You are on page 1of 9

17.12.2022.

To,
The Engineer in Chief,
Sanitation (RWS&S),
Rural Water Supply &
Odisha.
Jal 'O' Parimal Bhawan, Bhubaneswar,
block
at Kalampur, Jaipatna & Junagarh
Sub: Approval of Structural design & drawings for 26 Nos ESR,s limited.
& Infrastructure
of Kalahandi District as submitted by M/s Megha Engineering

Nos ESR,s at
Dear Sir, and drawings for 26
subject,review of the structural design Engineering &
With reference to the above submitted by M/s Megha
block of Kalahandi District as
Kalampur, Jaipatna & Junagarh been approved
and drawings have
ou that the Structural design
Infrastructure limited. It's to inform
as per standard procedure.
are requested to proceed submitted
with minor observation. Also, you which are marked in
recommended to kindly include all the observations
The agency is
or as mentioned below.
structural design and drawings

General Observationfor 26 Nos ESR's at Kalahandi


in design for water retaining-M30.
1. Grade of concrete considered water retaining-M25.
in design for other than
2. Grade of concrete considered
considered in design-Fe500.
3. Grade of steel as per approved GAD.
4. During execution all the levels shall be maintained
the agency is requested
structural changes arise after finalizing vendor document;
5. Any review.
document & drawing sheets for
to resubmit both design
stabilization of soil for RCC foundation shall be ensured during
6. Proper compaction and
site execution.
contractor will have to maintain all the items
as per the tender
7. During execution the
documents. instead of the RCC Ladder
8. Agency shall provide RCC staircase (with reinforcement)
provided for safety purpose.
250 KI@ 12 m Stagingat Kulhari GP of Kalahandi District
reinforcement provided as 16@175
mm c/c
at top and bottom face,
1. In conical dome hoop
mm c/c at both face.
which shall be revised to 16@150
at top and
reinforcement provided as 3-160 ST+2-16O (Extra support)
2. In bracing beam B1
2-200-1-160 ST+2-160 (Extra support) at top and bottom.
bottom, which shall be revised to
reinforcenment provided as 3-160 ST+2-120 (Extra support) at top
and
3. In bracing beam B1a
bottom.
bottom, which shallbe revised to 2-200-1-160 ST+2-160 (Extra support) at top and
4. In column vertical
reinforcement provided as 9-160, which shall be revised to 10-200.
as 1600 mm, but as per design calculation
5. In annular raft foundation width provided
recommended as 3600mm.
as 16@175 mm c/c both ways at bottom and
6. In annular raft foundation reinforcement provided
mm c/c both ways at top, whereas
recommended as 16@125 mm c/c both ways at
12@175
bottom and 12@150 mm c/c both ways at top.
280KI@16 m Staging at Naktiguda GP of KalahandiDistrict
1. In conical dome hoop reinforcement provided as 12@125 mm c/c at top and bottom face,
which shall be revised to 16@150 mm c/c at both face.
c/c at top and bottom face,
reinforcement provided as 10@150
mm
2. In conical dome radial
which shall be revised to 12@150 mm c/c at
both face.
10@200 mm c/c from 1100 to rest of wall,
3. In container wall hoop reinforcement provided as

1100 to rest of wall.


whereas recommended as 10@175
mm c/c each face from 225mm thk
200 thick at edge, which shall be revised to
4. Bottom dome thickness provided
as mm

at edge.
recommended as 250 mm.
In conical wall thickness provided as 225mm, whereas
5. at top and
4-160 ST+3-160 (Extra support)
reinforcement provided as
6. In bracing beam B1
at top and bottom.
to 3-200 ST+3-160 (Extra support)
bottom, which shall be revised
ST+2-160 (Extra mid) at
beam longitudinal reinforcement provided as 4-160
7. In bottom ring
to 4-200 ST+2-160 (Extra mid)
at bottom.
ottom, which shall be revised at top and
reinforcement provided as 4-160
ST+2-160 (Extra support)
8. In bracing beam B1a
at top and bottom.
which shall be revised to 3-200 ST+2-120 (Extra support)
bottom,
as 9-200, which shall
be revised to 11-200.
9. In column vertical reinforcement provided calculation
as per design
foundation width provided as 1850 mm, but
10.In annular raft
recommended as 2000mm.

280KI@16 m Staging at Talamala GP ofKalahandi District


as 12@125 mm c/c at top and bottom face,
1. In conical dome hoop reinforcement provided
which shall be revised to 16@150 mm c/c at
both face.
provided as 10@150 mm c/c at top and bottom face,
2. In conical dome radial reinforcement
which shall be revised to 12@150 mm c/c at both face.
to 225mm thk
3. Bottom dome thickness provided as 200 mm thick at edge, which shall be revised
at edge. wall,
10@200 mm c/c from 1100 to rest of
4. In container wall hoop reinforcement provided as

c/c each face from 1100 to rest of wall.


whereas recommended as 10@175 mm

recommended as 250 mm.


5. In conical wall thicknessprovided as 225mm, whereas
at top and
reinforcement provided as 4-160 ST+3-160 (Extra support)
6. In bracing beam B1
4-200 ST+3-160 (Extra support) at top and bottom.
bottom, which shall be revised to
at top and
reinforcement provided as 4-160 ST+2-160 (Extra support)
7. In bracing beam B1a
3-200 ST+3-120 (Extra support) at top and bottom.
bottom, which shall be revised to
reinforcement provided as 4-160 ST+2-160 (Extra mid) at
8. In bottom ring beam longitudinal
ST+2-160 (Extra mid) at bottom.
bottom,which shall be revised to 4-200
reinforcement provided as 9-200, which shall be revised to 11-200.
9. In column vertical
270KI@16 m Staging at Prattap Pur GP of KalahandiDistrict
hoop reinforcementprovided as 12@125 mm c/c at top and bottom face,
1. In conical dome
which shall be revised to 16@150 mm c/c at both face.
2. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,
face.
which shall be revised to 12@150 mm c/c at both
Bottom dome thickness provided as 200 mm
thick at edge, which shall be revised to 225mm thk
3.
at edge.
4. In conical wall thickness provided as 225mm, whereas recommended as 250 mm.

5. In bracing beam B1 reinforcement provided as 4-160 ST+3-160 (Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-200 (Extra support) at top and bottom.
beam B1a reinforcement provided as 4-160 ST+2-160 (Extra support) at top and
6. In bracing
bottom, which shall be revised to 3-200 ST+3-120 (Extra support) at top and bottom.
reinforcement provided as 4-160 ST+2-160 (Extra mid) at
7. In bottom ring beam longitudinal
ST+2-160 (Extra at bottom.
mid)
bottom, which shall be revised to 4-200
to 10-200.
8. In column vertical
reinforcement provided as 9-200, which shall be revised
as per design
calculation
foundation width provided as 1700 mm, but
9. In annular raft
recommended as 1900mm.
District
220 KI@ 16 mStaging at Bhainripali GP of Kalahandi top and bottom face,
reinforcement provided as 12@125 mm c/c at
1. In conical dome hoop
both face.
which shal be revised to 16@175mm c/c at
c/c at top and bottom face,
dome radial reinforcement provided as 10@150
mm
2. In conical
which shall be revised to 12@175 mm c/c at both face.
revised to 225mm thk
3. Bottom dome thickness provided as 200 mm thick at edge, which shall be
at edge.
4-160 ST+3-160 (Extra support) at top and
4. In bracing beam B1 reinforcement provided as

bottom, which shall be revised to 3-200 ST+3-160 (Extra


support) at top and bottom.
at top and
as 4-160 ST+2-120 (Extra support)
5. In bracing beam B1a reinforcement provided
bottom, which shall be revised to 3-200 ST+2-120 (Extra
support) at top and bottom.
as 4-160 ST+2-16O (Extra
at mid)
6. In bottom beam longitudinal reinforcement provided
ring
ST+2-160 (Extra mid) at bottom.
bottom, which shall be revised to 2-200+2-160
reinforcement provided as 9-200, which shall be
revised to 10-200.
7. In column vertical

230 KI@ 15 mStagingat Gandameher GP of Kalahandi District


mm at and
12@125 c/c top bottom face,
1. In conical dome hoop reinforcement provided as

which shall be revised to 16@175mm c/c at both face.


provided as 10@200 mm c/c at top and bottom face,
2. In conical dome radial reinforcement
which shall be revised to 12@175 c/c at both face.
mm

ST+2-160 (Extra support) at top and


3. In bracing beam B1 reinforcement provided as 4-160
at top and bottom.
bottom, which shall be revised to 3-200 ST+3-160 (Extra support)
4. In bracing beam B1a reinforcement provided as
4-160 ST at top and bottom, which shall be
revised to 3-200 ST at top and bottom.
thick at edge, which shall be revised to 225mm thk
5. Bottom dome thickness provided as 200 mm

at edge.
recommended as 600x900mm.
6. In bottom ring beam size provided as 450x1050mm, whereas
shall be
7. In bottom ring beam longitudinal reinforcement provided as 4-200 ST at bottom, which
revised to 4-200 ST+2-160 (Extra mid) at bottom.
8. In column size provided as 450x450mm, whereas recommended as 6000.
9. In column vertical reinforcement provided as 4-200+4-160, which shall be revised to 10-200.
10.in foundation ring beam size provided as 550x750mm, which shall be revised to 700x900mm.
11.in foundation ring beam longitudinal reinforcement provided as 4-160 at top, whereas
recommended as 5-160 (ST) at top.
12.In annular raft foundation width provided as 1550 mm, but as per design calculation
recommended as 2000mm.
13.In foundation reinforcement radial and hoop reinforcement provided as 12@150 c/c radial &
12@175 mm c/c hoop at bottom face, which shal be revised to 16@200 c/c radial & 12@175
mm c/c hoop at bottom face.

130KI@ 16mStagingat BoxitulasipaliGP of KalahandiDistrict


reinforcement provided as 12@200 mm c/c at top and bottom face,
1. In conical dome hoop
which shall be revised to 12@175mm c/c at both face.
at top and
as 4-160 ST+3-160 (Extra support)
2. In bracing beam B1 reinforcement provided
at top and bottom.
bottom, which shall be revised to 3-200 ST+3-160 (Extra support)
at top and
as 4-160 ST+2-120 (Extra support)
3. In bracing beam B1a reinforcement provided
at top and bottom.
bottom, which shall be revised to 3-200 ST+3-120 (Extra support)
170 KI@ 10 mStaging at Burdi GP of Kalahandi District
hoop reinforcement provided as 12@150 mm c/c at top and bottom face,
1. In conical dome
which shall be revised to 12@125mm c/c at both face.
mm c/c at top and bottom face,
2. In conical dome radial reinforcement provided as 10@200
which shall be revised to 12@175 mm c/c at both face.
which shall be revised to 225mm thk
3. Bottom dome thickness provided as 200 mm thick at edge,
at edge.
provided as 225mm, whereas recommended as 250
mm.
4. In conical wall thickness
shall be
5. In bracing beam B1 reinforcement provided as 4-160 ST at top and bottom, which
revised to 3-200 ST+2-120 (Extra support) at top and bottom.
1500 mm, but as per design calculation
6. In annular raft foundation width provided as

recommended as 1700 mm.

160KI12 mStaging at Nuagaon GP of Kalahandi District


1. Bottom dome thickness provided as 200 mm thick at edge, which shall be revised to 225mm thk

at edge.
2. In conical wall thickness provided as 225mm, whereas recommended as 250 mm.
3. In bracing beam B1 reinforcement provided as 3-160 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-160 (Extra support) at top and bottom.
4. In column vertical reinforcement provided as 7-200, which shall be revised to 9-200.

350KI@15mStagingat Atigaon GP of KalahandiDistrict


1. In bracing beam B1 reinforcement provided as 3-200 ST+2-160 (Extra support) at t
bottom, which shall be revised to 3-200 ST+3-160 (Extra support) at top and bottom.
2. In column vertical reinforcement provided as 8-200, which shall be revised to 10-20o.
3. In annular raft foundation width provided as 2000 mm, but as per design calculation
recommended as 2500 mm.
4. In design calculation SBC is taken as 30 t/sqm, but soil report recommended as SBC 24 t/sqm for
3 m depth. Kindly review and revise the design and drawing accordingly.
350
KL@15 mStagingat AtigaonGP of Kalahandi District
1. In bracing beam B1 reinforcement provided as 3-200 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 3-200 sT+3-160 (Extra support) at top and bottom.
2. In column vertical reinforcement provided as 8-200, which shall be revised to 10-200.
3. In annular raft foundation width provided as 2600 mm, but as per design calculation
recommended as 2850 mm.
340KI@ 18 mStaging at Plpalguda GP of Kalahandi District
1. In bracing
beam B1 reinforcement provided as 3-2000 ST+2-160
(Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-200 (Extra support) at top and bottom.
2. In bracing
beam B1a reinforcement provided as 4-160 ST+2-120
(Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-120 (Extra at support)
and top bottom.
be
beam longitudinal reinforcement provided as 4-160 ST at bottom, which shall
3. In bottom ring
evised to 4-200 ST+2-160 (Extra mid) at bottom.
whereas
4. In bottom dome reinforcement 10@200 mm c/c both ways both face,
provided as

recommended as 10@175 mm c/c both ways both face.


mm c/c at top and bottom face,
5. In conical dome radial reinforcement provided as 10@150
which shall be revised to 12@175 mm c/c at both face.
which shall be revised to 225mm thk
6. Bottom dome thickness provided as 200 mm thick at edge,
at edge.
to 14-200.
7. In column vertical reinforcement provided as 12-200, which shall be revised
330KI@20 mStagingat Mangalpur GP of Kalahandi District
ST+3-160 (Extra support) at top and
1. In bracing beam B1 reinforcement provided as 4-200
at top and bottom.
bottom, which shall be revised to 4-200 ST+3-200 (Extra support)
2. In bracing beam B1a reinforcement provided as 4-160
ST+2-12o (Extra support) at top and
at top and bottom.
bottom, which shall be revised to 3-200 ST+3-160 (Extra support)
3. Bottom dome thickness provided as 200 mm thick at edge,
which shall be revised to 225mm thk

at edge.
4. In annular raft foundation width provided as 1700 mm, but as per design calculation
recommended as 2400 mm.
5. In foundation reinforcement provided as 16@150 mm c/c radial & 12@175 mmc/c hoop at
bottom and 12@175 mm c/cboth ways top, whereas recommended as 16@125 mm c/c radial
&12@150 mm c/c hoop at bottom and 12@150 mm c/c both ways at top.
320 KI@22 mStaging at Pandigaon GP of kalahandiDistrict at top and
1. In bracing beam B1 reinforcement provided as 4-200 ST+3-160 (Extra support)
bottom, which shall be revised to 4-200 ST+3-200 (Extra support) at top and bottom.
2. In bracing beam B1a reinforcement provided as 4-160 ST+2-16o (Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-160 (Extra support) at top and bottom.
3. Bottom dome thickness provided as 200 mm thick at edge, which shall be revised to 225mm thk
at edge.
4. In bottom dome reinforcement provided as 10@200 mm c/c both ways both face, whereas
recommended as 10@175 mm c/c both ways both face.
5. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,
which shall be revised to 12@175 mm c/c at both face.
6. In annular raft foundation width provided as 1850 mm, but as per design calculation
recommended as 2400 mm.
7. In foundation reinforcement provided as 16@150 mm c/c radial & 12@175 mm c/c hoop at
bottom and 12@175 mm c/c both ways top, whereas recommended as 16@125 mm c/c radial
&12@150 mm c/c hoop at bottom and 12@150 mm c/c both ways at top.
320 KI@20 mStagingat Dundelmal GP ofkalahandi District
1. In bracing beam B1 reinforcement provided as 4-200 ST+3-160 (Extra support) at top and
bottom, which shall be revised to 4-200 ST+3-200 (Extra support) at top and bottom.
2. In bracing beam Bla reinforcement provided as 4-160 ST+2-160 (Extra support) at
bottom, which shall be revised to 3-200 ST+3-160 (Extra support) at top and bottom.
3. In foundation reinforcement provided as 16@150 mm c/c radial at bottom, whereas
recommended as 16@125 mm c/c radial at bottom.
4. In column vertical reinforcement provided as 9-250, which shall be revised to 11-250.
300 KI@12 m Staging at Baladiama GP of kalahandi District
1. In bracing beam B1 reinforcement provided4-160 ST+2-120 (Extra support) at top and
as

bottom, which shall be revised to 3-200ST 3-120 (Extra support) at top and bottom.
2. In bracing beam size provide 300x450, which shall be revised to 400x500mm.
3. Bottom dome thickness provided as 200 mm thick at edge, which shall be revised to 225mm thk
at edge.
4. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,
which shall be revised to 12@175 mm e/c at both face.
5. In annular raft foundation width provided as 1600 mm, but as per design calculation

recommended as 1900 mm.


6. In foundation reinforcement provided as 12@175 mm c/c radial at bottom, whereas
recommended as 16@150 mm c/c radial at bottom.
7. In column vertical reinforcement provided as 9-200, which shall be revised to 10-200.

360 KI@18 mStagingat Talpadar GP of kalahandiDistrict


1. Bottom dome thickness provided as 200 mm thick at edge, which shall be revised to 225mm thk
at edge.
2. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,
which shall be revised to 12@175 mm c/c at both face.
3. In annular raft foundation width provided as 1850 mm, but as per design calculation
recommended as 2100 mm.
4. In column vertical reinforcement provided as 12-200, which shall be revised to 14-200.
5. In bottom dome reinforcement provided as 10@200 mm c/c both ways both face, whereas
recommended as 10@175 mm c/c both ways both face.
6. In bottom ring beam longitudinal reinforcement provided as 4-160 ST + 2-160 (Extra mid) at
bottom, which shall be revised to 4-200 ST+2-160 (Extra mid) at bottom.

360KI@18 mStagingat S, kandmal GP of kalahandiDistrict


1. Bottom dome thickness provided as 200 mm thick at edge, which shall be revised to 225mm thk
at edge.
2. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,
which shall be revised to 12@175 mm c/c at both face.
3. In annular raft foundation width provided as 1850 mm, but as per design calculation
recommended as 2500 mm.
4. Tank foundation depth provided as 3.0 m, but as per soil report recommended as 4.5 m.
5. In column vertical reinforcement provided as 12-200, which shall be
revised to 14-200.
6. In bottom dome reinforcement provided as 10@200 mm c/c both ways both
face, whereas
recommended as 10@175 mm c/c both ways both face.
7. In bottom ring beam longitudinal reinforcement
provided4-160 ST + 2-160 (Extra mid) at
as
bottom, which shall be revised to 4-200 ST+2-160
(Extra mid) at bottom.
8. In foundation reinforcement
provided 16@175 mm c/c radial & 12@175 mm c/c hoop at
as
bottom and 12@175 mm c/c both ways top, whereas
recommended as 16@100 mm c/c radial
&12@125 mm c/c hoop at bottom and 12@125 mm c/c both
ways at top.
340 KI@ 22m Staging at Deydara GP of kalahandi District
1. In bottom dome reinforcement provided as 10@200 mm c/c both ways both face, whereas
recommended as 10@175 mm c/c both ways both face.
2. In bracing beam B1 reinforcement provided as 4-20o ST+3-200 (Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-200 (Extra support) at top and bottom.
3. In bracing beam B1 reinforcement provided as 4-160 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 4-160 ST+3-160 (Extra support) at top and bottom.

390KI@ 15m Stagingat BalagaonGP of kalahandi District


1. In bracing beam B1 reinforcement provided as 3-200 ST+3-160 (Extra support) at top and
bottom, which shall be revised to 3-20o ST+3-160 (Extra support) at top and bottom.
2. In bracing beam B1 reinforcement provided as 3-160 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 3-160 ST+3-160 (Extra support) at top and bottom.
3. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,

which shall be revised to 12@175 mm c/c at both face.


4. In column vertical reinforcement provided as 9-200, which shall be revised to 11-200.

5. In raft foundation outer projection provided as 600 mm, but as per design calculation
recommended as 1000 mm.
6. In container wall thickness provided as 200mm, whereas recommended as 250mm.

380KI@18 mStaging at Kuchagaon GP of kalahandiDistrict at top and


1. In bracing beam B1 reinforcement provided as 4-200 ST+3-160 (Extra support)
bottom.
bottom, which shall be revised to 4-200 ST+3-200 (Extra support) at top and
at top and
2. In bracing beam B1 reinforcement provided as 4-160 ST+2-160 (Extra support)
and bottom.
bottom, which shall be revised to 3-200 ST+2-160 (Extra support) at top
3. In conical dome radial reinforcement provided as 10@150 mm c/c at top and bottom face,

which shall be revised to 12@175 mm c/c at both face.


4. In column vertical reinforcement provided as 12-200, which shall be revised to 14-2000
5. In container wall thickness provided as 200mm, whereas recommended as 250mm.
6. In bottom dome reinforcement provided as 10@200 mm c/c both ways both face, whereas
recommended as 10@175 mm c/c both ways both face.
470KI@ 18 mStaging at Ranamal GP of kalahandi District
1. In bracing beam B1 reinforcement provided as 4-160 ST+4-160 (Extra support) at top and
bottom, which shall be revised to 4-2000 ST+4-160 (Extra support) at top and bottom.
2. In bracing beam B1 reinforcement provided as 4-160 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 4-160 ST+4-160 (Extra support) at top and bottom.
3. In conical dome radial rinforcement provided as 10@150 mm c/c at top and bottom face,
which shall be revised to 12@125mm c/c at both face.
4. In conical wall thickness provided as 275mm, whereas recommended as 300mm.
5. In bottom ring beam reinforcement provided as 4-200 ST+2-200 (Extra support) at top and 4
200 ST at bottom, which shall be revised to 4-200 ST+3-200 (Extra support) at top and 4-200
ST+3-200 (Extra mid) at bottom.
450 KI@18mStaging at PalashGP of kalahandiDistrict
1. In bracing beam B1 reinforcement provided as 4-160 ST+4-160 (Extra support) at top and
bottom, which shall be revised to 4-200 ST+4-160 (Extra support) at top and bottom.
2. In bracing beam B1 reinforcement provided as 4-160 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 4-160 ST+4-160 (Extra support) at top and bottom.
3. In conical wall thickness provided as 275mm, whereas recommended as 300mm.
4. In bottom ring beam
4-200 ST+2-200
reinforcement provided as 4-200 ST at
(Extra mid) at bottom, which shall be revised to
5. In annular raft bottom.
foundation width provided
recommended as 2000 mm. as 1800 mm, but as per design calculation
6. In annular raft foundation
shall be revised to 16
reinforcement provided as 16@200 c/c radial at bottom face, which
@175 mm c/c radial at bottom face.
1. In
520 Kl@ 22 m Staging at Bandigaon GP of kalahandi District
bracing beam B1 reinforcement
provided as 4-200 ST+4-160 (Extra support) at top and
bottom, which shall be revised to 4-200
2. In bracing beam B1
ST+3-200 (Extra support) at top and bottom.
reinforcement provided as 4-160 ST+4-120 (Extra
bottom, which shall be revised to 4-160 support) at top and
3. In bottom
ST+4-160 (Extra support) top
at and bottom.
ring beam reinforcement provided as 4-200
shall be revised to 4-200 ST+4-160 (Extra mid) at bottom, which
ST+3-200 (Extra mid) at bottom.
4. In annular raft
foundation width provided as 1700 mm, but as
per design calculation
recommended as 2200 mm.
5. In conical dome radial
reinforcement provided as 10@150 mm c/c at top and bottom face,
which shall be revised to 12@125mm c/c at both face.

630KI@ 16 mStaging at Uchhala GP of kalahandi District


1. Inbracing beam B1 reinforcement provided as 4-160 ST+3-160 (Extra
support) at top and
bottom, which shall be revised to 4-200 ST+3-200 (Extra
support) top and bottom.
at
2. In bracing beam B1 reinforcement
provided as 4-160 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 3-200 ST+3-160 (Extra support) at top and bottom.
3. In bottom ring beam reinforcement
provided as 4-200 ST+2-200 (Extra mid) at bottom, which
shall be revised to 4-20D ST+3-200 (Extra mid) at bottom.
4. In annular raft foundation width
provided as 1700 mm, but as per design calculation
recommended as 2250 mm.
5. In conical dome radial reinforcement provided as 12@175 mm c/c at top and bottom face,
which shall be revised to 12@125mm c/c at both face.
6. In annular raft foundation reinforcement provided as 16@200 c/c radial at bottom face, which
shall be revised to 16 @150 mm c/c radial at bottom face.
7. In conical wall thickness provided as 300mm, whereas recommended as 325 mm.
8. In container wall thickness provided as 200 to 225 mm thick, whereas recommended as 250mm
throughout.

600 KI@ 18 mStagingat Biimara GP of kalahandi District


1. In bracing beam B1 reinforcement
provided as 4-200 ST+2-160 (Extra support) at top and
bottom, which shall be revised to 4-200 ST+3-200 (Extra support) at top and bottom.
2. In bracing beam B1 reinforcement provided
4-160 ST+2-160 (Extra support) at top and
as
bottom, which shall be revised to 3-200 ST+3-160 (Extra support) at top and bottom.
3. In bottom ring beam reinforcement provided as 4-2000 ST+2-160 (Extra mid) at bottom, which
shall be revised to 4-200 ST+3-200 (Extra mid) at bottom.
4. In annular raft foundation width provided as 1700 mm, but as per design calculation
recommended as 2200 mm.
10@150 mm c/c at top and bottom face,
5. In conical dome radial reinforcement provided as

which shall be revised to 12@125mm c/c at both face.


at bottom face, which
radial
6. In annular raft foundation reinforcement provided as 16@175 c/c
shall be revised to 16@150 mm c/c radial at bottom face.
325 mm.
provided as 300mm, whereas recommended
as
7. In conical wall thickness
whereas recommended as 250mm
8. In container wall thickness provided as 200 to 225 mm thick,
throughout.

Yours Sincerely,
Yours Sincerely,

Lagnajit Das
Mudit Kumar Verma
Team Leader (Design Cell, RWS&S)
Structural Engineer (Design Cell, RWS&S)