Professional Documents
Culture Documents
Systems in
Buildings
Arch 502
3. Air Motion
air velocity should average 4.57 to 7.6
meters per min measured 36” above the
floor.
2. Condensers
a) Air-cooled Condensers - used in unit
and packaged-type air- conditioners up
to 3 tons refrigeration.
b) Water-cooled Condensers - Double- Evaporative Condenser
piped Condensers:
2. Cooling Coils
b) Viscous Filters
consist of metal deflecting plates or screens
coated with viscous oil.
a) Dampers
1. Sensing Devices
These control the flow of air and are in the
form of louvers.
a) Humidistat
or Hygrostat is a controller, sensitive to
b) Control Valves
the amount of humidity in the air.
These are valves with variable orifices
which are moved by motors to present
b) Thermostat
smaller or larger openings as directed by a
a controller which responds to changes in
thermostat.
temperature.
c) Relays
c) Pressure Regulators
These are devices that use electrical energy
are instruments sensitive to changes in
to amplify or convert the power of a
pressure. They may control a single
thermostat or other controllers so that the
pressure or a differential between two
resultant force will be sufficient and
pressures.
adaptable to operate a valve or damper.
Furnace Installation
Radiator Installation
HOT WATER
COLD
WATER
Floor installation
Ceiling installation
Wall installation
Process Machine
An equipment designed and operated for
a specific purpose.part of the
AC/refrigeration system in which liquid
refrigerant is vaporized to produce
refrigeration.
Refrigerant
A substance which produces refrigerating
updated by FJSL - Do not share this pdf
NBC Regulations 2. Smokestacks whether self supporting or
guyed, shall be of sufficient capacity to
Concerning HVAC handle fuel gases, shall be able to
withstand a wind load of 175 km per hour
Boilers and Pressure Vessels and shall rise at least 5 m above the eaves
of any building within a radius of 50 m.
1. Location of Boilers:
3. Manufacturers/assemblers of
a) Boilers may be located inside buildings boilers/pressure vessels/pressurized water
provided that the boiler room is of heaters shall stamp each vessel on the
reinforced concrete or masonry and that front head or on any other suitable location
the boiler room shall not be used for any with the name of the manufacturer, serial
other purpose. number, maximum allowable working
pressure, heating surface in sqm and year
b) In case the main building is not made of manufacture.
up of fire resistive materials, boilers shall
be located outside the building at a 4. Boilers of more than 46 sqm heating
distance of not less than 3.00 m from the surface shall each be provided with two
outside wall of the main building and the means of feeding water, one steam driven
building housing the boiler shall be made and one electrically driven, one pump and
up of fire resistive materials. one injector.
c) No part of the boiler shall be closer 5. Two check valves shall be provided
than one meter from any wall. between any feed pump and the boiler in
addition to the regular shut-off valve.
d) Fire tube boilers shall be provided
with sufficient room for 6. Where two or more boilers are
removal/replacement of tubes either thru connected in parallel, each steam outlet
the front or rear. shall be provided with a non- return valve
and a shut-off valve.
updated by FJSL - Do not share this pdf
7. Boiler rooms shall have at least two install a boiler/pressure vessel/pressurized
separate exits. water heater upon payment of the
installation fees thereof, it shall be the duty
8. In no case shall the maximum pressure of the Building Official to make periodic
of an old/existing boiler be increased to a inspection of the installation to determine
greater pressure than would be allowed compliance with the approved plans and
for a new boiler of same construction. specifications.
9. Each boiler shall have at least one 13. Upon the completion of the installation,
safety valve. For boilers having more than the Building Official shall conduct an
46 sqm pressure of water heating surface inspection and test, after which a certificate
or a generating capacity exceeding 907 of operation for a period not exceeding one
kg per hour, two (2) or more safety year shall be issued upon payment of the
valves shall be required. required inspection fees.
10. Each boiler shall have a steam gauge, 14. The Building Official shall notify the
with a dial range of not less than 1-1/2 owner in writing of the intended date of
times and not more than twice the the annual inspection at least 15 days in
maximum allowable working pressure. It advance. However, the owner may request a
may be connected to the steam space or postponement in writing of said inspection
to the steam connection to the water and the Building Official shall fix a date for
column. inspection agreeable to both, but not to
exceed 30 days from the intended date.
11. Whenever repairs/replacements are
made on fittings or appliances, the work 15. The owner or user of a boiler shall
shall comply with the section on New prepare the same for inspection by
Installation of the Philippine Mechanical cooling it down blanking off all connections
Engineering Code. to adjacent boilers, removing all soot and
ashes from tubes, heads, shell, furnace and
12. After a permit has been granted to combustion chamber. The owner shall
updated by FJSL - Do not share this pdf
assist the Building Official by providing 5. Where ducts pass thru walls, floors or
all labor and equipment required during partitions, the space around the duct shall
said inspection. be sealed with fire resistant material
equivalent to that of the wall, floor or
Refrigeration and Air- partition, to prevent the passage of flame
or smoke.
Conditioning
1. The temperature and humidity of the 6. When ducts or the outlets or inlets to
air to be used for comfortable cooling them pass through fire walls, they shall be
shall be maintained at 68-74oF effective provided with automatic fire dampers on
temperature at an air movement from both sides of the fire wall through which
4.57 to 7.60 MPM within the living zone. they pass.
2. Water from evaporators, condensers 7. Fire doors and fire dampers shall be
and other machinery shall be properly arranged to close automatically and remain
collected into a suitable water or tightly closed, upon the operation of a
drainage system. fusible link or other approved heat
actuated device, located where readily
3. Ducts shall be constructed entirely of affected by an abnormal rise of
non-combustible materials such as steel, temperature in the duct.
iron, aluminum or other approved
materials. Only fire retardant lining shall 8. Each refrigerating system shall be
be used on the inside of ducts. provided with a legible metal sign
permanently attached and easily accessible,
4. Access doors shall be provided at all indicating thereon the name of
automatic dampers, fire dampers, manufacturer or installer, kind and total
thermostats and other apparatus number of kgs of refrigerant contained in
requiring service and inspection in the the system and field test pressure applied.
duct system. 9. In refrigerating plants of more than 45
kg refrigerant, masks and helmets shall be
updated by FJSL - Do not share this pdf
used. These shall be kept in a suitable 15. Window type AC installed on ground
cabinet outside the machine room when floors of buildings shall not be less than
not in use. 2.13 m from the ground.
10. Not more than 136 kgs of refrigerant 16. Window type ACs shall be provided
in approved containers shall be stored in with exhaust ducts if the exhaust is
a machine room at any given time. discharged into corridors/hallways/
arcades/sidewalks etc.
11. Where ammonia is used, the
discharge may be into a tank of water, 17. Window type ACs installed along
which shall be used for no other purpose corridors/hallways/above the first floor
except ammonia absorption. At least one shall not be less than 2.13 m above the
gallon of water shall be provided for floor level.
every 0.4536 kg of ammonia in the
system. Piping
1. Piping shall, as much as possible, run
12. Refrigerant piping crossing a parallel to building walls.
passageway in any building shall not be
less than 2.3 m above the floor. 2. Grouped piping shall be supported on
racks, on either horizontal or vertical
13. In a refrigerating system containing planes.
more than 9 kgs, stop valves shall be
installed in inlets and outlets of
3. Piping on racks shall have sufficient
compressors, outlets of liquid receivers, space for pipe or chain wrenches so that
and in liquid and suction branch header. any single line can be altered/repaired/
replaced without disturbing the rest.
14. Window type ACs shall be provided
with drain pipe or plastic tubing for
4. Piping 100mm in diameter and above
discharging condensate water into a shall be flanged. Smaller sized pipes may
suitable container. be screwed.
updated by FJSL - Do not share this pdf
5. Piping subjected to varying temperatures
5. Piping subjected to varying d) Pneumatic Division
temperatures shall be provided with All piping – Gray
expansion joints.
e) Gas Division
6. Galvanized piping shall not be used for All piping – Black
steam.
f) Fuel Oil Division
7. Piping carrying steam, hot water of hot All piping – Black
liquids shall not be embedded in concrete
walls or floors and shall be properly g) Refrigerating Division
insulated to prevent accidental scalding Pipes – Black Fittings – Black
to persons and to minimize heat loss.
a) Steam Division
High Pressure- White
Exhaust System – Buff
b) Water Division
Fresh water, low pressure – Blue Fresh
water, high pressure – Blue Salt water
piping – Green
c) Oil Division
Delivery – Brass or Bronze
Discharge – Yellow