Professional Documents
Culture Documents
Introduction
The purpose of the substation structure design guide is to provide a comprehensive
document for the design of outdoor electrical transmission substation structures. The
recommendations of this document apply to substation structures that support
electrical equipment, rigid bus, and electrical cables/wires. The electrical equipment
can be of significant weight and have attachments of brittle porcelain components.
Specific guidelines for structural loads, deflection limits, analysis, design, fabrication,
maintenance and construction of substation structures are recommended. Guidelines
for the design of the structure to the foundation connections are provided. The design
criteria for substation structure foundations are not covered by this document.
Foundations in substations should be designed according to accepted engineering
practice, the same as foundations designed for other structures. The guide addresses
steel, concrete, wood, and aluminum used for the design of substation structures.
Design equations are provided when reference to existing structural design
documents are not appropriate or convenient. The intent of the design guide is to
cover structures that are located inside the fenced area of a substation yard. The
guidelines of this document may also be appropriate for structures that serve the
purpose of supporting electrical equipment located outside the substation fence that
are required to satisfy electrical substation design criteria.
210
structural design.
NESC* Y N N N
Ex#emeWind Y Y Y Y
Exlreme Ioe cnd Wind Y Y Y Y
Ecrthqucke Y Y Y Y
S h ~ t Circuit N Y Y N**
ConslTuclion & Mdntenaqoe Y Y Y Y
Opefaliond N Y N Y
Deflection Y Y Y Y
* Or other State or localregulatorycodes (i.e.,CaliforniaGeneralOrder95).
** Short circuitloads shouldbe consideredif the designengineerdeterminesthat this load
effect is significant,suchas for rigidbus connectedequipment.
Deflection Criteria
Deflection and rotation of substation structures and members can affect the
mechanical operation of supported electrical equipment, reduce electrical clearances,
and cause unpredicted stress in structures, insulators, connectors, and rigid bus. For
these reasons, structural deflections should be investigated and limited to magnitudes
that are not detrimental to the mechanical and electrical operation of the substation
equipment. The sensitivity of equipment to deflection of supporting structures varies
considerably. Disconnect switches, with complex mechanical operating mechanisms,
are highly susceptible to binding if the structure distorts from the installed geometry.
Conversely, structures supporting only stranded conductor bus or line dead-ends
could grossly deflect without any impact on operation.
structures for incoming transmission lines. Deflection limitations for these structures
are intended to limit "P-delta" stresses, wind-induced vibrations, and visual impact.
Downloaded from ascelibrary.org by Universidad de los Andes on 01/21/20. Copyright ASCE. For personal use only; all rights reserved.
Table 2 summarizes the structure classes and associated deflection limits. Equipment
manufacturers should be consulted to determine if any specific structure deflection
limits are required for their equipment.
Methods of Analysis
The design of substation structures require knowledge of the equipment being
supported by the structure, its operation, and electrical and safety codes. Analysis, as
used herein, is defined as the mathematical formulation of the behavior of a structure
under load. The solution yields the calculated displacements, support reactions and
internal forces or stresses. The analysis of a structure begins by developing a model
that defines the structure configuration, connection characteristics, support boundary
conditions, and loading cases. These items are discussed in this section of the
substation design guide.
Design
The guide refers to the industry codes for design guidelines and only notes any
exceptions, to the reference documents. Load factors and deflection criteria specified
on the Loading and Deflection Sections of the design guide must be used rather than
the load factors and deflection criteria specified in the referenced documents.
Factored loads must be used with ultimate strength design. Unfactored loads should
be used with allowable stress design. There is no intention to exclude any material or
structural section types. If the material or section type is not addressed in the guide,
the design engineer should reference an appropriate design code or document.
Downloaded from ascelibrary.org by Universidad de los Andes on 01/21/20. Copyright ASCE. For personal use only; all rights reserved.
Ultimate strength design and allowable stress design are both acceptable for the
design of substation structures. Ultimate strength design is recommended, since the
structural design trend is towards ultimate strength design. Structures that support
conductors and overhead groundwires that extend outside the boundaries of the
substation should meet or exceed the load and strength requirements of the NESC.
Testing
Full-scale structural proof tests are rarely performed on substation non-electrical
equipment support structures or wire-support structures. It is not cost effective to
perform a full-scale test because substation structures are not fabricated in large
quantities such as those used in a transmission line). Full-scale testing should be
considered if a particular substation structure is a standard and will be used in large
quantities or if the structure uses a unique structural system not typical of current
practice. However, component testing (a section of the tower, connections, etc.) may
be cost effective for substation structures. Electrical equipment support structures are
typically simple cantilever structures that are generally not proof tested for static
Downloaded from ascelibrary.org by Universidad de los Andes on 01/21/20. Copyright ASCE. For personal use only; all rights reserved.
loads. Seismic response (dynamic loading) requires that the support structure and
equipment be seismically tested or analytically evaluated as a system (equipment and
support structure). Seismic evaluations are performed in accordance with IEEE
Standard 693 (1997).
Worker safety is also discussed as a separate issue. All structures and equipment,
which will be inaccessible with bucket trucks or small ladders, should be considered
for climbing devices (ladders) mounted to the structure with a fall protection device.
Elevated areas that require personnel access, either during construction or for
maintenance, must have fall protection devices; i.e., safety cables for worker
attachment. In all cases, OSHA and local codes must be adhered to, especially in
energized substations.
Summary
Overviews of the contents of each section of the ASCE Substation Structure Design
Guide were presented. The objective of the subcommittee is to have this document
ready for publication by 2003.
Reference
IEEE Std 693, Recommended Practice for Seismic Design of Substations, Institute of
Electrical and Electronics Engineers, Pascataway, NJ, 1997