1. INPUT DATA.
1.1. Concrete Duct Bank Data.
Width, b = 550 mm
Thickness or depth, t = 500 mm CRITICAL POSITION OF AXLE @ MIDDLE
Clear concrete cover, cc = 75 mm
effective depth, de = 420 mm P P
Diameter of Cable conduit, dc = 110 mm
Number of Cable conduit, nc = 2 pcs.
Length (1-lane roadway), L = 5.00 m 1.80m Road level
2.3. Check shear capacity of reinforcement and concrete base on actual spacing
Av f yt d
Vs = 136.565 kN
S
Ø = 0.75 Shear reductor factor
Vn Vc Vs = 276.67 mm2 safe, shear capacity provided by shear reinf. and concrete is greater than Vu.
2.3.1. Transverse reinforcement bars.
Adopted ρ = 0.00180
As = 3,780 mm2 As = ρbd - - "Required steel area"
Am = 78.54 mm2 Am = πDm2/4 - - "Area of 1-longitudinal bar, selected"
N = 50 pcs N = As/Ab - - "Required number of steel"
Use 10mm @ 207mm O.C Ok, Actual spacing is adequate
fy
= 0.0213
fc
Moment capacity of section, M cap. fc ' bd 2 (1 .59 )
Mcap = 64.25 kN-m
3. ATTACHMENT:
M.O.T. Loading:
Calculation Sheet
1. INPUT DATA.
1.1. Concrete Duct Bank Data.
Width, b = 1050 mm
Thickness or depth, t = 500 mm CRITICAL POSITION OF AXLE @ MIDDLE
Clear concrete cover, cc = 75 mm
effective depth, de = 420 mm P P
Diameter of Cable conduit, dc = 110 mm
Number of Cable conduit, nc = 4 pcs.
Length (1-lane roadway), L = 5.00 m 1.80m Road level
2.3. Check shear capacity of reinforcement and concrete base on actual spacing
Av f yt d
Vs = 136.565 kN
S
Ø = 0.75 Shear reductor factor
Vn Vc Vs = 435.07 mm2 safe, shear capacity provided by shear reinf. and concrete is greater than Vu.
2.3.1. Transverse reinforcement bars.
Adopted ρ = 0.00180
As = 3,780 mm2 As = ρbd - - "Required steel area"
Am = 78.54 mm2 Am = πDm2/4 - - "Area of 1-longitudinal bar, selected"
N = 50 pcs N = As/Ab - - "Required number of steel"
Use 10mm @ 207mm O.C Ok, Actual spacing is adequate
fy
= 0.0213
fc
Moment capacity of section, M cap. fc ' bd 2 (1 .59 )
Mcap = 122.66 kN-m
3. ATTACHMENT:
M.O.T. Loading:
Calculation Sheet
1. INPUT DATA.
1.1. Concrete Duct Bank Data.
Width, b = 800 mm
Thickness or depth, t = 750 mm CRITICAL POSITION OF AXLE @ MIDDLE
Clear concrete cover, cc = 75 mm
effective depth, de = 670 mm P P
Diameter of Cable conduit, dc = 110 mm
Number of Cable conduit, nc = 6 pcs.
Length (1-lane roadway), L = 5.00 m 1.80m Road level
wqu
2. DESIGN CALCULATIONS & RESULTS.
2.1. Soil bearing pressure.
A = 4.00 m2 A = b*L - - "duct bank base area"
Wsoil = 36.00 kN Wsoil = ϒ*b*h*L - - "weight of backfill soil"
Wconc. = 72.00 kN Wconc. = ϒc*t*d*L - - "weight of concrete duct bank"
P = 130.00 kN Weight of per wheel axle
∑F = 368.00 kN ∑F = Wsoil + Wconc. + 2P - - "total vertical load"
qact = 92.00 kPa qact = ∑F/A - - "actual bearing pressure at bottom" Since, qact < qa, O.K.!
qu = 136.40 kPa qu = [1.2*(Wsoil+Wconc.)+1.6*2P]/A - - "net upward ultimate soil pressure"
Wqu = 109.12 kN/m Wqu = qu*b
Calculation Sheet
2.3. Check shear capacity of reinforcement and concrete base on actual spacing
Av f yt d
Vs = 348.566 kN
S
Ø = 0.75 Shear reductor factor
Vn Vc Vs = 665.73 mm2 safe, shear capacity provided by shear reinf. and concrete is greater than Vu.
2.3.1. Transverse reinforcement bars.
Adopted ρ = 0.00180
As = 6,030 mm2 As = ρbd - - "Required steel area"
Am = 78.54 mm2 Am = πDm2/4 - - "Area of 1-longitudinal bar, selected"
N = 80 pcs N = As/Ab - - "Required number of steel"
Use 10mm @ 136mm O.C Ok, Actual spacing is adequate
fy
= 0.0213
fc
Moment capacity of section, M cap. fc ' bd 2 (1 .59 )
Mcap = 237.83 kN-m
3. ATTACHMENT:
M.O.T. Loading:
Calculation Sheet