Id> 0.30In
Id>>
Relay Setting Slope-1
Slope-2
Sensitivity Test:
Current Pickup Breaker Signal
Phase Remarks
Injected Current Tripping Relay Panel Control Panel
Side 1 0.392A 0.392A OK 87T Operated
R Element
Side 2 0.262A 0.262A OK 87T Operated
Side 1 0.392A 0.392A OK 87T Operated
Y Element
Side 2 0.262A 0.262A OK 87T Operated
Side 1 0.392A 0.392A OK 87T Operated
B Element
Side 2 0.262A 0.262A OK 87T Operated
Slope Test:
High
Current Slope Actual
Phase I Diff I Rest % Error Set Remarks
Injected Given Slope
Test
Side 1
R Element
Side 2
Side 1
Y Element
Side 2
Side 1
B Element
Side 2
Add additional table if necessary
Tested By Checked By
N
Element
Tested By Checked By