FERTILISERSABAH
SDN BHD
BASIC DATA
PROJECT TITLE MAINTENANCE AND SERVICING OF FIRE AND GAS DETECTION SYSTEM
Breakdown / Repair Fire Alarm Panel
Service Maintenance / Flame Detector
TYPE OF SERVICES Troubleshooting & Inspection Manual Call Point
Testing & Commissioning Smoke detector
TYPE OF EQUIPMENT
Specialist Service Gas Detector
Heat Detector /
SERVICE ORDER NO.
Multisensor Detector
DATE 02/09/2022 Others
WORK GROUP Lester, Romiday & Joel
LOCATION / AREA ● Ammonia
SPECIFIC LOCATION ● SS200
SERVICE REQUIRED
a) PPM: 200HD-52 HD, SCE (W.O: 80743920)
b) PPM: 200HD-53 HD, SCE (W.O: 80743921)
c) PPM: 200HD-54 HD, SCE (W.O: 80743922)
d) PPM: 200HD-55 HD, SCE (W.O: 80743923)
e) PPM: 200HD-56 HD, SCE (W.O: 80743924)
f) PPM: 200HD-57 HD, SCE (W.O: 80743925)
g) PPM: 200HD-58 HD, SCE (W.O: 80743926)
SERVICE PERFORMED
⮚ PPM: 200HD-52
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-52
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 8 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
Time completed: 1030-1050 (20min) PASS
SAP Number: 80743920
⮚ PPM: 200HD-53
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-53
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 10 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
⮚ PPM: 200HD-54
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-54
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 9 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
⮚ PPM: 200HD-55
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-55
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 9 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
⮚ PPM: 200HD-56
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-56
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 7 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
⮚ PPM: 200HD-57
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-57
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 8 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
⮚ PPM: 200HD-58
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 200HD-58
AREA / LOCATION SS200
MODEL / TYPE AUTRONICA
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 9 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
N/A
PROGRESS STATUS
To Quote
To Follow Up
Pending
Complete /
Done performing PPM on unit 200 HD 52~58. All devices in good condition and can function properly.
Position Technician
Date 02/09/2022