ELECTRIC DUCT HEATERS 11/29/2022


CERTIFIED PRINTS

CUSTOMER INDEECO Sales Representative:


KBE

, N/A ,

PHONE NO : FAX NO: PHONE NO : FAX NO:


ATTENTION: ATTENTION: Jad Khalife
JOB NAME : FILE: PC-20221348Rev.1.pch
CUSTOMER P.O. NUMBER: REP. P.O. NUMBER:
INSIDE DUCT REFER TO ATTACHED SHEET FOR EXPLANATION
DIMENSIONS SUPPLY
ITEM IN INCHES LINE CTRL CTRL AIR OVER FIG
NO TAG NO QTY HEATER KW WIDTH HEIGHT VOLTS/ STGS VOLTS OPTION SPECIAL FEATURE CODE FLOW HANG NO
TYPE PHASE

1 EDH-01 8 ZB 0.80 7.87 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4


Low Airflow & Over Temp Relays
2 EDH-02 1 ZB 1.30 7.87 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
3 EDH-03 1 ZB 1.90 7.87 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
4 EDH-04 1 ZB 2.80 7.87 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
5 EDH-05 1 ZB 2.80 11.81 5.91 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
6 EDH-06 1 ZB 2.90 7.87 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
7 EDH-07 1 ZB 3.50 15.75 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
8 EDH-08 1 ZB 4.50 9.84 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
9 EDH-09 1 ZB 5.40 23.62 11.81 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
Page 1B of 4
ELECTRIC DUCT HEATERS 11/29/2022
CERTIFIED PRINTS
CUSTOMER P.O. NUMBER: MINIMUM INCOMING WIRE GAUGE AND QUANTITY - Wire gauge (GA) is based upon the
ampacities for 75 ºC rated wire (90 ºC for CSA listed heaters) in Table 310.15(B)(16) of the
APPROVALS - Any heater which MINIMUM AIR VELOCITY - This is the minimum uniform NEC (Table 2 of CEC for CSA listed heaters.) Maximum wire ampacities are derated per
contains a ""U"" in the ""HEATER face air velocity (in feet per minute or meters per minute) - NEC 424.22 and Table 310.15(B)(3)(a) (Table 5C and 62-114(7) of the CEC for CSA listed
TYPE"" column, is listed by required for proper operation of the heater at inlet heaters). When the load exceeds the capacity of 500 MCM wire, terminal blocks are
Underwriters Laboratories (UL). Any temperatures up to and including 80 °F (27 ° C) if furnished for two or more parallel conductors per phase. The number of such conductors is
heater which contains a ""C"" in this Application air velocities are less, contact your factory indicated under (QTY/PH) below. Aluminum conductors are not recommended and terminal
column, is listed by Canadian representative." blocks are not sized for aluminum wire. For heater/panel combination, the wire gauge shown
Standards Association (CSA)" on the heater line is for the heater to panel interconnecting wire. The wire gauge shown on
WIRING DIAGRAM - Wiring diagrams are typical the panel line is for the incoming power wiring."
and use numbered check blocks to fully detail the
specific built-in controls for each heater."

DIMENSIONS IN INCHES MINIMUM


REFER TO INDICATED FIG. ON ATTACHED DRAWING MIN WIRING DIAGRAM INCOMING
ITEM FIG VEL WIRE
NO W H C M OL OR P D E F G N NO AIR AMPS
FPM NUMBER CHECK BLOCKS GA QTY

1 7.87 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 142 Contact Factory 14 1 1.15
2 7.87 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 211 Contact Factory 14 1 1.88
3 7.87 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 290 Contact Factory 14 1 2.74
4 7.87 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 363 Contact Factory 14 1 4.04
5 11.81 5.91 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 340 Contact Factory 14 1 4.04
6 7.87 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 372 Contact Factory 14 1 4.19
7 15.75 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 278 Contact Factory 14 1 5.05
8 9.84 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 427 Contact Factory 14 1 6.50
9 23.62 11.81 8.00 24.00 12.50 3.50 14.00 1.00 6.00 1.00 1.00 4 197 Contact Factory 14 1 7.79

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
Page 2A of 4
ELECTRIC DUCT HEATERS 11/29/2022
CERTIFIED PRINTS

CUSTOMER INDEECO Sales Representative:


KBE

, N/A ,

PHONE NO : FAX NO: PHONE NO : FAX NO:


ATTENTION: ATTENTION: Jad Khalife
JOB NAME : FILE: PC-20221348Rev.1.pch
CUSTOMER P.O. NUMBER: REP. P.O. NUMBER:
INSIDE DUCT REFER TO ATTACHED SHEET FOR EXPLANATION
DIMENSIONS SUPPLY
ITEM IN INCHES LINE CTRL CTRL AIR OVER FIG
NO TAG NO QTY HEATER KW WIDTH HEIGHT VOLTS/ STGS VOLTS OPTION SPECIAL FEATURE CODE FLOW HANG NO
TYPE PHASE

10 EDH-10 1 ZB 8.50 19.69 11.81 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4


Low Airflow & Over Temp Relays
11 EDH-11 1 ZB 9.20 23.62 11.81 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
12 EDH-12 1 ZB 9.50 15.75 7.87 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
13 EDH-13 1 ZB 10.30 23.62 13.78 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
14 EDH-14 1 ZB 10.60 19.69 11.81 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
15 EDH-15 1 ZB 12.50 31.50 11.81 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
16 EDH-16 1 ZB 14.40 23.62 15.75 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
17 EDH-17 1 ZB 14.60 23.62 15.75 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
18 EDH-18 1 ZB 16.20 23.62 15.75 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
Page 2B of 4
ELECTRIC DUCT HEATERS 11/29/2022
CERTIFIED PRINTS
CUSTOMER P.O. NUMBER: MINIMUM INCOMING WIRE GAUGE AND QUANTITY - Wire gauge (GA) is based upon the
ampacities for 75 ºC rated wire (90 ºC for CSA listed heaters) in Table 310.15(B)(16) of the
APPROVALS - Any heater which MINIMUM AIR VELOCITY - This is the minimum uniform NEC (Table 2 of CEC for CSA listed heaters.) Maximum wire ampacities are derated per
contains a ""U"" in the ""HEATER face air velocity (in feet per minute or meters per minute) - NEC 424.22 and Table 310.15(B)(3)(a) (Table 5C and 62-114(7) of the CEC for CSA listed
TYPE"" column, is listed by required for proper operation of the heater at inlet heaters). When the load exceeds the capacity of 500 MCM wire, terminal blocks are
Underwriters Laboratories (UL). Any temperatures up to and including 80 °F (27 ° C) if furnished for two or more parallel conductors per phase. The number of such conductors is
heater which contains a ""C"" in this Application air velocities are less, contact your factory indicated under (QTY/PH) below. Aluminum conductors are not recommended and terminal
column, is listed by Canadian representative." blocks are not sized for aluminum wire. For heater/panel combination, the wire gauge shown
Standards Association (CSA)" on the heater line is for the heater to panel interconnecting wire. The wire gauge shown on
WIRING DIAGRAM - Wiring diagrams are typical the panel line is for the incoming power wiring."
and use numbered check blocks to fully detail the
specific built-in controls for each heater."

DIMENSIONS IN INCHES MINIMUM


REFER TO INDICATED FIG. ON ATTACHED DRAWING MIN WIRING DIAGRAM INCOMING
ITEM FIG VEL WIRE
NO W H C M OL OR P D E F G N NO AIR AMPS
FPM NUMBER CHECK BLOCKS GA QTY

10 19.69 11.81 8.00 24.00 12.50 3.50 14.00 1.00 6.00 1.00 1.00 4 320 Contact Factory 12 1 12.27
11 23.62 11.81 8.00 24.00 12.50 3.50 14.00 1.00 6.00 1.00 1.00 4 301 Contact Factory 12 1 13.28
12 15.75 7.87 8.00 30.00 18.50 3.50 10.00 1.00 6.00 1.00 1.00 4 518 Contact Factory 12 1 13.71
13 23.62 13.78 8.00 24.00 16.00 0.00 18.00 1.00 6.00 1.00 1.00 4 295 Contact Factory 12 1 14.87
14 19.69 11.81 8.00 24.00 12.50 3.50 14.00 1.00 6.00 1.00 1.00 4 366 Contact Factory 12 1 15.30
15 31.50 11.81 8.00 24.00 12.50 3.50 14.00 1.00 6.00 1.00 1.00 4 305 Contact Factory 10 1 18.04
16 23.62 15.75 8.00 24.00 16.00 0.00 18.00 1.00 6.00 1.00 1.00 4 331 Contact Factory 10 1 20.78
17 23.62 15.75 8.00 24.00 16.00 0.00 18.00 1.00 6.00 1.00 1.00 4 334 Contact Factory 10 1 21.07
18 23.62 15.75 8.00 24.00 16.00 0.00 18.00 1.00 6.00 1.00 1.00 4 355 Contact Factory 10 1 23.38

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
Page 3A of 4
ELECTRIC DUCT HEATERS 11/29/2022
CERTIFIED PRINTS

CUSTOMER INDEECO Sales Representative:


KBE

, N/A ,

PHONE NO : FAX NO: PHONE NO : FAX NO:


ATTENTION: ATTENTION: Jad Khalife
JOB NAME : FILE: PC-20221348Rev.1.pch
CUSTOMER P.O. NUMBER: REP. P.O. NUMBER:
INSIDE DUCT REFER TO ATTACHED SHEET FOR EXPLANATION
DIMENSIONS SUPPLY
ITEM IN INCHES LINE CTRL CTRL AIR OVER FIG
NO TAG NO QTY HEATER KW WIDTH HEIGHT VOLTS/ STGS VOLTS OPTION SPECIAL FEATURE CODE FLOW HANG NO
TYPE PHASE

19 EDH-19 1 ZB 16.30 31.50 17.72 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4


Low Airflow & Over Temp Relays
20 EDH-20 1 ZB 29.60 29.53 19.69 400/3 1 24 K B3,C9,E35,E22,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
21 EDH-21 1 ZB 36.00 70.87 23.62 400/3 1 24 K B3,C9,E35,E22,F,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
22 EDH-22 1 ZB 51.50 62.99 25.59 400/3 1 24 K B3,C9,E35,E22,F,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
23 EDH-23 1 ZB 61.30 62.99 23.62 400/3 1 24 K B3,C9,E35,E22,F,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
24 EDH-24 1 ZB 62.30 70.87 21.65 400/3 1 24 K B3,C9,E35,E22,F,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
25 EDH-25 1 ZB 65.40 55.12 27.56 400/3 1 24 K B3,C9,E35,E22,F,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
26 EDH-26 1 ZB 81.90 86.61 31.50 400/3 1 24 K B3,C9,E35,E22,F,L6,M6,P2,P4,Q,Q3,T2,U6,Z2 U6 L6 4
Low Airflow & Over Temp Relays
TOTAL 33

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
Page 3B of 4
ELECTRIC DUCT HEATERS 11/29/2022
CERTIFIED PRINTS
CUSTOMER P.O. NUMBER: MINIMUM INCOMING WIRE GAUGE AND QUANTITY - Wire gauge (GA) is based upon the
ampacities for 75 ºC rated wire (90 ºC for CSA listed heaters) in Table 310.15(B)(16) of the
APPROVALS - Any heater which MINIMUM AIR VELOCITY - This is the minimum uniform NEC (Table 2 of CEC for CSA listed heaters.) Maximum wire ampacities are derated per
contains a ""U"" in the ""HEATER face air velocity (in feet per minute or meters per minute) - NEC 424.22 and Table 310.15(B)(3)(a) (Table 5C and 62-114(7) of the CEC for CSA listed
TYPE"" column, is listed by required for proper operation of the heater at inlet heaters). When the load exceeds the capacity of 500 MCM wire, terminal blocks are
Underwriters Laboratories (UL). Any temperatures up to and including 80 °F (27 ° C) if furnished for two or more parallel conductors per phase. The number of such conductors is
heater which contains a ""C"" in this Application air velocities are less, contact your factory indicated under (QTY/PH) below. Aluminum conductors are not recommended and terminal
column, is listed by Canadian representative." blocks are not sized for aluminum wire. For heater/panel combination, the wire gauge shown
Standards Association (CSA)" on the heater line is for the heater to panel interconnecting wire. The wire gauge shown on
WIRING DIAGRAM - Wiring diagrams are typical the panel line is for the incoming power wiring."
and use numbered check blocks to fully detail the
specific built-in controls for each heater."

DIMENSIONS IN INCHES MINIMUM


REFER TO INDICATED FIG. ON ATTACHED DRAWING MIN WIRING DIAGRAM INCOMING
ITEM FIG VEL WIRE
NO W H C M OL OR P D E F G N NO AIR AMPS
FPM NUMBER CHECK BLOCKS GA QTY

19 31.50 17.72 8.00 18.00 10.00 0.00 20.00 1.00 6.00 1.00 1.00 4 283 Contact Factory 10 1 23.53
20 29.53 19.69 8.00 18.00 10.00 0.00 24.00 1.00 6.00 1.00 1.00 4 392 Contact Factory 6 1 42.72
21 70.87 23.62 8.00 24.00 16.00 0.00 28.00 1.00 6.00 1.00 1.00 4 216 Contact Factory 6 1 51.96
22 62.99 25.59 8.00 24.00 16.00 0.00 28.00 1.00 6.00 1.00 1.00 4 297 Contact Factory 3 1 74.33
23 62.99 23.62 8.00 24.00 16.00 0.00 28.00 1.00 6.00 1.00 1.00 4 343 Contact Factory 2 1 88.48
24 70.87 21.65 8.00 24.00 12.50 3.50 24.00 1.00 6.00 1.00 1.00 4 340 Contact Factory 2 1 89.92
25 55.12 27.56 8.00 24.00 16.00 0.00 30.00 1.00 6.00 1.00 1.00 4 352 Contact Factory 1 1 94.40
26 86.61 31.50 8.00 30.00 18.50 3.50 34.00 1.25 6.00 1.25 1.25 4 287 Contact Factory 1/0 1 118.21

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
Page 4of 4
ELECTRIC DUCT HEATERS 11/29/2022
CERTIFIED PRINTS

CUSTOMER INDEECO Sales Representative:


KBE

, N/A ,

PHONE NO : FAX NO: PHONE NO : FAX NO:


ATTENTION: ATTENTION: Jad Khalife
JOB NAME : FILE: PC-20221348Rev.1.pch
CUSTOMER P.O. NUMBER: REP. P.O. NUMBER:

INDEECO - 425 Hanley Industrial Court, St. Louis, MO, 63144, Phone (314) 644-4300, Fax (314) 644-5332, INDEECO.com
ELECTRIC OPEN COIL
DUCT HEATERS

HEATER TYPE SPECIAL FEATURES


Heaters are available with a wide variety of special features and constructions. Your quotation or certified print
This print covers the following heater types: includes a column for special feature codes. The codes in this column, as defined by the table below, describes
QUA/QCA Open Coil Standard, Slip-In XUB/XCB Open Coil Custom, Slip-In details of both the standard control options, as well as any special features on the heater in question.";
QUZ/QCZ Open Coil Standard, Flanged ZUB/ZCB Open Coil Custom, Flanged
860U/860C Standard Remote Panel 830U/830C Custom Remote Panel SPECIAL FEATURE CODE DEFINITIONS
A60, A62 PE Switch-Close on Rise H1 Aluminized Steel Frame & Terminal Box
H2 Stainless Steel Frame & Terminal Box
B Terminal Box-Bottom H3 Stainless Steel Elements (304 Series)
Duct heaters utilize the finest construction principles and techniques. 80% nickel, 20% chromium coils are
B1 Terminal Box-Side Cover H6 Stainless Steel Elements (316 Series)
supported by ceramic bushings mounted in corrosion-resistant steel brackets, using a patented floating design that
B2 Terminal Box-Insulated
prevents breakage due to thermal expansion. The coils are machine crimped into stainless steel terminals which
B3 Enclosure-Weatherproof NEMA 4 Type L3 to L6 Terminal Box Overhang (See Figs. 10 & 11)
are insulated with high temperature ceramic bushings. The heater frame is constructed of heavy gauge corrosion-
B4 Enclosure-Dust-Tight-NEMA 12 Type L7 No Overhang, C=M (See Fig. 7)
resistant steel and is provided with generous flanges for structural rigidity. All heaters, except QUZ, are suitable for
B5 Panelboard-Required for Heater Control
installation in ducts with up to one inch of interior lining.
B7 Enclosure-Dustproof M to M7 Manual Thermal Cutout
B8 Enclosure-Outdoor-3R Type M8 Remote Manual Reset Rod
B9 Enclosure-Stainless Steel Weatherproof
All heaters include thermal cutouts (not heat limiters or fusible links) in accordance with requirements of UL and
Nema 4X Type N(000) Fan Relay (000 is control voltage)
CSA. All controls are factory-wired to clearly marked terminal blocks for field connections. Properly sized
knockouts are provided. All heaters are supplied complete with wiring diagrams and installation instructions, and
C, C4, C8 Contactor-Magnetic De-energizing P1 Pilot Light Each Stage On
all are given a dielectric test at a minimum of 1200 volts before shipment.
C1, C5, C9 Contactor-Magnetic Disconnecting P2 Pilot Light Insufficient Air
C2, C6, C10 Contactor-Mercury De-energizing P3 Pilot Light Heater On
C3, C7, C11 Contactor-Mercury Disconnecting P4 Pilot Light-Overtemperature
AGENCY APPROVALS AND NATIONAL ELECTRICAL CODE
Duct heaters and panels with a “U” in the type designation are Listed by UL under Files E23192 and E53412 and
D3 Derated Coils-25 Watts per Square Inch Q, Q1 Disconnect Switch-Power
those with a “C” are Certified under CSA master contract 151727. As such, they are suitable for installation with
D4 Derated Coils-35 Watts per Square Inch Q2 Pilot Switch-Control Circuit
zero clearance to combustible surfaces and for use with heat pumps and central air conditioners. They are also
Q3, Q4 Airflow Switch Positive
supplied with all necessary provisions for installation in full accordance with the National Electric Code (NEC) and
E20 to E23 SCR Controller Q5, Q6 Airflow Switch Negative
Canadian Electrical Code (CEC).
E30 SCR input-2200 Ohms Q8 Disconnect Switch-Control Circuit
E31 SCR input-135 Ohms Q10 Disc. Switch-Control Circuit Fan Relay
E32 SCR input-with transducer
INSTALLATION
E33 SCR input-slave for vernier R1 Dry Contact for Remote Heater Enable
Slip-in duct heaters are installed by inserting through a rectangular opening cut in the side of the ductwork and are
E34 SCR input-4-20mA
secured to the duct with sheet metal screws. To install flanged duct heaters, flanges must be provided on the duct
E35 SCR input-0-10VDC S5 2200 Ohm input-Deadband
to match the heater flanges, both on the entering and leaving air sides. The heater is secured to the ductwork by
E36 SCR input-0-10VDC Thermostat S16 135 Ohm input-Proportional
sheet metal screws or bolts through the mating flanges.
Controlling Master SCR S18 4-20mA input-Proportional
E37 SCR input-Pulse Thermostat Controlling S19 with Transducer-Proportional
Slave SCR S20 0-10VDC input-Proportional
When the duct heater is being used in conjunction with an air conditioning or heat pump unit, it must be installed at
S21 Step Controller-0-10VDC Thermostat
least 48” from the unit. Sufficient working clearances must be provided on the terminal box side of the heater as
F Fuses-Minimum NEC
detailed in the NEC and/or CEC. Care should be taken to follow all instructions found in the Installation, Operating
F1 Fuses-Per Circuit T1, T5 Control Circuit Transformer, Fused
and Maintenance Instructions sheet supplied with each heater.
F3 Circuit Breaker-Minimum NEC Primary
F5 Circuit Breaker-Per Circuit T2 to T4 Control Circuit Transformer
CONTROL OPTIONS
F6 Time Delay Fusing
G = Basic
U3 to U9 Airflow Direction (See Figs. 10 & 11)
J = Pneumatic
G1 Slip-and-Drive Connection
K = Proportional
G2 Extended Cold Section V Protective Screens-Both Sides
G3 Recessed Terminal Box V1 Pressure Plate-Inlet Side
GG2 Insulated Duct Construction (extended V2 Protective Screens-One Side
cold section)
GG3 Insulated Duct Construction (recessed Z to Z5 Automatic Thermal Cutout
terminal box)