Professional Documents
Culture Documents
NM-Ground Fault in An Outlet - July 6 2020
NM-Ground Fault in An Outlet - July 6 2020
Title: Electric Outlet Ground Fault Site: CJ Plant, Korea Site Manager: Jason Lee Operation/Task: Chungju DC #3 Slitter / DC Slitter Date: 2020.07.06
Incident Description:
About 08:00 on July 6(Monday), an electric spark due to a short circuit was produced LOCAL SITE: Prevention Action(s)개선대책: Who When Y/N
from an electric outlet in CJ DC when a DC operator tried to plug in for a cooling fan
To check the condition of all electric outlets in AY,
installed on the wall before he started his shift. Fortunately he didn't have any injury and MA 7-10
CJ and DG to replace defective ones.
electric shock, but he visited a hospital and took a tranquilizer since he was so much
frightened from the noise. Then he came back to work but the site management made To inspect all electric circuits to find missing circuit
MA 8/30
him back home to take a rest since his state of mind can not be stable and focused for breakers and install them.
quite a while and there's a risk to cause at-risk behaviors if he continue work. Next day,
he was back to work without any problem.. To train and put warning sign not to use electric devices by
The primary cause was a defective electric outlet that caused a ground fault when the force. if there’s any abnormality, stop using it and call EHS 7/30
maintenance team.
operator plugged in by force because the spring inside the outlet didn’t work properly.
Observation, data collection,
Injury and Classification: Near miss To conduct an audit for MOC compliance EHS 7/20
Photoboard / Reconstruction of the Incident: To share this incident with employees EHS Done Y
● Are YOUR current controls good enough? (Think world-class; not average)
● What action is YOUR site taking to PREVENT a similar incident?