Holiday setting
°C/°F display
Schedule management
Clock display
Two permission levels
Override function
Daylight time saving
Control Solutions

Unit model recognition


Energy consumption calculation
Visual schematic
Energy management
Group management
Error check function
System query
USB access Error report, operation record and
Error report
Report display electricity consumption report
Email capability
Operation log
LAN access
Dimensions (W×H×D) (mm) 181x124x30 270x183x27
Power supply 12V DC 24V AC

48
Touch Screen Energy Management
The centralized controllers are designed with a touch screen vivid Multiple locking functions and set point limitations can be
display making the operation more convenient and user friendly. established using the centralized controllers that ultimately
translate into additional energy savings. The functions available
are: minimum cooling setpoint, maximum heating setpoint, fan
speed lock, operation mode lock, swing lock, remote and wired
controller lock.

Visual Schematic

Users can create a tailored system schematic enabling


monitoring and control of the indoor units through a clear visual
representation of the system layout. This is achieved by importing
floor plans and then dragging and dropping the indoor units to
Energy consumption calculation
their actual positions.
The TCONTCCM270A centralized controller uses a patented
algorithm to estimate the energy system consumption. The
outdoor unit power consumption is assigned among the indoor
units based on their usage demand. This feature allows a building’s
owner to determine each tenant’s energy electricity charge.

Total Energy
AC Unit 1
AC Unit 2
AC Unit 3

Control Solutions
120

100

80

60

40

20

0
January February March April May June

Group Management

The indoor units can be visualized in groups, systems or location


making the unit management easier and more convenient.

200 Units
Group System Map

Building One

Unit Group 1
Unit Group 2
4th Floor

5th Floor
Unit Group 3

Building Two

Building Three

Building Four
ON ON ON HEAT OFF

49
Outdoor Unit Configuration

Using the centralized controllers it is possible to monitor and


control different outdoor unit configurations and settings, without
having to access it on site.

Silent mode
setting
Static pressure Operation Priority mode Energy
setting capacity control setting setting

Unit Model Recognition LAN Access

The type of indoor and outdoor units are recognized by the Using the centralized controller LAN connection it is possible to
centralized controller assigning the correct unit icon for easy visualize and operate the system using a PC that could be installed
identification. locally or remotely (VPN required).
Control Solutions

Schedule Management

The schedule function can be used to create daily, weekly or


annual schedules. It is possible to define units setting such as on/
off, operating modes, setpoint temperatures, fan speed and indoor
unit swing.

50
Wiring Flexibility

For easy installation, the controllers can be connected to the


master outdoor unit directly.

X, Y, Up to
P,Q,E P,Q,E 64 Evaps
P,Q,E

TCONTCCM180A
X, Y,

P,Q,E P,Q,E Up to P,Q,E


64 Evaps

Até
64 Evaps

X, Y,
P,Q,E P,Q,E Up to P,Q,E
64 Evaps

Up to 8
Refrigerant Systems

Up to 8 refrigerant systems

X, Y, E P,Q,E P,Q,E Up to P,Q,E


64 Evaps

TCONTCCM270A Up to 8 refrigerant systems

X, Y, E Up to
P,Q,E P,Q,E P,Q,E

Control Solutions
64 Evaps

6 Ports Input
X,Y,E
Up to 64
Indoor Units

Up to 8 refrigerant systems

LAN Up to
X, Y, E P,Q,E P,Q,E 64 Evaps P,Q,E

51
Network Control System

Software model TCONTCNTSUT

TCONTWEBBAC01 TCONTCCM270A

Software model

Hardware model

Max. number per network system 10 10


Max. number of indoor units 2560 3040
Max. number of refrigerant systems 320 480
Temperature setting (0.5°C steps) (0.5°C steps)
Dual temperature setpoints
7-speed fan control
Auto swing
5-step swing louver
Outdoor unit Eco mode setting
Control Solutions

Holiday setting
Schedule management
Clock display
Two permission levels
Unit model recognition
Energy consumption calculation
Visual schematic
Energy management
Group management
Error check function
System query
Report output
Operation log
LAN access
Data backup
Remote VPN access
Dimensions (W×H×D) (mm) 251x319x66 270x183x27
Power supply 1 phase, 100-240V, 50/60Hz 24V AC

52
Data Converter

Hardware model

TCONTCCM15B

Application scenarios

Mobile Phone Application Cloud Server Website

Max. number of CCM-15 for one mobile APP 10 10


Max. number of indoor units 640 640
Max. number of refrigerant systems 80 80
On/Off
Mode selection
Temperature setting (1°C steps) (1°C steps)
7-speed fan control
Auto swing
5-step swing louver
Room temperature display
o
C/ oF display

Control Solutions
Weekly timer
Indoor unit type recognition
Energy management
Group management
User group management
Operation log
Device log
Login record
Error log
Configuration
Account registration
Virtual
Mode display
Languages supported English, French, Spanish English, French, Spanish
Dimensions (W×H×D) (mm) 187x115x28
Power supply 1 phase, 100-240V, 50/60Hz

53
User-friendly Interface Visual Schematic

The simple and practical user interface creates a user-friendly Users can create a tailored system schematic enabling
experience even for first timers. monitoring and control of the indoor units through a clear visual
representation of the system layout. This is achieved by importing
floor plans and then dragging and dropping the indoor units to
their actual positions.

245

Outdoor Unit Configuration


Using the centralized controllers it is possible to monitor and
control different outdoor unit configurations and settings, without
having to access it on site. Schedule Management
The schedule function can be used to create daily, weekly or
Operation Silent mode
Priority mode annual schedules. It is possible to define unit settings such as on/
capacity control setting
setting Energy off, operating modes, setpoint temperatures, fan speed and indoor
setting
unit swing.
Control Solutions

Energy Consumption Calculation

The TCONTCCM270A centralized controller uses a patented


algorithm to estimate the energy system consumption. The
outdoor unit power consumption is assigned among the indoor
units based on their usage demand. This feature allows a building’s
owner to determine each tenant’s energy electricity charge.

54
Network Flexibility

WLAN

Desktop
Desktop

Laptop Fire Wall


Laptop
Internet
Internet

or or

100%
100%

Tablet Web-Interface Tablet Web-Interface

LAN access Remote VPN access

Network Control

Control Solutions
Up to 10

LAN
Desktop

IMMPRO Gateway

Laptop
Up to 4 XYE ports

X Y E
100%

WLAN Tablet
P,Q,E

Outdoor unit

Indoor unit
Up to 64
P,Q,E
Indoor Units

Up to 8
Refrigerant Systems

Indoor

55
TCONTCCM270A

Up to 10

Desktop

Laptop

X Y E

100%
WLAN Tablet
P,Q,E

Outdoor unit

Indoor unit
Up to 64
P,Q,E
indoor units

Up to 8
Refrigerant Systems

Indoor
Control Solutions

56
BACnet® Gateway
TCONTWEBBAC01

MODEL BACnet Gateway

Max. number of indoor uznits 256


Max. number of refrigerant systems 32
On / Off
Mode selection
Control
Temperature setting
Fan speed
Energy management
Room temperature display
Indoor unit monitoring Error status

Full Integration Error alarms


Operating mode

The BACnet Gateway allows Trane TVR systems to be monitored Outdoor ambient temperature

and controlled alongside other building management technology Fan speed

that use the BACnet protocol such as access control, fire detection Outdoor unit monitoring Compressor operating frequency

and lighting systems. Discharge temperature


System pressure
Network Flexibility Error status
Error alarms

For easy installation, the BACnet gateway can be connected to the LAN access

master outdoor unit’s XYE ports directly. BTL certification

Up to 8 refrigerant systems

Control Solutions
P,Q,E P,Q,E Up to P,Q,E
64
X, Y, E

TCONTWEBBAC01
Up to 8 refrigerant systems

P,Q,E P,Q,E Up to P,Q,E


64
X, Y, E

Up to 4 XYE
Ports

Up to 8 refrigerant systems

P,Q,E P,Q,E Up to P,Q,E


LAN 64
X, Y, E

HUB
TCP/IP BACnet/IP protocol

Web access BACnet BMS

57
LonWorks® Gateway
TCONTCCM20

Model
MODEL LonWorks Gateway

Max. number of indoor units 64


Max. number of refrigerant systems 8
Mode selection
Temperature setting
Control
Fan speed
Group shut down
On / Off
Operating mode
Set temperature

Full Integration Fan speed


Indoor unit monitoring Online status
Operating status
The LonWorks Gateway allows Trane TVR systems to be monitored
Room temperature
and controlled alongside other building management technology
on the LonWorks platform such as security, fire safety and lighting Error status

systems. Outdoor unit monitoring Error status


Dimensions (HxWxD)( mm) 319×251×61

Network Flexibility Power supply


1 phase,
100-240V,
50/60Hz
Control Solutions

X,Y,E P,Q,E P,Q,E P,Q,E

TCONTCCM20

X,Y,E

P,Q,E P,Q,E P,Q,E

Up to 64
Indoor Units

X,Y,E

Up to 8
refrigerant systems P,Q,E P,Q,E P,Q,E

LonWorks BMS

58
Modbus® Gateway
TCONTCCM18E

MODEL Modbus Gateway

Max. number of indoor units 64


Max. number of refrigerant systems 1
On / Off
Mode selection
Control Temperature setting
Fan speed
Group on/off
Online status
Room temperature
Indoor unit monitoring
Full Integration Error status
Operating mode

The Modbus Gateway allows the Trane TVR system to communicate Operating mode

with other BMS configured over the Modbus communication Lock status

protocol. Fan speed


Outdoor unit monitoring
Set temperature
Network Flexibility Outdoor ambient temperature
Error status
LAN access
BTL certification 187×115×28
1 phase,
Power Supply 100-240V,
50/60Hz

Control Solutions

59
Hotel Key Card Interface Modules
Full Integration
Hotel Key Card interface modules are designed to energize the indoor units, only when the card is inserted into the card slot. In this
manner, indoor units operate only when necessary, and consequently saving energy.

Model TCONTNAM05A TCONTNAM05B

Appearance

CN20
Network CN20

CN2 CN2
Flexibility 220V
220V

Key card
AC contactor
Key card

Auto restart
Compatiblity Remote and wired controller Remote and wired controller
Dimensions
15.5x86x72.8 87x150x70
(HxWxD) (mm)
Power supply 5V DC (supplied by indoor unit) 1phase, 100-240V, 50/60Hz

Infrared Sensor Controller


Full Integration
Control Solutions

Infrared sensors are designed to detect movement. Once the sensor detects movement in the area, it automatically turns on the units; if
the area is found to be unnoccupied, it turns off the units. This accessory is suitable for hotels, offices, conference rooms and residences.
It helps in the reduction of energy waste.

Model TCONTNAM09A

Appearance

CN20
ABCDE

Wired controller CN2


Network flexibility CN1

Control Box

Infrared Sensor

Dimensions (H×W×D)(mm) Sensor 46×30×25.6, Control box 86×72.8×15.5


Power supply 5V DC (Supplied by indoor Unit)

60
Diagnosis Software
Monitor and Diagnose

The Trane TVR Diagnosis Software tool is used to monitor and


diagnose alarms and errors of the VRF system. System settings
and operating parameters can be easly accessed. This tool can also
review data logs for fault prevention purposes.

Additionally, a system schematic, a refrigerant flow diagram and


a parameter chart could be generated to provide a graphical
interpretation of the system status.

MODEL TCONTDIAGS

Max. number per network system 64


Max. number of refrigerant systems 1
Mode selection
Control Temperature setting
Fan speed
Operating mode
Capacity
Compressor operating frequency
Operating current
Outdoor unit monitoring
Error status
Temperatures T3,T4,Tp (See note 1)
Valve status SV4, SV5, SV6, ST1 (See note 2)
EXV position
Operating mode
Capacity
Fan speed
Indoor unit monitoring
Address
Temperatures T1, T2, T2B, TS (See note 3)
EXV position

Control Solutions
Error codes
Troubleshooting
Data logs

Diagrams System schematic, refrigerant


flow diagram, parameter chart
Languages supported English

61
VRF AHU Control Box Single AHU Control Box Connection

Blower, T1,T2,T2B
Wide Capacity Range Water pump and sensor

Four Control Boxes can be used in parallel setting, thus providing P,Q,E MAX-20HP
an overall capacity range of 3.2HP to 80HP.

TCONTAHUKIT1B TCONTAHUKIT2B TCONTAHUKIT3B


3.2-6HP 8-12HP 14-20HP

Multi AHU Control Boxes Connection


P,Q,E Blower, T1,T2,T2B
Water pump and sensor

Max- 80 HP

X,Y,E
Control Solutions

X,Y,E
TCONTAHUKIT3B
14-20HP

X,Y,E

Model 7&217$+8.,7% 7&217$+8.,7% 7&217$+8.,7%

Capacity HP 3.2-6  


Refrigerant 5$
Pipe connections (inlet and outlet) mm ĭ ĭ ĭ
Net dimensions (W×H×D) mm îî
Packed dimensions (W×H×D) mm îî
Net weight kg   
Gross weight kg   
Operating modes Cooling, heating and fan only
Standard controller Wired controller
Optional controller Wireless remote controller; SIEMENS controller

62
Heat Recovery Ventilator
Enhanced Efficiency Low Noise
The Trane TVR heat recovery ventilators can greatly reduce energy Sound attenuators are used to provide a quiet operation.
losses and room temperature fluctuations caused by the ventilation
process. Flexibility
The strong performance exercised by these units is a result of The height of the units can start as low as 264mm and could weigh
the advanced technology incorporated into their design. The as low as 23kg. These characteristics allow for easy installation
heat exchanger core made of especially treated paper provides even within space limitations.
enhanced temperature and humidity control. The temperature
exchange efficiency is over 65% and the enthalpy exchange
efficiency is between 50% and 65%.

264mm
TERV0120 TERV0300 TERV0900
TERV0175 TERV0470 TERV1200
TERV0235 TERV0600
RA
(Return air
from room)

SA
14°C
SA
Cold air (Supply air
0°C
to room)
Moisture
EA
Warm air
6°C Heat
20°C

Heat exchange plate


EA
(Exhaust air
to outdoors) OA
(Fresh air from
outdoors)

HRV

63
Specifications DC Series

Model HRV-D200 HRV-D300 HRV-D400 HRV-D500

Power supply V/Ph/Hz 220-240/1/50(60)

ŽŽůŝŶŐƚĞŵƉ͘ĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 76.1 74.8 76.2 76.1

ŽŽůŝŶŐĞŶƚŚĂůƉLJĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 77.3 76.1 78.7 78.2

,ĞĂƟŶŐƚĞŵƉ͘ĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 76.1 74.8 76.2 76.1

,ĞĂƟŶŐĞŶƚŚĂůƉLJĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 82.6 79.8 83.6 80.4

Sound pressure level dB(A) 27 30 32 35

3
ŝƌŇŽǁƌĂƚĞ m /h 200 300 400 500

džƚĞƌŶĂůƐƚĂƟĐƉƌĞƐƐƵƌĞ Pa 75 75 80 80

Motor type DC

Duct diameter mm Ɍ144 Ɍ144 Ɍ144 Ɍ194

Net dimensions (WxDxH) mm 852×665×264 928×734×270 928×940×270 1020×1036×270

Packed dimensions (WxDxH) mm 910×710×430 980×774×435 1010×1010×440 1120×1120×452

Net weight kg 25 27 32 35

Gross weight kg 37 40 46 51

o
KƉĞƌĂƟŶŐƚĞŵƉĞƌĂƚƵƌĞƌĂŶŐĞ C -7 to 43 DB, RH 80% or lower

Model HRV-D800 HRV-D100 0 HRV-D150 0 HRV-D200 0

Power supply V/Ph/Hz 220-240/1/50(60)

ŽŽůŝŶŐƚĞŵƉ͘ĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 76.9 75.8 77.8 77.2

ŽŽůŝŶŐĞŶƚŚĂůƉLJĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 78.1 76.9 79.2 78.7

,ĞĂƟŶŐƚĞŵƉ͘ĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 76.9 75.8 77.8 77.2

,ĞĂƟŶŐĞŶƚŚĂůƉLJĞdžĐŚĂŶŐĞĞĸĐŝĞŶĐLJ % 80.1 78.6 80.5 80.3

Sound pressure level dB(A) 39 40 51 53

3
ŝƌŇŽǁƌĂƚĞ m /h 800 1000 1500 2000

džƚĞƌŶĂůƐƚĂƟĐƉƌĞƐƐƵƌĞ Pa 100 100 160 170

Motor type DC

Duct dimensions mm Ɍ242 Ɍ242 346×326 346×326

Net dimensions (WxDxH) mm 1276×1020×388 1276×1269×388 1600×1270×540 1650×1470×540

Packed dimensions (WxDxH) mm 1355×1045×560 1400×1370×573 1710×1410×720 1760×1610×720


HRV

Net weight kg 58 69 151 165

Gross weight kg 77 90 184 198

o
KƉĞƌĂƟŶŐƚĞŵƉĞƌĂƚƵƌĞƌĂŶŐĞ C -7 to 43 DB, RH 80% or lower

1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valves.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.

64
Branch Joints

Type Appearance Model Packed Dimensions Gross Weight


Note
mm kg

two
TODK02UTHP 255×150×185 2.0
outdoor units

Branch joints for


outdoor units

three
TODK03UTHP 345×160×285 4.3
outdoor units

TRDK056HP 290×105×100 0.4 /

TRDK112HP 290×105×100 0.6 /

TRDK225HP 310×130×125 0.9 /

Branch joints for


TRDK314HP 04350×180×170 1.5 /
indoor units

Branch Joints

TRDK768HP 365×195×215 1.9 /

TRDK840HP 390×230×255 3.1 /

TRDK918HP 390×230×255 3.4 /

65
Branch Joints

66
Model

TODK03UTHP
TODK02UTHP
ID:38.1 ID:41.3 OD:44.5 ID:38.1
ID:31.8 OD:38.1 ID:44.5 ID:31.8 OD:38.1
Q2 OD:44.5 Q2 ID:38.1 OD:38.1
Outdoor Branch Joints

Q7 Q4 Q3
Q1
Q5
Q1 ID:38.1 ID:44.5 ID:54.0 ID:38.1 ID:41.3
ID:41.3 Q1
OD:38.1 ID:38.1 OD:38.1 ID:38.1 OD:38.1
Gas side joints

ID:38.1 ID:38.1 ID:25.4 ID:38.1 ID:31.8


ID:25.4 ID:25.4
ID:31.8 ID:31.8 OD:31.8 ID:28.6 ID:31.8 OD:38.1
OD:31.8 ID:28.6 OD:31.8 ID:28.6

ID:15.9 OD:19.1 ID:19.1 ID:22.2 ID:25.4


OD:19.1 OD:25.4 OD:19.1 ID:19.1
ID:15.9 ID:19.1
Y2 OD:19.1
Y6 Y1 Y7 Y4 Y2
Y1 Y6 Y3
ID:19.1 ID:22.2 ID:25.4 ID:28.6
Y1 ID:19.1 ID:22.2
OD:19.1 ID:19.1 OD:19.1 ID:19.1
ID:19.1 OD:19.1 ID:19.1
ID:19.1
ID:15.9 OD:25.4 ID:22.2 ID:19.1
ID:15.9
Liquid side joints

ID:15.9 ID:12.7
ID:12.7 ID:12.7 OD:15.9
OD:15.9 OD:15.9
Model

TRDK918HP
TRDK840HP
TRDK768HP
TRDK314HP
TRDK225HP
TRDK112HP
TRDK056HP
ID:22.2
ID:41.3 ID:19.1
ID:41.3 ID:34.9 ID:28.6 ID:15.9
ID:22.2 ID:15.9 ID:12.7 ID:12.7
ID:34.9 ID:19.1 ID:12.7
OD:54 ID:28.6 ID:19.1 ID:22.2 ID:15.9
ID:41.3 (ID:19.1) (ID:15.9)
Indoor Branch Joints

OD:54 OD:34.9
ID:22.2 (ID:19.1) (ID:15.9)
ID:34.9 ID:34.9 ID:41.3
ID:63.5 ID:63.5 ID:44.5 OD:34.9 OD:28.6 OD:22.2 OD:19.1
OD:22.2 OD:19.1
ID:41.3 ID:54 ID:41.3 OD:28.6
ID:54 ID:34.9
ID:28.6 ID:22.2 ID:19.1
Gas side joints

OD:54 OD:54 OD:41.3 OD:28.6 OD:22.2 OD:19.1

ID:54 OD:34.9 ID:28.6 ID:22.2 ID:19.1


ID:54 ID:41.3
ID:31.8 ID:25.4 ID:15.9
ID:63.5 ID:44.5 ID:34.9
ID:63.5
ID:38.1

ID:12.7 ID:15.9 ID:12.7


ID:9.5 ID:6.4 ID:6.4
ID:15.9
ID:19.1 (ID:19.1) ID:15.9 ID:12.7 ID:9.5
ID:15.9 (ID:19.1) (ID:15.9) ID:6.4
ID:19.1 ID:22.2 ID:9.5 ID:6.4 ID:9.5
(ID:19.1) (ID:15.9) ID:6.4
ID:22.2 OD:22.2 (ID:12.7)
(ID:19.1) OD:22.2 OD:19.1 (ID:12.7)
OD:28.6 OD:9.5
OD:22.2 OD:19.1 ID:9.5 ID:9.5
OD:28.6 OD:22.2 ID:25.4 OD:15.9 OD:12.7
ID:28.6 ID:22.2 ID:22.2 ID:19.1 OD:15.9 OD:9.5
OD:12.7
Liquid side joints

ID:12.7 ID:9.5
ID:15.9

OD:28.6 OD:22.2 OD:12.7 OD:12.7


ID:22.2 OD:22.2 OD:19.1
ID:28.6 OD:15.9
ID:31.8 ID:22.2 ID:19.1 ID:9.5
ID:25.4 ID:12.7
ID:15.9
ID:22.2 ID:19.1 ID:9.5
ID:25.4

67
Branch Joints
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and environments.
Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together
to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and

progress and enduring results.

Trane, the Circle Logo, Engineered Conversion, CenTraVac, EcoWise, Tracer, Tracer trane.com ingersollrand.com
AdaptiView, R’newal, and Let’s Go Beyond are trademarks of Trane in the United States
and other countries. ASHRAE is a registered trademark of the American Society of
Heating, Refrigerating, and Air-Conditioning Engineers, Inc. All trademarks referenced
are the trademarks of their respective owners.

We are committed to using environmentally conscious print practices that reduce waste. ©2019 Ingersoll Rand VRF-SLB031-EN Sep, 2019