Use multiple makeup water sources for redundancy and environmental sustainability, which created
several water treatment challenges:
Water Analysis
System Identification Cond. pH P Alk M Alk Cl TH PO4
Raw Water 806 7.9 0 90 80 160
Reclaimed Water 1449 8 0 80 190 210 5
Goals
Maximize reclaim water use and minimize chemical use without compromising heat
exchange surfaces to help prevent downtime and minimize plant power usage effectiveness
(PUE).
Maintain the ability to subsidize reclaimed water with city water.
Maintain cooling tower conductivity at a level that will not cause fouling but reduces cooling
tower bleed.
Reduce cooling tower bleed to minimize water usage effectiveness (WUE).
Solutions
Specific water treatment chemistries were selected to provide protection during variations in water
treatment makeup while maintaining water savings. Will set up treatment in the following manner:
Water meters placed on all incoming and outgoing water to maintain proper mineral
balances.
pH control with variable speed pumps to prevent scaling from high-hardness reclaimed
water.
o Controllers placed on each cooling tower system. Benefits include:
o -Volume regulation of differing makeup water
o -Chemical feed based on makeup flow rates
o -Remote accessibility with alarming feature reports
o -Versatile, non-proprietary technology
Results
Programming the controller with meter input allowed the system to automatically maintain stability.
Min: 100
Max: 8,200
Average: 136.93
Min: 100
Max: 1,700
Average: 112.66
Min: 5,928.935
Max: 6,426.607
Average: 6,244.340