You are on page 1of 8

Li-ion Battery Warranty Claim Information Feedback Form

1. Basic Information
Site IUBT02
Customer Telenor
Name
Battery Installation Customer
Site Location Alai Battagram Na Syed Jamil Shah
Date Engineer
Problem Occurrence 15/09/202 Engineer
Site Visiting Date 15/09/2022 03450027605
Date 2 Contact info
2. Site Application Mode & Parameters Setting

□ Core Site □ Hub Site □ Node Site □ Base Station □Outdoor Site □ Other
DC Power System Brand/Model ZTE Rectifier Model/Qty 1 Normally Working Qty 6

Rated Output Current (A) /pc 280 Site Load Current 45 A

Li-ion Battery Installation/Connection Method (Battery Overall Photos Needed)

Ambient Temperature 25 ℃ Li-ion Battery Cabinet Temperature 20 ℃


Battery replacement history: Replaced batteries qty and time
Displayed Battery Voltage 0 V DC Power Output Voltage 0 V
Battery Bank Terminals Actually Measured Voltage 53 V
Displayed Battery current 0 A Actual Measured battery current 0 A
Battery status when it was measured: □Open-circuit □Floating charge □Boost charge □Discharging
3. Li-ion Battery Information
KK25GXAT3FBA015
0
KK25GXAT3FBA006
4
KK25GXAT3FBA006
2
KK25GXAT3FBA007
Battery Brand
Li-ion Battery SACREDSUN Bar-code/serial number 6
Mark/Model
Basic Information KK25GXAT3FBA007
7
KK25GXAT3FBA004
2
KK25GXAT3FBA007
9

Manufacture Date 2021 Installed Battery Bank Qty 8


Is the battery appearance distorted? □Yes □No Details description:
Li-ion Battery
Is the battery appearance bulge? □Yes □No Details description:
Appearance
Is the battery terminal tight? □Yes □No Details description:
Checking
Are the battery connecting cables broken? □Yes □No Details description:
Rectifier Floating Charge
52 Equal Charge Voltage (V) 54
Parameter Voltage (V)
Setting Equal Charge 30 Battery Charge Current 0.6
Period (Day) Limit(C10)
Li-ion Battery Warranty Claim Information Feedback Form
1. Basic Information
LLVD (V) Load
voltage low BLVD (V) Battery
47 46.5
disconnect protection voltage
voltage
Battery voltage
Battery voltage low alarm
high alarm 56V 48
threshold(V)
threshold(V)
Battery period
boost charge Yes Boost charge period(day) 30
enable?
Battery charge
0.6
current limit(A)
Boost-Float charge
Remaining SOC:40
current:5HR
Discharge time:180 Boost-Float charge
MNTS current duration:4HR
Battery discharging Charge
The conditions to
voltage:50 The conditions to auto coefficient:0.6
auto start boost
Float-Boost charge stop boost charge
charge Maximum Boost
current:53
charge
Float-Boost charge
duration:10HR
current duration:120
Other conditions:OK
Other conditions ok

Abnormalities Description: Batteries test done and verify each parameter, complete BB faulty
and screen shown complete blank and black.

Rectifier History Please download history records from rectifier module. If test person is not on site, don’t need
Alarm to provide the rectifier history alarms temporarily.

1. If the li-ion battery pack keeps alarming, then please check below 1.1-1.3 information for faulty diagnostic.

1.1 BMS History Please login the BMS system of the alarming batteries and export the history records.
alarm logs Click the info and select the Record, click Display and export the records.
Li-ion Battery Warranty Claim Information Feedback Form
1. Basic Information

Please login the BMS system of the alarming batteries and find the Parameter interface and
make a screenshot.
Click the PARAM item, and read the parameters and take screenshots for all parameters.

1.2 BMS
Parameter
Setting

1.3 BMS Real Please login the BMS system of the alarming batteries and find the Info-SinglePack interface
Time Info and then make a screenshot.
If find the individual cell voltage low, please open battery pack and check the actual cell voltage
with volt-meter, if the measured voltage is same with monitoring voltage, then feedback to us
the information for suggestion. If the measured voltage was different with monitoring voltage,
then please check the connection of monitoring wire whether properly installed/broken or not?
If so please feedback pictures of this phenomenon for assistance.
Login the BMS system, Click the INFO item and select Singlepack and make screenshots for this
Li-ion Battery Warranty Claim Information Feedback Form
1. Basic Information
interface.(Sample pictures below)

2. If Li-ion Battery Pack couldn’t be restarted, BMS module is powering off.

2.1.1 If the lithium battery pack couldn’t be turned on normally, please open the front panel of
battery pack, measuring the cells total voltage directly.

2.1.1.1 If the total voltage is lower than 40.5V, further to confirm the actual individual cell
voltage.

2.1.1.1.1 If individual cell voltage have no obvious difference(generally, the voltage difference
not larger than 300mV), please charge the cell group directly bypassing the BMS
model with constant voltage 45V and limited current 0.1C 10 or 0.05C10 for around
5mins(according to the precision of your charger equipment) until the cell group
voltage reach up to 45V and could keep at around 45V steadily, then reconnect the
BMS module with cell group +/- terminals, the BMS is supposed to be restarted after
the cell group voltage be elevated. If the BMS could not restarted, then the BMS
might be faulty, please provide all above needful test evidence to us for warranty
claim.

2.1.1.1.2 If the individual cell voltage have big difference, please charge the faulty cell with
3.6V and limit current 5A-100Ah, 2.5A-50Ah to recover the weak cell.

2.1.1.2 If the cell total voltage is higher than 40.5V, but the BMS could not be restarted as well,
then please unplug-plug the positive power supply of BMS board to try to restart it, if
the BMS couldn’t be restarted, then the BMS might be faulty, please provide all above
needful test evidence to us for warranty claim replacement.

2.1.2 If operating through above process, the BMS could be started normally, please log in the
BMS and export the needful data as per 1.1-1.3 procedures for root cause analysis.
Li-ion Battery Warranty Claim Information Feedback Form
1. Basic Information

3. Temperature sensor error

3.1 Log in the BMS software, and operate as per 1.3 to check the real-time info, in order to
figure out which temperature sensor get faulty.
3.2 Use the new temperature sensor to replace the faulty one, the alarm will be eliminated.
Other tests you E.g.
have carried out 1) Charging Test (Test Data or Photos are required)
for Li-ion battery
pack to show the 2) Discharging Test (Test Data or Photos are required)
battery faulty
phenomenon 3) Individual Cell Voltage Test (Test Data or Photos are required)
CSU Setting

You might also like