Professional Documents
Culture Documents
Metal Detection
Table of Contents
Introduction .............................................................................................. 1-1
Copyright Notice .........................................................................................................................1-3
Aims of this Manual ....................................................................................................................1-3
IMPORTANT NOTICE ................................................................................................................1-4
Operating Principles ...................................................................................................................1-5
Vibration Signals .................................................................................................................1-5
Product Effect ......................................................................................................................1-5
Phase Control......................................................................................................................1-5
Features .....................................................................................................................................1-7
Product Numbers ................................................................................................................1-7
Timer Groups ......................................................................................................................1-7
Timer Types ........................................................................................................................1-7
Product Signal Cancellation (PSC) (option) ........................................................................1-7
Automatic Tracking (option).................................................................................................1-7
Inverse Detection ................................................................................................................1-7
Performance Validation Routines — PVR ...........................................................................1-7
Serial Communications........................................................................................................1-7
List of Abbreviations ...................................................................................................................1-8
Installation................................................................................................. 3-1
Warnings and Cautions...............................................................................................................3-3
Safety Instructions ......................................................................................................................3-4
Detector Precautions ..................................................................................................................3-5
Handling Instructions ..................................................................................................................3-8
Installing the Metal Detector .......................................................................................................3-9
Mechanical Installation................................................................................................................3-9
Metal Free Zone (MFZ)........................................................................................................3-9
Positioning the Detector’s Support Framework ...................................................................3-10
Positioning the Detector ......................................................................................................3-11
Electrical Installation ...................................................................................................................3-12
Electrical Connections .........................................................................................................3-12
General ................................................................................................................................3-12
Power Lead Connection ......................................................................................................3-12
Wiring and Circuit Breaker Details.......................................................................................3-13
Cable Installation .................................................................................................................3-13
Location and Layout of the Detector Terminals ...................................................................3-14
Removing the Power Supply Box Lid ..................................................................................3-14
Supplementary Information.........................................................................................................3-16
Magnetic Loops ..........................................................................................................................3-16
ATEX ..........................................................................................................................................3-17
1 Introduction
This chapter contains important information about the
the Metal Detector which must be read before the
detector is installed. This chapter also describes the
features of the detector as well as the basic operating
principles. It covers the following topics:
Features 1-7
Copyright Notice
Copyright © Mettler-Toledo Safeline Limited, 2009.
No part of this document may be reproduced, or translated, in any form, electronic or otherwise without the prior
written consent of SAFELINE limited. Neither SAFELINE nor its Agents will be liable for incidental or consequential
damage in connection with the use of this document. SAFELINE reserve the right to change the contents or form of
this manual at any time without prior notice having been given. This detector must only be used for the express
purposes as advertised by SAFELINE and as referred to in this and other SAFELINE approved literature.
If the document was purchased directly from SAFELINE, or the supplier is unavailable at the supplier address
given, then contact SAFELINE directly via the address given on the title page of this document.
If the owner of the manual has any comments or suggestions as to the form, content or presentation of this manual
then they should write their suggestions and send them to the Technical Department at the address given on the
title page.
For further information or to order copies of this document contact SAFELINE at the address shown on the title
page of this document, quoting the reference number given on the title page.
Note: An upgrade service is available from SAFELINE, at a fee, which will upgrade older detectors to the latest
specification, where possible. Please contact your supplier’s technical departments for information on this service.
Remember to have your serial number ready when making the call.
IMPORTANT NOTICE
1 Limitations of Use
Using metal detection inspection equipment is an important tool in minimizing the risk of shipping product from your
facility containing metal contaminants which could eventually pose a risk to a consumer.
Using this or any other metal detector inspection unit does not guarantee that all contaminated products will be
identified and rejected from the product flow. Metal contaminant orientation, geometry and composition will
influence the minimum size of contaminant that can and will be detected. In addition the metal detector settings,
used to suppress unwanted signals from the product under inspection or the system vibration, may also suppress
and in some instances prevent the detection of contaminant signals which are larger than the minimum detectable
ball size.
If any test shows a risk of either continuous or intermittent malfunction of the metal detection inspection system
procedures to isolate and either discard or re-inspect the product which may contain contaminants must be
initiated.
Ensuring that product containing metal contaminants do not leave the facility where the metal detection equipment
is installed and applied is therefore outside the reasonable control of SAFELINE.
Even though this equipment was cleaned prior to shipment, SAFELINE recommends you re-clean it with an
appropriate cleaning agent before using it for the first time.
Operating Principles
SAFELINE detectors utilise a low power, high Product effect signals can be represented
frequency, magnetic field coil system which has the diagramatically as a signal with amplitude and phase in
ability to sense minute disturbances created by metal the same manner as the signals from metallic particles.
particles. A metal particle passing through the aperture
of the detector will create changes in the magnetic field
inside the detector. Phase Control
The changes in the magnetic field will generate The SAFELINE metal detector contains a phase
electrical signals in the coil system which can be control circuit which discriminates between the wanted
characterised by the parameters Phase and Amplitude. signals from metal particles and the unwanted signals
from vibration and product effect, i.e. it maximises the
The amplitude/size of the signal is related to the size of detectors response to metal particles whilst minimising
the metal particle passing through the field, the larger the effects of the unwanted signals.
the metal particle the greater the amplitude of the
signal. Probably the simplest way of reducing the vibration or
product effect signals would be to adjust the sensitivity
Different types of metal generate signals which differ in control. However, the sensitivity control would reduce
phase angle. The term phase angle is a comparative the sensitivity to all signals, metallic signals, vibration
term and is a measurement of phase relationship and product signals alike.
relative to some reference
What is required is a more selective adjustment that
will discriminate between different signals. The phase
Vibration Signals control does this, it selectively reduces the signals from
vibration and product effect with minimal effect on the
Great care is taken in the design and manufacture of metallic signals.
the SAFELINE detectors to minimise the effect of
vibration on the performance of the detectors. However A comparison can be made with a domestic Hi-Fi
mechanical disturbances do create vibration signals system. The volume control of the Hi-Fi increases or
from the coil system. decreases the amplitude of all signals just like the
metal detector sensitivity control. The bass control of
Vibration signals can be represented in the same way the Hi-Fi selectively controls the low frequency notes
as signals generated by metal particles i.e. a signal only. This is similar to the phase control circuit,
with amplitude and phase. however the phase control circuit in a SAFELINE metal
detector is very much more selective.
The vibration signal is used as a reference when
comparing the phase angle of signals from the coil Signals from the detector coil system can be
system. For example, if we say stainless steel has a represented as shown in Figure 1-1.
particular value of phase angle, the phase angle is the
angle relative to vibration. Reasons for selecting
vibration as the reference phase will become apparent. Amplitude
Vibration Vibration
Product Effect
Ferrous Stainless
Metal detectors are used to inspect all types of Steel Non-Ferrous
products e.g. food, pharmaceuticals, plastics,
chemicals and many others.
The characteristic of the phase control circuit is shown In general if operating the detector with any product
in Figure 1-2 This shows the position of the phase which exhibits a product effect, the
control aligned to minimise the unwanted vibration Non-Ferrous/Stainless Steel sensitivity will decrease.
signal. All signals which break through the phase
control characteristic (the shaded area) will trigger the
detector. From this it can be seen that the amplitude of
the unwanted vibration signal would have to be
increased to trigger the detector.
Amplitude
Vibration Vibration
Ferrous Stainless
Steel Non-Ferrous
Amplitude
Product
Vibration Signal Vibration
Ferrous Stainless
Steel Non-Ferrous
0
200 400 600 800 0
1000 1200 1400 1600 0
0 90 180
Phase Value
Features
Product Numbers
Product Signal Cancellation (PSC) (option)
When installed on a product line there may be many
different types of product passing through the metal Note: This product does not use this feature.
detector at different times.
To get the maximum performance from your metal Automatic Tracking (option)
detector these different products may require different Note: This product does not use this feature.
settings for sensitivity and the phase control. For this
purpose SAFELINE metal detectors can store settings
for up to 21 products. These settings may then be Inverse Detection
recalled by the operator, as required, by selecting a Note: This product does not use this feature.
specific ‘product number’ for each product name in the
detector.
Performance Validation Routines — PVR
Timer Groups Two modes of detector operation, (QA Inspector mode
and QA Operator mode) help the user comply with ISO
Experience has shown that although there may be a 9001:2000, by ensuring that the metal detector system
need for up to 21 product settings for the sensitivity and is tested and operating to the user's specified quality
phase control, the type of reject mechanism used by assurance standards of performance.
the 21 products falls into one of a few groups.
SAFELINE metal detectors allow the engineer to set up Information may be transferred directly from the metal
a reject mechanism/timer type once and associate this detector to paper by using a printer. Refer to Chapter 5
with a timer group. for sample printouts.
Three different timer groups A, B and C are supported Timed requests for a check of the metal detector can
by SAFELINE metal detectors. Individual product be set.
numbers can then be assigned to one of these timer Logging of rejects and logging of changes in the
groups. This means that the reject timers do not have detectors settings can be set and these can be printed
to be set 21 times - just once for each group. In out on a timed basis e.g. for companies operating 8
general, only one timer type and setting will be required hour shifts, once every 8 hours.
for most applications.
Serial Communications
Timer Types
The metal detector has a serial communication port.
A wide range of timer types and settings are available The link is a two wire serial connection to allow
to the engineer. information to be transferred to and from the metal
Five different timer types are supported by SAFELINE detector. Refer to the Serial Communications chapter
metal detectors, each type has programmable settings. for more information.
List of Abbreviations
This operating guide uses the following abbreviations:
A Ampere
AC Alternating Current
AH Aperture Height
ATEX Atmospheres Explosibles
CMD Command
CRC Cyclic Redundancy Check
DC Direct Current
Fe Ferrous
ft Feet
Hz Hertz
k Kilo (103)
kHz KiloHertz
kV Kilovolt
kΩ KiloOhm
LCD Liquid Crystal Display
LED Light Emitting Diode
m metre
mA milliAmpere
MFZ Metal Free Zone
MHz Mega Hertz
min minute
mm millimetre
ms millisecond
non-Fe Non-ferrous
NPN Negative-Positive-Negative (type of transistor)
PCB Printed Circuit Board
PNP Positive-Negative-Positive (type of transistor)
PSC Product Signal Cancellation
PVR Performance Validation Routines
QA Quality Assurance
RC Reject Confirmation
RCU Reject Confirmation Unit
RMS Root Mean Square
V Volt
VA Volt Amps
W Watt
ºC Degree Celsius
ºF Degree Fahrenheit
2 Technical Specifications
This chapter presents the technical specifications of
the Metal Detector.
Technical Specifications
Technology
Temperature Range
High frequency, low powered, electromagnetic coil
system — monitored and controlled by a Storage: -10ºC to +50ºC (14ºF to 122ºF)
microprocessor system.
Operating: -10ºC to +45ºC (14ºF to 113ºF)
Units Fast
Environmental Protection
Min Max
m/min/mm of
GF, Painted & Stainless Steel: IP65, NEMA 12
0.05 7.5
aperture diameter
Pipeline, Stainless Steel: IP66, NEMA 4X
ft/min/inch of
4 600
aperture diameter
Throat, Painted: IP65, NEMA 12
Higher and lower speeds are available on request.
Throat, Stainless Steel: IP66, NEMA 4X
For connection to TN (EN60950-1:2001) power Switched live and neutral, non-switched earth. Not
distribution systems only. For connections to other internally fused.
power distribution systems please contact your
Maximum current: 1 A
supplier.
Maximum voltage: 250 Volts A.C., or 30 Volts D.C. RS232 Serial Communications
(non-inductive)
Two communication ports COM1 and COM2 are
available from within the power unit enclosure.
RCU/System Fault Relay (Optional)
Voltage levels as per RS232 standard, typically ± 9
Volt-free changeover contacts that operate when the volts.
Reject Confirmation Unit signals a reject fault.
Baud rate: 9600
Contact rating: see Reject Relay.
Data bits: 7 or 8
Maximum current: 100 mA COM1: 2 or 4 wire control for use with printer
(Hardware handshaking is only possible with 4 wire
control).
Fault/Detector Active Output
COM2: 2 wire control for communications with metal
Output that operates if a fault occurs in the metal detector.
detector or if the detector is inactive.
Note: This product does not use this feature. Non spherical objects such as wires will exhibit an
orientation effect, i.e. they can be more easily detected
in certain axis. If the diameter of the wire is less than
Speed Sensor Requirements the spherical sensitivity setting the sample may not be
detected in all orientations.
Note: This product does not use this feature.
Sensitivity Ratios
Dependent on frequency of coil system e.g. at
300 kHz.
Sensitivity Gradient
Less than two diameters.
Timer Ranges
3 Installation
This chapter contains information about how to install
the metal detector. Additionally, there is important
safety information which must be read prior to
installation. It covers the following topics:
WARNING
THE ABOVE CAPTION IDENTIFIES AN OPERATING PROCEDURE OR PRACTICE THAT COULD RESULT IN
PERSONAL INJURY OR DEATH.
! CAUTION
The above caption identifies an operating procedure or practice that could result in damage, or
destruction, of the detector, the process or its surroundings.
The above caption is used to draw the reader’s attention to a note of extra importance.
! CAUTION
This manual must always be kept with the detector for the whole of its operating life.
WHEN THIS CAPTION IS SHOWN ON THE EQUIPMENT IT IS USED TO INDICATE THE POSSIBILITY OF
ELECTRIC SHOCK.
!
WHEN THIS CAPTION IS SHOWN ON THE EQUIPMENT, IT IS USED TO INDICATE THAT THE MANUAL
MUST BE CONSULTED BEFORE PROCEEDING.
Safety Instructions
Most companies have a code of practice for their employees which is designed to ensure their safety in the working
environment. When new equipment is introduced it is important that operators, maintenance engineers and
supervisors are aware of the potential hazards.
The following guidelines must be followed by any person concerned with the operation, installation or handling of
the detector to ensure correct operation and to avoid any damage to the detector or to the person concerned.
WARNING
The equipment should only be used in accordance with the instructions given herein. Failure to comply with these
instructions may lead to the protection provided by the equipment becoming impaired. SAFELINE will not be liable
for incidental or consequential damage if the equipment is not installed in accordance with the instructions given.
WARNING
On no account should any of the electrical panels of your detector be opened by anyone other than a qualified
electrical engineer. Voltages in excess of 30 volts RMS or 50 volts DC. can, in certain circumstances be lethal.
When working on electrical or electronic equipment always follow current health and safety practices and observe
all other applicable regulations.
! CAUTION
For correct operation and to prevent any damage to the detector follow the instructions given in this document
under the heading 'Installation'.
! CAUTION
In accordance with EN 61010-1:2001 this equipment has been designed to operate safely under the conditions as
described in the Technical Specifications chapter.
Detector Precautions
During installation and operation of the detector the following points must be considered. Failure to do so may
result in difficulties of operation, degradation in the performance or damage occurring to your detector.
2 Power Source
• It is recommended that the power source should be taken from a source which supplies only low power
equipment.
• It is recommended that the detector should not be connected to power sources which are supplying
varying current loads, e.g. Inverters, variable-speed drives etc.
• It is recommended that the power source for the detector should be connected via an independent spur.
• The power source for the detector should be fitted with an isolation switch and the appropriate circuit
breaker and/or fuse.
3 Electromagnetic Interference
• It is recommended that the detector should not be installed in close proximity to any devices which may
emit electromagnetic interference e.g. Radio transmitters.
• Ensure all Invertors and variable-speed drives in the proximity of the detector are installed in full
accordance with their manufacturers instructions.
• Avoid placing any cables from Invertors, variable-speed drives etc. in close proximity to the detector or any
of the detector cables.
• In particular take care to avoid placing the detector in the proximity of any equipment that generates
electromagnetic interference in the same frequency range as the detector.
9 Orientation of Contaminants
• Metal detector sensitivity is expressed as the diameter of the smallest spherical object which can be
detected. (i.e. diameter of a ball).
• Sensitivity to non-spherical objects of the same material (e.g. wire fragments) will vary according to the
orientation of the object as it passes through the detector aperture. If the diameter of the object is less than
the stated spherical sensitivity the object may not be detected.
12 Static Precautions
• Where a metal detector is to be fitted on a conveyor or other support system, it is necessary to bond all
metal work to ground.
Handling Instructions
The detector does not contain any exposed noxious or dangerous substances.
When transporting and handling the detector, damage may result if any lifting equipment (i.e. sling, cable assembly
or by hand) passes through the aperture of the detector. The diagrams below show the incorrect way and the
correct way to lift and support the detector during transportation.
SAFELINE does not recommend the lifting or supporting of the detector by a person. Always use suitable lifting or
supporting apparatus. SAFELINE will accept no liability for personal injury caused by attempting to lift or move the
detector without the aid of a mechanical apparatus.
If supporting the detector in a sling or other lifting apparatus always ensure that the detector is securely held and is
not likely to unbalance during lifting.
Mechanical Installation
Metal Free Zone (MFZ)
To achieve optimum metal detector performance, an To Calculate the MFZ:
area surrounding the aperture of the detector known as
the MFZ should be kept free of metal. T-Series
The size of the MFZ will be dependent upon the • MFZ = 0.35 x AD for stationary metal.
Aperture Diameter (AD), the type of detector and the • MFZ = 0.5 x AD for moving metal.
operating sensitivity.
LZ-Series
G-Series, T-Series and LZ-Series products utilises
SAFELINE’s patented technology to minimise the MFZ, • MFZ = Zero
enabling them to be installed in extremely restricted
The MFZ requirements for the G-Series and LZ-Series
spaces. This does not, however, apply to any L-Series
metal detectors are covered in the documentation for
products.
Gravity Fall (GF) and Pipeline (LZ) systems and are not
Stationary metal may be positioned closer to the dealt with independently in this manual.
detector than moving metal. MFZ guidelines for these
Please consult the product data sheet for the MFZ of
detectors are shown in Figure 3-1.
other types of metal detector.
AD
MFZ
MFZ
best performance: 8
9
• Insulate/isolate all items bolted to the frame (e.g. 5
guards) using non-conducting insulators. 2
6 10
• Where applicable, mount the detector to its support 3 11
framework using the four plastic insulation sets
supplied with the detector. See Figure 3-2, Figure
3-3 and Figure 3-4.
• Avoid passing metal conduit or electrical cables
4
through the metal free zone or near the aperture of
the metal detector. Figure 3-3 Typical T-Series Installation
See the Magnetic Loops section on page 3-16 for the
theory behind the construction of the metal framework. Key
1 Funnel
2 Earth bonding wire
1 3 Metal supports
4 Thru-put tube
2 5 Earth strap
6 Head to thru-put tube adaptor
3 7 Insulating plate
4 8 Top hat insulator
9 Fixing bolt
10 Head mounting block (plastic)
5 11 End Plate
7
2
3 1
6 6
Key
1 Thru-put tube
2 Metal detector
3 End plate
4 Frame metalwork Figure 3-4 Typical L/LZ-Series Installation
5 Reject Housing
6 Power supply and control module Key
7 Reject housing inspection cover 1 Thru-put tube
8 Adjustable feet 2 Metal detector
3 End plate
4 Power supply and control module
5 Adjustable feet
6 Frame metalwork
Electrical Installation
WARNING
Key
1 Metallised prongs provide screen termination
2 Main body of gland
Location mark on cable, lined up with outer
3
face of nut
4 Nut (torque = 5.5nm)
Key
1 Terminal block
2 Live wire (L)
3 Neutral wire (N)
4 Protective earth wire (G/E) marked
5 Sheath clamp
6 Conclamp and ferrite sleeve assembly
7 Power lead
Location and Layout of the Detector Terminals Removing the Power Supply Box Lid
Access to the detector terminals is gained by removing 1) To remove the power supply box lid, remove the
the power supply box lid, as detailed in the next four screws.
section. Once the power supply box lid has been
2) Raise the power supply box lid.
removed, the terminals can be accessed.
3) Lift the power supply box lid completely away from
The layout of the terminals on the Power Supply
the power supply box.
Connection PCB is shown in Figure 3-8, Figure 3-9 and
Figure 3-10. To refit the power supply box lid, ensure that the seal
around the box lid is in place and undamaged then
carry out the above procedure in reverse order.
WARNING
2 1
The following procedure should only be carried out
by qualified SAFELINE personnel or qualified
SAFELINE agents.
45 46 47 48 49 50 51 52 53 54 55 56
1
2
3 4
5
6
7
WARNING
8
9 10 11 12 13 14 15 16 17 18 Layer 20
29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
Ensure all power has been disconnected from the
detector before attempting to work on any
19
1 2
57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74
3 4
Key
Fuse F1: 3.15 A (T)
(On the power supply module underneath the
1
connections board)
NOT A USER SERVICABLE PART
2 Switch Sw1
3 Fuse: 1.0 A (T) or Electronic Fuse
4 Optional Reject-Confirmation-Unit Circuit Board
Key
1 Module
2 Power Supply Connection PCB
3 Mains cable
4 The Power Lead Connection, see Figure 3-6
L Spare
45 46 47 48 49 50 51 52 53 54 55 56
Power Input N 15 V Pack Sensor *
2
+15 V
E 0V
3
E 0/1 Switch Output
4
Switched Power
L Spare
5
Output
N 15 V
6
+15 V Speed Sensor *
7
0V
Output
8
9 10 11 12 13 14 15 16 17 18 19 Spare
Reject Relay
15 V +15 V
0V RCU Sensor
Output
N.C.
Red
29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
Black
White
Relay 2 Blue
Brown
Purple
Spare
Latch Yellow Detector Head
20 21 22 23 24 25 26 27 28
57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74
GND
CTS
Yellow/Blue
Fault Det/Active
TXD
Screen
Yellow/Red
Red/Black
QA Overdue
RXD
Red/Brown
Blue/Black
White/Blue
White/Red
Orange/Blue
Comms
Port 1
Supplementary Information
Magnetic Loops
The design and Construction of the metal detector
support framework can influence the performance of
the detector.
ATEX
ATEX Directive (Applicable only to G-Series and ATEX System Label
T-Series detectors, and only if the ATEX Option is
Ordered)
SAFELINE
This product complies with ATEX Category 2D, zone Metal Detection
21 requirements.
System Identifier
A static hazard may exist: do not clean non-metallic Montford St. Year of Manufacture
Salford
parts with a dry cloth. England Model
System Rating IP Rating
Ensure torque setting on fixings highlighted below
conform to the values stated in the Technical Voltage/Spannung/ 100 - 240 VAC
Tension/Voltaje
Specification section. Max Current 1A
Frequency/Frequenz 50/60 Hz
Do not open any electrical enclosures when product is Fréquence/Frecuencia
present.
Max surface temp/ Maximale
oberflächentemperatur/ Température
Regular inspection of plastic and gasket materials
o
maximum de surface/ Temp. superficial max. 79 C
ATTENTION CAUCION
Voir le manuel Le refiere a manual
avant tout cablage por conection detalla
A static hazard may exist - do not clean non -metallic parts with a
dry cloth
Es gibt gegebenfalls Probleme mit statischen Aufladungen - Bitte
nicht-metallische Teile nicht mit trockenen Tüchern o.ä. reinigen
Figure 3-11 ATEX Fixing Bolts Figure 3-13 Static Warning Label
Key
ATEX Enclosure Warning Label
Power Supply Lid and Module
1 Cover Fixing Bolts
Warning Achtung
Detector Head Endplate Fixing
2 Do not open when Nicht Bei Anstehender
Bolts energised or when an Spannung Oder Explosiver
3 EX Label - see Figure 3-12 explosive dust ÖFfnen
atmosphere is present
Precaucion Attention
No abrir bajo tensión eléctrica Ne pas ouvrir sous
conectada , o cuando una tension ou en présence
atmosfera de polvo deflagrante d’une atmosphère
esté presente explosive
4 Operating Instructions
This chapter contains information on how to set up and
operate the Metal Detector. It covers the following
topics:
On the LCD a small pointer may appear adjacent to A small cursor bar will appear under the active digit on
the soft key. This indicates that a particular parameter the LCD display when a parameter is available for
can be changed. adjustment. For example: 1 2 3 4
If the parameter to be changed is a number and the One press of the cursor move key will move the cursor
appropriate soft key is pressed the pointer will now bar one step to the left. For example: 1 2 3 4
point inwards towards the number to be adjusted and a
Combined use of this key and the Up/Down keys will
cursor bar appears under the digit to be changed.
enable adjustment of all the digits.
(Refer to Changing Numeric Values for further
Note: This key will only operate when the cursor bar is
information).
visible on the LCD display.
If the parameter to be changed is not a number but
requires the user to make a choice, i.e. ON or OFF, Up/Down Keys
YES or NO the current selection will be indicated by a Use of these keys will increase or
flashing marker on the display. decrease the value of a particular digit.
Note: These keys will only operate when the cursor bar
is visible on the LCD display.
Security Key
When pressed in Running mode it will bring
up the ENTER SECURITY CODE display and
is the first step to gain access into other
modes.
ENTER Key
Used to enter data into the computer
memory. For example when changing the
sensitivity on the display it is necessary to
press the ENTER key to store the new value
in the computer memory.
RECALL Key
Use this key to scroll backwards to the previous
RECALL
display page in the menu.
SENS.###
RECALL
ETC PHASE ###.##
RECALL
1 2 3
3 2 4
Key
1 Security Key
Figure 4-3 Changing Numeric Values
2 Move Up/Down Key
3 ENTER Key
Key
The instructions below detail how to enter a security 1 Soft key
code. 2 Move Up/Down Key
3 Move Cursor Left Key
1) Press the SECURITY key. 4 ENTER Key
2) Use the Up and Down keys to alter the digit the If is not visible the value of that parameter cannot be
cursor is underneath. changed in the current mode.
3) When the correct value is showing on the digit Note: If the adjustable parameter is on the left side of
press the ENTER key. the display it will be indicated by which will change
to when selected.
4) The cursor will move one position to the right and
the entered digit will be replaced by an asterix To change the numeric value of a particular setting use
character, *. the following procedure.
5) Repeat steps 2) to 4) for all four digits. 1) Enter security code, and press the ETC soft key
until the correct page is shown.
6) When the final digit is entered the detector will
either: 2) Press the soft key to be adjusted. will now point
inwards towards the parameter and a cursor bar
a Go to the first display of the operating mode will appear under the first digit of the number.
whose security code was successfully entered.
3) Press the Up/Down keys and adjust the digit to the
or required value.
b Return to the Running Mode display if an 4) Press the cursor move key to move the cursor bar
incorrect security code was entered. to the next digit.
Note: Default values for the security codes can be 5) Repeat step 3).
found in the Introduction part of the Security Setup 6) Repeat steps 3) and 4) for each digit to set the
section, later in the manual, and at the start of the required value.
relevant sections within this chapter.
7) Press the key to store the new value in
memory.
Before attempting to use the ‘guides' the operator 2) Product Number Settings Guide
should read the following:
The detector has the ability to store settings for 21
1) The Introduction, Chapter 1. different product numbers. Each product number
contains a group of settings which are set to optimise
2) The Control Panel, page 4-2. the detector performance for a particular product. This
3) The Page Display System, page 4-3. guide takes the user through the setting up of this
group of settings for particular product types.
4) Entering Security Codes, page 4-4.
5) Changing Numeric Values, page 4-4. 3) Performance Validation Guide
All of the items below may be set whilst product All of the following items may be set from the Engineer
number 0 is selected as the current product number. Mode of operation.
2) Set Date and Time on page 4-32. In the majority of cases there will be no need to adjust
Set today’s date and the current time. the following items. The following items are shown here
for completeness.
3) Reject Inhibit on page 4-29 and page 4-31.
7) Detection Buzzer on page 4-31.
If you want to prevent the reject device activating
whilst setting up the detector. XT1.02 & Higher or Set whether you want the internal buzzer to sound
XT1.01 and lower XT1.00. at detection.
Set up the detector to the vibration characteristics If you are using the reject checking facilities of the
of your system. detector.
5) Reject Timers and subsequent timer sections on 9) Boost Mode on page 4-32.
page 4-60. At (or near to) full sensitivity, a further 20%
Set up the required timer groups to the appropriate sensitivity improvement may be possible.
timer types and settings.
The Product Number Settings Guide should be read All of the following items may be set from the QA
before this guide. Inspector Mode of operation.
The timer type will optimise reject operation. The worst case product effect condition is when the
greatest disturbance of the coil system/largest product
The phase control can play a dominant role in signal is experienced. This occurs when the coil
optimising the detectors performance for particular system condition changes from no product to
products. For many products, those which do not maximum product.
exhibit a product effect, the optimum setting of the
detector will be with phase set at around 0°. With those If the product is a continuous length/strip, the worst
products that exhibit a product effect, improved case product effect is given from the leading edge/face
detection sensitivity can be achieved by aligning the of the product. Product fully spanning the detector
phase control to minimise the product signal. head gives a much reduced signal.
When making adjustments to the detector for a For the majority of product types the worst case
particular product the user should ensure that product condition occurs the closer the product is to the faces
is passed through the detector aperture in its usual of the detector aperture.
manner to create a worst case product effect condition.
The technique of setting up to the worst case product
effect condition will ensure that no false product
rejections occur during normal running conditions.4
2) Enter the Supervisor/Engineer Access Code, 13) Now increase the phase setting in steps of 0.5º i.e.
page 4-4. 90.5º, 91º, 91.5º, 92º, etc. until the product effect
signal is reduced to a minimum and then just starts
3) Select lowest available product number (01 to 20), to increase again. Using the 0.1° digit adjust the
page 4-25. phase setting up and down until minimum signal
4) Set the Operating Frequency to HIGH (default i.e. the null point is found.
setting), page 4-22. 14) Although not always necessary a more precise null
point will be found by now using the 0.01º in a
5) Set the Power Drive to HIGH (default setting),
similar manner to the 0.1º digit as described in 13).
page 4-26.
Using the 0.01º digit adjust the phase setting up
6) Adjust the sensitivity so that the peak signal from and down until minimum signal i.e. the null point is
the product gives 3 to 4 bars on the LED bargraph found.
display. If the signal is very large, such that the
sensitivity control falls below a setting of 100 refer 15) The phase control circuit is now aligned to the
to note (1). product signal, next adjust the sensitivity so that
the product signal gives a maximum signal of 3 to 4
7) Press the ENTER key to store the new setting in green bars on bargraph display. If the sensitivity
memory. setting is less than 100 refer to note 1).
8) Set phase to 000.00º. 16) Check the susceptibility of the detector to vibration.
If unacceptable (i.e. system vibration is showing on
the bargraph) reduce the sensitivity until
acceptable.
Note 1
If during Manual Setup the sensitivity is adjusted below
100, then improved spherical performance may be
achieved by switching ‘Operating Frequency’ to LOW
and repeating the Manual Setup procedure, omitting
step 4).
Running Mode
Start of
Program Serial Number#####
Ver ###.### Model###.##
RECALL
Pressed
NAME..... PROD.##
ETC Safeline ltd
Prod.00 Sens.199
ETC Phase 000.00
SECURITY pressed
Go to one of the
Security Code
Protected Modes
Running Mode
Introduction
Please refer to Figure 4-4 for the complete sequence of
displays in the Running Mode.
1 3
NAME.......... PROD.##
ETC Safeline ltd
2 4
Figure 4-5 is the first display of the Running Mode, and Press the RECALL key to observe the following display,
is the display that the detector returns to when any of Figure 4-6, or press soft key 2 (ETC) to go to the next
the other operating modes are exited. display, Figure 4-7.
Model # # # # # # RECALL
Ver ###.##
The software version of your metal detector.
Pack Count
Note: This product does not use this feature.
1 3
Reject Count Pack Count ########
ETC Reject Count ####
This value shows the number of items that have been
2 4
rejected. It can be reset when in the Supervisor or
Engineer modes.
RECALL
Time
Figure 4-8 shows the current time and the time of the
next QA test.
1 3
Refer to the Engineer Mode for information on setting
Current Time ##:##
the current time on page 4-24. ETC Next QA Test ####
2 4
Refer to the QA Inspection Mode for information on
setting the Next QA Test time on page 4-48.
RECALL
Note: If no QA test is programmed, or the QA option is
not fitted, then ‘Next QA test ##:##’ will not appear.
PROD ##
This display shows the current product.
1 3
SENS ### Prod.00 Sens.199
This display shows the current sensitivity. ETC Phase 000.00
2 4
PHASE ### ##
This display shows the current phase. RECALL
1 3
Peak Hold ####
ETC hh:mm(#)####
2 4
RECALL
RECALL
NAME......... PROD.##
ETC Auto Setup
See
Automatic
Setup
SENS ###
ETC PHASE ###.##°
Operator Mode
Introduction
Please refer to Figure 4-13 for the complete sequence
of displays in the Operator Mode.
SENS
Press soft key 3 to change the Sensitivity value. Use
the cursor key and up and down keys to select a value 1 3
between 000 to 199. Press the ENTER key when the SENS ###
correct sensitivity is showing. ETC PHASE ###.##°
2 4
Note: At a sensitivity setting of 000 the metal detector
will still be able to detect very large pieces of metal.
RECALL
PHASE
Press soft key 4 to change the phase value. Use the
cursor key and up and down keys to select a value Figure 4-15 Sensitivity and Phase
between 0.00º and 180.00º. Note: This display is only available if operator access
Press the ENTER key when the correct phase is is set to Full.
showing only available on products 01 to 20.
NAME......... PROD.##
ETC Auto Setup
See
Automatic
Setup
SENS ###
ETC PHASE ###.##°
A Select Timer B
ETC Group C
Supervisor Mode
Introduction
Please refer to Figure 4-16 for the complete sequence
of displays in the Supervisor Mode.
SENS
Press soft key 3 to change the Sensitivity value. Use
the cursor key and up and down keys to select a value 1 3
between 000 to 199. Press the ENTER key when the SENS ###
correct sensitivity is showing. ETC PHASE ###.##°
2 4
Note: At a sensitivity setting of 000 the metal detector
will still be able to detect very large pieces of metal.
RECALL
PHASE
Press soft key 4 to change the phase value. Use the
cursor key and up and down keys to select a value Figure 4-18 Sensitivity and Phase
between 0.00º and 180.00º. Note: This display is only available if operator access
Press the ENTER key when the correct phase is is set to Full.
showing only available on products 01 to 20.
Operating Frequency
Note: This is only available on dual frequency heads.
HIGH
1 3
Press soft key 3 to make the current product number Operating Freq. HIGH
operate at the higher of the two frequencies. ETC LOW
2 4
LOW
Press soft key 4 to make the current product number
RECALL
operate at the lower of the two frequencies. The
currently selected frequency is indicated by a flashing
cursor.
Figure 4-19 Operating Frequency
Reject Count
This display shows the number of reject relay
operations. It does not show the number of detections
or the number of rejects. 1 3
Reject Count ####
RESET ETC RESET
Press soft key 4 to zero the Reject Count value. 2 4
RECALL
Pack Count
Note: This product does not use this feature.
1 3
Pack Count ########
ETC RESET
2 4
RECALL
See
TIMERS See Detection Buzzer ON
Setup TIMERS ETC OFF
Setup
A Select Timer B
ETC Group C See
TIMERS Reject Inhibit YES Versions XT1.00
Setup ETC NO and XT1.01
Inverse Detect YES
N/A
ETC NO
Reject Confirm
ETC
YES
NO
*
Automatic Tracking YES
ETC NO
N/A *
Reject Confirmation
ETC extn.time ###ms
*
Prod. Cancellation YES
ETC NO
N/A *
Boost Mode YES
ETC NO
Reject Count ####
ETC RESET
Language English
ETC
Pack Count ########
N/A
ETC RESET
ETC
Set Date
Set Time
*
Reject Inhibit YES Version
ETC NO XT1.02+
See
Printer Handshake
ETC
HW
SW
*
Vibration Setup VIBRATION
ETC Setup
* Optional
Engineer Mode
Introduction
Please refer to Figure 4-23 for the complete sequence
of displays in the Engineer Mode.
The Engineer’s mode gives access to all variables and
is used when first installing the metal detector or when Remember to record all settings on the Settings Sheets
making changes to setup characteristics. at the rear of the manual.
Various operating characteristics of the detector are
programmable and may be altered or configured to suit
the particular requirements of the application.
PROD ## RECALL
SENS
Press soft key 3 to change the Sensitivity value. Use
the cursor key and up and down keys to select a value 1 3
between 000 to 199. Press the ENTER key when the SENS ###
correct sensitivity is showing. ETC PHASE ###.##°
2 4
Note: At a sensitivity setting of 000 the metal detector
will still be able to detect very large pieces of metal.
RECALL
PHASE
Press soft key 4 to change the phase value. Use the
cursor key and up and down keys to select a value Figure 4-25 Sensitivity and Phase
between 0.00º and 180.00º.
Note: This display is only available if operator access
Press the ENTER key when the correct phase is
is set to Full.
showing only available on products 01 to 20.
Operating Frequency
Note: This is only available on dual frequency heads. HIGH
Press soft key 3 to select a product with no or small
This facility allows the performance of the detector to
product effect signal.
be optimised for different product types, and is
selectable for each product number. The choice of
LOW
setting, HIGH or LOW, depends on the size of the
product effect signal being produced by the product Press soft key 4 to select a product with large product
being inspected. effect signal.
Generally speaking, the HIGH setting will give The currently selected frequency is indicated by
improved spherical performance. flashing cursor.
Power Drive
This display allows the level of high frequency power HIGH
being fed into the coil system to be changed, and is Press soft key 3 to select the normal level of power
selectable for each product number. drive.
For a small number of applications where the product
LOW
being inspected has a large product effect signal, it
may be necessary to select the LOW power drive Press soft key 4 to select the reduced value of power
setting to reduce the sensitivity of the Detector. drive. The currently selected frequency is indicated by
flashing cursor.
For the majority of applications the HIGH power drive
setting will be used.
RECALL
! CAUTION
Inverse Detection
Note: This product does not use this feature.
1 3
Inverse Detect YES
ETC NO
2 4
RECALL
1 3
Automatic Tracking YES
ETC NO
2 4
RECALL
1 3
Prod. Cancellation YES
ETC NO
2 4
RECALL
Reject Count
This display shows the number of reject relay
operations. It does not show the number of detections
or the number of rejects. 1 3
Reject Count ####
RESET ETC RESET
Press soft key 4 to zero the Reject Count value. 2 4
Pack Count
Note: This product does not use this feature.
1 3
Pack Count ########
ETC RESET
2 4
RECALL
WARNING
NO
Figure 4-35 Reject Inhibit XT1.02 or Higher
Press soft key 4 for normal use.
Vibration Setup
Press soft key 3 to enter the Vibration Setup menu.
RECALL
1 3
Pack Sensor Setup
ETC
2 4
RECALL
Security Setup
Press soft key 3 to enter the Security Setup menu.
RECALL
Speed Setup
Press soft key 3 to enter the Speed Setup menu.
RECALL
1 3
Auto. Tracking Setup
ETC
2 4
RECALL
Detection Buzzer
ON
Press soft key 3 to turn on the Detection Buzzer, which
sounds when metal is detected. 1 3
Detection Buzzer ON
OFF ETC OFF
2 4
Press soft key 4 to disable the Detection Buzzer.
NO
RECALL
Press soft key 4 if the Reject Confirmation is not
required.
Figure 4-43 Reject Confirmation
Extension Time
This is the time taken for the external sensor to detect
that a contaminated package has been rejected. 1 3
Reject Confirmation
Figure 4-44 will only appear if YES was selected in the ETC extn. time ###ms
display Figure 4-43. For timer types tm3 and tm3G, 2 4
Extension Time is not used and Window Time is used.
Boost Mode
YES
Press soft key 3 to improve the sensitivity by 20% at a
sensitivity of 199. 1 3
Boost Mode YES
NO ETC NO
2 4
Press soft key 4 for normal sensitivity at 199.
RECALL
Language
Press soft key 3 to scroll through the languages
(including English).
1 3
The languages available are: English, French, Italian, Language English
Spanish, German, Dutch, Danish, Swedish, Japanese, ETC
Polish, Portuguese, Czech, Finnish and Turkish. 2 4
SET DATE
Press soft key 3 to set the date.
1 3
SET TIME SET DATE
Press soft key 4 to set the time. ETC SET TIME
2 4
YEAR
Press soft key 1 from Figure 4-48 to adjust the year. RECALL
Use the cursor key and up and down keys to select the
correct year. Press the ENTER key when the correct
year is set.
Figure 4-47 Date and Time
MONTH
Press soft key 3 from Figure 4-48 to adjust the month.
Use the cursor key and up and down keys to select the 1 3
correct month. Press the ENTER key when the correct #### YEAR MONTH ##
month is set. ETC DAY ##
2 4
DAY
Press soft key 4 from Figure 4-48 to adjust the day. RECALL
Use the cursor key and up and down keys to select the
correct day. Press the ENTER key when the correct day
is set.
Figure 4-48 Setting the Date
24 HOUR
Press soft key 3 from Figure 4-49 to adjust the hour.
Use the cursor key and up and down keys to select the 1 3
correct hour. Press the ENTER key when the correct 24 HOUR ##
hour is set. ETC MINUTE ##
2 4
Note: The clock uses the 24 hour format.
MINUTE RECALL
SW
RECALL
Press soft key 4 if a software handshake is required. If
this option is selected the detector uses X-ON X-OFF
flow control.
Figure 4-50 Printer Handshake
Refer to Chapter 5 for more information.
Automatic Setup
Introduction
The Automatic Setup feature may be used to Note: Automatic Setup will attempt to setup the
automatically set the following on products 1 to 20 (not detector in the currently selected Operating Frequency
product 0): setting. However there are two conditions where
Automatic Setup will change the currently selected
• Sensitivity 'Operating Frequency’ setting, these are:
• Phase 1) If 'Operating Frequency’ is set to HIGH, Automatic
• Frequency Setup will change this to LOW under large product
signal conditions.
The Automatic Setup feature is designed to make
setting up your metal detector as easy as possible by 2) If 'Operating Frequency’ is set to LOW, Automatic
requesting the operator to pass the product through the Setup will change this to HIGH under dry or very
aperture at specific times and NOT requiring the small product signal conditions.
operator to adjust any of the controls.
RECALL
RECALL
1 3
Automatic Setup Timed Out Display
Automatic setup
Figure 4-55 appears if no product was passed through timed out
the detector when requested. 2 4
RECALL
The correct setting of the phase will be one value which The phase control circuit is now aligned to the
will give minimum signal from the product on the product signal. Next, adjust the sensitivity so that
bargraph display, this is known as the "null point" the product signal gives a maximum signal of 3 to 4
setting. Changing the phase setting up or down in green bars on bar graph display.
value from this setting will increase the amplitude of the
signal. Note: When using the phase control to minimise
product signals the detector may become more
The correct setting of the sensitivity will be a value susceptible to vibration. The final setting of the
which gives a peak signal from the product of 3 to 4 sensitivity may be limited by vibration effects rather
bars on the LED bargraph display. When phase is at than product effect.
the null point described above.
6) Check the susceptibility of the detector to vibration,
1) Pass the product through the aperture in its normal if unacceptable (i.e. system vibration is showing on
manner to create a worst case product effect the bargraph) reduce the sensitivity until
signal, for more details refer to Notes On Passing acceptable.
Product Through the Detector on page 4-35.
7) Press the ENTER key to store the new settings in
2) Adjust the sensitivity so that the peak signal from memory.
the product gives a reading on the LED bargraph
display of approximately half full scale (i.e. 10
green bars), refer to Note 1 on 4-13).
3) To verify/optimise the "null point" set by the
Automatic Setup, increase the phase setting in
steps of 1º and at each step observe if the
amplitude of product signal indicated on the
bargraph display reduces. If an increase in product
signal is observed, then decrease the phase
setting in steps of 0.2º and at each step observe if
the amplitude of product signal indicated on the
bargraph display reduces.
For example if the Automatic Setup value is 90º,
and as the phase setting is increased there is a
clear reduction in signal as we change from 90º to
91º, and then from 91º to 92º the signal starts to
increase again, this indicates that the "null point" is
between 90º and 92º.
Vibration Setup
Introduction
This menu is used to set up the detector for optimum
performance with any vibration present in the system.
Remember to record all settings on the Settings Sheets
Note: When adjusting the sensitivity limit ensure that at the rear of the manual.
all mechanical and electronic equipment that may be a
source of vibration is operating (including reject
devices etc).
Sensitivity Limit
This display is used to manually or automatically set-up
the maximum sensitivity that will be set by the
Automatic Setup feature of the detector. The maximum 1 3
sensitivity must be reduced in situations where the Sensitivity limit ###
detector is subject to high vibration. ETC Auto. adjust
2 4
To set the Sensitivity Limit manually:
Security Setup
Engineers Mode
Security Setup
ETC
Operator Access FULL
ETC LIMITED
Note: This flow chart shows the sequence Change SUPERVISOR Code
when changing the Supervisor Security 0002
Code. The sequence is the same for the
Operator, Engineer, QA Inspector and
Viewing Security codes.
On Time Out or
Security Setup
Introduction The Security Setup sub-routine allows the changing of
the security codes for up to four of the operating modes
Please refer to Figure 4-58 for the sequence of (i.e. Supervisor, Engineer, QA Inspector and Viewing).
displays. The Security Setup sub-routine can only be accessed
from the Engineer Mode.
All SAFELINE metal detectors are shipped from the
factory with the following security codes
pre-programmed:
FULL
Press soft key 3 to allow any person with an Figure 4-59 Operator Access
OPERATOR security code to adjust phase and
sensitivity.
RECALL
1 3
Change Code-SUPERVISOR
ETC
2 4
RECALL
1 3
Change Code - ENGINEER
ETC QA INSPECTOR
2 4
RECALL
1 3
Change Code - VIEWING
ETC
2 4
RECALL
5) When the last digit has been set, press the ENTER
key to display Figure 4-65.
1 3
6) Press the ENTER key if the number is correct to New SUPERVISOR code
return to the Engineer Mode. 1234
2 4
7) If the number is not correct, press the RECALL key
and carry out Steps 1) to 6) again.
RECALL
8) If 6) or 7) is not carried out, a time-out occurs and
the new code is accepted as if was pressed.
Figure 4-65 New Supervisor Code
Speed Setup
Introduction Note: Any settings altered in this menu will affect ALL
of the product numbers.
This menu is used to set-up the speed range and
product speed for the detector. Note: The features Product Signal Cancellation and
Automatic tracking are not available in the VARIABLE
The performance of metal detectors may be improved speed range.
if a detector is able to focus in on a specific speed
range, rather than have to cope with unknown speed
ranges.
Speed Range
This display is used to select between one of three VARIABLE
possible speed modes. This mode allows for products with varying speeds to
be used. The additional performance increase of the
1) Press soft key 3 to see the different speed ranges.
NORMAL mode is NOT available in this mode.
2) When the required speed range is showing on the
display, press soft key 2 to move to the next FAST is the default for this product. NORMAL and
display, Figure 4-67. VARIABLE are settable, but are rarely used.
NORMAL
This mode allows for precise calibration of the speed of
1 3
the product to provide additional filtering inside the Speed range - VARIABLE
detector which in most cases will allow greater ETC
sensitivities to be used. 2 4
FAST
This mode allows for faster speeds than the NORMAL RECALL
Product speed
This display allows the speed of the product to be set
either manually or automatically.
1 3
To set the Product Speed manually: Prod.speed ###.#m/min
ETC Auto.Adjust
1) Press soft key 3.
2 4
2) Use the cursor key and up and down keys to set
the Product Speed.
RECALL
Q.A Modes
Entered
QA Inspector
Security
Code
Q.A.SETUP TEST
PRINT
Entered
QA Operator
LINE ID. #### Security
ETC Code
PRINTER YES
ETC NO
FERROUS NON FERROUS
EXIT STAINLESS STEEL
PRINTER FIXED
ETC PORTABLE **
Pass 0.0mm S/S sample
PASSED FAILED
STAINLESS STEEL
ETC #.#mm
Modified Settings IN
ETC OUT
Shift Report Start H:##
ETC M:##
Alarm If DUE
ETC OVERDUE
RECALL
Line Identification
This is a number that is printed near the beginning of
all printouts.
LINE ID
1) Press soft key 3 to set the Line ID. 1 3
LINE ID ####
2) Use the cursor and the up and down keys to set ETC
the line identification number. 2 4
Printer Fitted
YES
Press soft key 3 if a printer is installed.
1 3
NO Printer YES
Press soft key 4 if no printer is installed. ETC NO
2 4
RECALL
Printer Fixed/Portable
Portable printers will not give a “data collection unit not
ready” message if a QA test is performed without a
printer attached. Fixed printers will always give the 1 3
message if a printer is not connected. Printer FIXED
FIXED ETC PORTABLE
2 4
Press soft key 3 if the printer is permanently
connected.
PORTABLE RECALL
Test Samples
1) Press soft key 3 to select a Ferrous, Non-Ferrous
or Stainless Steel sample.
2) Press soft key 4 then use the up and down keys to 1 3
set the required sample size. STAINLESS STEEL
ETC #.#mm
3) Press ENTER when the correct size is showing. 2 4
Different sizes can be set for all three materials and for
each product number. RECALL
RECALL
Modified Settings
At the Modified Settings display, press either soft key 3 OUT
or soft key 4. Press soft key 4 to prevent the recording and print out
of any changes to the settings between shift printouts.
IN
Press soft key 3 to include certain settings which have
been changed since the last shift report, in the current
shift report. The shift report will include the settings 1 3
new value and the date and time that it was changed. Modified Settings IN
ETC OUT
The settings which are recorded are: 2 4
• Product Number
RECALL
• Sensitivity
• Phase
• Timer Type Figure 4-76 Modified Settings
M
Press soft key 4 to adjust the minute value between 0
and 59. Use the up and down keys to change the Figure 4-78 Shift Report Start Time
value. Press the ENTER key when the correct number
of minutes is shown.
Test Interval
Figure 4-79 allows the QA Inspector to set the time
period between when the detector requests the QA
personnel to carry out a performance check. 1 3
Test Interval H.##
At the time interval specified the message, REQUEST ETC M.##
FOR PERFORMANCE CHECK appears on the display. 2 4
H
Press soft key 3 to adjust the hour value. The Figure 4-79 Test Interval
maximum number of hours is 8. Use the up and down
keys to change the value. Press the ENTER key when
the correct number of hours is shown.
M
Press soft key 4 to adjust the minute value between 0
and 59. Use the up and down keys to change the
value. Press the ENTER key when the correct number
of minutes is shown.
Overdue Period
Figure 4-80 allows the QA Inspector to adjust the time
period allowed, following a performance check request,
before the test becomes overdue. 1 3
Overdue Period H.##
Once the test becomes overdue the REQUEST FOR ETC M.##
PERFORMANCE CHECK message is replaced with 2 4
OVERDUE FOR PERFORMANCE CHECK. At the same
time the bar graph display and buzzer are sequenced
on and off to attract the operator’s attention. RECALL
H
Press soft key 3 to adjust the hour value. The
Figure 4-80 Overdue Period
maximum number of hours is restricted to half of the
test interval time. Use the up and down keys to change
the value. Press the ENTER key when the correct
number of hours is shown.
M
Press soft key 4 to adjust the minute value between 0
and 59. Use the up and down keys to change the
value. Press the ENTER key when the correct number
of minutes is shown.
OVERDUE
Press soft key 4 if an alarm is required when a RECALL
memory.
4) Repeat the operation for as many QA Operators as
Figure 4-82 Change QA Operator Code
required.
5) Press soft key 2 (ETC) to return to the first display
of the QA Inspector Mode.
RECALL
RECALL
RECALL
QA Operator Mode
Introduction A QA Operator or the QA Inspector may perform these
tests to validate the detector at any time however note
Please refer to Figure 4-68 for the sequence of that the test interval timer will be restarted from 00:00
displays for this mode. minutes as soon as a test has been performed.
This mode is for carrying out a performance check of The time that the next test will be requested is
the detector, and thus provide immediate validation of displayed in the Running Mode. Refer to the Time
the detector’s integrity. section on page 4-16.
The QA Inspector has the facility to set a timer in the A printout is automatically printed immediately a
detector that will cause a REQUEST FOR performance check is carried out, providing the printer
PERFORMANCE CHECK message to appear at pre-set option has been selected by the QA Inspector.
intervals.
Refer to Chapter 5 for examples of typical printouts.
...etc
detector aperture.
2) Check that the test sample has been detected by
monitoring the detect LED on the detector front Figure 4-88 Select Test Result
panel.
3) Where applicable, check that the reject device
operates to reject the test sample.
4) From Figure 4-88, press soft key 2 if the sample
PASSED the test or soft key 4 if the sample
FAILED.
5) The display shown previously will re-appear.
6) If there are more test samples to be checked then
repeat steps 2) to 4) for each sample.
Damping # N/A
A Timer B ETC
ETC Group C
Detection Buzzer ON
tm1 Reject time ####ms ETC OFF
ETC
Language ENGLISH
ETC
Sensitivity Limit
Printer Handshake HW
*
Pack Sensor Fitted YES N/A ETC SW
ETC NO
A
QA SETUP
Sensor Distance ####ms N/A
ETC
* Optional B
Printer YES
ETC NO Shift Report Int. H:##
ETC M:##
Printer FIXED
ETC PORTABLE Shift Report Start H:##
ETC M:##
FERROUS
ETC #.# Test Interval H:##
ETC M:##
NON-FERROUS
ETC #.# Overdue Period H:##
ETC M:##
STAINLESS STEEL
ETC #.# Alarm if DUE
ETC OVERDUE
Viewing Mode
Introduction
Viewing Mode enables the user to see all the settings
available in the Engineer Mode and the QA Inspector
Mode, but does not allow any alteration of these Remember to record all settings on the Settings Sheets
settings. at the rear of the manual.
Reject Timers
Recommended Applications The engineer may allocate different timer types and
settings to group A, B or C, only three selections are
Listed below are various types of reject mechanisms
allowed. In general only one timer type and setting will
along with the recommended timer type for the
be required for all applications.
mechanism.
Both timer group selection and timer type setting may
Reject Mechanism Timer Type be made in the Engineer Mode but only timer group
tm1 tm2 selection for a product number can be made from the
Gravity Fall Systems Supervisor Mode.
Cowbell Preferred Ok
Y Valve Diverter Preferred Ok
Throat
Important Notes for Timer Setup
Double Bagmaker Preferred Ok
Bagmaker Stop Preferred Ok
Sample Size Selection
Cowbell Preferred Ok Small size metal contaminants should be used during
Diverter Preferred Ok the setting of the timers; the use of large contaminants
Pipeline will produce errors in the settings.
Three Way Valve Preferred Ok
Use the smallest metal sample that can be detected,
Pipeline Stop Preferred Ok
this should give approximately 2 to 3 red LEDs on the
Timed Audible Alarm Preferred Ok
bargraph.
Table 4-1 Reject Timer Applications
If this is not possible use the smallest sample available
and adjust the sensitivity setting so that the metal
About Reject Timers contaminant gives a bargraph indication of
approximately 2 to 3 red LEDs.
Both immediate and delayed programmable reject
timers are available to cover the range of reject devices
used for the removal of metal contaminated product in
Product Presentation
pipeline, gravity fed and vertical packaging type Sample products or product packs used to set up the
applications. timer should be passed through the detector aperture
at their normal speed and without skewing or slipping.
Rejection of product is generally achieved with a
suitable pneumatically controlled flap or valve diverter
mounted in-line below the detector. For some T-Series
applications, the reject timer may control the down
stream bagging machine, forcing it to stop the bagging
machine or produce a double bag on a reject event.
Tm1 Timer
From
Engineer Mode
A Select Timer B
ETC Group C
Go back to
Engineer
Mode
N/A
See the
tm2[G] Mode
tm1 Timer tm2[G]
ETC Type tm3[G]
N/A
Go back to See the
Engineer tm3[G] Mode
Mode
tm1 REJECT TIME ####ms
ETC
Or 5 second
timeout
Go back to
Engineer
Mode
Tm1 Timer
! CAUTION
Ensure you have read the Reject Timers section on Remember to record all settings on the Settings Sheets
page 4-60. at the end of this chapter.
If you have already selected the timer group and Figure 4-92 Selecting the Timer Group
pressed YES to update the group, as per the Engineer
Mode section earlier, then proceed to Step 3 on
page 4-63. Otherwise:
1) Press soft key 1, 3 or 4 to select Timer Group A, B
or C.
The currently selected timer group will be indicated
by a flashing cursor appearing over the group
letter.
2) Go to Step 2.
Step 2
In Figure 4-93, ‘X’ represents the timer group A, B or C
as selected in Step 1; tmxx represents the timer type
currently selected for this timer group. 1 3
1) If you only need to select the timer group for the Timer ’X’ type YES
current product number and not adjust any of the tmXX Update ? NO
2 4
timer group properties then either:
a Press soft key 4 (NO) and return to Step 1.
RECALL
Note: Although NO was selected, the group will
be changed to the group letter selected in
Step 1.
Figure 4-93 Current Timer Type
b Press soft key 3 (YES) and proceed to Step 3
on page 4-63.
Step 3
1) Press soft key 1 to select tm1.
2) Go to Step 4.
1 3
tm1 Timer tm2[G]
ETC type tm3[G]
2 4
RECALL
Step 4
1) Press soft key 3 to set the Reject Time.
2) Use the cursor and the Up and Down keys to
adjust the Reject Time to the required value. 1 3
tm1 REJECT TIME ####ms
3) Press the ENTER key to accept the new settings. ETC
2 4
4) Press the ENTER key again to proceed to the next
display.
RECALL
RECALL
See the
tm2[G] Mode See the Engineering Mode Display, Figure 4-23.
Is Current N/A
NO YES
tm2 Timer
Selection
Gated?
N/A
Gated timer YES
still required? NO
Or 5 second
timeout
Non-Gated Time ’X’ type tm2[G]
set/updated
Or 5 second
timeout
Ensure you have read the Reject Timers section on tm2 settings
page 4-60.
Signal Delay
Introduction This is the time taken for a metal contaminant to travel
The tm2 timer, when used in the non-gated mode, is from the metal detector to the reject device.
ideal for use with loose products where the reject
device is situated some distance from the metal Reject Time
detector. This is the time required by the reject device to reject
the contaminated product.
This timer type is suitable for reject devices which
include plough-action diverters, retracting bands etc.
Step 1
Figure 4-98 may be used to either:
Step 2
In Figure 4-99, ‘X’ represents the timer group A, B or C
as selected in Step 1; tmxx represents the timer type
currently selected for this timer group. 1 3
Timer Group ’X’ YES
1) If you only need to select the timer group for the Type tmXX Update ? NO
current product number and not adjust any of the 2 4
timer group properties then:
a Press soft key 4 (NO) and return to Step 1. RECALL
Step 3
If non-gated mode has been selected, the cursor will
flash over the t in tm2[G].
1 3
If gated mode has been selected, the cursor will flash tm1 Timer tm2[G]
over the G. ETC type tm3[G]
2 4
Note: Gated mode does not apply to this product.
1 3
Gated timer YES
still required ? NO
2 4
RECALL
Step 4
With this display, you can set the Signal Delay Time
and the Reject Time.
1 3
Note: Pressing ENTER will take you directly to the tm2 SIGNAL DELAY ####ms
tm2 Gated display, Step 5, on page 4-69. If you need to ETC REJECT TIME ####ms
configure the Signal Delay or the Reject Time, follow 2 4
the instructions below.
RECALL
Step 5
1) Press soft key 4 (NO).
1 3
tm2 Gated ? YES
NO
2 4
RECALL
2) Figure 4-104 will appear for five seconds before Figure 4-103 Gated Confirmation
returning to the display shown as Figure 4-98.
1 3
Timer ’X’ type tm2
set/updated
2 4
RECALL
RCU Settings
Depending on the timer type selected one of two
displays are available to allow the user adjustment.
1 3
tm1 and tm2 Timer Types REJECT CONFIRMATION
The detector needs to be told how long it must wait ETC exten. time ###ms
from releasing the Reject Mechanism, to receiving a 2 4
signal from the RC Sensor. This period plus a small
safety margin is known as the RC Extension Time and
RECALL
must be entered by the user.
Important Notes
1) The Reject Timer (i.e A, B or C) must have been
set-up prior to adjusting the RC Extension/Window
Time.
2) Small size metal contaminants (test samples)
should be used to set the RC Extension/Window
Time. The use of large test samples will produce
errors in the setting. If this is not possible use the
smallest test sample available and adjust the
sensitivity so that the test sample gives an
indication of 2 or 3 red bars on the bar graph
display.
3) For packaged product position the test Sample on
top of the pack at the front/leading edge.
Loose Product, Fast Speed Applications Packaged Product, Fast Speed Applications
1) From the running mode display press the 1) From the running mode display press the
SECURITY key. SECURITY key.
2) Enter the Engineers security code. 2) Enter the Engineers security code.
3) Press the ETC soft key until the Reject 3) Press the ETC soft key until the Reject
Confirmation (RC) display is reached. Confirmation display is reached.
4) Press the RC Extension Time soft key. 4) Press the Extension Time soft key.
5) Set the Extension Time to 100 ms. 5) Set the Extension Time to I00 ms.
6) Pass a test sample through the detector aperture 6) Pass a pack containing the test sample through the
to trigger the detector. detector aperture to trigger the detector.
The reject mechanism will respond according to its The reject mechanism will respond according to its
settings. When the reject mechanism is released settings. The rejected pack when leaving the
and moves from reject back to the pass position conveyor or entering the reject bin will pass the RC
the RC Sensor confirms reject operation, providing sensor, which will confirm reject operation to the
the Extension Time setting is long enough. RCU providing the Extension Time setting is long
enough.
7) If the detector goes into a reject fault condition,
increase the Extension Time by a further 100 ms. 7) If the detector goes in to a reject fault condition,
increase the Extension Time by a further 100 ms.
8) Repeat step 6) and 7) until the detector signals no
fault condition. 8) Repeat step 6) and 7) until the detector signals no
fault condition.
9) Increase the Extension Time by 200 ms and press
the ENTER key to enter the new value into memory.
Reject Fault
This fault display (Figure 4-106) indicates that the RCU
has signalled a reject fault condition.
1 3
Assuming the Reject Confirmation (RC) Extension Reject Confirmation
Window time has been set correctly, the fault condition REJECT FAULT
could be due to either or both of the following: 2 4
Input/Output Fault
Figure 4-107 indicates that a fault has occurred in the
input output circuitry from the Module to the RCU.
Setting Sheets
Record all your settings here, (use the Viewing Mode and Engineer Mode).
o Note: This is an optional item that may not be fitted in your detector.
Detector Details
Serial Number
Model
Software Version
Product Details
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
o Note: This is an optional item that may not be fitted in your detector.
Group Type
A
B
C
5 Printers
This chapter contains information on how to set up a
printer for use with the Metal Detector. It covers the
following topics:
Note 1
Note 1
**Settings**
Figure 5-2 Current Settings Printout Figure 5-3 Current Settings Printout (Continued)
QA Settings Printout
**QA Settings**
Line ID ; 0000
Timer Group ;B Printer ; YES
Type ; TM2 Printer ; FIXED
Reject Time ; 100ms Relay Rpt ; YES
Sig Delay ; 200ms Settings Rpt ; YES
Report Int ; 00:00
Timer Group ;C Test Int ; 0:00
Type ; TM3 Overdue Int ; 0:00
Reject Time ; 100ms Alarm ; DUE
Sig Shift ; 010
Prod No Fe N/Fe S/S
Ref Phase 1 ; -18.66 00 0.0 0.0 0.0
Ref Phase 2 ; -17.34 01 0.0 0.0 0.0
Buzzer ; ON 02 0.0 0.0 0.0
Pack Sensor ; YES 03 0.0 0.0 0.0
Sensor Distance ; 1000 mm 04 0.0 0.0 0.0
Speed Range ; NORMAL 05 0.0 0.0 0.0
Product Speed ; 001.0 m/min 06 0.0 0.0 0.0
Reject Inhibit ; NO 07 0.0 0.0 0.0
Reject Confirm ; YES 08 0.0 0.0 0.0
Reject Confirm ; 1000 ms 09 0.0 0.0 0.0
Auto. Track Rate ; 2.00 10 0.0 0.0 0.0
Auto. Track Span ; 30.00 11 0.0 0.0 0.0
Auto. Track Damp ;5 12 0.0 0.0 0.0
Boost ; NO 13 0.0 0.0 0.0
Printer Handshake ; SW 14 0.0 0.0 0.0
Current 15 0.0 0.0 0.0
Prod No ; 00 16 0.0 0.0 0.0
17 0.0 0.0 0.0
Figure 5-4 Current Settings Printout (Continued)
18 0.0 0.0 0.0
19 0.0 0.0 0.0
20 0.0 0.0 0.0
Prod No ; 01
Sens ; 180
Timer ;C
Current
Prod No ; 00
**Performance Check**
Date Time
01 Feb 08 14:37:37
Line ID ; 0205
Operator ; QA Inspector
Prod No ; 01
Sens ; 156
Phase ; 05.00
Timer ;B
Material ; Ferrous
Size ; 1.5 mm
Detection ; YES
Reject Rly ; YES
Result ; PASSED
6 Serial Communications
This chapter contains information about the Serial
Communications feature that allows information to be
transferred to and from the Metal Detector. It covers the
following topics:
2) Host commands
Test Mode
For the purpose of checking the serial link, the detector
will double echo any character sent as long as the
serial link is idling. The following character should not
be sent, as they are recognised as part of a normal
communication transmission: STX, ACK, NAK.
‘N?’ in Language ?
‘O’ n out Active mode
n = 0 : Running mode (no security code has been entered at the keyboard).
n = 1 : Operator mode.
n = 2 : Supervisor mode.
n = 3 : Engineer mode.
n = 4 : Viewing mode.
n = 5 : QA Inspector mode. X
n = 6 : QA Operator 1 mode.
.
.
n = 14: QA operator 9 mode.
n = Timer type
n = 0 : Timer type tm1
n = 1 : Timer type tm2
n = 2 : Timer type tm2G *
n = 3 : Timer type tm3 *
X
n = 4 : Timer type tm3G *
‘U?’ in Date ?
‘V’ f ‘,’ n in/out Sensitivity limit
f = Frequency offset, a single digit number in the range [0..1].
(Must be 0 for single frequency 1f heads)
0 = Low frequency 1 = high frequency F
n = Sensitivity limit, a three digit number in the range [0...199].
‘W?’ in Time ?
‘w’ m ‘,’ n’,’ o ‘,’ p in/out Automatic tracking setup *
m : Automatic tracking maximum rate, a three digit, fixed point, number in the range
[1.00...5.00].
n : Automatic tracking maximum span, a four digit, fixed point, number in the range
[3.00...45.00].
F
o : Automatic tracking damping, a single digit number in the range [1... 9].
p : Reserved, always zero.
Notes
Note: Those characters shown inside single quotes ‘ ’, Note: Not all the timer types use all the parameters
are to be sent as shown in the identifier column (ASCII that are transmitted with the ‘T’ identifier. However, the
representation of characters is used). host must always send the correct number of variables
to the detector, and similarly, the detector always
Note: xx? is a request to the detector for information, responds with the correct number of variables. To
(where xx is one of the identifiers in the identifier alleviate this restriction the detector will accept the
tables). value 0 for those values unused by the selected timer
type when transmitted from the host. The detector in
Note: The direction that the identifier may be
turn will send the current state of these values in its
transmitted is with reference to the detector. Where:
responses, independent of the timer mode.
Out = transmitted by detector
Note: For customers wishing to control our product via
In = received by detector serial link only (without a local Man Machine Interface
fitted to the detector), SAFELINE recommends to
Note: The “Type” field in the above table is used to implement an additional set of commands, to ensure
categorise the identifiers into their sphere of influence. full access to factory settings. This need may arise, if
Where: the original factory setting needs to be adjusted or
reset.
F = Factory Setting
If the above is required, contact your local supplier for
P = Product dependent setting the relevant information.
X = Neither of the above
completing the automatic setup, these messages will Pass the product through the Obtaining product
aperture... information 2
be resumed if they had been enabled prior to entering
the automatic setup.
4 14
Note: The command ‘b1’ cannot be sent if the current Product signal too large
Set up without the additive
Please wait...
product number is 0. Automatic setup is not available
on product number 0.
5 15
‘b90’ 8 96
This command should be sent when the detector is in a WARNING: The phase setting Automatic setup
may be in error... FAILED
state where a YES or NO decision is made.
Transmitting this command is equivalent to selecting 98
9
NO on the keypanel.
Product YES Automatic setup
timed out
‘b99’ Cancellation NO
e
Type of Error Description of Error
(Major Error)
0 No Error, OK Received command was OK.
The detector tried to send too
1 Protocol Error many commands, within a single
message, and caused a buffer
overflow, (see later).
An unknown identifier was
2 Identifier Error received. Please refer to the
tables of acceptable identifiers.
A comma was missing, wrong
value type, letter instead of
3 Value-list Error number in the received command,
etc.
A value was outside acceptable
limits. Please refer to the previous
4 Bounds Error
tables for the range that values
can take.
5 Not used Reserved for future development.
Commands the Host May Transmit Note: The special case n = 0 means that automatic
sensitivity limit is not running.
The host can send any of the following messages:
'j1' J1
'j?'
This returns the current state of the automatic
sensitivity limit procedure (see the 'j'n command
description below).
'j99'
This command is sent when the host wishes to abort
the automatic sensitivity limit procedure and return to
normal operation. This is equivalent to pressing the
front panel Security key during the automatic sensitivity
limit, and will cause the same action to occur in the
metal detector.
QA Operator Commands
QA Inspector Commands
In = received by detector
F = Factory Setting
P = Product-dependent setting
The host can send any of the following messages: Ensure nothing is passing The test sample
through the aperture is too large
'z02, 99'
This command is sent when the host wishes to abort
the automatic product-speed procedure and return to
normal operation. This is equivalent to pressing the
front panel security key during the automatic
product-speed, and will cause the same action to occur
in the metal detector.
Emulation Mode
Objective Principal of Operation
To generate a facility, which allows the remote control Presently, the metal detector software uses the keys of
of the metal detector via the existing serial link. The the key panel as input device and the LCD screen as
remote MMI will be a ‘look a like’ of the local key panel, the output device.
using the same display area as the LCD display (2 x 24
chars) and a copy of all the keys present on the local The remote hardware (e.g. PC) will duplicate the I/O
key panel. devices in a suitable way and as such provide the
same facility to the operator as the local key panel.
Note: In this mode the ‘z20’ command works under the The message format would look as follows:
normal protocol format using ACK’s and NAK’s.
(STX)G(VALUE)M(VALUE)z20,(ENCODED
DATAPACK)(ETX)(CRC)
3) Fast Emulation Mode
This mode makes use of the following commands: The ‘z20’ Command in Fast Emulation Mode
‘z15’, z16’, ‘z20’, ‘z22’. The ‘z20’ CMD is automatically transmitted on a timed
interval. (For timing see ‘z16’ CMD.)
In order to achieve a faster update rate, the ‘z20’ CMD
works outside the normal protocol. (All other The host processor must not respond with ACK/NAK’s
commands use the normal protocol format). for the ‘z20’ CMD.
Table 6-5
If neither bits 6 or 7 are set then no cursor should be
shown.
‘z22’ command
The single parameter transmitted with this command
represents the pressed key.
n = U: Up key
n = D: Down Key
n = E: Enter key
n = X: Recall key
CRC Generation
Introduction
A sixteen bit cyclic redundancy code (CRC) is used in
preference to the more common checksum technique
to minimize the possibility of the detector responding to
a corrupted transmission.
Method
A sixteen bit CRC accumulator is used, the data being
transmitted over the link is four bytes of ASCII encoded
hexadecimal with no leading zero suppression.
Polynomial used:
Table 6-8
C Program
/*
Straightforward, non optimized CRC-CCITT routine.
Assumes 16 bit integer variables.
MSB of integer is MSB of CRC result.
*/
#define POLY 0x8408 /* Polynomial */
void main(void)
{
unsigned int crc;
crc = 0xffff;
printf("crc of 'T' is 0x%x\n", bytecrc("T",&crc) );
crc = 0xffff;
printf("crc of 'THE' is 0x%x\n", blkcrc("THE",&crc,3) );
crc = 0xffff;
printf("crc of 'THE,QUICK,BROWN,FOX,0123456789' is
0x%x\n",blkcrc("THE,QUICK,BROWN,FOX,0123456789",&crc,30));
} /* end main */
unsigned int blkcrc(unsigned char *bufptr, unsigned int *crcres, unsigned int count)
{
int i;
for (j = 1; j <= 8; j ++ )
{
/* do each bit LSB first */
Q = (*crcres & 0x0001) ^ (ch & 0x0001);
/* Q = 1 if either crcres or data least significant bits are 1, but not both. */
if ( Q == 0x0001 )
{ /* Q is one */
*crcres = *crcres >> 1; /* shift right one */
*crcres = *crcres ^ POLY; /* XOR with POLYnomial */
}
else /* Q is zero */
{
*crcres = *crcres >> 1; /* just shift no XOR */
}
ch = ch >> 1; /* move next data into position */
}
return *crcres;
} /* end bytecrc */
HOST
DETECTOR
T1 T2 T3 T4
HOST
DETECTOR
1
T1 T5 T3 T4
Figure 6-5 Host Command type 1 (causes change in value of detector variable)
DETECTOR Ack
T1 T4
Figure 6-6 Host Command type 2, (causes NO change in value of detector variable)
EVENT
OCCURS T1 T4
HOST DETECTOR
Event
(E.g. Detection, Fault
T0, 1, 55, ...
Dnnn,xxx
Event Message
Detector Response
ACK
ACK
Appendix 1
This appendix contains text to be read together with your main manual. The text is added in accordance with
EN 61010-1:2010.
Chapter 2 > Environmental Protection. Note: If not using the MT power-supply unit enclosure,
make sure the power-supply unit enclosure used is suita-
bly IP rated.
Chapter 3 > Power Lead Connections. Periodic inspection of the power connection needed,
including protective earth check.
Chapter 3 > Detector Precautions. There are no user-replaceable serviceable parts. Please
contact your service representative for any service issues.
Chapter 3 > The section about power leads, under the fig- There are no internal user-replaceable fuses.
ure: 'Power lead preparation'.
Insulation Ratings
Chapter 3 > Power Lead Connection. Extra text at the end of the section:
The protection and isolation device should be:
• Installed close to the equipment.
• Within easy reach of the operator.
• Marked as the disconnecting device.
Chapter 3 > Figure: Layout of Components and Terminals. Extra text to accompany the figure:
See the Technical Specification section for more details.
Chapter 1 > Section: Aims of This Manual. Extra text for Touch LS manual only:
Read this manual together with your original manual.
Contact Details
Mettler Toledo Safeline Ltd Montford Street, Salford, M50 2XD, England, UK.
For technical support, please contact your local SAFELINE service representative: www.mt.com/slmd-contact.
3 Appendix
Mettler Toledo Safeline radio frequency metal detectors generate electromagnetic fields within the frequency
range 10 kHz to 1 MHz. This frequency range is within the range referred to as non-ionising electromagnetic
radiation (NIEMR).
Personnel fitted with cardiac pacemakers or other medical implants must always seek guidance from their doc-
tor or physician before operating or coming into close proximity of the metal detector aperture.
The fields generated are concentrated within and in close proximity to the metal detector aperture, with the high-
est levels found on the surface of the aperture lining.
Actual field strengths will depend on type, frequency and size of detector but for guidance the typical field
strength of a 350x175mm rectangular aperture detector is as follows:
Occasional exposure to the strongest fields inside the aperture is permitted; although long periods of exposure
in the aperture should be avoided.
The above information is intended as guidance only. The manufacturer of the product, Mettler Toledo Safeline
Ltd, does not have any control over the use or misuse of this product and assumes no liability therein. It is the
responsibility of the user to determine the proper suitability and safety of the product during normal use, and to
determine which safety regulations apply.
For further information and guidance please consult the equipment supplier.