Circuit breaker testing with CIBANO 500

Different ways to measure Motor Current

12 April 2021
Motor current test

Motivation Measurement done


▪ Detect if motor or operating mechanism ▪ Supply motor and record the current
drive is in good health
▪ Not sufficient lubrication ▪ Use a current clamp to record the
▪ State of the spring/hydraulic/pneumatic current when motor supplied from
drives station battery

Analysis
▪ Charging time
▪ Compare against manufacture values
▪ Comparing to previous results

▪ Inrush current
▪ Compare against manufacture values
▪ Comparing to previous results

▪ Current trace
▪ Graphical comparison

© OMICRON Page 2
Motor Current test with CIBANO 500 internal source

▪ Method for ganged LV/MV/HV circuit breakers


▪ Is an invasive measurement method
▪ Undervoltage and/or overvoltage supply tests can be performed
▪ Perform test with reduced supply voltage (e.g. 70/85%)
▪ Perform test with increased supply voltage (e.g. 110%)

© OMICRON Page 3
Motor Current test with CIBANO 500 internal source

▪ Method for testing IPO MV/HV circuit breakers


▪ Is an invasive measurement method
▪ Undervoltage and/or overvoltage supply tests can be performed
▪ Perform test with reduced supply voltage (e.g. 70/85%)
▪ Perform test with increased supply voltage (e.g. 110%)

© OMICRON Page 4
Motor Current test with external supply (station battery)

▪ Method for testing ganged MV/HV circuit breakers


▪ Is an invasive measurement method
▪ Used to check the condition of the station battery

© OMICRON Page 5
Motor Current test with external supply (station battery)

▪ Method for testing IPO MV/HV circuit breakers


▪ Is an invasive measurement method
▪ Used to check the condition of the station battery

© OMICRON Page 6
Motor Current test with current clamp with trigger

▪ Method for testing ganged MV GIS/HV circuit breakers


▪ Method is invasive when motor voltage is used as trigger
▪ Method is a non-invasive when current clamp is used as trigger

© OMICRON Page 7
Motor Current test with current clamp with trigger

▪ Method for testing IPO MV/HV circuit breakers


▪ Method is invasive when motor voltage is used as trigger
▪ Method is a non-invasive when current clamp is used as trigger

© OMICRON Page 8
Motor Current test with current clamp without trigger

▪ Method for testing ganged MV GIS/HV circuit breakers when,


▪ trigger signal is not available
▪ the trigger threshold is not known

▪ It is a non-invasive measurement method

© OMICRON Page 9
Motor Current test with current clamp without trigger

▪ Method for testing IPO MV/HV circuit breakers when,


▪ trigger signal is not available
▪ the trigger threshold is not known

▪ It is a non-invasive measurement method

© OMICRON Page 10