R22 air-cooled modular chiller 50Hz unit MCAC-ATSM-2012-02

130kw module
Dimension

Front view Side view

Top view Anchor hole


Unit: mm
Model A B C D E F G H

MGB-F130W/S 2000 1700 1940 350 1420 506 1550 1586


MCAC-ATSM-2012-02 R22 air-cooled modular chiller 50Hz unit

Specification
Model MGB-F130W/S MGB-F200W/S

Cooling Capacity kW 130 185


Heating Capacity kW 138 200
Power supply V/Ph/Hz 380/3/50 380/3/50
Type Fixed speed Scroll
Quantity Pieces 4 6
Model VR144KS-TFP-522 SM147A4ALB
Brand Copeland Danfoss
Compressor
Capacity W 35200×4 32561×6
Input W 10100×4 9214×6
Rated current(RLA) A 22.1×4 19.3×6
Locked rotor Amp(LRA) A 110×4 147×6
Cooling kW 40.4 63
Power input
Heating kW 39.0 61
Type R22
Refrigerant
Weight kg 30 42
Air side heat-exchanger type Fin-coil
Condenser Quantity of fan motor Pieces 4 6
3 3
(Air side) Air flow volume ×10 m /h 48 72
Fan motor input kW 0.55×4 0.55×6
Water side heat-exchanger type Shell and tube heat exchanger
Water resistance loss kPa 25 30
Water inlet/outlet pipeline
Evaporator mm DN65 DN80
diameter
(Water side)
Water flow volume m3/h 22.4 31.8
Max. Pressure MPa 1
Water pipe connection type Flexible joint
Dimension L×W×H mm 2000×1685×2090 2850×2000×2110
Packing size L×W×H mm 2080×1755×2240 2980×2135×2260
Net weight kg 1150 1730
Weight
Gross weight kg 1200 1780
2
Connection Power wiring mm ×No. 35×4+16 ×1 70×4+35 ×1
2
wiring Signal wiring mm ×No. 0.75×3-core
Control type Wired controller
High or low pressure switch, freeze-proof device, water flow
Safety protection device volume controller, overcurrent device, power phase sequence
device etc.
Noise level dB(A) 68 72
Operation water temp ℃ Cooling:5~17 Heating:45~50
Ambient temp ℃ Cooling:10~46 Heating:-10~21

Note: Specifications are based on the following conditions:


Cooling : chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
Heating : heat water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°C WB.
Water side fouling factor: 0.086m2˚C /kW.

Specification
MCAC-ATSM-2012-02 R22 air-cooled modular chiller 50Hz unit

130kw module

Installation
MCAC-ATSM-2012-02 R22 air-cooled modular chiller 50Hz unit

Installation mode B: less than 12 modules


13.2.7 Installation of water system pipeline for 130kw module
Installation of single-module water system pipeline

Electric control box

Total water outlet


temp sensor
Water intlet
Water outlet

Installation of multi-module water system pipeline


1) Installation mode I (recommended installation mode)
n : the module quantity, max8

No.1 unit No.(n-1) unit No.n unit (n≤8)


No.0 address(main unit) No.(2n-3) address No.(2n-1) address
No.1 address No.(2n-4) address No.(2n-2) address

Water flow switch


Pump

Drill dead hole at the


position, and move the
total effluent temperature
sensor at No.0 address to
the position

Installation mode B: less than 8 modules

Installation 79
MCAC-ATSM-2012-02 R22 air-cooled modular chiller 50Hz unit

2) Installation mode II
n : the module quantity, max8
No.n unit (n≤8) No.(n-1) unit No.1 unit
No.(2n-1) address No.(2n-3) address No.0 address(main unit)
No.(2n-2) address No.(2n-4) address No.1 address

Pump

Drill dead hole at the


position, and move the Water flow switch
total effluent temperature
sensor at No.0 address to
the position

Installation mode B: less than 8 modules

Table of diameter parameters of main inlet and outlet pipes for 130kw module

Total inlet and outlet water Total inlet and outlet water
Unit model x quantity Unit model x quantity
pipe diameter pipe diameter
130×1 DN65 130×5 DN125
130×2 DN100 130×6 DN150
130×3 DN100 130×7 DN150
130×4 DN125 130×8 DN200

86 Installation