1 BCU SCALING
2 MICOM RELAYS
3 ACCORD MFM
4 CONZERVE EM 3460
5 CONZERVE EM 6400
6 SECURE PREMIER 100
14 LG MFM _ L3999
15 LG MFM _ L5110
16 LG MFM _ L5410
17 AE 9000
18 SPACEMAKER HITACHI
a) Instantaneous Parameters
Note:
1 SxNy ----- x = Com Port Number (1,2,3 or 4); y= node number (= meter/PLC ID)
2 Intr = Intr_r = Intr _y = Intr_b
3 Max EU = 1.25 * Nominal Value (given by the customer)
4 Count --- it indicates that Max.EU and Max.Raw are same and are as specified in that column
5 Item gives the high byte address, the low byte is high byte - 1
b. INTEGRATED PARAMETERS
IMPORT
SxNy_KVAh_rev Reverse Apparent Energy 43151 L
SxNy_KWh_rev Reverse Active Energy 43153 L
SxNy_KVARh_rev Reverse Reactive Energy 43155 L
SxNy_PF_avg_rev Reverse Avg PF 43157 L
SxNy_null2 Dummy tag 43169 L
c. DEMAND PARAMETERS
Note:
1. SxNy --- x = Com Port Number (1,2,3 or 4); y = node number ( = meter / PLC ID)
2. Run Hours : The meter sends the data as seconds. It has to be converted to hours using scripts.
If the customer wants RunHours, then seconds have to be divided by 3600 and the
truncated integer value is taken. The decimal portion is divided by 6000 and added to
this integer value to get the actual RunHours.
3. Max EU = 1.25 * Nominal Value (given by the customer)
4. Count --- it indicates that Max. EU and Max. Raw are same and are as specified in that column
5. Item gives the high byte address, the low byte is high byte-1
d. PHASE PARAMETERS
e. THD PARAMETERS
a. For EMS
SxNy x=com port number (1,2,3 or 4); y = Meter ID
b. For PLCs
SxNy_DCz x=Com Port Number )1,2,3 or 4); y = PLC ID
z=Number of PLC
Note:
1. SxNy --- x = Com Port Number (1,2,3 or 4); y = node number (= meter / PLC ID)
2. z--- It is the number of PLCs used in eLAN in ascending order (I.e it will vary from 1 to the total number of PLCs)
3. Max EU = 1.25 *Nominal Value (given by the customer)
4. Count ---- It indicates that Max. EU and Max. Raw are same and are as specified in that column
5. Item gives the high byte address, the low byte is high byte -1
Max.Raw = Max.EU *
256
256
256
32,768
256
256 234.01172
256
256
(count) 999
256
256
256
32,768
256
256
256
(count) 999
256
256
256
32,768
256
256
256
(count) 999
256
256
256
32,768
256
256
256
(count) 999
PLC ID)
1
1
1
32,768
256
256
256
(count) 36,000,000
1
1
1
32,768
(count) 100
1
1
1
32,768
(count) 100
Max.Raw = Max.EU*
(count) 100
256
256
(count) 100
Max.Raw = Max.EU *
256
256
256
256
256
256
256
256
(count) 100
Max.Raw = Max.EU *
256
256
256
256
256
256
eter / PLC ID)
it will vary from 1 to the total number of PLCs)
Value features
Based on primary value of CT & PT
CONZERV METER EM-6400
Value Features* Scaling
DATA FORMATE Function
MIN MAX MIN MAX
REAL32_LW_HB 3 0 144 0 4.29E+09
REAL32_LW_HB 3 0 144 0 4.29E+09
REAL32_LW_HB 3 0 144 0 4.29E+09
REAL32_LW_HB 3 0 158.4 0 4.29E+09
REAL32_LW_HB 3 0 158.4 0 4.29E+09
REAL32_LW_HB 3 0 158.4 0 4.29E+09
REAL32_LW_HB 3 -460 460 -1.00E+09 1.00E+09
REAL32_LW_HB 3 -460 460 -1.00E+09 1.00E+09
REAL32_LW_HB 3 -1 1 -2.15E+09 2.15E+09
REAL32_LW_HB 3 45 55 0 4.29E+09
1
1
1
0.001*
0.001*
0.001*
1.00E-06
1.00E-06
1
1
ommunication Paramenter
9600
None Praity
1bit
8bit
MEASURMENTS MAPPING ADDDRESS
IR 2106
IY 2108
IB 2110
VRY 2100
VYB 2102
VBR 2104
P 2114
Q 2118
PF 2125
FREQUENCY 2129
MWH(EXP) 2402
MWH(IMP) 2400
MVAH(EXP) 2418
MVAH(IMP) 2416
SECURE PREMIER 100
0.005
0.005
0.005
1.73E-04
1.73E-04
1.73E-04
5.00E-04
5.00E-04
0.001
0.001
1*
1*
2*
3* * Based on the value "A"
coefficient will Change
MEASURMENTS MAPPING ADDDRESS
IR 2106
IY 2108
IB 2110
VR 2100
VY 2102
VB 2104
P 2114
Q 2118
PF 2130
FREQUENCY 2122
MWH(EXP) 2406
MWH(IMP) 2404
MVAR_IMP_LAG_Q1 2408
MVAR_EXP_LEAD_Q2 2412
MVAR_EXP_LAG_Q3 2414
MVAR_IMP_LEAD_Q4 2410
SECURE PREMIER 300
IR 113
IY 115
IB 117
VR 107
VY 109
VB 111
P (KW) 147
Q (KVAr) 155
S (KVA) 163
PF 139
FREQUENCY 171
MWH(EXP) 199
MWH(IMP) 201
SECURE ELITE 440
VALUE FEATURES SCALING
DATA FORMATE
MINIMUM MAXIMUM MIN ACQ MAX ACQ
REAL32_LW_HB 0 10000 0 1.00E+14
REAL32_LW_HB 0 10000 0 1.00E+14
REAL32_LW_HB 0 10000 0 1.00E+14
REAL32_LW_HB 0 10000 0 1.00E+14
REAL32_LW_HB 0 10000 0 1.00E+14
REAL32_LW_HB 0 10000 0 1.00E+14
REAL32_LW_HB -6.20E+10 6.20E+10 -1.00E+09 1.00E+09
REAL32_LW_HB -6.20E+10 6.20E+10 -1.00E+09 1.00E+09
REAL32_LW_HB -6.20E+10 6.20E+10 -1.00E+09 1.00E+09
REAL32_LW_HB -1.2 1.2 -1.00E+09 1.00E+09
REAL32_LW_HB 0 55 -1.00E+09 1.00E+09
REAL32_LW_HB -1.00E+09 1.00E+09 -1.00E+09 1.00E+09
REAL32_LW_HB -1.00E+09 1.00E+09 -1.00E+09 1.00E+09
A COEFFICIENT
1
1
1
1.00E-03
1.00E-03
1.00E-03
1.00E-03
1.00E-03
1.00E-03
1
1
1.00E-03
1.00E-03
MEASURMENTSMAPPING ADDDRESS
IR 55
IY 57
IB 59
VR 49
VY 51
VB 53
P (KW) 63
Q (KVAr) 67
S (KVA) 69
PF 74
FREQUENCY 78
MWH(EXP) 233
MWH(IMP) 217
SECURE SWIFT ELITE
IR 55 UINT32_HW_HB
IY 57 UINT32_HW_HB
IB 59 UINT32_HW_HB
VR 49 UINT32_HW_HB
VY 51 UINT32_HW_HB
VB 53 UINT32_HW_HB
P (KW) 63 INT32_HW_HB
Q (KVAr) 67 INT32_HW_HB
S (KVA) 69 INT32_HW_HB
PF 74 INT16
FREQUENCY 78 INT17
MWH(EXP) 233 UINT32_HW_HB
MWH(IMP) 217 UINT32_HW_HB
SECURE SWIFT ELITE ENTITY
0.08
0.08
0.08
0.001*
9.96E-04
9.96E-04
9.96E-04
9.96E-04
9.96E-04
0.001
0.001
0.001
0.001
0.01
1
1
1
1
ommunication Paramenter
19200
None Praity
1bit
8bit
S
MEASURMENTS MAPPING ADDDRESS
IR 3928
IY 3942
IB 3956
VRY 3924
VYB 3938
VBR 3952
KW 3902
KVAR 3904
PF 3906
FREQUENCY 3914
Value features
Based on primary value of CT & PT
SATEC E172E
Value Features* Scaling
DATA FORMATE Function
MIN MAX MIN MAX
REAL32_LW_HB 3 0 144 0 4.29E+09
REAL32_LW_HB 3 0 144 0 4.29E+09
REAL32_LW_HB 3 0 144 0 4.29E+09
REAL32_LW_HB 3 0 158.4 0 4.29E+09
REAL32_LW_HB 3 0 158.4 0 4.29E+09
REAL32_LW_HB 3 0 158.4 0 4.29E+09
REAL32_LW_HB 3 -460 460 -1.00E+09 1.00E+09
REAL32_LW_HB 3 -460 460 -1.00E+09 1.00E+09
REAL32_LW_HB 3 -1 1 -2.15E+09 2.15E+09
REAL32_LW_HB 3 45 55 0 4.29E+09
1
1
1
0.001*
0.001*
0.001*
1.00E-06
1.00E-06
1
1
ommunication Paramenter
9600
None Praity
1bit
8bit
SATEC P130M INTEGRATION
kV/Amp
PT PRIMARY 66 PT SECONDARY
CT PRIMARY 1200 CT SECONDARY
MIN MAX MIN ACQ MAX ACQ A1
CURRENT 0 1200 0 9999 0.240024002
VOLTAGE 0 79.2 0 9999 0.008640864
POWER -622.08 622.08 0 9999 0.124428443
PF -1 1 0 9999 0.00020002
FREQUENCY 45 65 0 9999 0.0020002
ENERGY -5.00E+09 5.00E+09 0 1.00E+09 0.001
NOTE: IF I AM KEEPING THE B COEFFICIENT FOR ENERGY VALUES I AM NOT GETTING THE VALUES, IF ZERO I AM G
9B1=0
O/9999B1=0
T RATIO/9999)B1=0 * No Modbus Address available for Line Voltage. Use the the multipication factor 1.732, for Line Voltage.
RATIO)(144*PT RATIO)]/100
Acquisition
MODBUS Function 7
Mappring address 0
Size to read 0
frame length 256
Scaling
Co-efficient
MAX
2000 1
2000 1
2000 1
10000 1
10000 1
10000 1
5.00E+09 1.00E-03
5.00E+09 1.00E-03
5.00E+09 1.00E-03
1 1
55 1
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
Communication Paramenter
Baud Rate 9600
Parity Even Praity
Stop bit 1bit
nb bits per char 8bit
MEASURMENTS MAPPING ADDDRESS
IR 150
IY 152
IB 154
VRY 134
VYB 136
VBR 138
KW 100
KVAR 108
KVA 124
PF 116
FREQUENCY 156
MWH (IMP) 158
MWH (EXP) 166
MVAH (IMP) 160
MVAH (EXP) 168
LG MFM - L5110
Value Features* Zero Value Scaling
DATA FORMATE Function
MIN MAX Suppression\ MIN
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -1 1 0.3 -1
REAL32_LW_HB 3 45 55 0.3 45
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
Acquisition
MODBUS Function 7
Mappring address 0
Size to read 0
frame length 256
Scaling
Co-efficient
MAX
2000 1
2000 1
2000 1
10000 1
10000 1
10000 1
5.00E+09 1.00E-03
5.00E+09 1.00E-03
5.00E+09 1.00E-03
1 1
55 1
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
Communication Paramenter
Baud Rate 9600
Parity Even Praity
Stop bit 1bit
nb bits per char 8bit
MEASURMENTS MAPPING ADDDRESS
IR 150
IY 152
IB 154
VRY 134
VYB 136
VBR 138
KW 100
KVAR 108
KVA 124
PF 116
FREQUENCY 156
MWH (IMP) 158
MWH (EXP) 166
MVAH (IMP) 160
MVAH (EXP) 168
LG MFM - L5410
Value Features* Zero Value Scaling
DATA FORMATE Function
MIN MAX Suppression\ MIN
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -1 1 0.3 -1
REAL32_LW_HB 3 45 55 0.3 45
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
Acquisition
MODBUS Function 7
Mappring address 0
Size to read 0
frame length 256
Scaling
Co-efficient
MAX
2000 1
2000 1
2000 1
10000 1
10000 1
10000 1
5.00E+09 1.00E-03
5.00E+09 1.00E-03
5.00E+09 1.00E-03
1 1
55 1
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
Communication Paramenter
Baud Rate 9600
Parity Even Praity
Stop bit 1bit
nb bits per char 8bit
MEASURMENTS MAPPING ADDDRESS
IR 150
IY 152
IB 154
VRY 134
VYB 136
VBR 138
KW 100
KVAR 108
KVA 124
PF 116
FREQUENCY 156
MWH (IMP) 158
MWH (EXP) 166
MVAH (IMP) 160
MVAH (EXP) 168
LG MFM - AE 9000
Value Features* Zero Value Scaling
DATA FORMATE Function
MIN MAX Suppression\ MIN
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 2000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 0 10000 0.3 0
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 0.3 -5.00E+09
REAL32_LW_HB 3 -1 1 0.3 -1
REAL32_LW_HB 3 45 55 0.3 45
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
REAL32_LW_HB 3 -5.00E+09 5.00E+09 - -5.00E+09
Acquisition
MODBUS Function 7
Mappring address 0
Size to read 0
frame length 256
Scaling
Co-efficient
MAX
2000 1
2000 1
2000 1
10000 1
10000 1
10000 1
5.00E+09 1.00E-03
5.00E+09 1.00E-03
5.00E+09 1.00E-03
1 1
55 1
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
5.00E+09 1.00E-06
Communication Paramenter
Baud Rate 9600
Parity Even Praity
Stop bit 1bit
nb bits per char 8bit
H
MEASURMENTS MAPPING ADDDRESS
AC HEALTHY 40016
AC TEMPERATURE 40011
Acquisition
MODBUS Function
Mappring address
Size to read
frame length
HITACHI_SPACEMAKER
Value Features* Scaling
DATA FORMATE Function
MIN MAX MIN
UINT16 3 0 1 0
UINT16 3 0 800 0
kV/Amp
PT PRIMARY 66 PT SECONDARY
CT PRIMARY 1200 CT SECONDARY
MIN MAX MIN ACQ MAX ACQ A1
CURRENT 0 1200 0 9999 0.240024002
VOLTAGE 0 79.2 0 9999 0.008640864
POWER -622.08 622.08 0 9999 0.124428443
PF -1 1 0 9999 0.00020002
FREQUENCY 45 65 0 9999 0.0020002
ENERGY -1 1 0 9999 0.00020002
9B1=0
O/9999B1=0
T RATIO/9999)B1=0 * No Modbus Address available for Line Voltage. Use the the multipication factor 1.732, for Line Voltage.
RATIO)(144*PT RATIO)]/100
0.0066
0.0066
0.0066
0.03
0.03
0.03
1.00E+04
0.00343
0.00343
0.00343
0.001
RISH M