Professional Documents
Culture Documents
UK
Read this manual carefully before installing, operating or carrying out maintenance on the device. Keep the manual in a
safe place for future reference and in perfect condition. This manual must accompany the device described herein in the
case of change of ownership and until the device is decommissioned.
ORIGINAL INSTRUCTION 1
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
SYMBOLS
The equipment is marked with this symbol wherever the user should refer to this manual in order to avoid possible
damage. The same symbol appears in the manual at points where warnings or particularly important instructions,
essential for safe, correct operation of the device, are given.
The equipment is marked with this symbol in the areas where there is dangerous voltage. Only trained maintenance
personnel should carry out work in these areas. The same symbol appears in the manual at points where essential
safety warnings are given.
The equipment is marked with this symbol in the areas where the user must be careful to avoid crushing of hands. Only
trained maintenance personnel should carry out work in these areas. The same symbol appears in the manual at points
where essential safety warnings are given.
The equipment is marked with this symbol in the areas where the user must be careful to avoid coming into contact with
moving components. Only trained maintenance personnel should carry out work in these areas. The same symbol
appears in the manual at points where essential safety warnings are given.
The equipment is marked with this symbol in the areas where the user must be careful to avoid crushing of feet. Only
trained maintenance personnel should carry out work in these areas. The same symbol appears in the manual at points
where essential safety warnings are given.
The equipment is marked with this symbol in the areas where there is the danger of unexpected bursts of compressed
air. Only trained maintenance personnel should carry out work in these areas. The same symbol appears in the manual
at points where essential safety warnings are given.
LASER LIGHT: This symbol appears in this manual at those points where warnings or information relating to laser
pointing devices are given. Such devices may be dangerous. Do not look into the laser beam!
The equipment is marked with this symbol in those areas where insertion of hands, other body parts or objects, is not
permitted, in order to avoid system malfunctions or dangerous situations.
The equipment is marked with this symbol in the areas where it is forbidden to extinguish a fire with water.
CEIA Metal Detectors employ low intensity electromagnetic fields in compliance with current legislation.
MAGNETIC FIELDS can affect pacemakers. Persons wearing pacemakers, cardiac defibrillators and other life support
devices must not operate less than 50 cm from the opening of the Metal Detector tunnel. Wearers of pacemakers must
not operate less than 1 meter from the Metal Detectors of the THS/MN21 series which use static electromagnetic fields.
Persons wearing pacemakers who may need to approach this equipment should consult their medical practitioner
beforehand.
The equipment is marked with this symbol in those areas where it is possible to perform a ground connection.
The equipment is marked with this pictogram in those places where the user is advised to refer to this instruction manual
before any operation.
This symbol appears in the manual at points where suggestions, additional information or other relevant notes are given.
2 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
UK
CONTENTS
1 SAFETY INSTRUCTIONS – WARNINGS ....... 9 2.6.2.1 Control Power Box and Field
Generator .................................. 37
2 DESCRIPTION ............................................... 10 2.6.2.2 Control Power Box with
2.1 General description ................................. 10 Remote Control Unit (THS/21E) ......... 37
2.6.2.3 Control Power Box with
2.1.1 Metal Detector .......................................... 10 Remote Control Unit (THS/21) ........... 38
2.1.2 Integrated System on conveyor belt ......... 11 2.6.2.4 Conveyor Control System ......... 38
2.1.3 Products that can be inspected ................ 11 2.6.2.5 Small size power supply unit ..... 38
2.2 Metal detector ......................................... 12 2.6.3 Remote Control Unit ...................... 39
2.2.1 THS/21E and THS/21E-3F ....................... 12 2.6.3.1 21E series .......................................... 39
2.6.3.2 21 series ............................................. 39
2.2.2 THS/21 and THS/MS21 ............................ 12
2.6.4 Integrated systems ................................... 40
2.2.3 THS/MN21 ................................................ 13
2.6.4.1 THS-FBB ............................................ 40
2.2.4 THS/G21E ................................................ 13 2.6.4.2 THS-FBBV.......................................... 42
2.2.5 THS/G21 and THS/GMS21 ...................... 13 2.6.4.3 THS-FBV ............................................ 42
2.6.4.4 THS-MBB ........................................... 43
2.2.6 Applicable power supply boxes ................ 14 2.6.4.5 THS-MBR ........................................... 46
2.2.6.1 Control Power Box .................... 14 2.6.4.6 THS-RB and THS-RBK ...................... 47
2.2.6.2 Conveyor Control System ......... 15
2.7 Options and Accessories ........................ 47
2.2.6.3 Small Size Power Supply Unit ... 15
2.2.6.4 Field Generator.......................... 15 2.8 Technical characteristics ........................ 48
2.2.7 Other options ............................................ 15 2.8.1 Metal Detector .......................................... 48
2.2.7.1 Remote Control Unit .................. 15 2.8.2 Integrated systems ................................... 50
2.2.7.2 Network card ............................. 15 3 INSTALLATION ............................................. 52
2.3 Integrated system with conveyor belt ..... 16 3.1 Minimum requirements ........................... 52
2.3.1 Inverting component positions .................. 17 3.1.1 Minimum installation clearance ................ 52
2.3.1.1 Inverting the transit direction ............... 17 3.1.1.1 Detection Probes ................................ 52
2.3.1.2 Inverting the ejection system position . 17 3.1.1.2 Integrated systems ............................. 52
2.3.2 Models ...................................................... 18 3.1.2 General guidelines for mechanical
2.3.2.1 THS-FBB (flat belt).............................. 18 installation ................................................ 53
2.3.2.2 THS-FBBV (flat belt) ........................... 20 3.1.2.1 Controls and Power Supply box ......... 53
2.3.2.3 THS-MBB (modular belt)..................... 22 3.1.2.2 Metal structures in proximity to the
2.3.2.4 THS-MBR (modular belt) .................... 24 Probe .................................................. 54
2.3.2.5 THS-FBV (flat belt).............................. 26 3.1.2.3 Load-bearing structure ....................... 56
2.3.2.6 THS-RB and THS-RBK ....................... 28 3.1.2.4 Conveyor belt and position inside the
2.4 Device identification ................................ 29 Probe .................................................. 57
3.1.2.5 Synchronization photocell................... 59
2.4.1 Detection Probe ........................................ 29
3.1.2.6 Metallic flanges ................................... 59
2.4.2 Control Power Box .......................... 29 3.1.2.8 Ejection area ...................................... 60
2.4.3 Conveyor Control System ............... 29 3.1.3 Electrical installation general rules for a
correct compatibility ................................. 61
2.4.4 CEIA conveyor structure........................... 30
3.1.3.1 Power supply of other devices............ 61
2.5 Functional diagrams ............................... 30 3.1.3.2 Signal cables ...................................... 62
2.5.1 THS with Control Power Box .................... 30 3.1.3.3 Pulsed-type noise sources ................. 62
3.1.3.4 Ground loops prevention .................... 63
2.5.2 THS with Conveyor Control System ......... 31 3.1.3.5 Conveyor belt motors ......................... 64
2.5.3 Integrated systems with Conveyor Belt .... 31 3.1.3.6 Selecting and installing connecting
cables ................................................. 65
2.5.4 THS-RB and THS-RBK ............................ 32
3.1.3.7 Multiple Metal Detectors close
2.6 Dimensions ............................................. 33 together .............................................. 65
2.6.1 Detection Probes ...................................... 33 3.2 Unpacking ............................................... 66
2.6.1.1 THS/21, THS/MS21, THS/21E, 3.2.1 Metal Detector .......................................... 66
THS/21E-3F ........................................ 33
3.2.1.1 Handling and moving the packaged
2.6.1.2 THS/SL21, THSSL21E ....................... 34
device ................................................. 66
2.6.1.3 THS/MN21 .......................................... 34
3.2.1.2 Unpacking procedure ......................... 66
2.6.1.4 THS/G21, THS/GMS21, THS/G21E ... 35
3.2.1.3 Packing list ......................................... 67
2.6.1.5 THS/G21-F, THS/GMS21-F,
3.2.1.4 Moving the Metal Detector.................. 67
THS/G21E-F ....................................... 36
3.2.2 CEIA Integrated Systems ......................... 68
2.6.2 Power supply units ................................... 37
ORIGINAL INSTRUCTION 3
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3.2.2.1 Handling and moving the package 3.6.3.2 THS/xx21E-3F .................................... 99
device ................................................. 68 3.6.3.3 THS/xx21 .......................................... 100
3.2.2.2 Unpacking procedure ......................... 68 3.6.3.4 THS/xxMS21 ..................................... 101
3.2.2.3 Packing list ......................................... 69 3.6.3.5 THS/MN21 ........................................ 102
3.2.2.4 Moving the Metal Detector .................. 69 3.6.3.6 Input for speed control through a 0-
3.2.3 THS-RB .................................................... 69 10V analogic signal ........................... 102
3.2.3.1 Handling and moving the package 3.6.4 IXC card (available on request) .............. 103
device ................................................. 69 3.6.5 Integrated Systems ................................. 104
3.2.3.2 Unpacking procedure ......................... 70 3.6.5.1 THS-FBB, THS-MBB, THS-FBV,
3.2.3.3 Packing list ......................................... 70 THS-FBBV without SCN board ......... 104
3.2.3.4 Moving the Metal Detector .................. 70 3.6.5.2 THS-FBB, THS-MBB, THS-FBV,
3.3 Mechanical installation ............................ 71 THS-FBBV with SCN board .............. 106
3.6.5.3 THS-MBR.......................................... 108
3.3.1 Probe ....................................................... 71
3.3.1.1 THS Models ........................................ 71 3.7 Description of electrical connections .... 110
3.3.1.2 THS/G models .................................... 71 3.7.1 00211ALM card ...................................... 110
3.3.2 Power supply unit ..................................... 72 3.7.2 Settings of SW1 minidip.......................... 114
3.3.3 Integrated systems ................................... 73 3.7.3 00211AL_ card ....................................... 114
3.3.3.1 External signalling unit (beacon)......... 73 3.7.4 Connection of push-buttons or sensors .. 115
3.4 Pneumatic installation ............................. 73 3.7.4.1 Sensor positioning ............................ 116
3.4.1 Minimum requirements ............................. 73 3.7.5 Connection of an ejection system ........... 117
3.4.2 Pneumatic circuit diagrams ...................... 74 3.7.6 Synchronization photocell ....................... 117
3.4.2.1 Ejector cylinder ................................... 74 3.7.7 Ejection check photocell ......................... 117
3.4.2.2 Air jet ejection system......................... 74
3.4.2.3 Ejector cylinder ................................... 74 3.7.8 Connection to other in-line devices or
machines ................................................ 118
3.4.3 Connecting up to the compressed air
supply....................................................... 75 3.8 Communication connections ................ 119
3.4.3.1 Ejector cylinder ................................... 75 3.8.1 RS232 Serial port connections ............... 119
3.4.3.2 Air jet ejector ...................................... 75 3.8.2 Bluetooth communication ....................... 119
3.4.3.3 Retracting belt .................................... 75
3.8.3 Ethernet / WiFi connections (on request,
3.4.4 Pressure adjustment ................................ 76 with IXC card) ......................................... 119
3.4.5 Flow adjustment ....................................... 77
3.9 Configuration ........................................ 120
3.4.5.1 Ejector cylinder ................................... 77
3.4.5.2 Air jet ejector ...................................... 78 3.9.1 System start-up ...................................... 120
3.4.5.3 Retracting belt .................................... 78 3.9.2 Preliminary settings ................................ 120
3.4.6 Padlocking the compressed air ................ 79 3.9.3 Checking the input and output
3.5 Electrical Installation ............................... 79 connections ............................................ 121
3.9.4 Motor (only with Conveyor Control
3.5.1 Installing connecting cables ..................... 79
System) .................................................. 121
3.5.2 Description of inputs................................. 80
3.9.5 Transit speed .......................................... 122
3.5.3 Description of outputs .............................. 81 3.9.5.2 Application with Conveyor Control
3.5.4 Description of I/O interfaces ..................... 82 System .............................................. 122
3.5.5 Connection of the CEIA Conveyor belt 3.9.6 Encoder .................................................. 123
Emergency circuit..................................... 83 3.9.7 Synchronization photocell ....................... 123
3.5.6 Connecting to the mains power supply .... 85 3.9.8 Ejection check photocell ......................... 124
3.5.6.1 Connection to earth ............................ 86
3.9.9 Ejection mode ......................................... 124
3.5.6.2 Power Switch ...................................... 86
3.9.9.1 Ejection with manual reset (EM=B) ... 125
3.6 Electrical diagrams .................................. 87 3.9.9.2 Photocell synchronized ejection, with
3.6.1 Functional diagrams ................................. 87 manual reset (EM=SB) ...................... 126
3.6.1.1 Control Power Box .................... 87 3.9.9.3 Reversing belt (EM=R) ...................... 127
3.9.9.4 Automatic ejection (EM=F) ................ 128
3.6.1.2 Conveyor Control System ......... 88
3.9.9.5 Automatic ejection with photocell
3.6.2 Power Supply units .................................. 89 synchronization (EM=S) .................... 129
3.6.2.1 Control Power Box .................... 89 3.9.9.6 Automatic ejection for high-speed
3.6.2.2 Small Size Power Supply ................... 91 applications (EM=FS)........................ 131
3.6.2.3 Field Generator for THS/MN21 . 92 3.9.10 Barcode reader ....................................... 133
3.6.2.4 Conveyor Control System – 3.9.10.1 With change of Detection Mode or
ALM card ............................................ 94 Band between two products .............. 133
3.9.10.2 Without change of Detection Mode or
3.6.3 SCD card ................................................. 98
Band between two products .............. 134
3.6.3.1 THS/xx21E ......................................... 98
4 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
UK
6 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
UK
Warranty terms
The warranty period on all CEIA products is 12 months from the date of delivery. The warranty
applies to all products supplied by us. The warranty covers defects of all components excluding
batteries. The warranty does not cover damage caused by improper or inappropriate use or use
for purposes other than those described in this manual. Do not tamper with the device. Do not
open the housing. Tampering with or opening the device will void the warranty.
CEIA operates a policy of continuous improvement to guarantee the maximum quality of its
products and services. Your suggestions and comments about our products and services are
an important part of the improvement process and we would be grateful if you could
complete the Customer Satisfaction form on the CEIA website at:
http://www.ceia.net/industrial/satisfaction
CEIA reserves the right to make changes to the content and systems described in this manual, at any time and
without prior notice. Indications of sizes and designs of Systems, therefore, have no binding character, but are given
for information purposes only.
REVISION HISTORY
Rev. Date Author Reference Description
1000 2010-09-16 TP2 – SP - First issue for all THS/21E and THS/21 models
- Small corrections
Management of external emergency buttons and
1100 2012-03-29 TP2 – SP -
other protections
Additional indications on bins and respect for the
2.8.2, 3.1.3, 4.5.6, 5.1
environment
1110 2012-06-26 TP2 – SP 6.1 CE Certificates updated
1200 2013-09-26 TP2 – SP - Software updated to THSV5412
- Added MN21 on THS-FBB
- Removed THS-FB, THS/M65, THS/M69K models
1210 2014-03-03 TP2 – SP
3.3.2 Added installation warning for Integrated Systems
2.6.4.2 Modified available dimensions for THS-MBB
1220 2015-01-13 TP2 – SP - Software updated to THSV5432 – ALMV5420
1300 2015-12-16 TP2 – SP - Software updated to THSV5436 – Added THS-RB
1310 2016-01-21 TP2 – SP 3.8.3 Added diagram
3.5.7.1, 3.6 Electrical diagrams updated
1400 2016-05-16 TP2 – SP
2.6.1.5, 3.3.1 Additional indications
3.5.3 Small correction
1410 2016-12-21 TP2 – SP 3.6 Added electrical diagrams
6.1 CE Certificates updated
1411 2017-06-27 TP2 – SP - Small corrections
Software updated to THSV5441 – ALMV5430 and
1490 2019-03-28 TP2 – SP -
THSV5741 – ALMV5730
1500 2019-04-02 TP2 – SP - Additional corrections
ORIGINAL INSTRUCTION 7
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
Preface
This document is the property of CEIA S.p.A. which reserves all rights. Total or partial copying,
modification and translation is forbidden.
CEIA reserves the right to make changes, at any time and without notice, to the models (including
programming), their accessories and options, and to the prices and conditions of sale.
The Metal Detector or the CEIA integrated system must be used only for the prescribed purpose and
in the ways described in this Manual. CEIA may not be held responsible for the consequences
resulting from a use other than that indicated in this Manual.
Warnings manual
The safety instructions specify the safety precautions to be implemented when installing and
operating CEIA products. These instructions must be implemented throughout the life cycle of the
product.
Programming Manual
The purpose of the Programming Manual is to provide a description of all the items of the System
Programming Menu to:
- define the users authorized to operate the System;
- program the Metal Detector in accordance with the type of product to be inspected;
- make remote connections with the Metal Detector, using the available communication
interfaces.
Operator Manual
The purpose of the Operator Manual is to provide all the information needed by the operator for daily
use of the system.
8 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
SAFETY INSTRUCTIONS - WARNINGS 1
ORIGINAL INSTRUCTION 9
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
2 DESCRIPTION
2.1 General description
CEIA THS inspection systems detect metals with high detection sensitivity, for industrial use in
inspecting food or other compatible products (see paragraph 2.1.3). They are available in two
versions:
- Metal Detector: Detection Probe with power supply unit
- Integrated system: Metal Detector integrated on a conveyor belt system
10 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.1.2 Integrated System on conveyor belt
With this version the CEIA THS Metal Detector is fully housed in a high-hygiene, stainless steel
structure fitted with a digital controller for controlling speed and the ejection stages for non-
conforming product.
CEIA inspections systems are available in a wide range of sizes suitable for a wide variety of
applications. The casing structure, the Metal Detector and the belt control panel are all made from
stainless steel.
The conveyor belt, the fully moulded cover for the ejection area and the reject product container are
all fully certified for food-safe applications.
ORIGINAL INSTRUCTION 11
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
The THS/21E-3F is a multi-frequency technology model, for use with a variety of products with
significant chemical-physical differences (dry, wet, frozen product, packed in metallized film). A slim
line version is also available: THS/SL21E-3F.
C Connecting cable
D Tunnel
The THS/MS21 is a multi-spectrum technology model, for use with a variety of products with
significant chemical-physical differences (dry, wet, frozen product, packed in metallized film). A slim
line version is also available: THS/SLMS21.
C Connecting cable
D Tunnel
12 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.2.3 THS/MN21
The THS/MN21 is a very-high sensitivity Metal Detector for detecting ferromagnetic metal
contaminants in products inside containers made from non-magnetic metal foil (e.g. aluminium foil)
or inside aluminium trays.
It is also used to detect needles in clothes with non-magnetic accessories (buttons, zips, etc. …).
2.2.4 THS/G21E
The THS/G21E is a high-sensitivity model with circular tunnel for products transported in tubing.
The Probe is designed to be fixed in an inaccessible position. The detector controls are therefore
incorporated in the power supply unit.
Its typical use is between multi-head weighing machines and packaging machines, or in gravitational
and pneumatic product transport systems in general (powders, granular material, liquids etc.).
The THS/GMS21 is a multi-spectrum model, for use with a variety of products with significant
chemical-physical differences (powders, granular material, liquids etc.).
ORIGINAL INSTRUCTION 13
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
Control Power Box Control Power Box with Remote Control Power Box with Remote
Control Unit (RCU), with 4-key Control Unit (RCU), with 16-key
keyboard and alphanumeric display keyboard and graphic display (21
(21E series) Series)
The basic version and the complete version of the Control Power Box are fitted with an card.
The difference between the two versions is in the type and number of connections for external
devices as detailed in the table below, where all data related to the small-size power supply unit
( card) are also reported:
card
IN / OUT
card Basic version Complete version
Auxiliary relay (AUX RELAY) OUT
Test request relay (TEST REQUEST RELAY) OUT
Upstream conveyor relay (PREC CONV RELAY) OUT
Ready relay (READY RELAY) OUT
Ejection relay (EJECT RELAY) OUT
Alarm relay (ALARM RELAY) OUT
RS-232 IN / OUT
Barcode Reader IN
Auxiliary RS-232 IN / OUT
RCU connection IN / OUT
Ejector OUT
Following Conveyor IN
Inhibition IN
Bin absent IN
Auxiliary input IN
Ejector position check IN
Ejection check IN
Ejection confirmation IN
Ejection synchronization IN
Reset IN
Low pressure IN
Encoder IN
Bin full IN
External beacon OUT
Emergency circuit IN
Bluetooth connection IN / OUT
Predisposition for Ethernet/WIFI card IN / OUT
14 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.2.6.2 Conveyor Control System
This unit has the same functions as the full version of the control power box
(CPB) and in addition has a conveyor belt motor driver/control section.
The Conveyor Control System also incorporates the main switch, the controls for activating the belt
and the LED indicators needed for operation.
ORIGINAL INSTRUCTION 15
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
Model THS-RB
THS-FBB THS-FBBV THS-MBB THS-MBR THS-FBV
THS-RBK
In horizontal
In horizontal In horizontal
In vertical packaging, In vertical In horizontal
Typical product packaging, packaging,
packaging, single or packaging, packaging,
that can be inspected single row; single row;
single row multiple row; single row single row
or loose or loose
or loose
Belt type Flat Flat Modular Modular Flat Round belt
Signalization
relay
Belt stop
Reversing
Available belt
ejection Reject pusher
mode cylinder
Reject air jet
Bridge ejector
Retracting
belt
THS/21x
Detection THS/MS21
Probe type THS/21E-3F
THS/MN21
from left
Transito to right
direction from right
to left
Towards
Ejection the front
direction Towards
the back
8 ÷ 40
10 ÷ 35
Speed
10 ÷ 55
(m/min)
14 ÷ 60
20 ÷ 80
: Standard - : Available on request - : Available on request, only on some configurations
: Not available - : Only SL version - : Only with belt length of 2000 mm
For details of customized versions with different dimensions and configurations, contact our Sales
Department.
16 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.3.1 Inverting component positions
2.3.1.1 Inverting the transit direction
It is possible, as an option at the order stage, to invert the transit direction, with respect to the
Detection Probe Control Panel.
ORIGINAL INSTRUCTION 17
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
2.3.2 Models
2.3.2.1 THS-FBB (flat belt)
18 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
Available features and options
THS-FBB Belt length (BL) 1000 1300 1500 1800 2000*
F Signalling lamp
white
- Belt type polyurethane (PU)
high contrast blue
adjustable feet (±75mm)
M Stand type
lockable castors (±50mm)
75 mm
M Belt height extension (only with feet)
125 mm
- Side panels for product containment
belt stop
reversing belt
L Ejection system type reject pusher cylinder
reject air jet
bridge ejector (bidirectional upon request)
standard size (400mm product input width)
large size (650mm product input width)
H Reject bin double bin (standard or large)
rollers with cover
double rollers with cover
standard (only ejection area)
P Output cover Extended (until belt end)
with inspection door and Emergency sensor
retro-reflection
E Synchronization photocell
retro-reflection, laser
retro-reflection
- Ejection confirmation photocell
retro-reflection, barrier
Bin full, Low air pressure
- Additional Sensors kit Electrick lock for Bin open/absent
Electrick lock with Emergency Stop function
- Encoder
retro-reflection
- Ejection verification photocell
retro-reflection, laser
- Shutters for sensors functional verification
Available only on some models of standard systems, without height extensions Standard
Optional, only with bridge ejector Optional accessory
Only with Probe height DH275 Not available
Only on models with ejection system * Only with THS/MN21 Probe
Only on models with additional sensors kit
Only on belt width BW400
ORIGINAL INSTRUCTION 19
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
20 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
Available features and options
THS-FBBV Belt length (BL) 1500
F Signalling lamp
white
- Belt type polyurethane (PU)
high contrast blue
M Stand type adjustable feet (±75mm)
M Belt height extension (only with feet) 125 mm
R Side panels for product containment
reject pusher cylinder
L Ejection system type
reject air jet
H Reject bin standard size (400mm product input width)
P Output cover standard (only ejection area)
retro-reflection
E Synchronization photocell
retro-reflection, laser
retro-reflection
- Ejection confirmation photocell
retro-reflection, barrier
Bin full, Low air pressure
- Additional Sensors kit Electrick lock for Bin open/absent
Electrick lock with Emergency Stop function
- Encoder
retro-reflection
- Ejection verification photocell
retro-reflection, laser
- Shutters for sensors functional verification
Standard
Optional accessory
ORIGINAL INSTRUCTION 21
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
22 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
Available features and options
THS-MBB Belt length (BL) 1030 1330 1530 1830
F Signalling lamp
flush grid
- Belt type modular (PE)
flat top
adjustable feet (±75mm)
M Stand type
lockable castors (±50mm)
75 mm
M Belt height extension (only with feet)
125 mm
- Side panels for product containment
belt stop
reject pusher cylinder
L Ejection system type
reject air jet
bridge ejector (bidirectional upon request)
standard size (400mm product input width)
large size (650mm product input width)
H Reject bin double bin (standard or large)
rollers with cover
double rollers with cover
standard (only ejection area)
P Output cover Extended (until belt end)
with inspection door and Emergency sensor
retro-reflection
E Synchronization photocell
retro-reflection, laser
retro-reflection
- Ejection confirmation photocell
retro-reflection, barrier
Bin full, Low air pressure
- Additional Sensors kit Electrick lock for Bin open/absent
Electrick lock with Emergency Stop function
- Encoder
retro-reflection
- Ejection verification photocell
retro-reflection, laser
- Shutters for sensors functional verification
Available only on some models of standard systems, without height extensions Standard
Optional, only with bridge ejector Optional accessory
Only with Probe height DH275 Not available
Only on models with ejection system * Only with THS/MN21 Probe
Only on models with additional sensors kit
Only on belt width BW400
ORIGINAL INSTRUCTION 23
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
24 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
Available features and options
THS-MBR Belt length (BL) 1700 2000
F Signalling lamp
flush grid
- Belt type modular (PE)
flat top
M Stand type adjustable feet (±75mm)
M Belt height extension
R Side panels for product containment
L Ejection system type retracting belt
H Reject bin standard size (400mm product input width)
P Output cover standard
retro-reflection
E Synchronization photocell
retro-reflection, laser
- Ejection confirmation sensor
- Ejector position check sensor
bin absent sensor with Emergency stop function
- Additional Sensors kit electrick lock with Emergency stop function
bin full, Low air pressure
Standard
Accessorio opzionale
Non disponibile
ORIGINAL INSTRUCTION 25
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
26 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
Available features and options
THS-FBV Belt length (BL) 1500
F Signalling lamp
white
- Belt type polyurethane (PU)
high contrast blue
M Stand type adjustable feet (±75mm)
M Belt height extension 125 mm
- Side panels for product containment
reject pusher cylinder
L Ejection system type
reject air jet
H Reject bin standard size (400mm product input width)
P Output cover standard (only ejection area)
E Synchronization photocell
O Ejection confirmation photocell
Bin full, Low air pressure
- Additional Sensors kit Electrick lock for Bin open/absent
Electrick lock with Emergency Stop function
- Encoder
N Ejection verification photocell
- Shutters for sensors functional verification
U Remote control unit
Standard
Optional accessory
ORIGINAL INSTRUCTION 27
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
C Main switch
E Synchronization photocell
G Emergency button
P Protection cover
28 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.4 Device identification
The ID plates here below are provided as examples only. The values shown vary from model to model.
31002xxxxxx
THS/MS21-xxxxx
THS/MS21 100 – 120 Vac
31002xxxxxx 50/60 Hz – 1ph
100 – 240 Vac x kA rms
Symmetrical
50/60 Hz – 1ph xx V max
x kA rms Symmetrical X.X A
xx V max
IP65
XX,X A
4X
IP65
2017
2017
E3xxx E3xxx
XX.X A
XXX Vac
XX Hp
T/MS21-xxxxx/ 31002xxxxxx
FBB-1500x300xxx
XX,X A IP65
IP65 4X
2017
2017
E3xxx E3xxx
ORIGINAL INSTRUCTION 29
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
30 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.5.2 THS with Conveyor Control System
ORIGINAL INSTRUCTION 31
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
32 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.6 Dimensions
2.6.1 Detection Probes
2.6.1.1 THS/21, THS/MS21, THS/21E, THS/21E-3F
ORIGINAL INSTRUCTION 33
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
Family DW DH TH FD TW
A 100 310
B 150, 200, 250, 275, 125, 150 360
300, 325, 350, 375, DW+50 DW+387
C 400, 450 175, 200 410
D 225, 250, 275 460
2.6.1.3 THS/MN21
Model DW DH TH FHD TW
125 350, 500, 550 125 545
150 350, 500, 550 150 570
DW+60 DW+620
200 350, 500, 550 200 620
250 350 250 670
34 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.6.1.4 THS/G21, THS/GMS21, THS/G21E
HL
TW
VL
DH VL
øT
Model T TW DH VL HL
THS/G21x-50 50
360 250 205 226
THS/G21x-100 100
THS/G21x-150 150 410 300 255 276
THS/G21x-175 175 435 325 280 301
THS/G21x-200 200 460 350 305 326
THS/G21x-250 250 510 400 355 376
ORIGINAL INSTRUCTION 35
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
Model T Te TW DH VL HL VD
THS/G21x-150F 150 168 435 300 255 276 150
THS/G21x-175F 175 193 460 325 280 301 162,5
THS/G21x-200F 200 218 485 350 305 326 175
THS/G21x-250F 250 268 535 400 355 376 200
On THS/G21x-xxF models absolutely forbidden to remove the extensions screwed on carpentry. The extensions are
needed to the Metal Detector correct functioning and they are not intended for the product transit.
36 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.6.2 Power supply units
2.6.2.1 Control Power Box and Field Generator
ORIGINAL INSTRUCTION 37
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
38 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.6.3 Remote Control Unit
2.6.3.1 21E series
2.6.3.2 21 series
ORIGINAL INSTRUCTION 39
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
BH TW 3 DE
BL BW extension TA TB BC CL
feet castors piston air blow fam.A fam.B
75 125 250
Conveyor belt with nominal height 700
200 350
300 450
1000 7001 7751 8251 705 750 750 590 625
400 550
500 7452 650
200 350 1030÷1180 825
300 450 1130÷1280 925
1300 7001 7751 8251 1010 590 910 910
400 550 1230÷1380 1025
500 7452 650 1330÷1480 1125
200 350 1030÷1180 825÷915
300 450 1130÷1280 925÷1015
1500 7001 7751 8251 1205 590 950 1050
400 550 1230÷1380 1025÷1115
500 7452 650 1330÷1480 1125÷1215
200 350 1030÷1180 825÷915
300 450 1130÷1280 925÷1015
1800 7001 7751 8251 1505 590 1205 1305
400 550 1230÷1380 1025÷1115
500 7452 650 1330÷1480 1125÷1215
Conveyor belt with nominal height 875
200 500
300 600
1000 7001 7751 8251 705 750 750 590 625
400 9202 700
500 800
200 500 1030÷1180 825
300 600 1130÷1280 925
1300 7001 7751 8251 1010 590 910 910
400 9202 700 1230÷1380 1025
500 800 1330÷1480 1125
200 500 1030÷1180 825÷915
300 600 1130÷1280 925÷1015
1500 7001 7751 8251 1205 590 950 1050
400 9202 700 1230÷1380 1025÷1115
500 800 1330÷1480 1125÷1215
200 500 1030÷1180 825÷915
300 600 1130÷1280 925÷1015
1800 7001 7751 8251 1505 590 1205 1305
400 9202 700 1230÷1380 1025÷1115
500 800 1330÷1480 1125÷1215
Not available; 1 ±75; 2 ±50; Dimensions in mm; 3 Greater dimensions in case of large size reject bin
40 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
With Family C Probes
BH DE
BL BW extension TA TB TW 3 BC CL
feet castors fam.C
75 125 250
400 700 1050
1500 8751 9501 10001 1205 590 1260
500 800 1150
400 700 1050
1800 8751 9501 10001 1505 590 1260
500 800 1150
400 600 1050÷1275
2000 8751 9501 10001 11251 1705 590 1260
500 800 1150÷1475
Not available; Available; 1 ±75; Dimensions in mm; 3 Greater dimensions in case of large size reject bin
ORIGINAL INSTRUCTION 41
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
2.6.4.2 THS-FBBV
BH TW
BL BW extension TA TB BC DE
feet castors piston air blow
75 125 250
1500 150 8751 10001 1205 660 970 765 600 1260
Not available; ±75; Dimensions in mm
1
2.6.4.3 THS-FBV
BH TW
BL BW extension TA TB BC DE
feet castors piston air blow
75 125 250
1500 150 8751 10001 1124 660 910 705 695 1195
Not available; 1 ±75; Dimensions in mm
42 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.6.4.4 THS-MBB
With Family A and B Probes
ORIGINAL INSTRUCTION 43
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
BH TW 3 DE
BL BW feet
extension
castors
TA TB piston air blow
BC fam.A fam.B
CL
75 125 250
Conveyor belt with nominal height 700
200 350
300 450
750 750
1030 400 7001 7751 8251 705 550 590 625
500 650
7452
600 750
200 350 1030÷1180 825
300 450 1130÷1280 925
1330 400 7001 7751 8251 1010 550 1230÷1380 1025 590 910 910
500 650 1330÷1480 1125
7452
600 750
200 350 1030÷1180 825÷915
300 450 1130÷1280 925÷1015
1530 400 7001 7751 8251 1205 550 1230÷1380 1025÷1115 590 950 1050
500 650 1330÷1480 1125÷1215
7452
600 750
200 350 1030÷1180 825÷915
300 450 1130÷1280 925÷1015
1830 400 7001 7751 8251 1505 550 1230÷1380 1025÷1115 590 1205 1305
500 650 1330÷1480 1125÷1215
7452
600 750
Conveyor belt with nominal height 875
200 500
300 600
750 750
1030 400 8751 9501 10001 11251 705 700 590 625
9202
500 800
600 900
200 500 1030÷1180 825
300 600 1130÷1280 925
1330 400 8751 9501 10001 11251 1010 700 1230÷1380 1025 590 910 910
9202
500 800 1330÷1480 1125
600 900
200 500 1030÷1180 825÷915
300 600 1130÷1280 925÷1015
1530 400 8751 9501 10001 11251 1205 700 1230÷1380 1025÷1115 590 950 1050
9202
500 800 1330÷1480 1125÷1215
600 900
200 500 1030÷1180 825÷915
300 600 1130÷1280 925÷1015
1830 400 8751 9501 10001 11251 1505 700 1230÷1380 1025÷1115 590 1205 1305
9202
500 800 1330÷1480 1125÷1215
600 900
Not available; 1 ±75; 2 ±50; Dimensions in mm; 3 Greater dimensions in case of large size reject bin
44 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
With Family C Probes
BH DE
BL BW extension TA TB TW BC CL
feet castors fam.C
75 125 250
400 700 1050
1530 500 8751 9501 10001 1205 800 1150 590 1270
600 900 1250
400 700 1050
1830 500 8751 9501 10001 1505 800 1150 590 1270
600 900 1250
Not available; Available; 1 ±75; Dimensions in mm
ORIGINAL INSTRUCTION 45
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
2.6.4.5 THS-MBR
BL BW BH TA TB TW BC DE CL
46 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
2.6.4.6 THS-RB and THS-RBK
BL DW
= =
BW
UH
TH
BH
FL FW
TW
BL BW BH FL FW TW BC UH
200
800 300 875±50 400 BW+250 BW+485 BH+175 65, 90, 115, 140, 165
400
ORIGINAL INSTRUCTION 47
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
48 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
ORIGINAL INSTRUCTION 49
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
2 DESCRIPTION
50 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
DESCRIPTION 2
ORIGINAL INSTRUCTION 51
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
3 INSTALLATION
Before starting any installation operation, carefully read all warnings and precautions described in this section and in the
Warnings Manuals supplied with the device.
Observe current regulations regarding electrical and personal safety for both the operator and the installer when
installing the device.
IN OUT
275.00
500.00
52 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.1.2 General guidelines for mechanical installation
The following guidelines provide the necessary information to install the system, guaranteeing
minimum clearance for the Metal Detector. Additional indications are also given for THS Systems
intended for installation on final Customers' conveyor belts
For the installation checks you need to be able to switch on the system, understand the signals given
during use and set the applicable operating parameters. These operations are described in the first
part of section 4 – Use of the device.
ORIGINAL INSTRUCTION 53
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
THS/21x THS/MN21
Df DH 3 DH Static metal masses
2 DH Small moving metal masses (i.e. piston rod)
Dm 10 DH *
4 DH Bigger moving metal masses
* Magnetic metal masses
54 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.1.2.2.1 Free-fall products
S Metal Detector Probe
P Stainless steel load-bearing structure
f Stainless steel moving part
t Plastic material
Insulation of the load-bearing structure
Pi (P)
see paragraph 3.1.2.3
Fixing and insulation of the Probe (S)
Si see paragraph 3.3.1.2
Insulation of metal flanges
Fi see paragraph 3.1.2.6
DH Diameter of the Probe S transit tunnel
Respect distance between Probe S
Df and any static metal masses
see table below
Respect distance between Probe S
Dm and any moving metal masses
see table below
Distance between Probe S and
H support structure P
H > Df
Moving part reference dimension
V V = 200x160x2 mm
Installation example for a THS/G21 with free-fall product
THS/G21x THS/G21x-F
Df 0,5 DH 0,4 DH Static metal masses
Small moving metal masses (i.e. piston rod)
Dm 1,5 DH DH
Bigger moving metal masses
ORIGINAL INSTRUCTION 55
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
Take into consideration the fact that a conveyor belt mat is subject to metal contamination and must be periodically
disassembled to be cleaned or replaced. Set up the system to facilitate this operation.
During assembly the solidity of the load-bearing structure should be borne in mind, in order to ensure
that the detector does not oscillate, causing false alarms.
The load-bearing structures of the transport system must be stable and not subject to detectable
vibration when the belt is moving.
For a THS/MN21 the structure of the transport system must be in non-magnetic steel (e.g. AISI 316).
i: insulating material
56 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.1.2.4 Conveyor belt and position inside the Probe
3.1.2.4.1 Conveyor belt mat
For the product transport inside the Probe, use belts NOT containing metallic nets
or filaments (i.e. antistatic belts) and, for flat belts, it is recommended to use the
ones with finger joint (hot).
It is recommended to adopt adequate countermeasures to avoid metallic contaminations or residues of the conveyed
product to accumulate on the belt, because they can negatively affect the Metal Detector optimal performances.
However provide adequate systems to allow easy disassembly of the belt for its replacement or periodic cleaning.
DO NOT use antistatic belts.
With flat belt, consider the transit of the belt through the
Probe in both directions, to avoid its cut in case it has to be
disassembled during cleaning or periodical maintenance
operations; Consider also proper systems to ease its
disassembly.
Belt and insulating sheet must not touch the Probe (the
figure shows a gap of 10 mm) in order to avoid vibrations
to the Probe or damages to it, and to prevent eventual belt
small contaminations (during the operative cycle) to already
interfere with the device correct functioning.
In any case, if there is a supporting metal layer for the belt,
when it arrives at the Probe, it must be interrupted for a
distance D, on both sides of the Probe. Position of the conveyor belt inside the Probe
With products in metallic packaging, or with physical characteristics of high electric conductivity, or with magnetic
properties, it is recommended to position the sliding plane so as the product will be as centered as possible in the Probe
aperture.
In some systems, the belt can accumulate electrostatic charges during its movement, thus generating noises to the Metal
Detector correct functioning; it is recommended to adopt adequate countermeasures to ensure the ground discharge.
In case conductive parts are used, in contact with the belt, to perform it, check that these are of a material suitable for not
contaminating the belt and connect them to the ground through a connection to only one side of the bearing structure.
ORIGINAL INSTRUCTION 57
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
I: insulated support;
C: non-insulated support;
S: screening Metal drive rollers
One side of the roller must be insulated from the metal frame of the conveyor belt, to prevent the formation of
electromagnetic coils which might interfere with the operation of the Metal Detector and allow in any way the ground
discharge of any electrostatic charges accumulated by the belt in motion.
It is recommended, where possible, to use plastic rollers or metallic rollers covered by insultaing material, so as to save
the belt from metallic contaminations.
58 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
Examples of roller insulation
Insulation of the roller pin Insulation of the roller pin support Insulation of the bearing support of a
roller pin
R: roller; B: spacers in insulating material; P: side bulkhead of the belt frame
The photocell must be positioned at a height where the beam is always interrupted by the objects transiting on the
conveyor belt. It is also recommended to place it at the minimum possible distance from the Probe side and sufficiently
set back with respect to the transit tunnel, according to the free metal zone indicated on paragraph 3.1.2.2 (expecially
when it has a body or other elements made of metal).
PD PD
S
S
F F
N N
Photocell installed at the entrance Photocell installed at the exit from the Probe
Install the photocell as close as possible to the Detection Install the photocell as close as possible to the Detection
Probe entrance. Probe exit.
N: conveyor belt; S: electronics unit; F: photocell; PD: distance photocell- electronics unit;
With Ejection Mode = FS (see section Configuration > Ejection mode) the photocell shall be installed at the Probe exit.
B: materiale isolante;
ORIGINAL INSTRUCTION 59
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
The position of the ejection area E, located at the Probe exit, is constrained by the following
conditions:
PD + DW + PL < ED < 62 x ( PL + Dp )
PL < ED < 62 x ( PL + Dp )
For high speed applications, the response time of the photocell, Metal Detector and ejector can be not negligible.
It is suggested to always verify by experiments the correct ejector actioning during the final detection verifications of
metallic samples, eventually increasing the distance of the ejector from the Probe.
The distancew between packs Dp shall be compatible the Ejection System activation and deactivation times, in order to
grant the correct ejection of two or more consecutive packs.
60 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.1.3 Electrical installation general rules for a correct compatibility
Electrical and electronic devices (and related cables) in the installation environment, can generate
interference signals for the Metal Detector, due to their position or caused by the presence of
uncontrolled paths, inside the ground equipotential circuit, for the generated noise currents (ground
loops).
The following are the main guidelines to ensure the best compatibility of the installation environment,
which, however, depends on the operating conditions of the Metal Detector and on the characteristics
of the environment in which it is installed.
It is therefore recommended to define the installation (laying and installation of cables, motors and
other electrical/electronic devices involved in the installation environment) only after the final checks
of correct installation and configuration (par.3.12) of the System.
It is recommended to use shielded signal cables, with the shield connected to ground only
from the side of the power supply box.
No power cable must pass along the conveyor belt structure.
In case of CEIA Integrated Systems fitted with cable trays, they are to be used only with cables of
the System itself and signal cables from other in-line devices.
- Do not connect in any way power supply cables of other devices inside the Metal Detector
power supply box.
ORIGINAL INSTRUCTION 61
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
F F
Example with a THS-RB
F: Signal cables;
- Provide each inverter with EMI filters at their infeed, selected according to the inverter
manufacturer's recommendations.
- Provide the connection cable to the motor with a ferrite to be placed near the inverter, passing
one or more coils of the phase conductors through the ferrite itself, according to the inverter
manufacturer's recommendations.
62 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.1.3.4 Ground loops prevention
Ground loops are unwanted or uncontrolled currents along the earth connection, which generate
noises and interfere with the functioning of the Metal Detector.
- Keep the Metal Detector Detection Probe insulated from the load-bearing structure and from
other metal structures or conductors. For Metal Detectors not integrated in CEIA systems,
refer to the section on Mechanical Installation in the Metal Detector Installation Manual.
- Keep the load-bearing structure of the Metal Detector insulated from other metal structures or
conductors.
- Avoid any mechanical or ground connection to by-pass the electric insulation of the Probe
supports. For Metal Detectors not integrated in CEIA systems, refer to the section on
Mechanical Installation in the Metal Detector Installation Manual.
- Use a dedicated earth connection for the Metal
Detector, which comes directly from the electricity QE M1 MD M2
supply board.
- Connect the motors driven by the inverter (of the Metal Detector transport system and near it)
using screened triphase+earth cable: the frame of the motor and the screen must be
connected only to the PE terminal of the inverter.
- Provide the connection cable to the motor with a ferrite to be placed near the inverter, passing
one or more coils of the phase conductors through the ferrite itself.
- Prevent electric motors driven by the inverter (placed near the Metal Detector) from having the
frame connected electrically to the load-bearing metal structure.
- Keep all metal frames, of the devices connected to the Metal Detector (i.e. encoder), insulated
from the loaf-bearing structure and connect them to the ground only towards the power supply
box.
- The connections of external signals, to the Metal Detector, shall use clean contacts (relais) or
signals insulated from the ground of the device which generates them (i.e. using optocouplers).
Check that the signal cable shield is connected to the ground only towards the power supply
box.
- Check the absence of possible ground loops generated by the interconnection of equipotential
circuits of devices beside the System.
IMPORTANT: Do not connect the Metal Detector Probe to earth because this is already earthed over the connecting
cable to the power supply.
ORIGINAL INSTRUCTION 63
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
C: non-insulated support;
I: insulated support;
S: screening
- Insulate the metal frame of the motor from the conveyor belt structure, in order to avoid
potentially critical ground loops; connect the motor to the ground only through the Inverter PE
terminal.
- Use, for the motor, 3 phases + GND shielded cables, connecting the shield to earth only to the
Inverter PE terminal.
- In case of motors driven by an inverter, if absent, equip the inverter with the EMI filter
recommended by the Manufacturer and connect to the motor as indicated in the picture below.
Install the filter holding the filter input and output cables well separated.
- Install a ferrite toroidal core on the three motor phase cables, making one or two windings inside
it.
64 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.1.3.6 Selecting and installing connecting cables
The following instructions refer to connecting cables to external equipment and servo systems.
- Only use cables with a circular cross-section and a smooth surface.
- Only connect one cable to each cable gland.
- At the end of the installation, check that all cable glands are correctly tightened.
- In case of replacement, use CEIA cable glands and caps only. Refer to Spare Parts Manual.
Close all non-used cable glands holes with the proper caps. Do not use the device with not-closed holes.
To identify sources of electrical and mechanical noise which might disturb operation of the Metal Detector, see the
instructions in the Compatibility Procedure (section 5.5).
ORIGINAL INSTRUCTION 65
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
3.2 Unpacking
Store the system in its original packaging, or in a way that protects it adequately from atmospheric
agents or other possible causes of damage (moving objects, weights, solvents etc.).
To move and handle the packaged device, use a forklift truck with a
sufficient load-bearing capacity. Ensure that the load is balanced during
handling and transport.
Other transport methods are forbidden.
Place the equipment, still in its package, as close as possible to the final
installation site.
Read the packing list to check that Using cutters, cut and remove all Using pliers, extract all metal
the packing content is complete. plastic straps from the packing. staples from the upper surface of
the packing.
Open the box and remove the Using pliers, extract all metal Lift the box upwards from the
protective support. staples from the bottom side wooden base, taking care that the
surface of the packing. Power Supply Box does not fall
out.
66 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
Put the Power Supply Box down Using cutters, cut and remove all The Metal Detector is ready for
on the floor and remove the plastic straps from the Probe. installation.
protective support.
Use forklift trucks or sling the load-bearing structure. Ensure that the load is balanced during
movement. Avoid deforming the structure or its component parts.
When transporting and handling the Metal Detector DO NOT pass slings, ropes, forklift forks, hands or any other lifting
equipment through the Probe aperture.
ORIGINAL INSTRUCTION 67
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
To ensure a balanced lifting and movement of the equipment, position the lift truck forks in the positions
indicated on the package.
Crushing hazard. Exercise caution when handling empty packaging.
Take precautions to prevent the crushing hazard when handling empty packaging.
68 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.2.2.3 Packing list
The package contains:
- CEIA Integrated System comprising the conveyor belt, the Metal Detector Probe, the power
supply box and all options and accessories ordered
- Warnings Manual, Operator Manual and a sheet with an unique code to download all
Installation, Maintenance and Programming Manuals
- Quality Control Test Samples (if ordered)
Use forklift trucks or sling the load-bearing structure. Ensure that the load is balanced during
movement. Avoid deforming the structure or its component parts.
If the system is fitted with castors, ensure that these are released before you start moving the device.
When transporting and handling the Metal Detector DO NOT pass slings, ropes, forklift forks, hands or any other lifting
equipment through the Probe aperture.
3.2.3 THS-RB
Store the system in its original packaging, or in a way that protects it adequately from atmospheric
agents or other possible causes of damage (moving objects, weights, solvents etc.).
ORIGINAL INSTRUCTION 69
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
Handle the system via a proper sling. Ensure that the load is balanced during movement. Avoid
deforming the structure or its component parts.
If the system is fitted with castors, ensure that these are released before you start moving the device.
When transporting and handling the Metal Detector DO NOT pass slings, ropes, forklift forks, hands or any other lifting
equipment through the Probe aperture.
70 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.3 Mechanical installation
3.3.1 Probe
3.3.1.1 THS Models
Insert the Probe onto the structure of the production line and fix it with screws and plastic spacers,
using the holes provided on the underside.
For the fixing distances see the Dimensions section for the relevant model, in chapter 2 –
Description of this manual.
For Detection Probes with a rectangular opening, fasten the Detection Probe with the holes in the
support feet, using screws of the appropriate length which never come into contact with the Detection
Probe frame.
WARNING! The Detection Probe with rectangular opening is fitted with appropriate insulated support feet. The Detection
Probe structure is connected to earth with the connection cable with the power supply unit; it must not be connected to
other metal parts and the support feet must always be insulated.
WARNING! Do not perform any mecanichal operation on the Probe structure, such as weldings or drilling.
Do not remove the support feet and do not perform mechanical or electric connections on them.
ORIGINAL INSTRUCTION 71
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
In applications where the Probe need to be installed on a horizontal pipe, set the Probe by placing
it, with proper plastic or rubber spacers, on the smaller side with fixing holes (if screws are present,
remove and install them on the unused fixing holes) and fix it as per the free-falling assembly.
During the installation procedure, if the connection cable between the Probe and the power supply
box needs to be disconnected, do it from the power supply box side and not from the Probe side.
This operation requires the terminals to be disconnected from the connector connected to the ALM
card and the screen to be disconnected from the earth screw on the bottom of the container.
Fix the Probe cable to the power supply unit so that it cannot oscillate or vibrate.
If the cable is too long, DO NOT CUT THE CABLE: COIL UP THE EXCESS inside the power supply box.
72 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.3.3 Integrated systems
Position the CEIA integrated system directly on
the production line.
Adjust the height of the conveyor belt so that it
is aligned with the production line. To do this,
adjust the height of the four feet or the four
castors.
Loosen the lock nut and turn the pin to raise or
lower the foot as required.
When you have adjusted the height, lock the
lock nuts and then brake the castors with the
locking lever or anchor the four feet to the floor.
Warning! Some models can have a high centre of gravity. While moving and carrying out
the installation procedure, take precautions to ensure that the detector cannot fall over. Once
installation is completed, the structure to which the Metal Detector is attached must ensure
its stability.
Important! When you adjust the height of the CEIA integrated system, ensure that the sling
surface remains parallel with the floor.
Example
ORIGINAL INSTRUCTION 73
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
# Description # Description
P1 Compressed air supply Y1 5/3-way directional control valve, exhaust neutral
AM39 3/2-way manual control valve Y2 position
AM40 Adjustable pressure regulator with return flow action AM42
Adjustable flow regulator
AM15 Adjustable pressure switch (optional) AM43
AM44 Actuator
# Description # Description
P1 Compressed air supply AM15 Adjustable pressure switch (optional)
AM40 Adjustable pressure regulator with return flow action AM42 Adjustable flow regulator
AM41 Pneumatic capacitor Y1 3/2-way directional control valve
AM39 3/2-way manual control valve
# Description # Description
P1 Compressed air supply Y1 5/3-way directional control valve, exhaust neutral
AM39 3/2-way manual control valve Y2 position
AM40 Adjustable pressure regulator with return flow action AM42
Adjustable flow regulator
AM15 Adjustable pressure switch (optional) AM43
AM44 Actuator
74 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.4.3 Connecting up to the compressed air supply
If present, remove the protective casing, removing the screws, and connect the pneumatic pressure
source according to the ejector type.
ORIGINAL INSTRUCTION 75
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
1. Remove the lock (be it the factory bolt 2. Remove the cap 3. Open the protection and remove it from
or the padlock provided by the Customer) the knob
4. Lift-up the knob 5. Rotate the knob clockwise, to increase, 6. Press the knob down to lock it back
or anti-clockwise, to decrease the
pressure
7. Place back the protection around the 8. Place back the cap 9. Lock back
knob
76 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.4.5 Flow adjustment
3.4.5.1 Ejector cylinder
If the factory settings for the cylinder piston speed is not suitable for the product to be ejected, you
can adjust it using the IN and OUT flow regulators AM42 and AM43 on the cylinder.
Using a N.32 wrench, unlock and remove the piston Pull the carter out of its place
carter nut
A
A
B
B
Loose the blocking nut A, adjust the IN flow by rotating Loose the blocking nut A, adjust the OUT flow by rotating
the knob B, then lock again tightening the nut A the knob B, then lock again tightening the nut A
ORIGINAL INSTRUCTION 77
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
B
A
Loose the two nuts A located inside the Open the carter by rotating them on the Loose the blocking nut A, adjust the air flow
carter, accessible from below, then loose lower pivots by rotating the knob B, then lock again
nut B also tightening the nut A
78 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.4.6 Padlocking the compressed air
Before any maintenance work, the interception valve of the
pneumatic circuit must be closed with a padlock when it is in
the discharge position.
Close off any unused cable gland holes with the plugs provided. Do not use the equipment with the cable gland holes
open.
ORIGINAL INSTRUCTION 79
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
INPUTS CONNECTION
Use or description with activated line Name on diagram
Following Conveyor consent
FOLLOWING
Activation of the CEIA conveyor belt or the ejection cycle of a non-integrated system, J16 N/A CONVEYOR
from a following conveyor or other machine in the line.
Metal Detector inhibition
Inhibition of the Metal Detector from a machine in the line. As an alternative the input J16 N/A INHIBITION
can be programmed to manually force the ejection cycle.
Bin absent
Indicates that the reject bin is absent. J16 N/A BIN ABSENT
Auxiliary input
To start test manually without accessing programming.
J16 N/A IN AUX1
Encoder
Connection of an encoder to measure the speed of transit in conveyor belt J17 J5 ENCODER
applications.
Bin full
Indicates that the reject bin is full. J17 N/A BIN FULL
Reset
Manual reset of the Metal Detector from Metal Alarm or Diagnostics conditions.
J17 J5 RESET
External emergency
Connection of a button or single external contact (NC) to the Metal Detector system, J19 N/A EXT EM BUTTON
which activates the Emergency Circuit.
Emergency EM STOP 1A/1B
Connection of a button with double NC contact to activate the Emergency Circuit.
J19 N/A EM STOP 2A/2B
J10
80 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.5.3 Description of outputs
On CEIA Integrated Systems, some of this outputs are already connected and configured.
OUTPUTS CONNECTION
Use or description with activated line Name on diagram
Auxiliary relay
Signal of a specific status of the Metal Detector (programmable).
J01 N/A AUX RELAY
Ejection relay
Signal of ejection. J02 J1 EJECT RELAY
Alarm relay
Signal of metal alarm.
J02 N/A ALARM RELAY
Ejector in operation
Activation of the single or double solenoid ejector. J14 N/A EJECT NO
Ejector in operation
Deactivation of the double solenoid ejector.
J14 N/A EJECT NC
Bin unlock
Activation of the rejected bin electric lock. J15 N/A BIN UNLOCK
J01 J02
ORIGINAL INSTRUCTION 81
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
00211AL_ board Standard 00211ALM board Complete 00211ALM board IXC Network card (optional)
82 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.5.5 Connection of the CEIA Conveyor belt Emergency circuit
The Emergency circuit of CEIA integrated systems can be conveniently connected with that of the
Customer line in which it is integrated, in such a way that the activation of one will result in the
activation of the other and vice versa.
- towards the Production Line Emergency circuit, connect the NC (normally closed) free contact
inside every Emergency button of the CEIA Integrated System, in order to obtain that pressing
any button will result in the Emergency stop of the whole Production Line.
Unscrew and remove the Release the pre-pressed Insert an M20 cable gland Insert a cable of the right
cover of the emergency hole on the emergency and lock on the hole size for the gland, so that the
button, to access the button container degree of protection is
contacts inside guaranteed, and connect the
terminals to the free contact
- from the Production Line Emergency circuit, connect a clean NC (normally closed) contact to
the EXT EM BUTTON input of the CEIA Integrated System (refers to the electric diagram), in
orcder to obtain that the activation of the Production Line Emergency circuit will also
determines the Emergency stop of the CEIA Integrated System.
The CEIA standard conveyor belts incorporate Emergency stop functions with Performance Level PL c, according to EN
ISO 13849-1. In non-standard systems it is avaialble, on request, also with PL d; in this case, for the Emergency circuit
connections, refers to the electric diagrams supplied with the System.
ORIGINAL INSTRUCTION 83
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
- Select a cable, with a circular section and screened, with 3 phase and one earth wires
(minimum cross section of 2.5 mm2 - AWG14). Pass it through the suitably sized cable gland.
- Take the ferrite supplied and insert the three wires inside as shown to create a
coil. The ferrite must be placed as near as possible to the inverter connection
terminals.
WARNING! The motor frame must be electrically insulated from the conveyor belt structure and from other metal parts,
and earthed ONLY using the wire connected to the inverter earth terminal, to avoid any possible interference to the
Metal Detector.
WARNING! The motor must be installed as near as possible to the Probe, depending on its power (see the table in the
General Rules for Electrical Installation). This distance is indicative and also depends on the load conditions, the size of
the Probe and on the detection settings of the Metal Detector.
After performing the connections, temporarily check the motor running direction (powering up the system) and, if
incorrect, reverse the two phase conductors.
84 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.5.6 Connecting to the mains power supply
Only make connections to the internal terminals of the power supply unit when the unit is disconnected from the mains.
If the power supply to the device is different from that specified on the plate, permanent damage may be caused to the
device. CEIA declines all liability for injury to persons and damage to property resulting from failure to follow this
instruction.
Checking that the power supply conforms to the values specified above and to current regulations is the
sole responsibility of the customer.
- Select a cable with wire minimum cross section of 2.5 mm² (AWG14), maximum 4 mm2
(AWG10) and pass it through the suitably sized cable gland.
Disconnect the terminal block Connect the mains power supply to the Refit the terminal block to the DIN
from the DIN bar by pressing it terminals (L1 and L2) of the terminal bar as shown here. Position the
downwards and then rotating it block as shown in this figure. cable inside the enclosure and close
upwards. the door.
ORIGINAL INSTRUCTION 85
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
If necessary, the Conveyor Control System switch can be locked in the OFF
position with a padlock.
When the switch is in the OFF position, depress the central part of the switch
and insert the padlock in the slot created. In this way the switch cannot turn
to the ON position until the padlock has been removed.
86 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.6 Electrical diagrams
Before consulting the electrical diagrams, check the applicable wire diagram numbers indicated by the FAT (Factory
Acceptance Test).
ORIGINAL INSTRUCTION 87
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
88 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.6.2 Power Supply units
3.6.2.1 Control Power Box
THS/xx21E
E3168A
ORIGINAL INSTRUCTION 89
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
THS/xx21
E3167A
90 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.6.2.2 Small Size Power Supply
card
E2888
Wrap the output wires of the AC/DC module on the ferrite supplied with the board.
ORIGINAL INSTRUCTION 91
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
Trimmers on AM3 and AM2 are preset to obtain an output voltage of 21.8V on each
module.
92 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
ORIGINAL INSTRUCTION 93
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
94 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
ORIGINAL INSTRUCTION 95
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
MAIN OVERCURRENT
PROTECTION TO BE PROVIDED
ON SITE
- MAX 15 A CC CLASS FUSE
FOR UL508A APPLICATIONS
PROTECTION DE LIGNE A
MAXIMUM DE COURANT A
INSTALLER SUR LE SITE
- FUSIBLE CLASS CC 15A MAX
POUR APPLICATION UL508A
96 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
ORIGINAL INSTRUCTION 97
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
98 ORIGINAL INSTRUCTION
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
INSTALLATION 3
3.6.3.2 THS/xx21E-3F
ORIGINAL INSTRUCTION 99
FI002K0018v1500hUK – THS/21 Instruction manual for installation, use and maintenance
3 INSTALLATION
3.6.3.3 THS/xx21
3.6.3.5 THS/MN21
1 2 3 4 5 6
11 12 13 14 15 16
ANALOG COMMON
ANALOG INPUT
Perform the connection to the network through one of the Ethernet ports available. The free port can be used
for the direct connection to a PC or for the cascade connection with another System: in this latter case,
however, the network connection will not be anymore available in case of shutdown of the System where it is
connected.
The WiFi Dongle USB adapter is reserved for the system's wireless interface. Its removal determines the
interruption of the functions associated with it.
SCN SCN card Connections box AM15 Pressure switch Bin lock connected to the
SM19
Ejection Confirmation AM16 Ejection check Emergency circuit
AM13
photocell Y1 Ejector activation SM19 Double bin lock for two reject
AM13 Ejection Confirmation Ejector deactivation bins, connected to the
Y2 SM20 Emergency circuit
AM19 photocells (not used with air blow)
AM14 Bin Full photocell SM17 Bin lock EM2 Emergency Button
AM14 SM17 Double bin lock for two reject Optional
Bin Full photocells
AM20 SM18 bins
3.6.5.3 THS-MBR
CCS Conveyor Control System AM25 Flashing lamp MC Motor connections box
EM1 Emergency buttons AM11 Synchronization photocell
SCN SCN Connections box Bin lock connected to the Y1 Ejector activation
SM19
AM11 Ejection Confirmation sensor Emergency circuit Y2 Ejector deactivation
AM14 Bin Full photocell Bin absent/open sensor EM2 Emergency Button
AM15 Pressure switch SM23 connected to the Emergency Optional
AM29 Ejection check sensor circuit
J06 Reserved
1 - - - -
2 - - - - Reserved
3 - - - -
4
]
J071 Emergency reset input
5 Keep jumpered on Control Power Box
6 - - - -
Reserved
7 - - - -
J08 Reserved
1 Connector present only on card, full version
Range/Max.
Connector Pin Label IN/OUT Type Function
value
1 BU -16V
2 RD +16V
3 BN +5.6V
Reserved
4 GN GND
J09 Reserved for the Detection Probe connection
5 WH Data
6 -
7 BK Data
8 -
1 +24V 100 mA max
2 RXD RS-232 serial connection
The 24 V on pin 1 is present only if the minidip VRS232
J10 3 - TXD
of switcher SW1 is set to ON. By default it is set to
5 0V OFF.
6 DTR
1 GND GND
2 GND GND Barcode reader connection
- If the Barcode reader connected needs a current higher
J111 3 RXD Data
than 150 mA, an external power supply must be used
4 TXD Data leaving pin 5 disconnected.
5 +24V BC Reader +24V 150 mA max
1 GND GND
2 TXD Data
J12 - Auxiliary serial port communication
3 RXD Data
4 +V +24V 150 mA max
1 GND GND
2 GND GND
Reserved
3 TXD Data
J13 Reserved for RCU connection
4 RXD Data
5 +5V +5V
6 +V 24V
1 GND GND
2 0V 0V
3 0V 0V
4 Vout 2 Output 24V
5 Vout 2 Output 24V
J14 6 Vdd
7 - Reserved
8 -
9 0V 0V
10 Ejector NO 2,3 Output 0 ÷ Vout
Ejection system connection
11 Ejector NC 2,3 Output 0 ÷ Vout
1 Connector present only on card, full version
2 The output can provide an overall maximum current of 150 mA. In case of an emergency, the output is set to 0 V.
3 Ejector driving: Ejector NO: NO solenoid valve driving; Ejector NC: NC solenoid valve driving.
Range/Max.
Connector Pin Label IN/OUT Type Function
value
1 0V 0V
Right align.
2 Input
photocell Reserved
Right align.
3 Output 0-24V
valve
4 0V 0V
5
6 0V 0V
Left align.
7 Input
photocell Reserved
J15 Left align.
8 Output 0-24V
valve
9 0V 0V
10
11 0V 0V
12
13
14
15 0V 0V
Connection of Bin electric lock
16 Bin unlock Output 24V 2
1 0V 0V
2 Ej. check Input Connection of ejection system check sensor
3 +Vin 24V 2
4 0V 0V
5 EJ.POS. CHK Input Connection of ejector position check sensor
6 +Vin 24V 2
7 0V 0V
Connection of a button (NA) to activate Test
8 IN AUX1 Input
request
9 +Vin 24V 2
J161
10 0V 0V
11 Bin absent Input Connection of bin absent sensor
12 +Vin 24V 2
13 0V 0V
Connection of Metal Detector inhibition signal or to
14 Inhibition Input
force the ejection cycle
15 +Vin 24V 2
16 0V 0V
Connection for Following Conveyor enabling signal
17 Foll.Conv. Input
by means of a clean contact
18 +Vin 24V 2
1 Connector present only on card, full version
2 The output can provide an overall maximum current of 150 mA. In case of an emergency, the output is set to 0 V.
5 0V 0V Connection of an encoder
6 Encoder Input Maximum pulse frequency: 3 kHz
7 +Vin 24V 2 Type: push-pull 24 V
8 0V 0V
9 Low pressure Input Connection of a low pressure sensor
J17 10 +Vin 24V 2
11 0V 0V
12 Reset Input Connection of a reset pushbutton (NO)
13 +Vin 24V 2
14 0V 0V
15 Photocell Input Connection of the synchronization photocell
16 +Vin 24V 2
17 0V 0V
18 EJ.CONFIRM Input Connection of ejection confirmation sensor
19 +Vin 24V 2
1 GND GND
2 0V 0V
3 RED LAMP Output Fault signal 0/24V
4 YELLOW L. Output Alarm signal 0/24V Connection of the beacon and horn
3 TXD Data
J2 Reserved for RCU connection
4 RXD Data
5 +5V +5 V
6 +V +24 V
1 +24 V 100 mA max
2 RXD RS-232 serial connection
The 24 V on pin 1 is present only if the minidip VRS232
J3 3 - TXD
of switcher SW1 is set to ON. By default it is set to
5 0V OFF.
6 DTR
1 GND GND
2 TXD Data
J4 - Auxiliary serial port communication
3 RXD Data
4 +V +24 V 150 mA max
1 GND
2 +Vin 24V
3 EJ.CONFIRM Input Connection of ejection confirmation sensor
4 0V 0V
5 +Vin 1 24V
6 Photocell Input Connection of the synchronization photocell
J5 7 0V 0V
8 +Vin 1 24V
9 Reset Input Connection of a reset push-button
10 0V 0V
11 +Vin 1 24V
12 ENCODER Input Connection of an encoder
13 0V 0V
J6 Reserved
4 GN GND
J9 Reserved for the Detection Probe connection
5 WH Data
6 -
7 BK Data
8 -
The power supply voltage of the Vin inputs is protected by an auto-resetting fuse which can be activated if the device is
connected wrongly.
The input devices may be simple contacts (relays or buttons) or sensors with a transistor output (with
saturation voltage less than 1 V, of the push-pull type, PNP or NPN, with 24 V output).
The input logic (positive or negative, depending on whether they are active at the high level +Vin or
the low level 0 V, respectively) can be selected in programming ( Input logic parameter, see the
Programming Manual) and is valid for all the inputs.
The outputs of all the sensors and the connection mode of the contacts must be in the selected logic.
For the inputs reserved for sensors, however, the operating mode can be set subsequently based on the type of control
performed by the connected sensor.
For sensors that share the same operating mode (see 3.9.3), connect the same type of output.
- EJECT RELAY (J02 on ALM card, J1 on AL_ card) usable as ejection signalization through a
clean contact;
- EJECTOR NO (J14 on ALM card, not present on AL_ card) usable with single solenoid ejectors
or double solenoid ejectors (24 Vdc / 150 mA max), in combination with EJECTOR NC;
- EJECTOR NC (J14 on ALM card, not present on AL_ card) usable with double solenoid
ejectors (24 Vdc / 150 mA max) in combination with EJECTOR NO.
The EJECTOR NO output is activated (and EJECTOR NC deactivated) together with EJECT Relay
The photocell must be positioned at a height where the beam is always interrupted by the objects transiting on the
conveyor belt.
PD PD
S
S
F F
N N
Photocell installed at the entrance Photocell installed at the exit from the Probe
The photocell shall be installed after the ejector and in a position that grant the correct activation by the objects passing
on the conveyor belt, and at the same height (respect to the transit surface) of the synchronization photocell.
For systems installed in the line, the READY RELAY should be connected in order to guarantee the appropriate actions on
the production line, in case of a fault with the Metal Detector. The READY RELAY stays active with the metal Detector
operative and it is immediately deactivated in case of Diagnosis status and/or Metal Detector shut down.
Closed contact
Relay Activation condition Notes
(activated relay)
Metal Detector ON and
READY RELAY C-NO
without diagnosis
ALARM RELAY Metal alarm Programmable (AT parameter) C-NO
Activation according to the
ejection cycle parameters; The
EJECT RELAY Ejection C-NO
opposite logic can also be
selected (ERL parameter)
Test request or Test in
TEST REQUEST RELAY Programmable (TRM parameter) C-NO
progress
Specific status of the Metal
AUX RELAY Programmable (ARM parameter) C-NO
Detector
Activable (PC parameter, only
PREC CONV RELAY Belt in movement with Conveyor Control System or C-NO
encoder)
3.9 Configuration
CEIA integrated systems are already configured (see Factory Acceptance Test enclosed with the
manual).
On non-integrated systems, the programming parameters must be set to match the type of
installation.
For instructions on entering the programming phase, refer to paragraph 4.5.
Verify that the power supply door is properly closed before starting the System.
When it is first powered up, the Metal Detector configuration includes 6 factory-set passwords (shown on the test card at
the end of the manual). It is extremely important that the person in charge of the detector modifies the passwords,
in order to avoid unauthorized access to programming.
Check the correct settings for date and time in order to grant a correct traceability of all events recorded on the Metal
Detector memory. The DST setting, where it is applied, shall be performed manually.
- In the case of adjacent Metal Detectors, if necessary, set a transmission channel different from
the other Metal Detector, using the TX channel parameter.
2. Enter the Configuration-adv > I/O Status > Inputs menu and simulate the operating
condition for activation of each connected input line, verifying that the corresponding status
changes correctly from L to H.
3. For the input lines reserved for sensors, the Selection Operative
Input
activation operating mode must be set correctly parameter mode1
in accordance with the input status. For example, PHOTOCELL
for the PHOTOCELL input connected to a single IP NO/NC
EJECTION CHECK
output photocell NO, with reflector, set
Configuration-adv > PHOTOCELL input = NC EJECT. CONFIRMATION IE NO/NC
2
to activate the input line with pack in transit in EJ.POS.CHECK 𝐼𝐸 NA/NC
front of the photocell. LOW PRESSURE IAP NO/NC
BIN FULL IL NO/NC
BIN ABSENT IA NO/NC
FOLLOWING CONVEYOR IW NO/NC
AUX IN - NO
RESET - NO
INHIBITION - NO
1 with input activated ENCODER - -
2 logic opposite to that set with IE IN_AUX - NO
4. Enter the Configuration-adv > I/O Status > Outputs menu and check also that each
connected output has been activated, changing the status of the corresponding line from L to
H , pressing the key E to select the line and the arrow keys to change its status; press E again
and the line is reset as not activated.
Programme the inverter only from the Metal Detector control panel.
1. Enter the Configuration-adv menu and set the parameter K transmis. = 1.000 and the
parameter Speed = 50 (m/min);
2. Enter the programming mode. In the motor configuration parameters (Configuration (adv) >
Motor config.) enter the rating plate values of the motor connected up (voltage, current,
nominal frequency). For all the parameters relating to the inverter, refer to the Programming
Manual.
Check that the transit direction is correct before installing the belt. If the motor rotates in the wrong
direction, invert two of the three phase wires.
3. Start the conveyor belt, checking that it starts correctly, and perform a tachymetric
measurement of the current speed of the conveyor belt (Vn).
Remote
Programming menu Description Allowed values
parameter
Gear motor transmission
Configuration(adv) > K transmiss KT constant
0
On systems with conveyor belt, it is recommended to use an encoder for the correct synchronization
of the ejector with the movement of the belt.
On free-falling applications, check that BS is set to a value equal or not lower than the expected
product transit speed at the Probe entrance, in order to guarantee an optimal detection and ejection
response from the System.
On applications with discontinuous transport (i.e. pumping of the product in a duct), set BS the
speed with active transport and consider the Metal Detector synchronization with the product
transport device (see Timings and Following Conveyor enabling).
Set BL and BM values as close as possible to BS, according to the specified settings, as this can increase the Metal
Detector immunity to interference.
Remote
Programming menu Description Allowed values
parameter
Gear motor transmission See procedure for the
Configuration(adv) > K transmiss KT constant motor connection
Configuration(adv) > Min speed BL Minimum transport speed 10 x KT - BM m/min
Configuration(adv) > Speed BS* Transport speed BL - BM m/min
Configuration(adv) > Max. speed BM Maximum transport speed BL - MI x KT m/min
Configuration(adv) > Max inv.freq. MI Maximum inverter frequency 60 - 100 Hz
* Where an encoder is present (KE>0) this parameter is not available.
By modifying the value of KT, the parameters BL and BM are automatically set to nominal values, respectively 30 x KT
and 60 x KT. BL and BM can also be modified manually. The value set on BS can be successively modified also through
the proper keys on Conveyor Control System panel.
In presence of an encoder, the parameter BS is always available, but the ejection cycle is determined according to the
speed measured by the encoder itself (see Timings).
Set BL and BM values as close as possible to BS, according to the specified settings, as this can increase the Metal
Detector immunity to interference.
Remote
Programming menu Description Setting
parameter
Pulses per encoder revolution 1 - 1000
Configuration(adv) > K encoder KE (PPR) pulses/rotation
Configuration(adv) > Diameter DI Diameter 10 - 250 mm
The diameter DI (mm) refers to the diameter of the encoder wheel or to the diameter of the drive
roller to which it is fixed, increased by twice the thickness of the belt.
Given the maximum speed of the line (vmax in m/min), the encoder must be set for a number of pulses
per rotation (PPR) as defined by this formula:
DI 180
PPRmax
vmax
Start the transport, enter the I/O Status > Measures menu and verify, using a tachymeter, that the
speed measured (Speed) corresponds to the current one.
Use an Encoder with the maximum available value of PPR, however lower than PPRmax value.
If an Encoder is not used, leave KE=0.
Remote
Programming menu Description Setting
parameter
Position of the photocell relative
Configuration(adv) > Position pcell PH to the Probe
IN / OUT
In the ejection mode FS (see its description on paragraph Configuration > Ejection mode), the parameter PH is not
available and the synchronization photocell shall be installed only at the exit from the Probe.
PD PD
S
S
F F
N N
Photocell installed at the entrance Photocell installed at the exit from the Probe
N: conveyor belt; S: electronics unit; F: photocell; PD: distance photocell- electronics unit
The photocell shall be installed after the ejector and in a position that grant the correct activation by the objects passing
on the conveyor belt, and at the same height (respect to the transit surface) of the synchronization photocell.
Remote
Programming menu Description Setting
parameter
Distance between the Metal
Configuration(adv) > Check phot.dist ECPD Detector and the Ejection Check 0 - 6000 mm
photocell
Enter the Programming phase, on menu Ejection select the parameter Ejection mode and set it
according to the current application. See the following descriptions:
Operation with ejection activation (i.e. halting of the transport system) until the manual elimination of
the contaminated material and manual reset by the operator.
On CEIA Integrated Systems this mode determines the stop of the conveyor belt.
Remote
Programming menu Description Setting
parameter
Halting of the transport system and manual
Ejection > Ejection mode EM elimination of the contaminated material
B
Generic example
After an alarm, the Metal Detector does not check if there are any other metallic fragments in the material immediately
following. This means that you must remove all the material between the Probe entrance and the removal area.
To minimize waste of material it is advisable to select a low setting for the ED parameter.
In free-falling applications, or whenever the immediate activation of the ejection after an alarm is required, set ED=0.
After an alarm, if the conveyor belt is stopped, pressing STOP or one of the transport system emergency buttons
before the contaminated material has reached the predefined stop position means the Metal Detector will remain in
alarm status and cannot be reset until the belt is restarted, allowing the contaminated pack to reach the predefined stop
position.
Operation with ejection activation synchronized by photocell (i.e. halting of the transport system),
manual elimination of the contaminated material and manual reset by the operator.
On CEIA Integrated Systems this mode determines the stop of the conveyor belt.
Remote
Programming menu Description Setting
parameter
Halting of the transport system and manual
Ejection > ejection mode EM elimination of the contaminated material
SB
Generic example
Generic example
After an alarm, the Metal Detector does not check if there are any other metallic fragments in the material immediately
following. This means that you must remove all the material between the Probe entrance and the removal area.
To minimize waste of material it is advisable to select a low setting for the ED parameter.
After an alarm, if the conveyor belt is stopped, pressing STOP or one of the transport system emergency buttons before
the contaminated material has reached the predefined stop position means the Metal Detector will remain in alarm status
and cannot be reset until the belt is restarted, allowing the contaminated pack to reach the predefined stop position.
This mode cannot be used with the integrated systems: THS-MBB, THS-MBR or on all the other systems involving
inversion of the direction of travel.
Operation with automatic ejection of contaminated material, by reversing the belt direction.
Remote
Programming menu Description Setting
parameter
Inversion of the direction of travel to divert the
Ejection > Ejection mode EM product into the removal area
R
Generic example
Free-falling product
Remote
Programming menu Description Setting
parameter
Automatic removal of contaminated material
Ejection > Ejection mode EM with alarm synchronization
F
Ejection > Ejection time ET Ejection relay minimum activation time 0.01 - 120.00 s
In free-falling applications, or whenever the immediate activation of the ejection after an alarm is required, set ED=0.
Set ET at the minimum value that grant the correct removal of the contaminated material.
In applications at high trasnport speed, where the ejection activation time is not negligible, it is possible to anticipate its
activation through the parameter ERT.
THS-RB systems
The ejection signal is sent to the checkweigher that will manage the ejection itself.
In this case set EM=F and ED=0.
Operation with ejection cycle activation, synchronized by photocell, for the automatic ejection of the
single contaminated pack.
In CEIA Integrated Systems fitted with an ejector, this mode determines the automatic ejection and
removal of the contaminated material in the reject bin. For this systems it is recommended to set a
transit speed lower than 60 m/min.
Remote
Programming menu Description Setting
parameter
Automatic removal of contaminated material
Ejection > Ejection mode EM with contaminated pack synchronization
S
Ejection > Ejection time ET Ejection relay activation time 0.01 ÷ 120.00 s
THS-RB systems
The ejection signal is sent directly to the ejector. In this case all conveyor sections must have the
same speed and their start must be synchronized. Parameters values can be set as indicated in
paragraphs describing other conveyor belt types.
E
F2: Ejection check sensor
PL: Pack length
F1 C F2
Use this ejection mode only if a Synchronization photocell is present; the product transit shall also be correctly aligned in
front of the photocell and the operational spacing between packs shall be compatible with the time needed for the
complete activation and deactivation of the used ejector.
Set ET at a value always higher than the ejector complete activation time, so as to grant the correct ejection of
contaminated packs, one after the other.
In applications at high trasnport speed, where the ejection activation time is not negligible, it is possible to anticipate its
activation through the parameter ERT.
The use of this ejection mode is indicated with products close to each other and passing through at high speed, so as the
ejection mode S does not grant the correct ejection of consecutive packs.
Operation with ejection activation for the automatic set-aside of the material contained in an area
that include the contamination; the area is accurately rejected through the synchronization photocell.
In CEIA Integrated Systems fitted with an ejector, this mode determines the automatic ejection and
removal of the contaminated material in the reject bin.
Remote
Programming menu Description Setting
parameter
Automatic removal of contaminated material
Ejection > Ejection mode EM with synchronization on the removing area
FS
Ejection > Ej. distance ED Distance of ejector from the centre of the Probe 0 - 6000 mm
Ejection > Eject.sync.start ES Synchronizing zone for the start of ejection 0 - 250 mm
Ejection > Eject.sync.end EE Synchronizing zone for the end of ejection 0 - 250 mm
Generic example
S: Metal Detector Probe
N: Conveyor belt
A: Air jet ejector
F1: Synchronization
photocell
F2: Ejection check sensor
PL: Pack length
DW: Detector width
ED: Ejection distance
PD: Photocell distance
ECPD: Photocell distance
In high speed applications, the ejection activation time is not negligible with respect to the ejection delay, so it is possible
to anticipate the activation and the deactivation through the parameters ERT and ERF respectively.
E: Ejected pack;
C: Contaminated and ejected pack;
EE: Ejection end synchronization area;
ES: Ejection start synchronization area
R: Minimum removal area = DW + 2PL
Re: Actual removal area = R+x+y
Following an alarm, the ejector will be activated for the time of the alarm and to eject all products in
the R area (Minimum removal area = PL+DW+PL).
A control can be introduced, from the photocell, of two areas alongside the removal area, in order to
synchronize the start and end of the ejection with the packs in transit (ES and EE respectively).
In this way, if packs are standing across the end or the beginning of the Minimum removal area, the
ejector is adequately activated to remove a bigger area (Re), synchronized with those packs borders.
Remote
Programming menu Description Setting
parameter
Code provided by CEIA to enable 6-digit alphanumeric
Configuration(adv) > Barcode enable BE the barcode reader. string
Barcode reader * - Barcode reader settings -
* The menu is shown only when the barcode reader is enabled.
The serial port of the barcode reader must be set to: 9600,N,8,1.
The following code formats are supported:
- XXXXXX<CR>
- XXXXXX<CR><LF>
- <STX>XXXXXX<ETX>
Where XXXXXX is a string of 48 characters (max.)
Refers to the electrical connections description (par.3.7.1) for the requested electrical requirements
of the barcode reader.
S: Probe/electronics unit of the Metal Detector; L: length of Probe; N: conveyor belt; BR: Barcode reader;
Dsbr:Distance THS/21 Probe-barcode reader; Dp: Distance between the packs of different products
DDD: Distance allowing the Metal Detector to change configuration after a Band/Detection mode change, before the
pack reaches the Probe. It dependes on pack speed, sensitivity settings and Probe dimensions and it must be
determined experimentally.
Installing the barcode reader closer than 3000 mm will result in product ejection during two detection
mode cycles. After the cycle time, the system will be operated normally.
N
Dp L + 300 mm Dsbr 300 mm
Dsbr L
S: Probe/electronics unit of the Metal Detector; L: length of Probe; N: conveyor belt; BR: Barcode reader;
Dsbr: Distance THS/21 Probe-barcode reader; Dp: Distance between the packs of different products
These distances are indicative and also depend on the speed of transit of the products involved.
3.10 Timing
This section describes the timings for the signals activated after an alarm occurred with product
transport activated.
For systems fitted with a Conveyor Control System or Control Power Box with encoder, the
timings are based on the actual speed of the conveying system.
For systems with a Control Power Box without encoder, the timings are based on the speed set
in the BS parameter and do not take into account any transit stoppages after an alarm or during
ejection. In applications with intermittent product conveying, we therefore recommend synchronizing
with the conveyor signal (for details see paragraph 3.10).
On the following timings the status of Inputs and Outputs, that together with the Alarm determine the ejection cycle, are
represented graphically. (high level: line activated; low level: line deactivated).
The activation of the Ejection relay (EJECT RELAY) entails the simultaneous activation of the EJECT NO output and
deactivation of the EJECT NC output, used for the direct driving of the ejector.
Generic example
S: Metal Detector Probe
N: Conveyor belt
C: Contaminated pack
PL: Pack length
DW: Detector width
ED: Ejector distance
*: It is possible to perform an Alarm reset also through the command buttons available (see Operator Manual)
3.10.2 EM = SB
Photocell at the entrance (PH=IN)
Generic example
S: Metal Detector Probe
N: Conveyor belt
C: Contaminated pack
F: Synchronization photocell
PL: Pack length
DW: Detector width
ED: Ejection distance
PD: Photocell distance
Generic example
S: Metal Detector Probe
N: Conveyor belt
C: Contaminated pack
F: Synchronization photocell
PL: Pack length
DW: Detector width
ED: Ejection distance
PD: Photocell distance
Generic example
S: Metal Detector Probe
N: Conveyor belt
PL: Pack length
DW: Detector width
If an Alarm is still present after the belt moved backward for a space ED, the belt will move another ED space backward.
3.10.4 EM = F
Generic example
S: Metal Detector Probe
N: Conveyor belt
C: Contaminated product
DW: Detector width
ED: Ejection distance
Waveform Description
Signal over the alarm threshold
Metal alarm
with transport activated
ALARM RELAY External alarm signalling
ALARM RELAY and YELLOW LAMP can be programmed to stay activated, after an Alarm, until a manual reset
(parameter AT)
3.10.5 EM = S
Photocell at the entrance (PH=IN)
Generic example
S: Metal Detector Probe
N: Conveyor belt
E: Ejector
F: Synchronization photocell
PL: Pack length
DW: Detector width
ED: Ejection distance
PD: Photocell distance
ED
Example with THS-RB
PL PD S
ECPD
S: Metal Detector Probe
E
E: Ejector
F1 F2 F: Synchronization photocell
PL: Pack length
DW: Detector width
ED: Ejection distance
DW PD: Photocell distance
Generic example
S: Metal Detector Probe
N: Conveyor belt
E: Ejector
F1: Synchronization photocell
PL: Pack length
DW: Detector width
ED: Ejection distance
PD: Photocell distance
Waveform Description
Signal over the alarm threshold
Metal alarm
with transport activated
Pack in front of the photocell
PHOTOCELL
(at the entrance, in the example)
ALARM RELAY External alarm signalling
For more accurate adjustment of the delay in activating the ejector, early activation can be adjusted based on the actual
response time of the ejector. See the parameter ERT.
In Conveyor Control Systems, or with encoder installed, the ejection cycle occurs only when the belt is moving.
ALARM RELAY and YELLOW LAMP can be programmed to stay activated, after an Alarm, until a manual reset
(parameter AT)
Waveform Description
Signal over the alarm threshold
Metal alarm
with transport activated
PHOTOCELL -
The effective removal area Re is determined through the Sinchronization photocell, setting EE and ES to a value at least
equal to PL. This area is necessary to grant a correct ejection in case of product across the beginning and the end of the
removal area set (R). Setting EE=ES=0, the removal area will always be equal to R.
E: Ejected pack;
C: Contaminated and ejected pack;
EE: Ejection end synchronization area;
ES: Ejection start synchronization area
R: Minimum removal area = DW+2PL
Re: Actual removal area = R+x+y
For more accurate adjustment of the delay in activating and deactivating the ejector, early and delayed activation can be
adjusted based on the actual response time of the ejector. See the parameters ERT and ERF.
ALARM RELAY and YELLOW LAMP can be programmed to stay activated, after an Alarm, until a manual reset
(parameter AT)
By setting parameter IN to a numeric value greater than 0, use of the INHIBITION input, to inhibit the
detection of metals by the Metal Detector, is enabled.
When this input is activated, the Metal Detector remains inhibited. The Metal Detector will become
active again after IN seconds of the deactivation of the input, as shown in the diagram below.
Waveform Description
INHIBITION Metal Detector inhibition
In systems with a Conveyor Control System, the parameter IN also indicates how long the Metal
Detector is inhibited each time the conveyor belt is started up.
Setting IN = E it is possible to force the ejection cycle, according to the selected ejection mode,
indipendently from the presence or not of Alarms, through the activation of the INHIBITION input.
IW Logic (NO/NC)
In systems with a Control Power Box without encoder (KE=0), used with discontinuous product
transport, ejection can be synchronized with the product transit, by connecting a signal, by a relay,
to the FOLLOWING CONVEYOR input so that its status represents the movement or stopping of the
transport system.
a + b = ED / BS
In the ejection modes with automatic ejection, the ejection activation time is also counted only when the FOLLOWING
CONVEYOR input is active.
PREC_CONV RELAY -
At the end of the installation and checks, before commissioning the equipment, remove all keys used
to open the fixed guards, so that the normal operators do not have direct access to them.
The requirements contained in the Regulation are grouped into two categories:
- Requirements applicable to the intrinsic operation and to the programming of the System
under test.
- Requirements that govern correct management and control actrivity by the Customer, so as
to guarantee complete compliance with the Regulation.
The respect of all requirements guarantees the complete compliance with the Regulation.
In Countries where DST is in effect, verify the correct setting to always ensure proper data
traceability. With CEIA THS Production software the time of all connected Metal Detectors is
automatically synchronized with the PC server where the software is installed.
Save the data file from the Metal Detector to a text file, through USB, Web Server or a serial
connection. Connect to the site www.ceia.it/cfr21validation and, from the web page, select the local
file to be analysed and send it for the validation (Send button); subsequently press the Check Digital
Signature button. If the file is valid, the message Valid Digital Signature is shown, otherwise, in
case of incomplete or partially altered data, the message Not valid Digital Signature is shown; in
this case the relevant data needs to be saved again.
Save data on a Report created with the CEIA THS Production software. Select the desired Report.
The software will automatically check the Digital Signature; in case the check fails, the Report needs
to be created again. Refers to the software instructions manual for more information.
Before starting to use the device, carefully read the Safety instructions – Warnings section of this manual
4.1 Indicators
4.1.1 Optical indicators
4.1.1.1 Control panel
The control panel, containing the optical indicators and the Metal Detector controls, is located on the
Probe or on the power supply box (if fitted with RCU remote control unit):
THS/21 THS/21E
Control Panel Control Panel
1 Flashes to indicate that the belt has been stopped by the FOLLOWING CONVEYOR input deactivation and is waiting
to be restarted automatically (see parameter RE, in Programming Manual).
The external beacon, by default, sounds only to indicate faults, but can also be programmed to sound
when the detector detects metal fragments. In this case refer to the Programming Manual for more
information.
4.2 Controls
4.2.1 Control Panel
The control panel keyboard is used to control the Metal Detector and set the device parameters. The
control panel keys and their functions are shown below:
Only on THS/xx21
Key Function
Key Function
Increase speed
Manual forward Programmable.
Decrease speed See the table below.
Manual reverse
Can be disabled.
Metal Detector alarm reset
See Programming Manual
Emergency reset
The motor speed control keys, depending on UD and MM parameters, can have different functions:
MM
OFF ON
No function Manual forward
OFF
No function Manual reverse
UD
Increase speed Manual forward
ON
Decrease speed Manual reverse
Set MM=OFF on systems with THS-MBB, THS-MBR or on systems where the conveyor direction of travel cannot be
reversed.
The manual forward/reverse controls are only enabled when the belt is stopped.
The increase/decrease speed controls are enabled both when the belt is stopped and the belt is running.
1 1
THS/21x
Power supply unit
There are dangerous voltages inside the
power supply unit. Close the cover and
keep the key safe so that it is only
available for use by trained personnel (EN
1
60204 Standard). This will also prevent
accidental switching when the cover is
closed. On the switch can be
padlocked in the OFF position during
maintenance.
Covers and shelters
Check that all fixed covers and
2
protections are correctly fitted and
fastened in place.
Reject bin
3 Check that the reject bin is in position and
THS-FBB, THS-MBB, THS-FBBV, THS-FBV correctly fastened.
Floor fixing
If requested, check that the structure is
4
firmly anchored to the floor. In case of
castors, check that they are locked.
Obstructions on belt
Before you start the conveyor belt, check
5
that there are no extraneous objects on
the belt.
Emergency buttons
Check that all the emergency buttons and
6
safety switches installed in the system,
work correctly
Product exit
Check it is correctly placed next to the
7
THS-MBR following conveyor or that there is an
unloading belt with fixed guard.
LOTO devices
2
2 In case of maintenance operations in
2
progress, check that the main switch knob
8
5 and that of the compressed air shut-off
7 valve are in the position that cuts the
power sources and locked with a padlock.
Door with magnetic safety sensor
6 9
(optional)
4
4
THS-RB
1. Start the conveyor belt and, activating each emergency device (pressing the emergency
buttons or opening the covers protected by a magnetic switch), check that the belt stops and
that the optical and acoustical indicators are correctly activated.
2. Release the emergency device (releasing the button or closing the cover protected by a
magnetic switch) and press the R button to reset the system.
In case the THS system is connected to the Production Line emergency circuit, perform the check
also for the external buttons.
4.3.2 Switching on
Do not start a system whose safety systems are not fully efficient.
Do not tamper with safety devices. The manufacturer declines all
liability for damage resulting from tampering with safety features.
Before powering up the System, check that power supply box is
closed.
To switch off the system, turn completely the knob to 0 position (OFF).
The switch cut the power supply of the Metal Detector and all System moving parts.
The intermediate position (T) is associated with the automatic tripping of the automatic safety switch
inside the container; with the knob is in this position, it must be completely rotated to position 0 (OFF)
before the system can be switched on again.
In case of the automatic tripping of the main switch, contact the Assistance Service.
When the device is turned on, the display lights up, as do the indicators located on
the front of the electronics unit.
The display shows, in sequence, the serial number and the version of the software program that
drives the power supply unit.
On integrated systems, the display shows the message EMERGENCY RESET and waits for you to
press the Emergency Reset key.
After this the following display appears:
THS/xx21E
THS/xx21E V5.xxx The first line identifies the model and the software version of the
Prod. PROD01 Metal Detector. The second line indicates the type of programming,
specific to one product which may be chosen from among 250 stored
^
sets.
THS/xx21
CEIA THS/xx21
ALM V5.xxx THS V5.xxx The first line identifies the model. The second line identifies the
software version of the Metal Detector. The last line indicates the
type of programming, specific to one product which may be chosen
from among 500 stored sets.
Product:PROD01
On models where a Remote Control Unit is installed (because the Probe is installed in a position which is not
accessible to the operator), the control panel on the Probe is disabled (the message “Remote control ON” appears).
THS/xx21E THS/xx21
THS/xx21E V5.xxx CEIA THS/xx21
ALM V5.xxx THS V5.xxx
Prod. PROD01
THS/xx21E THS/xx21
THS/xx21E V5.xxx CEIA THS/xx21
ALM V5.xxx THS V5.xxx
Prod. PROD01
The Metal Detector is in normal
operating mode.
^
Product:PROD01
Password Password
#_____ #_____
Programming access step. The Metal
Detector requests a password.
Reset @ Reset~~~~~~~~~~~~~~~@
Products
Products Autolearn
Detection The Metal Detector has been set to
Autolearn Ejection programming mode: accessible
Detection parameters can be modified.
TEST ** TEST **
Prod. PROD01
The Metal Detector requests a functional
test (see paragraph 4.8).
^
Product:PROD01
THS/xx21E THS/xx21
THS/xx21E V5.xxx CEIA THS/xx21
ALM V5.xxx THS V5.xxx
Product: PROD01 To show the Metal Detector activity, the
colons beside the selected product indication,
^ blinks.
Product:PROD01
THS/xx21E V5.xxx CEIA THS/xx21
Batch: 1234
ALM V5.xxx THS V5.xxx If the system is set to include the batch
number also, on product selection, then the
batch number is shown alternatively to the
^ selected product name.
Batch:1234
THS/xx21E V5.xxx CEIA THS/xx21
Product: PROD01
ALM V5.xxx THS V5.xxx If the system is correctly connected via
Bluetooth, a symbol is shown on the right side
B Ð of the display. If the symbol blinks, data
^ transmission is in progress.
Product:PROD01
I
F
N
S: Metal Detector Probe; N: Conveyor belt;
F: Synchronization photocell;
I: Correct area where the product shall be loaded Photocell at the exit
Indicator Status
Mains voltage ON
Press the Start GREEN button to start the motor: check that it starts up, and that the
“motor on” indicator comes on.
To stop the motor, press the Stop RED button : check that it stops, and that the “motor
on” indicator goes off.
For systems which allow inversion of the direction of travel, the and buttons can be
programmed for the forward and reverse movement of the belt, respectively. In this case, the speed
can be set only by going in to programming.
The manual forward/reverse movement of the belt is performed by holding pressed the corresponding button.
The increase/decrease speed controls are enabled both when the belt is stopped and the belt is running.
During programming of the Metal Detector, speed adjustment using the and keys is disabled.
When the Conveyor Control System keys are being used, the Metal Detector programming is disabled.
Minimum~speed~~~~~~~20@ The “Speed” reading indicates the speed set, and varies in real
Speed 40
time when the and keys are pressed. Any modification of
Maximum speed 60 the speed is stored to memory as a parameter specific to the
current product type and it is maintained also in case of system
shutdown.
Self-diagnosis status
If there are self-diagnosis messages, the conveyor belt stops automatically.
The green indicatori s OFF.
It is possible to disable the belt stop if there are self-diagnosis messages. However, the READY relay is
deactivated. See the Programming Manual (Configuration menu).
RESET EMERGENCY
(press R button)
Trace and remove the cause of the emergency stop and then
reset the system by pressing the Emergency Reset key
Product:PROD01
If necessary, the main system switch can also be used for automatic stop of the conveyor belt.
in operation with automatic ejection of the contaminated material, the transport is not stopped
and the contaminated product is sent into a reject bin which should be emptied at regular
intervals by the operator. In this case, the System resets automatically.
in operation with manual ejection, the
transport is stopped and the
contaminated product is positioned in
the exit area of the Metal Detector for
manual removal by the operator.
During this operation exercise extreme caution. The reject bin could be heavy. You should define a procedure for this
operation. The manufacturer declines all liability for injury to persons or damage to property caused by emptying the bin
in an incorrect manner.
The bin has a maximum bearable load, shown on a label clearly placed on the bin itself. The
operator is responsible for emptying the bin periodically before this weight is exceeded.
Example of label
If the reject bin is fitted with an electric lock, you need to unlock it using the Unlock bin command in Programming. You
must then open the bin within the preset Unlock bin time (default value 10 s, max .value 30 s) and empty it.
At the end of the operation, close the reject bin back.
4.4.8.2 THS-MBR
The reject bin is fitted with a safety magnetic sensor that, when the bin is removed, set the machine into the Emergency
status. After replacing the bin, to reset the system press the Emergency Reset button.
In case the access level without authentication (user 000000) is enabled, after pressing P the screen will list the enabled
menus for that access level. In order to access a different level, hold the P key pressed until the password request will
prompt.
They are entered using the keypad or using the and keys Password
***#__
and confirming each character with the key.
After the password has been entered, the Metal Detector is inhibited, access to programming is
given, and the display shows the parameters available for the programming level in question:
Parameter
value
Sensitivity~~~~~~265@
Products
Parameter
name
Cursor
THS/xx21E THS/xx21
Product PROD01* Product~~~~~~PROD01§
Access to Programming phase and, with the
cursor positioned on the first voice of any menu,
press the key for at least 5 seconds.
==================== [\\\\\\\\\\\\\\\\\\]
Do you want to
The screenshot beside will be prompted. Do you want to
change password? change password?
Press again to confirm.
^UP^=YES------NO=^E^
{| $=YES ||| NO=E |}
THS/xx21E THS/xx21
Product selection * Product~selection~~@
Access the programming mode as an operator by
pressing . Where requested, enter a user
name and password.
Select the Product selection menu.
Product DEFAULT* Product~~~~~DEFAULT§
Select the Product option to start the selection of a
new product.
It is the Customer responsibilty to define the Users enabled to this function (predefined user: 000004).
For any information about programming the test type and eventually its periodic request, refers to the Programming
Manual – Q.C.setup menu
Upon this request, access to Programming, under the MD test menu, and perform the test as
described in the following paragraph.
If the periodic test is started beyond the maximum allowed time, the TEST TIME OUT message is displayed and, according
to the Metal Detector configuration, a manual reset from a diagnosis status can be requested, before performing the test.
If the periodical test request has been programmed, on the Status screenshot it is possible to see the next Test time.
THS/21E THS/21
To perform the Metal Detector test FE~test~-0.80~~~~~~~@
FE test -0.80 @ NFE test-1.00
(independently or in response to the NFE test-1.00
SS test -1.20
automatic request), access to
SS test -1.20
Programming, select MD Test > FE
test and press E key.
The customer is responsible for ensuring that the test samples are undamaged, clean, used correctly and are suitable
for the current product. The customer is responsible for following its own QA procedures
The test samples must be used only under the environmental conditions indicated as operative (see Technical
Characteristics) and in compliance with QA procedures.
The test is successful if all the test samples are detected (with an amplitude not higher than 12dB, according to the
predefined value set in the SAC parameter) and if the ejector has been correctly activated (i.e. the ejection
confirmation sensor has been triggered).
The operator is responsible for checking that the sample is correctly removed from the reject bin.
3- EJECT.NOT CONFIRM
3- SYNC PHOTOC.ERROR
TEST ABORTED
If the self-diagnosis system detects a THS/21E THS/21
fault of any kind, the test procedure FE~Test~-0.80~~NO(1)@
will be interrupted and the message ===================== NFE Test-1.00
[\\\\\\\\\\\\\\\\\\\]
shown here will be displayed. TEST ABORTED TEST ABORTED
In this case, the “REMOVE FAULT {|||||||||||||||||||}
CONDITIONS” message warns that ---------------------
the test cannot be repeated without
first resetting the system.
In the event of an unsuccessful test, the “TEST FAILED” message is displayed and, if previously programmed, the fault
condition is activated. In this case you must perform a system reset before restarting the test.
5 MAINTENANCE
Before starting any maintenance operation, carefully read the Warnings Manual enclosed.
Before starting any maintenance operation, it is recommended to remove all electric and pneumatic sources of the
System, and to secure them by applying the proper LOTO (Lock Out / Tag Out) procedures
Any maintenance or repair of the device while open and powered up should be avoided and in any case should only be
carried out by trained personnel who are fully aware of the risks which the operation entails, following the instructions
given in the Maintenance section.
The operator must monitor the condition of the system and its suitability for use and consult the maintenance personnel
if necessary.
5.2.2 Cleaning instructions for the parts in contact with the product
In order to clean the parts in contact with the product, follow the procedure described in section 5.2.3.
Only use the materials indicated in the following table:
B
E
A
F
E
D
B
G C C
G B
F F
C
E
THS-RB THS-MBR
A B C D E F G
up to 50°C
Water
up to 80°C
Alkaline and acid-based pharmaceutical Check the product's compatibility with the materials used, the characteristics of which
cleaning agents CEIA can supply on request
Mild soap solutions
Hydrogen peroxide up to 10%
Alcohol up to 30%
Ammonia solution
Allowed Not allowed
If the conveyor belt is fitted with an ejection system, perform the following steps, before continuing:
Remove all supply sources by means of the LOTO Unlock the transparent cover of the ejection area, using
devices and lock them in OFF position. its key.
Remove the transparent cover from the ejection area. Empty product from the bin, then lift it up and remove it
from its supports.
Unlock the belt by raising the idle roller Extract the idle roller from the side Pull the idle roller out of the belt
support supports
Raise the sliding surface from its position Remove the drive roller from the guides on Raise the support surface from its position
and pull it out of the belt the other side of the motor thus freeing the and from the belt
support surface.
Open the drive roller and remove the belt To refit the belt, follow this procedure in
which is now free and ready to be reverse order.
cleaned.
Crushing and cutting hazard. When you are positioning the support surface on the entrance side, take precautions to
prevent the risk of crushing between the surface and the belt frame.
5.2.3.2 THS-FBV
Unblock the sideboards on input side, by Unblock the sideboards on output side, Using a N.10 wrench remove the two
loosening the indicated knobs. by loosening the indicated knobs. cover fixing screws shown above
Remove the two sideboards.
Using the same N.10 wrench, remove all The cover is now free. Using a N.13 wrench, loosen the two bolts
the cover fixing screw Remove it from its position. in the bottom part of the ejector support,
without removing them.
Using two N.10 wrenches, remove the Slightly tilt the ejector group back, Using a N.13 Wrench and a N.5 Allen
two bolts fixing the ejector to the in order to release the belt. wrench, remove the 4 sliding surface
sliding surface. fixing screws indicated above.
Using a N.10 wrench, remove the 2 sliding With the same N.10 wrench, remove the Manually dismount the synchronization
surface fixing screws indicated above. two input sliding surface fixing screws. photocell and remove it from its support.
Using a N.19 wrench, unlock and loose the Using a N.13 wrench remove the output Grab the output roller group with two
two indicated nuts, on both sides, so as to rolle group bolts indicates above, from hands and rotate it upward.
loose the conveyor belt tension. both sides of the conveyor belt.
Pull the roller group away from under the Remove the input sliding surface from the Remove the input sliding surface from
conveyor belt. Repeat the last three steps joint with the output sliding surface, as under the conveyor belt.
with the input roller group. shown above.
Remove the output sliding surface from Using a flat screwdriver, remove the Using a N.5 Allen wrench, unlock the
under the conveyor belt. indicated Sieger, located on motor left motor shaft.
side.
Pull the motor block away from its shaft, Using a n.7 pipe wrench, remove the With a n.10 wrench, remove the output
holding it with two hands and carefully transparent cover indicated above. transparent cover.
placing it on the ground.
Remove the inner transparent cover. Using a n.3 Allen wrench, loose the two Using a n.17 wrench, unlock the motor
grains in the main roller shaft roller by removing the three indicated
bolts.
Push the motor roller horizontally Remove the motor roller from under the
out of its position. conveyor belt that is now free and can be
replaced.
On the bottom of the belt, grip the rod in Push the rod slightly to the side and past Once past the belt edge, pull the rod out
the opening near the belt edge. the retention feature. to open the belt.
When you have cleaned the belt, Join belt ends together so the hinges are Use a screwdriver to push the rod past
return it to its position aligned and insert the rod through the the retention feature. Ensure the rod is
hinges as far as possible. fully inserted.
Insert a screwdriver between two flush Use a screwdriver to push the rod out Once the rod is out of the opposite belt
edges. Twist the screwdriver to bend and from the opposite belt edge edge, pull it out by hands and open the
push the rod through the retention feature belt.
and out of the belt
When you have cleaned the belt, Join belt ends together so the hinges are Use a screwdriver to push the rod past
return it to its position aligned and insert the rod through the the retention feature. Ensure the rod is
hinges as far as possible. fully inserted.
5.2.3.4 THS-RB
Remove the four locking pins Lift up the belt block from its housing Remove the belt block from the detection
tunnel
Unlock the belt by raising the idle roller Centre the belt on the roller and adjust the Relock the belt by lowering the idle roller
support tension using the screw, checking it support.
subsequently with the belt repositioned
Start the Conveyor belt and check that the belt is correctly centered; if the belt starts to move towards the right or the left side, adjust
by rotating clockwise the corresponding screw or anti-clockwise the opposite one.
5.2.4.2 THS-FBV
Using a n.13 wrench unlock the tension The position of the bolt sets the belt Lock back the two tension bolts,
bolt, loosing the indicated nut, on both tension, pushing the roller away. tightening their nuts.
sides of the conveyor. Also check the belt centering, using the
two bolts independently on both sides.
5.3 Troubleshooting
All the power supply voltages in the power supply card are protected by self-resetting fuses which can be activated if
there is an overload or faulty connection, for the voltage values on the card, except for the mains voltage. Refer to
the description of the inputs and outputs.
The THS systems have a self-diagnosis system which displays error messages, strictly related to
the operation of the Metal Detector or to controls activated on the system input lines. For these
messages, refer to the 5.6 Self-diagnosis section.
For fault conditions not indicated because of faulty electrical installation or configuration of the Metal
Detector, see the following tables:
Check that for all connected sensors the corresponding diagnosis has been correctly activated, so as to
always have a correct diagnostic signalization in case of fault.
Refers to the Programming Manual (Diagnosis menu).
A Relays contacts protection 5x20 T 2,5A/250V F1, F2, F3, F4, F5, F6 F1, F2 -
B Protection on ALM 24V input 5x20 T 2,5A/250V F10 F10 - -
C AC/DC input protection 5x20 F 10A/250V - F11, F12 - F20, F21
Switch off the device and disconnect the system from all power sources.
Release the control panel from the The card is fastened to the back of the Remove the internal connectors J13
Detection Probe by unscrewing the 4 control panel. Remove the panel and J15 shown in the figure
fastening bolts with a 10 mm spanner taking care not to pull the internal
In case of electric screwdrivers, cables too much
operate them at reduced speed to
avoid the loss of the bolt stop rings,
located on the back of the panel.
Using a 2.5 flathead screwdriver, Unscrew and remove the SPM Disconnect the terminals from the
unlock and disconnect the memory card from the card to be connectors J19 and J20 at the base
terminals shown replaced of the SCD card, using a 3.5 flathead
The SPM card contains all the data on screwdriver and holding the panel by
the configuration and the products of hands
the equipment for which it was
programmed. Do not install the SPM
card in other equipment.
Remove the card to be replaced from Reconnect the terminals to the Reposition the SPM memory card
the steel panel, unscrewing the 6 nuts connectors J19 and J20 at the base on the new card.
with a 5.5 mm spanner. of the SCD card.
Fasten the new card in place Refer to the electrical diagram for the
relevant THS model for the correct
positioning of the terminals
Reconnect the terminals shown next Reinsert the connectors J13 and J15 Reinsert the control panel on the
to connector J13 shown in the figure Detection Probe , tightening the 4
fastening bolts again with a 10 mm
spanner
Of the 4 panel bolts, 3 are installed
Refer to the electrical diagram for the with a plastic bush and one with a
relevant THS model for the correct metal bushing. At the end of the
positioning of the terminals assembly, check that they are all
present and in good condition.
4. At the end of the procedure, check the Metal Detector correct functioning for each of the
available Products; it may be necessary to perform a new Autolearn.
If there are environmental noises during the execution of TA Autolearn, it may be aborted (message “AUTOLEARN
ABORTED”).
- Electrical Noise. Generated by electromagnetic sources out of the Metal Detector itself, can
be conducted through the power cables and/or the connection with other devices or radiated
through the same cables or from electromagnetic sources (including possibly adjacent Metal
Detectors) in the nearby of the Metal Detector Probe. Disabling temporarily the Metal Detector
transmission (TX=OFF), the contributions of this type of noise remain always visible in the
bargraph.
- Mechanical noise. Caused by the presence, near the probe opening, of fixed or moving metal
masses (see also minimum respect distances) or intermittent loops 1(rings).
Disabling temporarily the Metal Detector transmission (TX=OFF), the contributions of this type
of noise are not visible anymore in the bargraph.
If the noise is not immediately identifiable, the Metal Detector has some procedures to be performed
with the operative detection settings and without the product in transit, whose results give a
qualitative measure of the noise and can provide information about possible sources.
The described verifications give qualitative indications about the installation environment compatibility.
It is however necessary, after the corrective actions, to verify the correct operative functioning of the Metal Detector with
the product in transit, in the normal operative conditions.
Before performing the verifications, check that the noise is not due to a nearby Metal Detector; in such case simply
synchronize the two Metal Detectors through the selection of different transmission channels (see Configuration menu).
1 The presence of contacts between metal parts can determine the formation of one or more conductive ring paths,
along the bearing structure or others adjacent to the Probe; in case these contacts are accidental or made through
discontinuous junctions (due to vibrations, bending of the structure or variations in the electrical characteristics of the
joints themselves), these could cause an interference signal for the Probe itself, the greater the more the surface of the
created loop is large and close to the Probe opening. Possible causes: rollers or crossbars screwed on the conveyor
belt; intentional contacts between metal parts or accidental (i.e. broken or corroded welds).
- Ensure that the same product, with which the noise has been detected during the normal
operations, is selected.
- At the end of the procedure the Metal Detector indicates the estimated degree of
environmental compatibility: INSUFFICIENT / SUFFICIENT / GOOD. This result takes into
account the actual Metal Detector settings; however, its correct functionality needs to be
verified, including with product in transit.
- Ensure that the same product, with which the noise has been detected during the normal
operations, is selected.
Step 1 Step 2
Transport stopped Transport running
- At the end of the procedure the Metal Detector indicates the estimated degree of
environmental compatibility: INSUFFICIENT / SUFFICIENT / GOOD. This result takes into
account the actual Metal Detector settings; however, its correct functionality needs to be
verified, including with product in transit.
At the end of the procedure, a list with maximum (pk) and average (av) values of the signal received
on each of the four steps performed, are shown. These values are expressed in relation to the alarm
threshold (i.e. pk=1 maximum value equal to the alarm threshold).
If the Metal Detector does not give any indication, the nature of the detected noise can be located
using the indicative table below. For each step, the peak value and the average value can suggest if
the noise is due to transient effects or not.
- Adjust the valus of BL and BM the most nearest to the range of expected operating speeds; if
this is not enough, gradually decrease of parameter ADS from 0 to the minimum negative
value (absolute) to guarantee a noise level compatible with the Metal Detector operative
working: in this case, successively perform a verification of the correct detection and ejection
of the Test Samples, at the minimum and maximum operating speed provided;
- Compatibly with any other adjacent Metal Detector, check the noise level in the other
transmission channels (CH) available;
- Where applicable, perform the product Autolearn disabling the automatic selection of band or
detection mode, by selecting it manually in order to eventually find the one that leads to the
best noise reduction, compatibly with the required performances;
- As last, reduce the Sensitivity (SE) to a value that guarantee a noise reduction and the best
detection performances.
It is recommended to disable the Product tracking parameter (FO) in case that periodic cleaning or replacing of the belt
has not been performed regularly.
It is recommended to periodically check the belt status, cleaning and, expecially for flat belts, replacing it, as also
indicated in the Maintenance procedures for CEIA Integrated Systems. In case of a CEIA conveyor belt, refers to the
Installation Manual for instructions on how to disassembly it.
After the procedure described above, you can have an approximate measure of the current cleaning
status of the belt, to be carried out without product in transit.
- Access programming in the Configuration > Compatibility chk menu and check that the full
extended length of the belt has been set correctly in Belt length .
- Access the Configuration > Compatibility chk > Belt contam.check menu and press the E
key to start the procedure. The Metal Detector will ask to stop or start the conveyor belt,
according to the sequence given below:
At the end of the procedure the Metal Detector will show the estimated level of belt contamination:
VERY HIGH, HIGH, LOW, NO CONTAMINATION, together with the signal values (av and pk)
received in the steps performed during the procedure.
The result takes account of the current Metal Detector settings, without considering the signal related to the product,
therefore it is necessary to check that, with the product in transit, the belt contamination level will not cause false alarms.
If there is a mechanical or electrical disturbance, the Metal Detector gives the message that the belt
contamination state cannot be shown and that the general compatibility of the Metal Detector must
be assessed first (IMPROVE COMPATIBILITY).
The following is the complete description of Diagnosis and their possible corrective actions.
After removing the cause, some Diagnosis are self-resetting (indicated by ) while other require a
manual reset (indicated by ).
The diagnosis indicated by can be automatically or manually reset, according to the programming
of the relative parameters PFR and SFR.
For the Diagnosis related to connected sensors, the I/O status menu can help to visualize the input
and output lines status.
Refer also to the electrical diagrams included in this manual.
The System is pre-configured also for the activation of the ejector (by means of EJECT NO and EJECT NC outputs) in
case of power loss. See the Inputs complete description (SW1).
The Emergency circuit has been Close back the guard and reset the Emergency.
GUARD EMERGENCY activated by opening a guard In Systems where no Emergency Guard is -
(J13 5-6 and 9-10, J16 14-15 open) provided, set IN G.
A manual reset is required after the Reset the System by pressing button on
emergency condition has been or by temporaring closing contacts on J5 pins 4-5. -
RESET EMERGENCY
removed or when starting the On Systems without Emergency devices or
System Emergency Reset buttons, keep J5 4-5 jumpered.
Check that the SPM memory is connected to the
SPM Memory faulty or absent
SPM NOT DETECTED
(THS system not operative)
SCD card. If the problem persists, contact -
Maintenance Service.
24 V supply to the supply card too
V SUPPLY TOO HIGH Check the power supply.
high (higher than 40 V)
BIN FULL
Check the sensor mechanical and electrical
installation and its correct activation
Sensor connected to the BIN
FULL input faulty or In absence of the installed sensor, deactivate the
disconnected diagnosis (LF=OFF)
If the problem persists, contact Assistance Service
Ejection of the product in the bin
not occurred within the Check the correct electric and mechanical installation,
programmed time limit (CT) the correct pneumatic setup and activation of the
ejector.
Complete activation of the Check that the time limit (CT) is adequate for the
ejector not occurred within the application.
programmed time limit (CT)
Check that the contaminated product (ejected inside
Incorrect activation of the
the bin) is correctly detected by the Ejection
Ejection Confirmation photocell
Confirmation photocell
Check that there have been packages not spaced
Multiple spurious readings on the enough for their correct ejection
ejected package, by the
NO EJECT.CONFIRM Synchronization photocell Check that the photocell is correctly set to aovid
or packages too close spurious readings caused by the pack shape (see
PML and GML)
Check that BS parameter or the speed read by the
encoder, correspond to the actual transit speed
Incorrect parameters
Check that the ejector related parameters (ED, ERT)
are correctly set
Check the sensor mechanical and electrical
installation and its correct activation
Sensor connected to the
EJ.CONFIRMATION input faulty In absence of the installed sensor, deactivate the
or disconnected diagnosis (CE=OFF)
If the problem persists, contact Assistance Service
continue >>
Air supply pressure in the Check the absence of throttling in the tubes of the
pneumatic circuit lower than the pneumatic circuit
limit set on the flow regulator Check the pressure of the pneumatic supply source
LOW AIR PRESSURE
Check the sensor pneumatic and electrical installation
and its correct activation
Sensor connected to the LOW
PRESSURE input faulty or In case a sensor is not connected, deactivate the
disconnected diagnosis (AP=OFF).
If the problem persists, contact Assistance Service.
Ejection Confirmation photocell
Remove the obstruction condition of the photocell
obstructed
Ejector stuck in the ejected
Remove the stuck condition of the ejector
position
continue >>
The Metal Detector is inhibited by If the message is shown at startup and if the
external device connected to the function is not required, deactivate it (IN=0)
Detect.inhibited
INHIBITION input or at the
If the Metal Detector remain continuously inhibited, check
startup the INHIBITION input line functioning.
The product ejection is forced by
Enforced eject external device connected to the If the function is not required, deactivate it (IN=0)
INHIBITION input
EJECTION
MUST BE ON Ejection is disabled at Test start-up Activate the ejection system, before starting a Test
EJECTION Previous ejection not concluded at In ejection mode with belt stop, complete the ejection
IN PROGRESS Test start-up before starting a Test.
This function will be automatically enabled at the system
The Metal Detector ejection system
EJECTION OFF reboot or by manually reactivating the relevant parameter
has been disabled.
(EJ=ON).
This function will be automatically enabled at the system
TRANSMISSION OFF Transmission has been disabled. reboot or by manually reactivating the relevant parameter
(TX=ON).
The FOLLOWING CONVEYOR input is not activated.
The system awaits for the enabling
TRANSPORT STOPPED In case the message persists, check the input connection.
signal.
If this control is not required, it can be disabled (FC=OFF).
Check the IXC card connection to the ALM card.
WARN: IXC timeout IXC card disconnected or damaged Switch the Metal Detector off and on.
If the problem persists, contact Assistance Service.
Uninstall the Probe and the Power Supply Box from the production line and place them apart.
5.7.2 Packing
5.7.2.1 Probes
Place the Probe on the wooden base. Place the manuals inside the tunnel and fix the Position the Power Supply Box on top
Probe to the wooden base with the plastic of the Probe, placing the cable around
straps as shown in the figure. Remember to the base.
protect the Probe surface, on top, with card
strips.
Refit the package to the wooden base. Fill the empty space around and on top of the Close the package with plastic straps.
Power Supply Box and close the package.
B
Using a forklift truck with a suitable Fix the system to the pallet by Place any accessories inside the
load-bearing capacity, move the passing the plastic straps around the reject bin or on top of the conveyor
conveyor belt unit onto its original horizontal beams of the system. belt. Accessories should be
pallet. Pass two straps around the top part individually packed and fixed so that
alongside the (A), and three straps they cannot move around or knock
around the bottom beams (B). Do other parts during shipping.
not pass the straps around the
conveyor belt.
Fit the original cardboard box and fix Fix the box to the pallet with steel Finally, close the packaging by
it at the bottom to the pallet. staples wrapping two plastic straps around it
as shown in the figure.
Using a forklift truck with a suitable Fix the system to the pallet by passing Fit the original cardboard box and fix it
load-bearing capacity, move the the plastic straps around the horizontal at the bottom to the pallet.
conveyor belt unit onto its original beams of the system, as indicated
pallet. above. Do not pass the straps
around the conveyor belt.
Fix the box to the pallet with steel Finally, close the packaging by
staples. wrapping two plastic straps around it
as shown in the figure
6 APPENDICES
6.1 CE Declaration of Conformity
6.1.1 THS/21E
6.1.3 THS/G21
6.1.5 THS/MS21