Specification for Power Transformers Version 4.0
Signed : ...........................................................
Saif Al Sumry, TTE
CFDH, Electrical Engineering (UEE)
The following is a brief summary of the 4 most recent revisions to this document. Details of all
revisions prior to these are held on file by the issuing department.
Contents
1. Introduction ............................................................................................. 3
1.1 PURPOSE ............................................................................................................ 3
1.2 APPLICABLE STANDARDS, SPECIFICATIONS AND CODES ................... 3
1.3 COMPLIANCE WITH STANDARDS ............................................................... 3
1.4 PRODUCT/ASSET WARRANTY ..................................................................... 3
2. Amendment/Supplement ........................................................................ 5
2.1. DEP PART II CLAUSE 1.2 - SERVICE CONDITIONS ................................... 5
2.2 DEP PART II CLAUSE 8.4.2 - WINDINGS AND TAPPINGS ........................ 5
2.3 DEP PART II CLAUSE 8.4.7.1 – GENERAL .................................................... 5
2.4 DEP PART II CLAUSE 8.4.7.2 - MAIN CONNECTING CABLE BOXES...... 5
2.5 DEP PART II CLAUSE 8.4.8 - CABLE TERMINATIONS .............................. 5
2.6 DEP PART II CLAUSE 8.4.24 - PACKAGING FOR TRANSPORT ................ 6
2.7 DEP PART II CLAUSE 8.6 - ADDITIONAL REQUIREMENTS FOR
CONSERVATOR TYPE TRANSFORMERS .................................................... 6
2.8 DEP PART II CLAUSE 8.4.22 – SURFACE PREPARATION
GALVANISING AND FINISHING.................................................................... 6
2.9 PURCHASE ORDER .......................................................................................... 7
APPENDICES
APPENDIX A: GLOSSARY OF DEFINITIONS, TERMS AND ABBREVIATIONS ................... 8
SP USER-COMMENT FORM
FACTORY INSPECTION CHECK LIST ..................................................................................................... 9
1. Introduction
1.1 PURPOSE
This specification is an amendment and supplement to DEP 33.66.40.31-Gen., Power
Transformers. It contains additional and/or modified requirements specific to the Company
and shall be used in conjunction with the above DEP.
DEP clause numbers used in this SP refer to the relevant clause number in DEP 33.66.40.31-
Gen, issue dated October, 2001.
plant or component shall have the same service life and efficiency as the component
originally manufactured.
The Vendor shall also warrant all equipment and component parts against defective material,
design and /or workmanship. Merely extending a Sub-Vendor’s warranty is not acceptable.
The approval of the Company's Representative of inspection and/or test results will not
prejudice the right of the Company's Representative to reject an item of equipment if it does
not comply with the specification when erected or prove completely satisfactory in service.
Product/asset warranty shall further refer to the requirement as specified in the commercial
package of the contract document.
2. Amendment/Supplement
Liquid filled power transformers shall be installed outdoors without sun protection shields
and shall be designed for a maximum ambient temperature of 55°C. Dry type power
transformers shall be installed indoors. For atmospheric outdoor and indoor conditions refer
to SP-1103.
All joint faces shall be arranged to prevent the ingress of water or leakage of oil with a
minimum of gasket surface exposed to the action of oil or air.
Oil resisting synthetic rubber gaskets shall not be permissible except where the synthetic
rubber is used as a bonding medium for cork or similar material or where metal inserts are
provided to limit compression.
Gaskets shall be as thin as is possible consistent with the provision of a good seal and full
details of all gasket sealing arrangements shall be shown on the drawings.
Flange edges of pipes exposed to sunlight shall be provided with suitable gaskets to
withstand direct sunlight.
skid and all welds shall be free of any cracks/ linear defects. All welding and load test shall
be certified by the Company approved Third Party Inspection agency (refer SP-1171).
The purchase order shall be prepared using the latest revision of the following standard form:
Requisition form: DEP 33.65.40.93-Gen.
The following terms and abbreviations used in this document, are defined below:
General Terminology
Shall - The word 'shall' is to be understood as mandatory.
Manufacturer/Vendor The party responsible for the manufacture of equipment and services to
perform the duties specified by the Consultant or Company.
Abbreviation
BS - British Standard
DEP - Design and Engineering Practice ( SIEP/SIOP)
ERD - Engineering Reference Document (old revision of SP).
HV - High Voltage.
IEC - International Electrotechnical Commission.
PDO - Petroleum Development Oman LLC.
SIOP - Shell International Oil Products B.V.
SP - Specification (PDO)
GU Guidelines
SP User-Comment Form
If you find something that is incorrect, ambiguous or could be better in an SP, write your comments
and suggestions on this form. Send the form to the Document Control Section (DCS). They make a
record of your comment and send the form to the correct CFDH. The form has spaces for your
personal details. This lets DCS or the CFDH ask you about your comments and tell you about the
decision.
Comments:
Suggestions:
CFDH Actions
Recd Decision: Inits: Ref. Date:
Date: Reject: Ind:
Accept, revise at next issue:
Accept, issue temporary amendment
Comments:
MANDATORY REQUIREMENTS
TESTS
10
a) Routine test Formatted: Numbered + Level: 1 +
b) Type tests Numbering Style: a, b, c, … + Start at: 1 +
c) Special tests Alignment: Left + Aligned at: 0.5" + Tab after:
0.75" + Indent at: 0.75"
GENERAL
a) Finishing 8.4.22 Formatted: Numbered + Level: 1 +
b) Rating plate Numbering Style: a, b, c, … + Start at: 1 +
7 Alignment: Left + Aligned at: 0.5" + Tab after:
c) Packaging
8.4.24 0.75" + Indent at: 0.75"
d) Final release 2.6
11
Specification for Power Transformers Version 4.0
inspection
Type of
Accept
Reject
INSPECTION, TESTING & CERTIFICATION
REQUIREMENTS
CORE DETAILS
check: S
- Cores are laminated low loss grain oriented Si-steel, Si protected, de- Formatted: Bulleted + Level: 1 + Aligned at: 0.08" +
burred, insulated with mitred joints, 3 phase transformers have in line 3 Tab after: 0.33" + Indent at: 0.33"
limb cores
- All metal parts except core laminations, core bolts and side clamping
COOLING
Check: S
- Details as per data sheet Formatted: Bulleted + Level: 1 + Aligned at:
- Oil immersed transformers cooled by bolted flange mounted radiators. 0.08" + Tab after: 0.33" + Indent at: 0.33"
Welded cooling tubes prohibited. Corrugated walls acceptable up to and
including 1600kVA. Oil is conforming to either IEC 60296 Class I A
and Class II A or IEC 61099 specification. (check – P/O specification).
Oil containing Polychlorinated biphenyl (PCBs) not allowed.
CABLE / TERMINATIONS
Check:
S
- Cable termination boxes to IEC 600529 IP 53 (outdoor use) IP 41 Formatted: Bulleted + Level: 1 + Aligned at:
(indoor use), IP 21 (indoor use with protective barriers). Check also 0.08" + Tab after: 0.33" + Indent at: 0.33"
data sheet & SP-1117, clause-2.4, 2.5.
- Separate cable boxes provided for HV side, LV side, auxiliary circuits,
on load tap changer & forced air circulation installation (if provided)
- Cable boxes have glands plates mounted on underside
- Cable boxes are air insulated with insulated / shrouded live parts
- Requisition for special earthing requirements for LV & auxiliary circuit
if these are insulated from the main transformer frame
- Requisition for sum / rain canopy requirements, at least 50mm overhang
and free air space required over cable boxes.
- Main cable boxes allow conductors to be connected to terminals without
harmful bending. Parallel conductors connected straight using copper
bars or flags. Certificates to be reviewed showing ability to stand
continuous rated and short circuit currents. Space available for stress
relievers.
- Main cable termination boxes and sleeves for multicore cables are split
types. Termination either air insulated or epoxy resin sealed to cable
crutch. Single core cable termination use bronze / brass or aluminium
(as per requisition spec.) compression glands in non-magnetic base
plate.
- Cover plates have simple handles, over 25 kg lifting lugs.
- Auxiliary cable boxes mounted 400 to 1800 mm above transformer
11/08/2011
Specification for Power Transformers Version 4.0
CURRENT TRANSFORMERS
Check:
- Current transformers are in accordance with data sheet, DEP clause Formatted: Bulleted + Level: 1 + Aligned at: 0.08" +
8.4.17 and IEC 60044 in respect of rated output, primary current Tab after: 0.33" + Indent at: 0.33"
(current ratio if specified) and secondary current (normally 1 A), remote
indication (if specified), class of accuracy. Short time thermal current R
rating – Is, check P/O. Measuring current transformers saturation factor
‘n’ not more than 5 at maximum fault current.
Secondary terminals of current transformers wired terminal block with
short circuiting links in auxiliary cable connecting box and one side of
winding connected to earth bar at this terminal block. Protective current
11/08/2011
Specification for Power Transformers Version 4.0
DEP 33.65.40.31-Gen
the maximum sound pressure level(SPL) at a
distance of 0.3 m shall not exceed the value given
by the following equation:
SPL = 45 + 8 Log10 P dB(A)
where P is stated in kVA
ROUTINE TESTS
Check:
S
- Winding resistance measurement uses DC Wheatstone bridge on each Formatted: Bulleted + Level: 1 + Aligned at: 0.08" +
winding and results recorded with winding temperature (after 3 hours Tab after: 0.33" + Indent at: 0.33"
non-excitation and taken as equal average of top & bottom oil
temperature).
- Voltage ratio and voltage vector relation ship measured on each
tapping. Polarity of single phase and connection symbol of 3 phase
transformers checked
- Impedance voltage (principal tapping), short circuit impedance and load
loss shall be measured at rated frequency using sinusoidal supply to one
winding the other short circuited with winding connected on the relevant
11/08/2011
Specification for Power Transformers Version 4.0
• temperature rise of top oil with conservator or sealed 60oC,otherwise Formatted: Bulleted + Level: 1 + Aligned at: 0" +
55oC measured with thermometer R Tab after: 0.25" + Indent at: 0.25"
• temperature rise dry type of windings and adjacent cores A (60oC), E
(75oC), B (80oC), F (100oC), H (125oC) and above by agreement.
Terminal temperature rise 65oC maximum. Winding temperature
determined by interchangeable PTC thermistor in each winding and
located such that no over voltage protection is required.
• P/O for operational air temperature. If maximum daily temperature is
above 40oC, average daily above 30oC or yearly average above 20oC
reduce allowable temperature rise by 5oC if excess is less than 5oC or 10
o
C for excess between 5 and 10 oC. Excess above 10 oC or cooling water
over 25 oC rise to be agreed
• P/O for altitude de-rating factors for operation over 1000m
• agreed method of verification of forced – directed oil flow transformers
• non-identical concentric windings temperature rise agreed with purchaser.
Identical winding use arithmetic mean for temperature rise
• air temperature measured with at least 3 thermometers, cooling water
temperature measured at intake as average of at least 3 readings at
intervals less than 1 hour. Readings to be taken during last quarter of test
period
• Winding temperature rise: Formatted: Bulleted + Level: 1 + Aligned at: 0" +
- measured by D.C. resistance method Tab after: 0.25" + Indent at: 0.25"
(for superposition method see IEC 600279) Formatted: Indent: Left: 0.24", Hanging: 0.31",
Bulleted + Level: 1 + Aligned at: 0.08" + Tab after:
and calculated according to: 0.33" + Indent at: 0.33", Tab stops: Not at 0.33"
T2 = {(R2/R1)*(C+T1)} - C
where C = 235 for Cu and 225 for Al
- final temperature calculated from linear plot of temperature Formatted: Indent: Hanging: 0.1", Bulleted + Level:
rise increments with time, last increment less than 3 oC in 1 1 + Aligned at: 0.08" + Tab after: 0.33" + Indent at:
hour or taken as top oil temperature when stable to 1oC over 4 0.33", Tab stops: Not at 0.33"
consecutive hourly readings. (dry type temperature rise
measured at 90% or more of rated current value until
temperature is steady. Calculation of rise according to 3.6 of
IEC 60076-2).
- temperature rises measured at 90% or more of rated current on all Formatted: Indent: Left: 0.24", Hanging: 0.2",
windings (appropriate tapping current) and frequency with correction Bulleted + Level: 1 + Aligned at: 0.08" + Tab after:
factor 0.33" + Indent at: 0.33", Tab stops: Not at 0.33"
- oil immersed transformers loaded directly or by short circuit
method (dry type loaded back to back directly)
- reading with water pumps and fans switched off, oil pump Formatted: Indent: Hanging: 0.1", Bulleted + Level:
running, soon after inductive effect has disappeared. 1 + Aligned at: 0.08" + Tab after: 0.33" + Indent at:
0.33", Tab stops: Not at 0.33"
Correction made to readings for delay between shutdown and
measurement.
• Check dielectric tests: Formatted: Bulleted + Level: 1 + Aligned at: 0" +
- type test according to table-1of IEC 60076-3 Tab after: 0.25" + Indent at: 0.25"
Formatted: Indent: Hanging: 0.16", Bulleted + Level:
1 + Aligned at: 0.08" + Tab after: 0.33" + Indent at:
SPECIAL TESTS 0.33", Tab stops: Not at 0.33"
Check:
• identical construction and rating of transformers cited in special test Formatted: Bulleted + Level: 1 + Aligned at: 0" +
reports as certification for those ordered Tab after: 0.25" + Indent at: 0.25"
• Dielectric Tests: see table IEC 60076-3 (& ‘ROUTINE TESTS’, sec.3, of
S
this plan)
• Measurement of zero sequence impedance (s) on 3 phase transformers at
RATING PLATE
Check:
• Stainless Steel or other corrosion resistant metal nameplates permanently Formatted: Bulleted + Level: 1 + Aligned at:
fixed to non-removable part of transformer 0" + Tab after: 0.25" + Indent at: 0.25"
• information given in all cases;
V
Manufacturer
Serial number
Year of manufacture
Number of phases
Rated power
Rated frequency
11/08/2011
Specification for Power Transformers Version 4.0
Connection diagram
Insulation levels
Tapping details
P/O number
Transformer type
Specification number
Rated voltage
Rated current
Connection symbol
Impedance voltage 9at rated current)
Cooling type
Total mass
Mass of insulating oil
Check P/O for any additional requirements.
PACKAGING – Check:
• packaging appropriate to P/O stated requirements Formatted: Bulleted + Level: 1 + Aligned at: 0" +
• shock recorders are mounted Tab after: 0.25" + Indent at: 0.25"
• special tools identified and shipped together with transformer
V
FINAL RELEASE – Check:
• completeness of all test and inspection records Formatted: Bulleted + Level: 1 + Aligned at: 0" +
• completeness of order including special tools, erection materials etc. as Tab after: 0.25" + Indent at: 0.25"
required by P/O against hardware and packing notes
Issue release note / note of non-acceptance as appropriate.
W