Professional Documents
Culture Documents
H,
^>v*
x
v
Precise Control of
Diesel Generating Sets
SOCIETY OF A U T O M O T I V E E N G I N E E R S
680577
Precise Control of
Diesel Generating Sets
given application may involve operation in all three modes AMPLIFIER CHASSIS
ABSTRACT■
Components include electrical circuits for sensing speed
In speed control of prime movers, precise steady-state and load and an electrohydraulic actuator which converts
and transient control of frequency and close control of elec electrical signals from the amplifier into useful mechanical
trical load division among paralleled generators are a chal motion for operation of an engine fuel control. This system
lenge to the control designer. The inherent adaptability of has been used with all type engine-generator sets. It is also
an electrical device to control these electrical character readily adaptable to high speed compressors and pumps.
istics, makes it a good choice for this type of application. Reliability is a proved feature as its design is very conserva
The electrical speed-control system discussed in this paper tive and all components being used are well within their
fulfills these requirements. ratings.
Downloaded from SAE International by University of New South Wales, Monday, August 27, 2018
IW»T
l \!
mis
SPEC!
lEcmuv
HITS
SETT I K
! i
CLOSE FH 1
CURRENT
TRANSFORMER
Fig. 3 - Electrohydraulic actuator schematic
Fig. 5 - Load-sensor circuit (for one phase)
tegrating and power amplifiers to convert the generator creases greatly after saturation because the inductive re
frequency and load current into appropriate voltage signals actance in the primary becomes very small. This high pri
which in turn operate the actuator. The input signals to mary current maintains saturation until point B. Then the
the amplifier include an adjustable speed reference voltage. direction of flux reverses, as does the voltage, and satura
tion is again reached at point C. These pulses are rectified
SENSING CIRCUITS and filtered to give a d-c voltage level proportional to the
number of pulses per second, or frequency. It should be
The three-phase voltage of the generator is a required noted that a change in the magnitude of input voltage makes
input to the control circuit to provide a voltage phase ref the pulses higher, but narrower, keeping the area under the
erence which is needed for computing real load on the gen curve (average d-c) the same. Consequently, the d-c level
erator for load sharing. Power supply and speed signals are is essentially unaffected by reasonable variations in input
taken from one phase only. voltage. This voltage proportional to frequency is applied
A d-c voltage is developed in a speed-sensor circuit to the amplifier input with a polarity tending to reduce en
which is proportional to the frequency of the generator out gine speed.
put. This is accomplished by means of a saturable trans The foregoing signal is opposed by the speed-reference
former and rectifier. The circuit is designed with the core voltage which is also applied to the amplifier input. The
area limited so that the core will saturate at approximately speed-reference voltage tends to increase engine speed.
the halfway point of each half-cycle of the input. When When the speed or frequency matches the speed setting, the
this occurs at point A in Fig. 4, the rate of change of core signals cancel and no speed correction is made. Accurate
flux falls off to zero and with it the secondary voltage. The speed-reference voltage is obtained from a Zener diode
primary current, which determines the amount of flux, in circuit. The power for this circuit is available from the rec-
Downloaded from SAE International by University of New South Wales, Monday, August 27, 2018
tified single phase power supply included in the electrical units and a selector switch is set to the "normal" position.
control. A voltage signal proportional to load from one unit is com
A load-sensor circuit is used to produce a d-c voltage pared to a similar signal from the other unit or units. The
proportional to real load. A burden resistor is connected difference voltage, proportional to load unbalance, biases
across each current transformer to produce a voltage drop the speed setting of each unit and adjusts fuel to equalize
proportional to, and in phase with, load current for each the loads, while maintaining a constant system frequency.
generator phase. As shown in Fig. 5, the voltage, V . from If an engine-generator set is operated in parallel with a
large system it must have speed droop in order to hold a fixed
the burden resistor is applied to transformer T . The vol
load. A selector switch is set to the "droop" position for
tage V adds vectorially to V and V to give resultant this type of operation. The d-c voltage proportional to real
H A B
load is applied to a variable resistor in the droop circuit
voltages V and V R2 . These voltages are half wave rec
and results in an adjustable amount of voltage change with
tified and subtracted to provide d-c voltage, V , which is real load. This signal biases the speed setting as a function
o of load level resulting in a droop governor. This is similar
proportional to load on that phase. When the load is zero, to the action of the output servo adjusting the spring speed
V andV are zero. This circuit measures current mae-
c 1 o reference in a mechanical flyball governor. In this manner
nitude and phase angle of the current with respect to the stable load conditions exist in parallel since a load increase
voltage. The voltage V is, therefore, approximately pro on the generator will be effective in lowering the speed
setting and thereby reducing the load until equilibrium is
portional to I cos e. In the normal system the regulated reached. The droop is adjustable in the range of 0-10%.
voltage is essentially constant and thus V is proportional to The amount of load on the generator is controlled with the
o speed-setting potentiometer.
EI cos 6 or kilowatts. The V from each phase is added to
o r A typical electrical control assembly for engine-generator
give a d-c voltage approximately proportional to the total control is pictured in Fig. 6.
three phase load. AMPLIFIER
The d-c voltage proportional to load is used in different
ways depending upon the mode of operation. For isochronous The speed and load signals which have been discussed
load sharing between two or more engine-generator sets previously are added together at the input of a solid-state
operating in parallel in an isolated load system, paralleling amplifier. As can be seen in Fig. 2, the amplifier is built
lines are connected, through the circuit breaker, between
Downloaded from SAE International by University of New South Wales, Monday, August 27, 2018