Professional Documents
Culture Documents
FERTILISERSABAH
SDN BHD
BASIC DATA
PROJECT TITLE MAINTENANCE AND SERVICING OF FIRE AND GAS DETECTION SYSTEM
Breakdown / Repair / Fire Alarm Panel
Service Maintenance / Flame Detector
TYPE OF SERVICES Troubleshooting & Inspection Manual Call Point
Testing & Commissioning Smoke detector
TYPE OF EQUIPMENT
Specialist Service Gas Detector
Heat Detector /
SERVICE ORDER NO.
Multisensor Detector
DATE 14/09/2022 Others /
WORK GROUP Lester, Romiday, Aron & Joel
LOCATION / AREA ● UTILITY
● OFFSITE
SERVICE REQUIRED
a) REM: To replace one set beacon finding DM 50GD-031GF (W.O: 80562503)
b) PPM: SCE, 300HD-01, DS001 (W.O: 80764609)
c) PPM: SCE, 300HD-02, DS001 (W.O: 80764610)
d) PPM: SCE, 300HD-03, DS001 (W.O: 80764611)
e) PPM: SCE. 300HD-04, DS001 (W.O: 80764612)
f) PPM: SCE, 300HD-05, DS001 (W.O: 80764613)
g) PPM: SCE, 300HD-06, DS001 (W.O: 80764614)
SERVICE PERFORMED
⮚ PPM: 300HD-001
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 300HD-001
AREA / LOCATION SS300
MODEL / TYPE FANWALL
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 7 Seconds
⮚ PPM: 300HD-002
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 300HD-002
AREA / LOCATION SS300
MODEL / TYPE FANWALL
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 9 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
Time completed:
SAP Number: 80764610
PASS
3. PPM: Heat Detector (300HD-003)
I. Preventive maintenance
i. Perform function test
ii. Visual inspection
iii. Housekeeping
⮚ PPM: 300HD-003
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 300HD-003
AREA / LOCATION SS300
MODEL / TYPE FANWALL
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 9 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
Time completed:
SAP Number: 80764611
PASS
⮚ PPM: 300HD-004
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 300HD-004
AREA / LOCATION SS300
MODEL / TYPE FANWALL
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 7 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
Time completed:
SAP Number: 80764612
PASS
⮚ PPM: 300HD-005
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 300HD-005
AREA / LOCATION SS300
MODEL / TYPE FANWALL
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 8 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
Time completed:
SAP Number: 80764613
PASS
⮚ PPM: 300HD-006
INSTRUMENT DEPARTMENT
DETECTOR TYPE Heat Detector
TAG NUMBER 300HD-006
AREA / LOCATION SS300
MODEL / TYPE FANWALL
VOLTAGE (V) 24V
DETECTOR/SENDOR FUNCTION TESTING
SIGNAL OUTPUT
HEAT/SMOKE AS FOUND AS LEFT
FAP ALARM DCS ALARM FAP ALARM DCS ALARM
ON ON OFF ON OFF
OFF OFF OFF OFF OFF
Response Time 8 Seconds
DETECTOR STATUS
REMARKS: HD still can function properly and in good condition.
Time completed:
SAP Number: 80764614
PASS
*Remark: Done perform beacon replacement and perform functional test. Beacon is in good condition.
RECOMMENDATIONS
N/A
PROGRESS STATUS
To Quote
To Follow Up
Pending
Complete
/ Done performing PPM on all six (6) units of 300HD and REM to replace the beacon for unit 50GD-031GF. All
devices in good condition.
Position Technician
Date 14/09/2022