Professional Documents
Culture Documents
QC Working Procedure
QC Working Procedure
Work Procedure
Q. What is QA/QC?
Q. What is ITP’s?
ITP means “Inspection and Test Plan” details of work scope and required types of
Inspections.
Hold Point (H) is the level of inspection that client inspection must required through RFI
and cannot be proceed until inspection is done by client.
a) Hold Points (H): The inspection activity will not proceed without the presence
of client Inspector.
Witness Point (W) is the level of inspection that inspection activity can be preceded
without client inspection or client is not available as per RFI timing.
b) Witness Points (W): Inspection activities can be proceeding after issuing RFI.
Q.What are the difference between Inspection, Surveillance, witness and Hold point?
Inspection : Work can be execute without clients inspection and it can be Inspect some
part of them if it required.
Surveillance (S):Inspector has right to conduct random inspection of works.
Witness: (W) is the level of inspection that inspection activity can be preceded without
client inspection, or client is not available as per RFI timing. Work can be executed
without client inspection and then it can be inspected upon the completion of work.
Hold Point: (H) is the level of inspection that client inspection must require through RFI
and cannot be proceed until inspection is done by client. or Work can’t be executed
without client inception.
A1 100% Actual Inspection / Test H Mandatory Hold Point
W1 100 % Witness Inspection/Test H1 100% Hold Point for QC Inspection or
Test
W2 Sample Witness Inspection/Test H2 Sample Hold Point for QC Inspection or
Test
R1 100% Review of Documents RH1 100% Review and Approval of
Documents
R2 Sample Review of Documents RH2 Sample Review and Approval of
Documents
S1 Surveillance S2 10% Surveillance
Q.What is final RFI? When it shall be raised up?
When the QA/QC department of contractor is satisfied that the work detailed in the
construction RFI is completed then request submitted for inspection to the client QA/QC
department.
Q.What is NCR? Why does it need for a QA/QC personal?
NCR means Non‐Compliance Report, QA/QC personal has reserve the right to issue a
warning if the contractor doesn’t comply or violate with the standard procedure.
: NCR (Non Compliance Report) for issuing in case of major violation etc.
Q.Whatare the general work procedures (WP)?
a) Receiving Drawing and Documents
b) Reproductionof Drawings
c) Issuing ofDrawing to site
d) New‐Issuing New Revisions
e) ShreddingofDrawings
f) RedliningDrawings
g) Transmittal of redlines to Client (As-built)
h) Restricted access to the DCO
i)Work Permit prior to start the works
j)Record
Electrical.
o Area Classification Drawings
o One-Line Diagrams
o Low and Medium Voltage Substation Design
o Power Distribution System Analysis
o Fault Current Studies
o Capacitor Banks
o Motors and Motor Control Centers
o Motor Control Schematics
o Cable Tray Design
o Underground Duct Banks
o Induction and Synchronous Motor Applications
o Variable Speed Drive Applications
o Resistance Heat Tracing
o Inductive Heat Tracing
o Grounding Systems
o UPS Systems
o Junction Boxes, Terminations, and Grounding
o Conduit Plans and Details
o Cabling and Wiring Systems
o Lightning and Surge Protection
o Intrinsic Safety Systems
o Fiber Optic Systems
o Communication Systems
o Security Systems
o Electrical Design for Hazardous Locations
Q.Whatare area classifications? Give a brief.
As per NEC and NACA, following are the hazard classification;
Class I :Location in which flammable gases or vapors may be present in the atmosphere
in quantities sufficient to produce explosive or ignitable mixture.
Nec
Standard Nema For Motar Standard ? 5
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS 110
OVERCURRENT PROTECTION 240
grounding 250
WIRING METHODS 300
CABINETS, CUTOUT BOXES, AND METER SOCKET ENCLOSURES 312
314
OUTLET, DEVICE, PULL, AND JUNCTION BOXES; CONDUIT BODIES; FITTINGS; AND HANDHOLES
ARMORED CABLE: TYPE AC 320
MEDIUM VOLTAGE CABLE: TYPE MV_______________________________________________ 328
METAL-CLAD CABLE: TYPE MC____________________________________________________ 370
MOTORS, MOTOR CIRCUITS, AND CONTROLLERS nec 430
AIR-CONDITIONING AND REFRIGERATING EQUIPMENT nec 440
Transformer nec 450
switchgare and panel bord hazard area 500
Sabic Standards
Sabic
E02-G01 electrical criteria E04-S01,S02,S03 transformer E06
EO7 for motors gen E 11-SO1,SO2,S03 for grounding E12
for dc system E 20 fo lighting
E22 for cables termination E 23 for conduie E24
cable tray E 26 underground and E29 for catholic
protection.
IECStandards
IEC 60034 Rotating Electrical Machines
IEC 60060 High-voltage test techniques
IEC 60071 Insulation co-ordination
IEC 60076 Power Transformers
IEC 600156 Insulating liquids – determination of the breakdown
voltage at power frequency. Test method.
IEC 60364-4-41 Electrical installation of building – Protection for safety Protection
against electric shock
IEC 60502-2 Power cables with extruded insulation for rated voltage
from 1kV up to 30kV
IEC 60599 Mineral oil – impregnated electrical equipmentin service.
Guide to the interpretation of dissolved and free gases
IEC 62271 High voltage switchgear and control gear
IEC 60694 Common specification for HV switchgears andcontrol gear
standards
Saudi Aramco Forms and Data Sheets
Form SA – 7823 Saudi Aramco H.V Cable Test Records.
Saudi Aramco Precommissioning Forms
Form P – 004 Cables –Medium Voltage
Form P –005 Cables – High Voltage
Precommissioning Execution
IEC 60034 Rotating Electrical Machines
IEC 60060 High-voltage test techniques
IEC 60071 Insulation co-ordination
IEC 60076 Power Transformers
IEC 600156 Insulating liquids – determination of the breakdown
voltage at power frequency. Test method.
IEC 60364-4-41 Electrical installation of building – Protection for safety –
Protection against electric shock
IEC 60502-2 Power cables with extruded insulation for rated voltage
from 1kV up to 30kV
IEC 60599 Mineral oil – impregnated electrical equipment in
service. Guide to the interpretation of dissolved and free gases
IEC 62271 High voltage switchgear and controlgear
IEC 60694 Common specification for HV switchgears and controlgear
International Electro technical Commission
IEC 60227 Polyvinyl Chloride Insulated Cables of Rated Voltages up to and Including
450/750 V
IEC 60228 Conductors of Insulated Cables
IEC 60332-1 Tests on Electric Cables under Fire Conditions Part: 1 Test on a single
vertical insulated wire or cable
IEC 60332-3 Test on Electric Cable under Fire Conditions
Nema ve2, This Publication Address Shipping, Handling, Storing, And Installation Cable
Tray System .Information And Maintenance Also Modification.
Nema ve1, This Specification Help ,We Can Design Cable Tray According To (Cec)And
(Nec).
Q.Per Aramco Standards, what is minimum separation between low voltage power
cables and instrumentation cables in cable trays.
Minimum “300 mm.”
Q.Per NEC, what is the maxm. Distance between supports for 2 inch rigid steel
conduit.
Horizontal : 4.9 mtrs. (16 Feet) Vertical:6mtrs.As Per NEC Article –Table 344:30 (B) (2)
See SAES B‐068, Para 5.3
Q.Per Saudi Aramco standard, what is the minimum size of grounding grid
conductor [cable]?
70mm2
Q.On electrical equipment being used in hazardous area you may see the letter UL
or C.S.A, what do these abbreviations stand for?
UL–Under Writer LaboratoriesC.S.A–Canadian Standard Association
Q.What type of conduit must be used within Class Ι zone 0/1 area?
Threaded Rigid Metal Conduit.
CONDUIT
Q.What is the minimum size of conduit for instrumentation and its support distance
1.A conduit outlet box shall be installed within 18 inches of the field device, and the
cable to the Instrument shall be looped one or more timeswithin this fitting.
2.Flexible conduit shall be used at the instrument end of the conduit to provide isolation
from vibration and protection against thermal expansion of the rigid conduit.
3.Conduit above ground in severe corrosive environments shall be PVC coated
min.thickness is 40 mils per NEMA RN 1.
4.Conduit fittings for outdoor rigid steel conduit and liquid tight flexible metal conduit
shall be cast or forged steel, cast iron or malleable iron, either hot-dip galvanized or zinc
electroplated (no aluminum fittings or fittings accessories shall be used in outdoor
installation)
5.Conduit and cable entries to field junction boxes shall be through the bottom.Top
entries are allowable and provide a drain seal installed on the conduit within 18 inches
away from the enclosure.
CABLE TRAY
A.Connections at field instruments shall be screw type terminal blocks. Wire nuts and
spring type terminals shall not be used. Instruments’ with integral terminal blocks shall
be connected directly to the field cable.
B.The outer jacket of shielded twisted single pair/triad cables shall be left intact up to the
point of termination. Drain wires and Mylar shields on shielded cables shall be cut and
insulated with heat shrink sleeve at the field instrument unless otherwise specified by the
Instrument manufacturer.
C.Twisted multi-pair triad cables shall be cut to the appropriate length to minimize
looping and flexing of the cable within the junction box.
COLOR CODING Power and signal wiring shall be color coded as follows:
AC Supply
Phase Black
Neutral White
Ground Green or green with yellow tracer
DC Supply
Positive Red or red sleeve over any color except green
Negative Black or black sleeve over any color exceptgreen
Signal Pair
Positive Black
Negative White
Signal Triad
Positive Black
Negative White
Third Wire Red
17.2Safety Ground
17.2.1 All exposed non‐current‐carrying metallic parts that could become energized
with hazardous potentials must be reliably connected to the equipment grounding circuits.
This assures that hazardous potential differences do not exist between individual
instrument cases or between an instrument case and ground. Therefore, all metal
equipment and enclosures within a panel or series of panels (i.e., instrument cases,hinged
doors, racks, etc.) shall be bonded with bonding jumpers and connected to a safety
ground bus with a minimum copper wire size of 4mm²cross‐sectional area. Two copper
conductors, 25mm² minimum, shall be connected from the safety ground bus to a single
tie point on the safety ground grid in a closed loop configuration. Safety ground
connections must be made such that when a case‐grounded instrument is removed, the
integrity of the rest of the safety ground system is maintained.
PVC 70 C
EPR (Ethylene-Propylene 90 C
Rubber) & HF EPR (Halogen
Free EPR)
XLPE (Cross-Linked 90 C
Polyethylene) & HF XLPE
(Halogen Free XLPE)
susceptible to firedamp
Group II Group IIA Methanol, Benzene,
Methane etc
T1 > 450 oC
T2 300<T<=450
T3 200<T<=300
T4 135<T<=200
T5 100<T<=135
T6 85<T<=100
Screen (Individual & Overall for Analog Aluminum / Polyester tape, copper drain
Signal Cable, Overall only for Digital Signal wire according to IEC 60092-
Cable) 350Thickness as per IEC 60092-376