Professional Documents
Culture Documents
REPORT
ON
I am highly indebted to Mr. Ram Singh (Asst. Manager, 220 KV DTL S/S
Sarita Vihar) for their invaluable support without which the project could have
not been worked out the way it has. I am very much thankful to Mr. Hans
Kumar (J.E. 220 KV DTL S/S Sarita Vihar) who helped me immensely in
understanding the basics and complexities of along with additions that made
the quality of report better.
I would also like to extend a note of thanks to all other employees of Delhi
Transco Limited who helped me directly or indirectly in successful
completion of my project.
Last but not the least, I would like to thank my parents & all my fellow
trainees who have been a constant source of encouragement & inspiration
during my studies & have always provided me support in every walk of life
1. Introduction
1.1 Introduction to Delhi Transco Limited
1.2 DTL Network
1.3 Grid Diagram of Delhi
2. Introduction to Substation
5. Protection System
5.1 Over Voltage Protection
5.1.1 Ground Wire
5.1.2 Earth Screen
5.1.3 Lightning insulator
5.2 Over Current protection
5.3 Earth fault protection
5.4 Primary and back up protection
5.5 Relays
5.6 Fuses
5.7 Earthing System
6. Control Room
7. Battery Room
8. PLCC and SCADA System
9. Operation and maintenance of Substation
9.1 Introduction
9.2 Maintenance activity
9.3 Maintenance Schedule
9.4 Maintenance Schedule Table of
9.4.1 Oil filled power transformer
9.4.2 SF6 Circuit Breaker
9.4.3 Relays and protection circuit
9.4.4 Arrestors
9.4.5 Transmission lines
9.5 Thermo Scanning
10. General Safety Precautions
11. Conclusion
References
1. INTRODUCTION
1.1 AN INTRODUCTION TO DELHI TRANSCO LIMITED
Delhi Transco Limited, a successor company of erstwhile Delhi Vidhyut
board, came into existence on 1st July 2002, as a State Transmission
Utility of the National Capital. After unbundling of DVB the distribution sector
has been handed over to private companies while the generation and
transmission are still with the government. Over the years, DTL has evolved
as a most dynamic performer, keeping pace with the manifold challenges
that confront the ever increasing demand-supply power situation and
achieving functional superiority on all fronts.
Being the capital of India and the hub of commercial activities in the
Northern Region, coupled with the prosperity of population, the load
requirement of Delhi has been growing at a much faster pace. Added to that,
being the focus of socio-economic and political life of India, Delhi is
assuming increasing eminence among the great cities of the world. Plus the
vgision- 2021, aiming to make Delhi global Metro politic and world class city
demand greater infrastructure to enrich many services of infrastructure
development. DTL has been responsibly playing its role in establishing.
Upgrading, operating and maintaining the EHV (Extra High Voltage)
network. DTL has also been assigned the responsibility of running the State
load Dispatch Centre (SLDC) which is an apex body to ensure integrated
operations of power system in Delhi. Delhi Transco is also committed to
promote energy conservation not only in its own establishments but also in
the entire Delhi. The company has done a lot to educate and sensitize the
general public about the need of energy conservation. Transmission loss
level has been reduced from 3.84 per cent in 200-203 to 1.38 per cent in
2009-10, which is one of the lowest transmission loss level in the country. To
ensure adequate and efficient power supply. DTL has been continuously
upgrading its biggest achievement has been its ability to handle the highest
ever peak demand of 4720 MW in July 2010. The total availability of its
transmission system stood 98.78%. The modern technologies are being
implemented in DTL by way of constructing GIS sub stations and laying
XLPE 220 KV cable by employing cable link techniques and would be the
largest network of its kind in India.
➢ Voltage transformation
➢ Connection point for transmission lines
➢ Switchyard for network configuration
➢ Monitoring point for control center
➢ Protection of power lines and apparatus
➢ Communication with other substations and regional control center
Making an analogy with the human body, the role of substation in the
power system to address the above mentioned issues is pivotal: the
substations are the center of the “nervous, immune, musculoskeletal and
cardiovascular” subsystems of the entire power system “body”. The
“nervous” subsystem role of the substation is to allow the central system
to sense the operating states, view status of the equipment, and make
assessments of the system criticality. The “immune” subsystem role is to
develop self-defense means and sustain self healing strategies. The
“musculoskeletal” subsystem role is to maintain the system topology,
switch the equipment state and restore the power flows. The
“cardiovascular” subsystem role is to sustain normal power flow and
control the synchronization.
The substation includes the primary equipment (such as circuit breakers,
transformers, instrument transformers, etc.) and the secondary
equipment (monitoring, control and protection devices) which are
installed in control house.
In the primary side, a large number of breakers and disconnectors are
used in order to allow for maintenance and repair with a minimum of
interruption, which occupy large space. Oil-insulated transformers are
used to step-up or step-down the voltage level for purposes needed. Oil-
insulated transformers usually have big size and have potential explosion
problems. In addition, the maintenance is also elaborate and the noise of
those transformers is also a big issue. The breakers also need an
insulation media which may be oil, gas, or air.
Conventional current and potential transformers (CTs and VTs) are used
to convert the primary current and voltage to an operation range (0-5A
and 115V) for metering and protection. The CT saturation and open
secondary CT circuit safety issue are primarily of concern in such devices.
All interfaces between primary and secondary equipment are connected
by hard-wired cabling. Different length and types cables are bundled as
shown in Fig.1.2, which makes it labor intensive for future maintenance
and modification. In addition, due to the large number of wires in a highly
electromechanically “polluted” substation switchyard environment, the
wiring may experience significant electromagnetic interference (both
conducted and radiated).
3. 220/66/11 KV GRID SUBSTATION AT SARITA VIHAR:
I. Isolator arrangement
7) The second bus bar arrangement is also a two bus bar system each
connected with Potential Transformer (PT). There is again a bus
coupler between the two bus bars to couple them. Here a Capacitor
Bank is provided to increase the incoming voltage if there is any
voltage drop in the incoming. It can enhance the incoming voltage
by 3 to 4 KV.
8) From the 66 KV bus bar there are four outgoing circuits transmitting
power at 66KV to:
And there are two circuits for 66/11 KV transmission. These two 66
kV incomers from the 66 KV bus bar is fed to the two Transformers
of 20 MVA each.
In this category the EHV lines viz. extra high voltage lines of 400kv,
220kv, 132kv, and 66kv are considered. These high voltages are
transmitted from one sub-station to other sub-station through various
types of conductors.
For 400 KV line: Taran, Tulla and Marculla conductor.
For 220 KV line: Zebra conductor is used composite of Aluminum
strands and steel wires.
For 66kv, 33kv lines: Panther conductors is used composite of
Aluminum strands and steel wires.
The materials used in these conductors is generally Aluminum
conductor steel reinforced (ASCSR).
4.2 BUS-BAR
It consists of a single bus-bar and all the incoming and outgoing lines are
connected to it. The disadvantage of this type of system is that if repair is
to be done on the bus-bar or a fault occurs on the bus. There is a
complete interruption of the supply. This arrangement is not used for
voltages exceeding 33KV.
This system consists of two bus bars, a “main” bus bar and a “spare”
bus bar. Each bus bar has the capacity to take up the entire substation
load. The incoming and out going lines can be connected to either bus
bar with help of bus bar coupler which consist of a circuit breaker and
isolators. Ordinarily, the incoming and outgoing lines remain connected to
the main bus bar of fault occurring on it, the continuity of supply to the
circuit can be maintained by transferring it to spare bus bar.
4.3 ISOLATORS
The earth switch is connected between the line conductor and earth.
Normally, it is opened when the line is disconnected. The earth switch is
closed so that the voltage trapped in line is discharge to earth. There
some voltage lines due to changing current. This voltage is significant in
high voltage system. Before, proceeding with the maintenance work. This
voltage is discharge to earth by closing the earth switch. Normally earth
switches are maintained on the frame of isolator.
4.4 TRANSFORMER
4.4.1 INTRODUCTION:
i. Transformer core
ii. Windings
iii. Tank
iv. Conservator
v. Breather
vi. Bushing
vii. Air Cell
viii. Tap Changer and O.L.T.C.
ix. Cooling Equipments
Various types of windings are used for coils these are as follows:-
a. Low voltage winding - Spiral or helical
b. High voltage winding - Partially inverted disc / layer winding.
c. Tertiary winding - Spiral / Helical / Disc
d. Tapping winding - Inter wound spiral or helical paper covered
insulated copper strips or continuously cable are used for making
winding.
vi. BUSHING: -
Up to a voltage of 33kv,
ordinary porcelain insulators
can be used. Above this
voltage the of conductor or oil
filled terminal bushing, or a
combination of two has to be
considered .Of course, any
type of conductors can be
effectively insulated by air
provided that it is at a
sufficient Distance from other
conducting bodies and
sufficiently to prevent corona
phenomena.
The high voltage connections
pass from the winding to
terminal bushing. Thermal
bushings up to 36kv class, 3150 Ampere are normally of plain
Porcelain and Oil communicating type .Higher current rated bushings
and bushings of 52kv class and above will be of oil impregnated paper
condenser type. The oil inside the condenser bushings and will not be
communicating with the oil inside the transformer oil level gauge is
provided on the expansion chamber of the condenser bushings.
Oil in the condenser bushing is hermetically selected and it should not
be disturbed in normal operation. Oil level and oil leakage may be
checked regularly.
On load tap changer is the device for changing the tapping connections of
a winding, whilst the transformer is connected is on load
When the transformer is connected to a system it is some time necessary
to vary the voltage on the secondary side to meet the load demands,
as such transformer tap changer must be capable to varying the turn
ratio without interruption of supply. On a double wound transformer the
best position to place the tapping is at the neutral end of high voltage
winding .The positioning of the tapping on the lower voltage winding is not
applied on account of high current rating which would result.
The tapping of the windings are brought out through a terminal board to a
separate oil filled compartment, in which the on- load tap changer selector
is housed. As the selector must not break current ,a further separate oil
filled compartment is provided to house the diverter switch which breaks
the load current by an interrupted arc forming carbon ,therefore the oil I
the diverter switch compartment must be prevented from missing with
the oil in the main tank.
The tap changer is operated by a motor operated driving mechanism by
local or remote control and a handle is fitted for manual operation in an
emergency.
As the changing must take place on load, the contact for the tap changer
are so arranged that before one tapping is left , contact must be made
with the next . This could cause a short circuited no. of turn and large
current are prevented by the use of resistor or reactors.
IV.4.4 COOLING EQUIPMENT: -
Transformer is having a single or mixed cooling of ONAN, ONAF,
OFAF, and OFAN by means of radiators, fans, pumps, & heat
exchanger etc.
In Power transformer cooling are of following Types:
1. ONAN with 50% efficiency
2. ONAF with 70% efficiency
3. OFAF with 100% efficiency
1. Buccholtz relay
2. Pressure relief valve
3. Oil temperature indicator
4. Oil level indicator
5. Winding temperature indicator
6. Dehydrating Breather
7. Earthing Arrangements
relay
Buccholtz
1. BUCHHOLTZ RELAY: -
It is used for protection of oil filled transformer from incipient faults below
oil level. It is installed between tank and conservator. In this relay two
mercury contacts are provided. The device comprises of a cast iron
housing containing the hinged floats, one in upper part other in lower
part. Each float is filled with the mercury switch; leads of a switch are
connected to a terminal box for tripping.
APPLICATIONS:-
Double element relays can be used in detecting miner fault in a
Transformer
The alarm element will operate, after a specified volume of gas has
collected to give an alarm indicator.
o FANS ON = 60 deg C
o PUMP ON = 75 deg C
o ALARM = 90 deg C
o TRIP = 100 deg C
Winding temperature relay indicates the winding temperature of the
transformer and operates on the principle of thermal imaging and it is not
actual measurement.
Winding temperature indicators consist of sensor bulb placed in oil filled
pocket in the transformer tank top cover. The bulb is connected to the
instrument having by means of two flexible capillary tubes. One capillary
tube is connected to the measuring below of the instrument and the other to
compensation below. The measuring system is filled with a liquid which
changes its volume with rising temperature inside the instrument is filled
with a heat resistance which is fed by a current proportionate to the current
flowing through the transformer winding.
The instrument is provided with maximum temperature indicator the heating
resistance is fed by current transformer associated to the loaded winding of
the transformer .The increase in the temperature of the resistance is
proportionate to that of the winding. The sensor bulb of instrument is located
in the hottest oil of the transformer the winding temperature indicates a
temperature of hottest oil plus the winding temperature rise above hot it
.i.e. the hot spot temperature.
6. DEHYDRATING BREATHER: -
The conservator or the air cell is connected to the outside atmosphere
through the breather (silica gel) to make sure that the air in the
conservator or cell is dry. When silica is saturated with moisture its color
changes to pink. It can be made reusable by heating it at 100 deg C. for
48 hours.
7. EARTHING ARRANGEMENTS :-
a) Core Earthing
Connecting leads from core and end frame are being terminated at the
top of the cover, By connecting them to tank cover, core and frame
becomes earthed .Insulation resistance between the leads from core and
end frame or between leads from core and earth point can be checked by
500 volts megger. Leads from end frame have been brought out for
proper earthing for end frame.
c) Earthing of Tank
For earthing of tank nut-bolts & studs are required to make perfect
earthing between pads on tank and external earthing strip.
POSSIBLE LEAKAGE
6.Noload voltage 11 11 11
TV(kv)
Functions: -
High current line can be reduced to low current to measure easily with the
help of normal ammeter. To measure the very high current of the
running line with out distributing it, a spilt core type current transformer
is used. It is step up transformer the primary windings consist of thicker
conductor having less number of turns. Some time, only a straight
conductor also serves the purpose of primary winding. The secondary
winding is done with thicker conductor having more number of turns.
The primary winding is connected in series with the line and the M I is
connected across the secondary of the current transformer. it should
be clearly understood that the secondary winding of the current
transformer is never opened. It should be always short circuit i.e. the
secondary is
open, there is no current in the secondary winding hence, the M.M.F. of
primary will not be opposed and the cares will have high flux which will
cause high E.M.F. Induced or the primary and secondary winding. This
E.M.F. Is dangerous and may give sever shock.
The secondary of the current transformer should be earthed to avoid the
danger of shock to the operator.
The current transformer is kept in category of instrument transformers.
The CT’s are used to reduce / stepping down A.C. from high value to
lower value for measurement / protection / control.
PROPERTIES OF CT:
a) Standard - IS 2705
b) Highest system voltage (kv) - 245
c) Insulation level (kv) - 460/1050
d) Frequency - 50 Hz
e) Rated primary current - 600A
f) ST current KA/ sec - 27 /1
(a) Rated Voltage: The voltage of the P.T., which it can withstand.
(b) Rated Transformer Ratio: The ratio of rated primary voltage
to the rated secondary voltage.
(c) Rated secondary voltage: e.g. 130/ root (3) = 63.3 VAR.
Type: WP-245 V
It extinguishes the arc drawn between the contacts when the circuit
breaker open.
WORKING
o To improve the power factor of the system & there by regulating the
system voltage
o Reactive power compensation
o To reduce the loss
o Increased voltage level at the load
o Reduced system losses
o Increase power factor of loading current
Fig.13.1-Capacitor Bank
Benefits of using the capacitor bank are many and the reason is that
capacitor reduces the reactive current flowing in the whole system
from generator to the point of installation.
The insulator for the overhead lines provides insulation to the power
4.8 INSULATOR
The insulators are connected to the cross arm of supporting structure and
the power conductor passes through the clamp of the insulator. The
insulators provide necessary insulation between line conductors and
supports and thus prevent any leakage current from conductors to earth.
In general, the insulator should have the following desirable properties:
High mechanical strength in order to withstand conductor
load, wind load etc.
2. Suspension type
3. Strain insulator
PIN TYPE:
SUSPENSION TYPE:
STRAIN INSULATOR:
The strain insulators are exactly identical in shape with the suspension
insulators. These strings are placed in the horizontal plane rather than the
vertical plane. These insulators are used where line is subjected to
greater tension. For low voltage lines (< 11KV) shackle insulator are used
as strain insulator.
5. PROTECTION SYSTEM
INTRODUCTION: -
CAUSES OF OVER-VOLTAGE: -
INTERNAL CAUSES: -
A. Switching surges
B. Arcing grounds
C. Insulation failure
D. Resonance
EXTERNAL CAUSES OF OVER-VOLTAGES: -
LIGHTNING: -
It has been seen that the internal causes in increase the voltages of the
power system really double to that of the normal operating voltage where
as the external causes may increase the voltage several times (of the
order of 200 MV) to that of normal operating voltage of twice the value of
normal operating voltage of the system for a reasonable length of time
and to provide protective devices for the voltage having value more than
this.
Those devices are known as over voltage protection devices. The
common device used for the protection of power system against over–
voltages is:
1. Ground wires
2. Earth screens
3. Lightning arrestors of surge diverters
5.1.1 GROUND-WIRE: -
There are many types of lightning arrestors which are used to protect the
power system against over-voltage some of them are:
1. Rod gap arrestor
2. Horn gap arrestor
3. multi gap arrestor
4. Thyrite arrestor
5. Electrolytic arrestor
6. Oxide film arrestor
7. Expulsion type arrestor
8. Value type arrestor
Lightning arresters are protective devices for limiting surge voltages due
to lightning strikes or equipment fault or other events, to prevent damage
to equipment and disruption of service. Also called surge arresters.
There are times when the primary protection may fail. This could be due
to failure of CT/VT or relays, pr failure of circuit breaker one of the
possible causes of the circuit breaker failure is the failure of the trip-
battery due to inadequate maintenance.
5.5 RELAYS
A relay is a low-powered device used to activate a high-powered device.
Relays are used to trigger circuit breakers and other switches in
substations and transmission and distribution systems.
The electrical quantities which may change under fault condition are:
1. Voltage
2. Current
3. Frequency
4. Phase angle
TYPES OF RELAY
o Electromagnetic attraction
o Electromagnetic induction
But different relay based on this are used in this S/S such as:
Differential
RESE/F +O/L
relay
Protection relay
O/F protection
+FFR Group A
Breaker failure
relay trip relay
DRearth switch
relay
Protection Relays
1. DIFFERENTIAL RELAY: -
A differential relay is “the relay that operates when the vector difference
of two or more similar electrical quantities exceeds a pre determined
amount.” Almost every type of relay when connected in a certain way can
be made to operate as differential relay, mast of the differential relays are
of the “current differential type.” Fig.1 shows the over current relay used
as “differential relay” and operates when the currents at two points of the
system are unusual. For example of the current on at two ends of
alternator, windings are unusual. There is either a fault to earth or b/w
phases. When there is continuous over current and the current over
current and the current on both sides are equal, than the relay will not
sense the fault. It will sense fault only if there is a difference of current on
two sides of circuit.
A very important disadvantage in simple balance system is due to
inequalities of current transformers. Hence the differential CT’s should not
be erroneous or should be identical.
This disadvantage can also be overcome by using a based beam
relay. Fig : Differential Relay
2. DISTANCE RELAYS: -
4.
The non directional relay can operate for fault flow in either direction. In
order to achieve operation for the fault flowing in a specific direction, it is
necessary to add a directional element to the non directional element.
Such a relay which responds to fault flow in a particular directional is
called a directional relay
5. IDMT RELAY:
The IDMT relay work on the induction principle, where an aluminum or
copper disc rotates between the poles of electromagnet and damping
magnet. The fluxes induce eddy current in the disc which interact and
produce rotational torque. The disc rotates to a point where it operates a
pair of contact that breaks the circuit and removes the fault condition.
6. RESTRICTED EARTH FAULT PROTECTION RELAY:
An REF relay works by measuring the actual current flowing to earth from
the frame of the unit. If that current exceeds a certain preset maximum
value of milliamps (mA) then the relay will trip to cut off the power supply
to the unit.
7. TRIPPING RELAY:
AUXILIARY RELAY:
Auxiliary Relay
An auxiliary relay is used to indicate the fault by glowing bulb alert the
employee.
5.6 FUSES :
Fuse is a essentially a short piece of metal ( or a fusible material )
inserted in a circuit which melts when a predetermined value of current
flows through it and thus breaks the circuits .The protective element of the
fuse is a fuse-link inserted in series with the circuit being protected . The
most generally material used for fuse element is a low melting point
material such as tin, lead or zinc .Fuses may be low voltage type or high
voltage type : low voltage can be further divided into two classes namely
semi- enclosed rewire able fuse and the cartridge type fuse.
NEUTRAL EARTHING:
Neutral earthing of power transformer all power system operates with
grounded neutral. Grounding of neutral offers several advantages the
neutral point of generator transformer is connected to earth directly or
through a reactance in some cases the neutral point is earthed through an
adjustable reactor of reactance matched with the line.
The earth fault protection is based on the method of
neutral earthing.
6. CONTROL ROOM
7. BATTERY ROOM
Battery is the heart of power system control and protection as all the
power system protection equipment and the communication equipments
works on D.C supply. In the event of failure of station supply if standby
D.C supply is not available then it will be dangerous for the breaker and
other protective equipment so also the communication system will be
great hampered and during such emergency there will be no
communication for help or to transmit information to the concerned
authorities and the fault would be attended very late. Thus battery
installation, its commissioning and subsequent maintenance plays very
important role.
Maintenance of Battery
TECHNICAL PARTICULARS:
A) TELECOMMUNICATION
SCADA SYSTEM
SLDC Minto road has a large and active 'Mimic Board' in its Control room.
This mimic board displays single line diagram of intra State transmission
system i.e. grid network of 400KV, 220KV and important 66 KV sub-
stations, transmission lines, thermal powerhouses. Outgoing feeders,
shown in the mimic board, have 'achieve' (LED display) colored
indications, of three different colors, to show the range of power flow at
any moment i.e. 'Normal', 'Nominal' or 'Maximum' of its line capacity. For
new substations and lines, displays in active and passive forms are
required to be made in the Mimic diagram. But, Mimic Board has a
limitation that it cannot incorporate/add large volume of displays for
substations/power houses/transmission lines in 'active' form due to space
constraint and congestion. Due to this Mimic Board is going to be
supplemented with a Video Projection System (VPS) at SLDC, Minto
Road in near future. Also in SLDC & subLDCs, displays of single line
diagrams of RTU sub-stations/power house are viewed on VDUs of large
size (21").
9. Operation and Maintenance of 220KV
Substation
9.1. INTRODUCTION
HT Circuit breakers
➢ Clean the porcelains
➢ Check the connections for loose contact
➢ Check tripping through relays
➢ Check the wiring for loose contact
➢ Vermin Proofing of control box
➢ Check annunciation scheme
➢ Lubricate moving/link mechanisms wherever recommended
by manufacturer
➢
HT: CT’s, PT’s & Lightning arresters.
➢ Clean the porcelain and metal body
➢ Check connection both primary and secondary for tightness
➢ Check oil level
➢ Take IR values
➢ Check earth connection for proper contact
11 kV Switchgears
➢ Clean the breakers, panels and bus bars thoroughly, clean
insulators with CTC or Petrol
➢ Check II values of the bus bars and individuals, breakers
between phases and earth
➢ Check operation of breakers on local remote through relay
and corresponding annunciation
➢ Check and lubricate operating mechanism wherever
necessary
➢ Tighten the terminal connection of all auxiliary circuit and
wiring
➢ Check all earth connections between the panel and
electrodes for tightness and check the contact resistance of
earth connection.
➢ Check contact travel, contact erosion in VCB
➢ Check 11 kV CT’s and PT’s connections
Isolator
➢ Check jump connection and replace PG clamps, if necessary
➢ Check the alignment of isolator
➢ Cleaning and applying petroleum jelly to contacts
➢ Check clean and grease the GOS and check contacts for
erosion, clean insulator
➢ Check operation for proper closing of the insulator
➢ Check the fuses and renew the same wherever HR fuses are
provided
➢ Check the earth resistance of earthing mat and all
individual earthing if any, the resistance should be within the
prescribed limit, otherwise action should be taken to Bering
the same to within limit immediately as it is very important
aspect for the safety of the equipment in any station.
Recommended Interval
Maintenance or Test
Fault/load study and
5 years
recalculate settings
A sub station having worth crores of rupees can be scanned in two days
time for which charges for scanning comes around Rs. 30,000. By thermo
scanning any incipient fault can be identified in its initial stages if thermo
scanning is done on regular interval.
Thus damage of equipment worth of crores of rupees can be avoided
and also this technique prevents disruptions of power to
Customers in case of damage of equipment.
(d) Keep the work area clean, dry and free of obstructions.
(f) Lubricate the M/C part with both hands. Use cotton waste
brush etc.
(i) Ensure all tools are in good conditions. Look and report any
accident hazard.
(j) For any injury whether small or big get first aid first.
CONCLUSION
The architecture of the Sub-Station and the way various equipments are
linked together to work as a unit and methodological approach in working
of whole s/s is controlled renders the impression that engineering is not
just learning the structured description and working of various
equipments, but greater part is of planning proper management.
It was definitely a knowledgeable experience and pride to be a part of 220
kv Sarita Vihar s/s for such a short period of time.
No doubt it showed that mere theoretical and bookish knowledge need to
be supplemented with able practice knowledge. And this opportunity to
gain practical knowledge, imparted by very able personals of DTL at Srita
Vihar, New Delhi was a learning experience.
220 KV JAGITYAL-1
MVA
160
220 KV Vemunur
132 KV
MVA
160
220 KV
BUS COUPLER
NTPC AUTO-3
(250MVA)
220 KV
JAGITYAL-3
220 KV MEDARAM
220 KV
220 KV RFCL
220 KV MANTHANI
220 KV DURSHED-1
220 KV DURSHED-2
220KV JAGITIAL-2
220KV MURMUR
220KV MANDAMARRI
NTPC AUTO-2
(315MVA)