Voltage and Phase


Heaters are available in the voltage and phase combinations
shown below. All are for operation at 50 or 60 Hz.
When three-phase is specified, each heating stage will be
furnished with a multiple of three elements to give a balanced
three-phase load.
Voltage 208 240 380 400 415 480 600
Phase 3

Project Specification - 301-91-EL-SPC-00014 - Page:12


Duct Heater Banks- Duct Electric Heaters
(1) Heater bank element shall be of the mineral Insulated, or equivalent, type with
Integral and fully Insulated Terminals.
(2) Heater bank element shall be connected in a three (3) phase star configuration, with
the neutral point available, for connection to the heater supply indicated in
paragraph 4.2.
(3) Each heater bank shall have its own Isolating Switch mounted adjacent to it.
(4) Heater banks located in hazardous area shall be certified for use in that area. See
Section 9.
(5) Heater bank controls shall be electrically interlocked with the air flow switch serving
the system, and shall include thermostats to control inside room air temperature.
Also, “HIGH SURFACE TEMPERATURE CUT-OUT” thermocouples shall be
mounted on the elements.
Project Specification - 301-91-EL-SPC-00014 - Page:9
Electricity Supply Characteristics
Electrical equipment shall be suitable for operation at the nominal supply voltage indicated below.
The a.c. system frequency is 50 Hz.
Service Voltage Phase Connection to Earth
High Resistance Earthed
Primary Distribution 415V 3
(No neutral available)
Motors
415V 3 High Resistance Earthed
(0.2 kW to 149 kW)
240V 1 Neutral Solidly Earthed
(up to 0.2 kW)
Space heaters
415V 3 Neutral Solidly Earthed
(above 3 kW)
240V 1 Neutral Solidly Earthed
(up to 3 kW)
3
Lighting and Small Power 415/240V Neutral Solidly Earthed
1
Computers/Instrument
120V a.c. 1 Earthed
Power
Shutdown/Alarm 24V d.c. - Unearthed
Motors for critical service
415V 3 High Resistance Earthed
(0 kW to 149 kW)