STRUCTURAL CALCULATIONS

FOR BLOCKS 107 & 206 TO 210 SUBSTRUCTURE AND


FIRST FLOOR

SE1146

Greenwich Millennium Village Phase 2

August 2015
Rev A

Ref: SE1146-DC-01
SE1146
Greenwich Millennium Village Phase 2
Greenwich

STRUCTURAL ENGINEERING
CALCULATIONS

Abstract: Package of design calculations covering the substructure and superstructure design
up to first floor for buildings 107 & 206 to 210

Prepared by: Alan Werrett Date: August 2015

Checked by: Matthew Jones Date: August 2015

Report Issue

Revision Date Notes

A 21/08/15 Building control first issue

This report has been prepared by Iesis Special Structures for the sole use of
the client. It may not be assigned to, relied upon or used by any third party in
part or in whole without the written permission of Iesis Special Structures.
Iesis Special Structures GMV2
Consulting Civil & Structural Engineers

CONTENTS

DESIGN STATEMENT 1

SUMMARY SHEET 2

LOADINGS 3

SUBSTRUCTURE 4

STABILITY 23

GROUND FLOORS 88

FIRST FLOORS 108


SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

DESIGN STATEMENT

The proposed development consists of six new residential buildings as part of the wider Greenwich
Millennium Village development.

The site is split into two zones, Hornlink Way forms the Southern and Eastern boundaries to the site
of blocks 107 & 206-210 with Pear Tree Way forming the Western boundary. To the North the site is
bounded by the first phase of the development (blocks 106 and 109). Block 103 is further North,
adjacent to block 104 of the first phase.

The design proposal for the superstructure is a reinforced concrete frame with flat slabs wherever
practicable. This solution has been chosen because of the residential usage, the number of storeys in
the building and to minimize the size of elements being delivered to site.

Please see the accompanying design philosophy statement for further details and rationale on the
design of the structure.

1
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

SUMMARY SHEET

Job No. SE1146 Date 07/08/15

Client GMVL Prepared by AW

Project GMV Buildings 107 & 206 to 210 Checked by MJ

Building Regulations Authority Approved Inspector – Butler and Young

Design Codes BS5950-1 : 2000


BS6399-1 : 1996
BS6399-2 : 1997
BS6399-3 : 1988
BS8002 : 1994
BS8110-1 : 1997
BS8110-2 : 1985

Intended Use of Structure Residential

Progressive Collapse Class Varies, class 2A to 2B - Horizontal and vertical ties to be provided

Wind Loading Conditions Basic Wind Speed, 21 m/s


Vs
Building Type: Framed Building with Structural Walls Around Lift
Shaft
Terrain Category: Town

Any Special Exposure Conditions Design Chemical Class for buried concrete DC-4
Exposure Class XC1 for internal concrete

Subsoil Conditions A significant depth of made ground over alluvium subsoils and river
terrace deposits

Foundation Types CFA piled foundations and pile caps

Material Grades/Strengths Concrete generally grade C32/40, columns below 4th floor to be grade
C50/60

Any Other Relevant Information Fire period to blocks 107 and 210 to be 90 minutes, remaining blocks 60
(e.g. fire requirements) minutes

2
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

LOADINGS

Typical floors

Dead Load (kN/m2) Imposed Load (kN/m2)

Slab Self Weight Depth x 24 Residential 1.5

Services and ceiling 0.3

Screed and finishes 1.8 Partitions 1.0

Total S.W + 2.1 Total 2.5

Other imposed loads

Intensity of Concentrated
distributed load load
Value of loading Value of loading
(kN/m2) (kN)
Corridors, hallways, Corridors, hallways,
3.0 4.5
stairs, landings stairs, landings

Toilets & bathrooms 2.5 Toilets & bathrooms -

1.5 per m run


concentrated at
Balconies 1.5 Balconies
outer edge.
1.0 at 1m
centres
Plant rooms 7.5 Plant rooms 4.5

Roof with access 1.5

3
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

SUBSTRUCTURE

Each of the buildings has been modelled in ETABS analysis software and the foundation loads
extracted (these loads include the wind element from the stability design covered later in this report).
These have been hand checked by way of an area load take down for typical columns.

Pile caps have been designed using a combination of SCALE and the TCC concrete design
spreadsheets with the worst case caps being designed. Unusual load arrangements or geometry has
been designed individually.

The following pages cover the Foundation loadings and the design of the pile caps.

4
SE1146-DC-01 Rev A

5
SE1146-DC-01 Rev A

6
SE1146-DC-01 Rev A

7
SE1146-DC-01 Rev A

8
SE1146-DC-01 Rev A

9
SE1146-DC-01 Rev A

10
SE1146-DC-01 Rev A

11
SE1146-DC-01 Rev A

Project GMV Blocks 107 & 206 to 210 IESIS SPECIAL STRUCTURES
Client BYUK Made by Date Page
Location Typical ajw 23-Jun-15 1
Double Pilecap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146

MATERIALS fcu 40 N/mm² h agg 20 mm γc 1.5 concrete


fy 500 N/mm² T&S cover 50 mm γs 1.15 steel
Pile capacity 800 kN Btm cover 75 mm steel class A
min link Ø 8 mm
DIMENSIONS mm Conc density 24 kN/m³
COLUMN PILECAP
→ = 600 A= 400
↑ = 200 B= 1500
C= 400
Pile Ø = 500 E= 750
Tolerance = 150 depth H = 850

COLUMN ACTIONS kN, kNm characteristic


DEAD IMPOSED WIND
Axial (kN) 1100 460 0 PLOT (to scale) KEY
M (kNm) 0 0 0
H (kN) 0 0 0 STATUS VALID DESIGN

REINFORCEMENT PILE REACTIONS kN


BOTTOM M = 915.0 kNm PILE 1 PILE 2
d = 754.5 mm, As = 2,965 mm² Gk + Qk 798.8 798.8
7 H25 B = 3,436 mm² Gk + Qk +Wk 798.8 798.8
TOP M = 0.0 kNm
d = 784.0 mm, As min = 884 mm²
5 H16 T = 1,005 mm² 5 H16 02 T
LINKS
V = 1160.8 kN, v = 1.923 N/mm²
vc 1.5d/av = 1.387 N/mm² 7 H25 01 B
(v - vc)b = 429.2 N/mm Links 6 H8 03.250 + 3x6 H8 04.250
5 Legs H8 @ 250 LINKS = 437.1 N/mm ELEVATION

12
SE1146-DC-01 Rev A

Project GMV Blocks 107 & 206 to 210 IESIS SPECIAL STRUCTURES
Client BYUK Made by Date Page
Location Pilecap F13 ajw 23-Jun-15 1
Triple Pilecap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146
DIMENSIONS mm
COLUMN PILECAP
→ = 600 A= 400
↑ = 200 B= 1500
C= 1300
Pile Ø = 500 E= 433.33
Min spacing = 1500 depth H = 850
Tolerance = 150

COLUMN ACTIONS kN, kNm characteristic PLOT (to scale) KEY


DEAD IMPOSED WIND
Axial (kN) 1520.0 800.0 STATUS VALID DESIGN
Mx (kNm)
My (kNm) PILE REACTIONS kN characteristic
Hx (kN) PILE 1 PILE 2 PILE 3
Hy (kN) Gk + Qk 799.5 799.5 799.5
Gk + Qk +Wk 799.5 799.5 799.5
REINFORCEMENT
EW (2-3) M = 1,055.4 kNm, b = 1,200 mm
d = 749.0 mm, As = 3,412 mm² 5 H12 06 T1
5 H32 B = 4,021 mm²

V = 1,172.7 kN, bv = 1,200 mm 5 H32 05 B1


v = 1.305 N/mm², (v-vc)b = 480 N/mm Links 6 H10 07 350 + 3x6 H10 08 350
5 Legs H10 @ 350 LINKS = 488 N/mm ↑ ELEVATION

NS (1-2/3) M = 1,133.6 kNm, b = 2,146 mm


d = 715.0 mm, As = 3,839 mm² 5 H12 10 T2
5 H32 B = 4,021 mm²

V = 1,172.7 kN, bv = 1,435 mm 5 H32 09 B2


v = 1.143 N/mm², (v-vc)b = 574 N/mm Links 4 H12 11 425 + 3x4 H12 12 425
5 Legs H12 @ 425 LINKS = 579 N/mm ← ELEVATION

13
SE1146-DC-01 Rev A

Project GMV Blocks 107 & 206 to 210 IESIS SPECIAL STRUCTURES
Client BYUK Made by Date Page
Location Pilecap E12 ajw 21-Aug-15 1
4 Pile Cap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146

DIMENSIONS mm PILECAP
COLUMN A= 400
→ = 200 B= 1500
↑ = 600 C= 1500
D= 750
Pile Ø = 500 E= 750
Tolerance = 150 depth H = 850

COLUMN ACTIONS kN, kNm characteristic PLOT (to scale) KEY


DEAD IMPOSED WIND
Axial (kN) 1600.0 1490.0 STATUS VALID DESIGN
Mx (kNm)
My (kNm) PILE REACTIONS kN
Hx (kN) PILE 1 PILE 2 PILE 3 PILE 4
Hy (kN) Gk + Qk 799.5 799.5 799.5 799.5
Gk + Qk +Wk 799.5 799.5 799.5 799.5
REINFORCEMENT
EW(1/3-2/4) M = 1,910.0 kNm, b = 2,300 mm
d = 762.5 mm, As = 6,065 mm² 5 H20 14 T1
13 H25 B1 = 6,381 mm²

V = 2,387.5 kN, bv = 2,300 mm 13 H25 13 B1


v = 1.361 N/mm², (v-vc)b = 920 N/mm 6 Link Legs
5 Legs H12 @ 250 LINKS = 984 N/mm ↑ ELEVATION

NS(1/2-3/4) M = 1,432.5 kNm, b = 2,300 mm


d = 737.5 mm, As = 4,703 mm² 6 H20 16 T2
10 H25 B2 = 4,909 mm²

V = 2,387.5 kN, bv = 2,300 mm 10 H25 15 B2


v = 1.408 N/mm², (v-vc)b = 920 N/mm Links 6x8 H12 17 300
6 Legs H12 @ 300 LINKS = 984 N/mm ← ELEVATION

14
SE1146-DC-01 Rev A

Project GMV Blocks 107 & 206 to 210 IESIS SPECIAL STRUCTURES
Client BYUK Made by Date Page
Location Pilecap D11 ajw 21-Aug-15 1
5 Pile Cap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146
DIMENSIONS mm
COLUMN PILECAP
→ = 200 A= 400
↑ = 600 B= 1500
C= 2600
Pile Ø = 500 D= 750
Min spacing = 1500 E= 1300
Tolerance = 150 depth H = 850

COLUMN ACTIONS kN, kNm characteristic PLOT (to scale) KEY


DEAD IMPOSED WIND
Axial (kN) 2000.0 1825.0
Mx (kNm)
My (kNm) STATUS VALID DESIGN
Hx (kN)
Hy (kN)

PILE REACTIONS kN
PILE 1 PILE 2 PILE 3 PILE 4 PILE 5
Gk + Qk 796.9 796.9 796.9 796.9 796.9
Gk + Qk +Wk 796.9 796.9 796.9 796.9 796.9

REINFORCEMENT
EW(1/3-2/4) M = 1,901.9 kNm, b = 3,400 mm
d = 730.5 mm, As = 6,303 mm² 8 H20 19 T2
13 H25 B2 = 6,381 mm²

V = 2,377.3 kN, bv = 3,400 mm 13 H25 18 B2


v = 0.957 N/mm², (v-vc)b = 1,360 N/mm Links 8x11 H12 20 200
8 Legs H12 @ 200 LINKS = 1,967 N/mm ↑ ELEVATION

NS(1/2-3/4) M = 2,733.9 kNm, b = 2,300 mm


d = 759.0 mm, As = 8,823 mm² 6 H20 22 T1
11 H32 B1 = 8,847 mm²

V = 2,377.3 kN, bv = 2,300 mm 11 H32 21 B1


v = 1.362 N/mm², (v-vc)b = 1,317 N/mm 8 Link Legs
6 Legs H12 @ 200 LINKS = 1,475 N/mm ← ELEVATION

15
SE1146-DC-01 Rev A

Project GMV Blocks 107 & 206 to 210 IESIS SPECIAL STRUCTURES
Client BYUK Made by Date Page
Location Pilecap C10 ajw 21-Aug-15 1
6 Pile Cap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146

DIMENSIONS mm PILECAP
COLUMN A= 350
→ = 200 B= 1500
↑ = 2000 C= 1500
D= 750
E= 0
depth H = 850
Pile Ø = 500
Min spacing = 1500
Tolerance = 150

COLUMN ACTIONS kN, kNm characteristic PLOT (to scale) KEY


DEAD IMPOSED WIND
Axial (kN) 2400.0 2200.0
Mx (kNm) STATUS VALID DESIGN
My (kNm)
Hx (kN)
Hy (kN)

PILE REACTIONS kN
PILE 1 PILE 2 PILE 3 PILE 4 PILE 5 PILE 6
Gk + Qk 794.3 794.3 794.3 794.3 794.3 794.3
Gk + Qk +Wk 794.3 794.3 794.3 794.3 794.3 794.3

REINFORCEMENT
EW(1/5-2/6) M = 2,845.0 kNm, b = 3,700 mm
d = 762.5 mm, As = 9,033 mm² 10 H20 24 T1
19 H25 B1 = 9,327 mm²

V = 3,556.2 kN, bv = 3,700 mm 19 H25 23 B1


v = 1.261 N/mm², (v-vc)b = 1,480 N/mm 6 Link Legs
10 Legs H12 @ 325 LINKS = 1,513 N/mm ↑ ELEVATION

NS(1/2-5/6) M = 1,541.0 kNm, b = 2,200 mm


d = 737.5 mm, As = 5,059 mm² 6 H20 27 T2
11 H25 B2 = 5,400 mm²

V = 2,370.8 kN, bv = 2,200 mm 11 H25 26 B2


v = 1.461 N/mm², (v-vc)b = 880 N/mm Links 6x12 H12 28 325
6 Legs H12 @ 325 LINKS = 908 N/mm ← ELEVATION

16
Iesis Special Structures Page: 1SE1146-DC-01 Rev A
Leyton high Road Made by: AJW
Date: 18.07.14
Ref No: SE1151
───────────────────────────────────────────────────────────────────────
Office: 6428

Location: Typical 2 pile cap

Design to BS8110(1997) with partial safety factor for steel gammaS=1.15


Pilecap for two piles
├─────────A────────┤ ─────────────────────
─┬─ ┌──────────────────────────────────┐ Designed by Bending Theory.
│ │ _│_ _│_ │
│ │ / • \─┬─ ▄▄▄▄ / • \ │ Calculations are in
ly •│── |• ─┼─ •|cy ████ ──|• ─┼─ •|───│• accordance with BS8110.
│ │ \ _:_ /─┴─ ▀▀▀▀ \ _:_ / │
│ │ │ ├cx┤ │ │ For bond calculations,
─┴─ └──────────────────────────────────┘ any high-yield bars are
├────────────────lx────────────────┤ assumed Type 2 deformed.

Total ultimate load on column N=2350 kN


Column dimension cx cx=200 mm
Column dimension cy cy=1500 mm
Nominal pile diameter PileD=500 mm
Spacing of pile centres A=1500 mm
Overhang: pile face to cap edge olap=150 mm
Length of pile cap lx=2300 mm
Width of pile cap ly=1500 mm
As pile spacing does not exceed 3φ, shear stress can be enhanced across
entire breadth of pilecap (see Clause 3.11.4.4b):
Effective breadth for shear 1500 mm
Concrete grade fcu=40 N/mm2
Steel strength fy=500 N/mm2
High-yield reinforcement
Ultimate bond stress (3.12.8.4) fbu=0.50*SQR(fcu)=0.50*SQR(40)
=3.1623 N/mm2
Cover to underside of main bars Cover=100 mm
Side and top cover to main bars SCover=50 mm
Data 50 entered, is less than minimum expected value 60
Cover to main steel is less than the recommended minimum value.
Since 0.8√(fcu) exceeds 5 N/mm2,
maximum shear stress in concrete Vmax=5 N/mm2
Chosen depth of pilecap h=850 mm
Corresponding effective depth d=h-Cover-20=850-100-20=730 mm

Design of main reinforcement


────────────────────────────
Total moment M=N/2*(A-cx)/2*1000
=2350/2*(1500-200)/2*1000
=763.75E6 Nmm
Resistance-moment factor K=M/(ly*d^2*fcu)
=763.75E6/(1500*730^2*40)
=0.023887
Lever-arm factor z'=(0.5+SQR(0.25-K/0.9))
=(0.5+SQR(0.25-0.023887/0.9))
=0.97271
but must not exceed z'=0.95
Lever arm z=z'*d=0.95*730=693.5 mm
Area of steel required AreaT=M/(z*fy/gammaS)
17 =763.75E6/(693.5*500/1.15)

=2533 mm2
Iesis Special Structures Page: 2SE1146-DC-01 Rev A
Leyton high Road Made by: AJW
Date: 18.07.14
Ref No: SE1151
───────────────────────────────────────────────────────────────────────
Office: 6428
Main steel diameter dia=20 mm
Main steel spacing Space=150 mm
Number of bars required NumBar=1+INT((ly-2*SCover-dia)/Space)
=1+INT((1500-2*50-20)/150)
=10
Steel area provided AProv=PI/4*dia*dia*NumBar
=3.1416/4*20*20*10
=3141.6 mm2
Actual stress in steel fbt=fy/gammaS*AreaT/AProv
=500/1.15*2533/3141.6
=350.55 N/mm2
Value of ab for bearing calcs = side cover + half bar size, i.e. 60 mm
Min.bend radius for full stress Radius=PI*dia*fbt*(1+2*dia/ab)/8/fcu
=3.1416*20*350.55*(1+2*20/60)
/8/40
=114.72 mm
Length to start of bend LenB=(lx-A+0.6*PileD)/2-Radius-SCover
=(2300-1500+0.6*500)/2-114.72-50
=385.28 mm
Stress transferred before bend br=LenB*fbu*4/dia=385.28*3.1623*4/20
=243.67 N/mm2
Stress in bar at start of bend fbr=fbt-br=350.55-243.67
=106.88 N/mm2
Minimum bend radius (3.12.8.25) Radius=PI*dia*fbr*(1+2*dia/ab)/8/fcu
=3.1416*20*106.88*(1+2*20/60)
/8/40
=34.977 mm
Increase to minimum bend radius Radius=MinRad=70 mm
Bond length required (3.12.8.3) ABondR=5*(1+INT(fbt*dia/(4*fbu)/5))
=5*(1+INT(350.55*20/(4*3.1623)
/5))
=555 mm
Minimum bond length (=eff.depth) ABondM=d=730 mm
Bond length provided ABondR=ABondM=730 mm
Since four times the internal radius of the bend exceeds 12φ,
Eff.anchorage length of bend EffAL=12*dia=12*20=240 mm
Actual anchorage length of bend ActAL=Radius*PI/2+4*dia
=70*3.1416/2+4*20
=189.96 mm
Since Effective anchorage length exceeds Actual anchorage length (see
Clause 3.12.8.23(b)), use EffAL (i.e. 240. mm)
At pilecap ends main bars must turn through 90° to an internal radius
of 70 mm and then extend to within 600 mm of top of pilecap.

Distribution steel
──────────────────
Minimum percentage of steel required in top and bottom in
each direction (Table 3.25) Pmin2=Pmin1*100=0.0013*100
=0.13 %
Minimum area required Amin=Pmin1*1000*h=0.0013*1000*850
=1105 mm2/m
Diameter of bar LSize=16 mm
Spacing of bars LSpac=150 mm
Area of dist.steel provided A2=PI*LSize^2*250/LSpac
=3.1416*16^2*250/150
18

=1340.4 mm2/m
Iesis Special Structures Page: 3SE1146-DC-01 Rev A
Leyton high Road Made by: AJW
Date: 18.07.14
Ref No: SE1151
───────────────────────────────────────────────────────────────────────
Office: 6428
The IStructE/ICE 'Manual for the design of reinforced concrete building
structures' recommends that 12 mm horizontal bars, spaced vertically at
not more than 250 mm centres should be provided in the sides of the cap.
Provide 3 No.12 mm horizontal U-bars at 250 mm centres in the sides.

Check shear resistance (Clause 3.11.4.4)


──────────────────────
Design concrete shear stress taken from formula in Table 3.8.
Effective depth of section d=h-Cover-dia/2=850-100-20/2
=740 mm
Reinforcement factor C1=100*AProv/(ly*d)
=100*3141.6/(1500*740)
=0.28303
Effective-depth factor C2=(400/d)^0.25=(400/740)^0.25
=0.85745
Concrete-grade factor C3=fcu/25=40/25=1.6
Design concrete shear stress vc=0.79*C1^(1/3)*C2*C3^(1/3)/1.25
=0.79*0.28303^(1/3)*0.85745*1.6^(1
/3)/1.25
=0.41614 N/mm2
Distance from col.to crit.plane av=A/2-0.3*PileD-cx/2
=1500/2-0.3*500-200/2
=500 mm
Since the distance from the column face to the critical plane as defined
in Clause 3.11.4.3 is less than twice the effective depth, (Cl.3.4.5.8)
Shear-enhancement factor Sef=2*d/av=2*740/500=2.96
Modified concrete shear stress VMod=vc*Sef=0.41614*2.96
=1.2318 N/mm2
Total shear resistance provided VProv=(VMod*CP1+vc*CP2)*d/1000
=(1.2318*1500+0.41614*0)*740/1000
=1367.3 kN
Total shear resistance required N/2 =1175 kN
Shear resistance is satisfactory.

Check punching shear at column face (Clause 3.11.4.5)


───────────────────────────────────
Length of column perimeter uo=2*(cx+cy)=2*(200+1500)
=3400 mm
Punching-shear resistance prov. VpRes=Vmax*uo*d/1000=5*3400*740/1000
=12580 kN
Punching-shear resistance reqd. N =2350 kN
Punching-shear stress on perimeter of column is satisfactory.

MAIN REINFORCEMENT Characteristic strength 500 N/mm2


SUMMARY Diameter of bars 20 mm
Number of bars 10
Spacing 150 mm
Area required 2533 mm2
Area provided 3141.6 mm2

Shape code=21 ( A=C=150 mm )


( B=2200 mm )

Volume
19 of steel 7508.4 cm3
Weight of steel 58.941 kg
Iesis Special Structures Page: 4SE1146-DC-01 Rev A
Leyton high Road Made by: AJW
Date: 18.07.14
Ref No: SE1151
───────────────────────────────────────────────────────────────────────
Office: 6428
DISTRIBUTION REINFORCEMENT Characteristic strength 500 N/mm2
SUMMARY Diameter of bars 16 mm
Number of bars 15
Spacing of bars 150 mm
Area required 1105 mm2
Area provided 1340.4 mm2

Shape code=99 ( A=732 mm )


( B=1432 mm )
plus Shape code=21 ( A=1432 mm )

Volume of steel 14501 cm3


Weight of steel 113.83 kg

TOP BARS SUMMARY Characteristic strength 500 N/mm2


Diameter of bars 16 mm
Number of bars 10
Spacing of bars 150 mm

Shape code=00 ( A=2200 mm )

Volume of steel 4423.4 cm3


Weight of steel 34.723 kg

SIDE BARS SUMMARY Characteristic strength 500 N/mm2


Diameter of bars 12 mm
Number of bars/side 3
Spacing of bars 250 mm

Shape code=00 ( A=2200 mm )

Volume of steel 1492.9 cm3


Weight of steel 11.719 kg

QUANTITIES Total volume of concrete needed 2.9325 m3


Total area of formwork 6.46 m2
Total volume of steel 27925 cm3
Total weight of steel 219.21 kg

Approx. self-weight of pile cap 98.532 kN


Approx. total load on each pile 1225 kN
No742

20
SE1146-DC-01 Rev A

Project GMV Blocks 107 & 206 to 210 IESIS SPECIAL STRUCTURES
Client BYUK Made by Date Page
Location Pilecap F12 ajw 20-Jun-15 1
Triple Pilecap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146
DIMENSIONS mm
COLUMN PILECAP
→ = 600 A= 400
↑ = 200 B= 1500
C= 1300
Pile Ø = 500 E= 235
Min spacing = 1500 depth H = 850
Tolerance = 150

COLUMN ACTIONS kN, kNm characteristic PLOT (to scale) KEY


DEAD IMPOSED WIND
Axial (kN) 1620.0 250.0 STATUS VALID DESIGN
Mx (kNm)
My (kNm) PILE REACTIONS kN characteristic
Hx (kN) PILE 1 PILE 2 PILE 3
Hy (kN) Gk + Qk 364.3 792.2 792.2
Gk + Qk +Wk 364.3 792.2 792.2
REINFORCEMENT
EW (2-3) M = 1,016.6 kNm, b = 1,200 mm
d = 749.0 mm, As = 3,286 mm² 5 H12 06 T1
5 H32 B = 4,021 mm²

V = 1,129.6 kN, bv = 1,200 mm 5 H32 05 B1


v = 1.257 N/mm², (v-vc)b = 480 N/mm Links 6 H10 07 350 + 3x6 H10 08 350
5 Legs H10 @ 350 LINKS = 488 N/mm ↑ ELEVATION

NS (1-2/3) M = 643.8 kNm, b = 2,375 mm


d = 718.5 mm, As = 2,169 mm² 5 H12 10 T2
5 H25 B = 2,454 mm²

V = 519.0 kN, bv = 1,435 mm 5 H25 09 B2


v = 0.503 N/mm², (v-vc)b = 574 N/mm Links 4 H12 11 425 + 3x4 H12 12 425
5 Legs H12 @ 425 LINKS = 579 N/mm ← ELEVATION

21
SE1146-DC-01 Rev A

Project Spreadsheets to BS 8110 The Concrete Centre


Client BYUK Made by Date Page
Location Offset Cap to 107 ajw 05-Aug-15 1
4 Pile Cap
PILECAP DESIGN to BS 8110:2005 Checked Revision Job No
Originated from RCC82.xls v 4.1 on CD © 2006 TCC - - SE1146

DIMENSIONS mm PILECAP
COLUMN A= 400
→ = 275 B= 2115
↑ = 275 C= 1500
D= 1058
Pile Ø = 500 E= 750
Tolerance = 75 depth H = 1200

COLUMN ACTIONS kN, kNm characteristic PLOT (to scale) KEY


DEAD IMPOSED WIND
Axial (kN) 2810.0 500.0 STATUS VALID DESIGN
Mx (kNm)
My (kNm) PILE REACTIONS kN
Hx (kN) PILE 1 PILE 2 PILE 3 PILE 4
Hy (kN) Gk + Qk 875.4 876.2 875.4 876.2
Gk + Qk +Wk 875.4 876.2 875.4 876.2
REINFORCEMENT
EW(1/3-2/4) M = 2,489.8 kNm, b = 2,300 mm
d = 1,112.5 mm, As = 5,418 mm² 7 H20 14 T1
12 H25 B1 = 5,890 mm²

V = 2,501.0 kN, bv = 2,300 mm 12 H25 13 B1


v = 0.977 N/mm², (v-vc)b = 920 N/mm 8 Link Legs
7 Legs H12 @ 350 LINKS = 984 N/mm ↑ ELEVATION

NS(1/2-3/4) M = 1,720.2 kNm, b = 2,915 mm


d = 1,090.0 mm, As = 3,821 mm² 8 H20 16 T2
15 H20 B2 = 4,712 mm²

V = 2,502.2 kN, bv = 2,915 mm 15 H20 15 B2


v = 0.787 N/mm², (v-vc)b = 1,166 N/mm Links 8x7 H12 17 325
8 Legs H12 @ 325 LINKS = 1,210 N/mm ← ELEVATION

22
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

STABILITY

The wind loadings and notional horizontal forces have been calculated for each block within the
ETABS design package.

An additional typical block wind loading analysis has been carried out using the METSPEC design
package.

The following pages cover the ETABS and METSPEC wind loading analysis and the design of the
vertical elements.

23
SE1146-DC-01 Rev A

GMV

BUILDING 206

24
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm

S T A T I C L O A D C A S E S

STATIC CASE AUTO LAT SELF WT NOTIONAL NOTIONAL


CASE TYPE LOAD MULTIPLIER FACTOR DIRECTION

DEAD DEAD N/A 1.0000


LIVE LIVE N/A 0.0000
SDL SUPER DEAD N/A 0.0000
WINDX WIND BS6399-95 0.0000
WINDY WIND BS6399-95 0.0000

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDX

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 0 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 11370.282 16458.796 5685.141


STORY3 D1 11370.282 16458.796 5685.141
STORY2 D1 11370.282 16458.796 5685.141
STORY1 D1 11370.282 16458.796 5685.141

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 21.55 0.00 0.00 0.000 0.000 -1174.550


STORY3 43.11 0.00 0.00 0.000 0.000 -1477.263
STORY2 43.11 0.00 0.00 0.000 0.000 -1656.205
STORY1 43.11 0.00 0.00 0.000 0.000 2386.407

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDY

25
SE1146-DC-01 Rev A

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 90 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 32917.592 16458.796 5685.141


STORY3 D1 32917.592 16458.796 5685.141
STORY2 D1 32917.592 16458.796 5685.141
STORY1 D1 32917.592 16458.796 5685.141

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 0.00 62.40 0.00 0.000 0.000 -2552.570


STORY3 0.00 124.80 0.00 0.000 0.000 -9161.616
STORY2 0.00 124.80 0.00 0.000 0.000 -8289.087
STORY1 0.00 124.80 0.00 0.000 0.000 -10213.422

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm July 6, 2015 17:17 PAGE 6

M A S S S O U R C E D A T A

MASS LATERAL LUMP MASS


FROM MASS ONLY AT STORIES

Masses Yes Yes

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm July 6, 2015 17:17 PAGE 7

D I A P H R A G M M A S S D A T A

STORY DIAPHRAGM MASS-X MASS-Y MMI X-M Y-M

ROOF D1 2.299E-01 2.299E-01 2.230E+07 16499.701 5630.650


STORY3 D1 2.439E-01 2.439E-01 2.420E+07 16532.204 5650.873
STORY2 D1 2.438E-01 2.438E-01 2.418E+07 16525.212 5646.723
STORY1 D1 2.670E-01 2.670E-01 2.576E+07 16540.631 5740.498

S T O R Y F O R C E S

STORY LOAD P VX VY T MX MY

26
SE1146-DC-01 Rev A

ROOF WINDX -4.665E-05 -2.155E+01 -5.583E-05 1.225E+05 1.633E-01 -6.466E+04


STORY3 WINDX -1.463E-04 -6.466E+01 7.135E-04 3.676E+05 -1.986E+00 -2.587E+05
STORY2 WINDX -2.993E-04 -1.078E+02 7.117E-04 6.127E+05 -4.137E+00 -5.820E+05
STORY1 WINDX -3.515E-04 -1.509E+02 8.644E-04 8.578E+05 -6.734E+00 -1.035E+06
ROOF WINDY 1.834E-04 -1.872E-08 -6.240E+01 -1.027E+06 1.872E+05 -2.639E+00
STORY3 WINDY 5.629E-04 -4.553E-08 -1.872E+02 -3.081E+06 7.489E+05 -8.099E+00
STORY2 WINDY 1.097E-03 -5.567E-08 -3.120E+02 -5.135E+06 1.685E+06 -1.579E+01
STORY1 WINDY 1.256E-03 -7.013E-08 -4.368E+02 -7.190E+06 2.995E+06 -1.807E+01

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm July 6, 2015 17:17 PAGE 15

STORY DRIFTS

STORY DIRECTION LOAD MAX DRIFT

ROOF X WINDX 1/10398


ROOF Y WINDX 1/9636
STORY3 X WINDX 1/9625
STORY3 Y WINDX 1/8642
STORY2 X WINDX 1/10797
STORY2 Y WINDX 1/9574
STORY1 X WINDX 1/14893
STORY1 Y WINDX 1/12281
ROOF Y WINDY 1/2178
STORY3 Y WINDY 1/2119
STORY2 Y WINDY 1/2442
STORY1 Y WINDY 1/4213

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm July 6, 2015 17:17 PAGE 16

DISPLACEMENTS AT DIAPHRAGM CENTER OF MASS

STORY DIAPHRAGM LOAD UX UY RZ

ROOF D1 WINDX 0.7252 -0.2046 -0.00006


STORY3 D1 WINDX 0.5250 -0.1446 -0.00005
STORY2 D1 WINDX 0.3125 -0.0818 -0.00003
STORY1 D1 WINDX 0.1269 -0.0292 -0.00001
ROOF D1 WINDY -0.5760 2.3606 0.00015
STORY3 D1 WINDY -0.4053 1.7070 0.00010
STORY2 D1 WINDY -0.2275 1.0188 0.00006
STORY1 D1 WINDY -0.0843 0.3912 0.00002

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm July 6, 2015 17:17 PAGE 17

STORY MAXIMUM AND AVERAGE LATERAL DISPLACEMENTS

STORY LOAD DIR MAXIMUM AVERAGE RATIO

ROOF WINDX X 1.0746 0.7286 1.475


STORY3 WINDX X 0.7876 0.5266 1.496
STORY2 WINDX X 0.4777 0.3136 1.523
STORY1 WINDX X 0.2014 0.1262 1.597
ROOF WINDY Y 4.6809 2.3545 1.988
STORY3 WINDY Y 3.3219 1.6995 1.955
STORY2 WINDY Y 1.9251 1.0149 1.897
STORY1 WINDY Y 0.7122 0.3895 1.828

27
SE1146-DC-01 Rev A

28
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV BLDG 206 Units:KN-mm

GMV 206 - SHEAR WALL DESIGN

SUMMARY OUTPUT DATA - UNIFORM REINFORCING PIER SECTIONS - CHECK (BS8110 97)

Story Pier Sta Edge End Edge D/C Pier Shear Asv
Label Label Loc Bar Bar Spacing Ratio Leg mm^2/m

STORY1 P1 Top 12d 16d 250.000 0.0829 Top Leg 1 203.555


Bot 12d 16d 250.000 0.1110 Bot Leg 1 203.555

STORY1 P2 Top 12d 16d 250.000 0.1138 Top Leg 1 203.555


Bot 12d 16d 250.000 0.1455 Bot Leg 1 203.555

STORY1 P3 Top 12d 16d 250.000 0.1024 Top Leg 1 203.555


Bot 12d 16d 250.000 0.1304 Bot Leg 1 203.555

STORY1 P4 Top 12d 16d 250.000 0.4103 Top Leg 1 203.555


Bot 12d 16d 250.000 0.6204 Bot Leg 1 203.555

STORY1 P5 Top 12d 16d 250.000 0.0697 Top Leg 1 203.555


Bot 12d 16d 250.000 0.3091 Bot Leg 1 203.555

STORY1 P6 Top 12d 16d 250.000 0.1587 Top Leg 1 203.555


Bot 12d 16d 250.000 0.2653 Bot Leg 1 203.555

29
SE1146-DC-01 Rev A

30
SE1146-DC-01 Rev A

31
SE1146-DC-01 Rev A

32
SE1146-DC-01 Rev A

33
SE1146-DC-01 Rev A

34
SE1146-DC-01 Rev A

GMV

BUILDING 208

35
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV BLDG 208 Units:KN-mm

S T O R Y D A T A

STORY SIMILAR TO HEIGHT ELEVATION

ROOF None 3000.000 12000.000


STORY3 ROOF 3000.000 9000.000
STORY2 ROOF 3000.000 6000.000
STORY1 ROOF 3000.000 3000.000
BASE None 0.000

S T A T I C L O A D C A S E S

STATIC CASE AUTO LAT SELF WT NOTIONAL NOTIONAL


CASE TYPE LOAD MULTIPLIER FACTOR DIRECTION

DEAD DEAD N/A 1.0000


LIVE LIVE N/A 0.0000
SDL LIVE N/A 0.0000
WINDX WIND BS6399-95 0.0000
WINDY WIND BS6399-95 0.0000

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDX

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 0 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 11750.036 11907.689 5875.018


STORY3 D1 11750.036 11907.689 5875.018
STORY2 D1 11750.036 11907.689 5875.018
STORY1 D1 11750.036 11907.689 5875.018

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 22.27 0.00 0.00 0.000 0.000 4044.426

36
SE1146-DC-01 Rev A

STORY3 44.55 0.00 0.00 0.000 0.000 6928.866


STORY2 44.55 0.00 0.00 0.000 0.000 9944.322
STORY1 44.55 0.00 0.00 0.000 0.000 7992.316

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDY

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 90 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 30112.208 11907.689 5875.018


STORY3 D1 30112.208 11907.689 5875.018
STORY2 D1 30112.208 11907.689 5875.018
STORY1 D1 30112.208 11907.689 5875.018

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 0.00 57.08 0.00 0.000 0.000 -30728.702


STORY3 0.00 114.17 0.00 0.000 0.000 -59129.798
STORY2 0.00 114.17 0.00 0.000 0.000 -22358.555
STORY1 0.00 114.17 0.00 0.000 0.000 -54574.053

M A S S S O U R C E D A T A

MASS LATERAL LUMP MASS


FROM MASS ONLY AT STORIES

Masses Yes Yes

D I A P H R A G M M A S S D A T A

STORY DIAPHRAGM MASS-X MASS-Y MMI X-M Y-M

ROOF D1 2.111E-01 2.111E-01 1.684E+07 12445.995 6056.588


STORY3 D1 2.246E-01 2.246E-01 1.819E+07 12425.608 6030.550
STORY2 D1 2.311E-01 2.311E-01 1.898E+07 12103.528 6098.238

37
SE1146-DC-01 Rev A

STORY1 D1 2.252E-01 2.252E-01 1.816E+07 12385.704 6054.422

S T O R Y F O R C E S

STORY LOAD P VX VY T MX MY

ROOF WINDX -1.454E-04 -2.227E+01 -3.188E-07 1.309E+05 -1.284E-01 -6.682E+04


STORY3 WINDX -3.316E-04 -6.682E+01 5.026E-07 3.926E+05 -2.798E-01 -2.673E+05
STORY2 WINDX -4.377E-04 -1.114E+02 -6.555E-08 6.543E+05 -3.528E-01 -6.014E+05
STORY1 WINDX -5.263E-04 -1.559E+02 3.080E-07 9.160E+05 -4.364E-01 -1.069E+06
ROOF WINDY 1.166E-04 8.337E-05 -5.708E+01 -6.797E+05 1.713E+05 -1.923E+00
STORY3 WINDY 2.991E-04 1.055E-04 -1.713E+02 -2.039E+06 6.850E+05 -4.983E+00
STORY2 WINDY 4.218E-04 1.115E-04 -2.854E+02 -3.399E+06 1.541E+06 -6.918E+00
STORY1 WINDY 4.721E-04 1.048E-04 -3.996E+02 -4.758E+06 2.740E+06 -7.534E+00

ETABS v9.6.0 File:GMV BLDG 208 Units:KN-mm August 18, 2015 17:31 PAGE 15

STORY DRIFTS

STORY DIRECTION LOAD MAX DRIFT

ROOF X WINDX 1/3572


ROOF Y WINDX 1/3443
STORY3 X WINDX 1/3431
STORY3 Y WINDX 1/3295
STORY2 X WINDX 1/3827
STORY2 Y WINDX 1/3657
STORY1 X WINDX 1/7027
STORY1 Y WINDX 1/6662
ROOF Y WINDY 1/1381
STORY3 Y WINDY 1/1379
STORY2 Y WINDY 1/1616
STORY1 Y WINDY 1/3398

ETABS v9.6.0 File:GMV BLDG 208 Units:KN-mm August 18, 2015 17:31 PAGE 16

DISPLACEMENTS AT DIAPHRAGM CENTER OF MASS

STORY DIAPHRAGM LOAD UX UY RZ

ROOF D1 WINDX 1.9069 -0.4521 -0.00018


STORY3 D1 WINDX 1.3506 -0.3099 -0.00013
STORY2 D1 WINDX 0.7847 -0.1456 -0.00008
STORY1 D1 WINDX 0.2722 -0.0500 -0.00003
ROOF D1 WINDY -0.9460 4.3164 0.00019
STORY3 D1 WINDY -0.6432 3.0285 0.00013
STORY2 D1 WINDY -0.3504 1.7096 0.00007
STORY1 D1 WINDY -0.0978 0.6021 0.00002

ETABS v9.6.0 File:GMV BLDG 208 Units:KN-mm August 18, 2015 17:31 PAGE 17

STORY MAXIMUM AND AVERAGE LATERAL DISPLACEMENTS

STORY LOAD DIR MAXIMUM AVERAGE RATIO

ROOF WINDX X 2.9099 1.8744 1.552


STORY3 WINDX X 2.0750 1.3306 1.559
STORY2 WINDX X 1.2061 0.7677 1.571
STORY1 WINDX X 0.4269 0.2672 1.597
ROOF WINDY Y 7.0701 4.2884 1.649
STORY3 WINDY Y 4.9043 3.0120 1.628
STORY2 WINDY Y 2.7348 1.7232 1.587
STORY1 WINDY Y 0.8829 0.6004 1.470

38
SE1146-DC-01 Rev A

39
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV BLDG 208 Units:KN-mm

GMV 208 SHEAR WALL DESIGN

SUMMARY OUTPUT DATA - UNIFORM REINFORCING PIER SECTIONS - CHECK (BS8110 97)

Story Pier Sta Edge End Edge D/C Pier Shear Asv
Label Label Loc Bar Bar Spacing Ratio Leg mm^2/m

STORY1 P1 Top 12d 16d 250.000 0.0970 Top Leg 1 203.555


Bot 12d 16d 250.000 0.1092 Bot Leg 1 203.555

STORY1 P2 Top 12d 16d 250.000 0.1026 Top Leg 1 203.555


Bot 12d 16d 250.000 0.1488 Bot Leg 1 203.555

STORY1 P3 Top 12d 16d 250.000 0.1375 Top Leg 1 203.555


Bot 12d 16d 250.000 0.2354 Bot Leg 1 203.555

STORY1 P4 Top 12d 16d 250.000 0.1486 Top Leg 1 203.555


Bot 12d 16d 250.000 0.2676 Bot Leg 1 203.555

STORY1 P5 Top 12d 16d 250.000 0.0531 Top Leg 1 203.555


Bot 12d 16d 250.000 0.2254 Bot Leg 1 203.555

STORY1 P6 Top 12d 16d 250.000 0.2660 Top Leg 1 203.555


Bot 12d 16d 250.000 0.3810 Bot Leg 1 203.555

40
SE1146-DC-01 Rev A

41
SE1146-DC-01 Rev A

42
SE1146-DC-01 Rev A

43
SE1146-DC-01 Rev A

44
SE1146-DC-01 Rev A

GMV

BUILDING 209

45
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm

S T O R Y D A T A

STORY SIMILAR TO HEIGHT ELEVATION

ROOF STORY4 3000.000 15000.000


STORY4 None 3000.000 12000.000
STORY3 STORY4 3000.000 9000.000
STORY2 STORY4 3000.000 6000.000
STORY1 STORY4 3000.000 3000.000
BASE None 0.000

S T A T I C L O A D C A S E S

STATIC CASE AUTO LAT SELF WT NOTIONAL NOTIONAL


CASE TYPE LOAD MULTIPLIER FACTOR DIRECTION

DEAD DEAD N/A 1.0000


LIVE LIVE N/A 0.0000
SDL SUPER DEAD N/A 0.0000
WINDX WIND BS6399-95 0.0000
WINDY WIND BS6399-95 0.0000

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDX

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 0 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 12113.529 7586.555 6056.764


STORY4 D1 12113.529 7586.555 6056.764
STORY3 D1 12113.529 7586.555 6056.764
STORY2 D1 12113.529 7586.555 6056.764
STORY1 D1 12113.529 7586.555 6056.764

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

46
SE1146-DC-01 Rev A

STORY FX FY FZ MX MY MZ

ROOF 22.96 0.00 0.00 0.000 0.000 4302.109


STORY4 45.93 0.00 0.00 0.000 0.000 7926.067
STORY3 45.93 0.00 0.00 0.000 0.000 7926.067
STORY2 45.93 0.00 0.00 0.000 0.000 7926.067
STORY1 45.93 0.00 0.00 0.000 0.000 7926.067

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm August 18, 2015 17:46 PAGE 5

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDY

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 90 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 23973.765 7586.555 6056.764


STORY4 D1 23973.765 7586.555 6056.764
STORY3 D1 23973.765 7586.555 6056.764
STORY2 D1 23973.765 7586.555 6056.764
STORY1 D1 23973.765 7586.555 6056.764

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 0.00 45.45 0.00 0.000 0.000 -47595.129


STORY4 0.00 90.89 0.00 0.000 0.000 -93940.166
STORY3 0.00 90.89 0.00 0.000 0.000 -93940.166
STORY2 0.00 90.89 0.00 0.000 0.000 -93940.166
STORY1 0.00 90.89 0.00 0.000 0.000 -93940.166

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm August 18, 2015 17:46 PAGE 7

D I A P H R A G M M A S S D A T A

STORY DIAPHRAGM MASS-X MASS-Y MMI X-M Y-M

ROOF D1 1.690E-01 1.690E-01 9.194E+06 8633.814 6244.108


STORY4 D1 1.796E-01 1.796E-01 1.004E+07 8620.061 6229.342
STORY3 D1 1.796E-01 1.796E-01 1.004E+07 8620.061 6229.342

47
SE1146-DC-01 Rev A

STORY2 D1 1.796E-01 1.796E-01 1.004E+07 8620.061 6229.342


STORY1 D1 1.796E-01 1.796E-01 1.004E+07 8620.061 6229.342

S T O R Y F O R C E S

STORY LOAD P VX VY T MX MY

ROOF WINDX -6.867E-08 -2.296E+01 8.721E-07 1.391E+05 -2.852E-03 -6.889E+04


STORY4 WINDX -1.049E-07 -6.889E+01 7.030E-07 4.173E+05 -5.101E-03 -2.756E+05
STORY3 WINDX -2.230E-07 -1.148E+02 -4.115E-07 6.954E+05 -4.304E-03 -6.200E+05
STORY2 WINDX -4.268E-07 -1.607E+02 -6.064E-07 9.736E+05 -3.224E-03 -1.102E+06
STORY1 WINDX -4.611E-07 -2.067E+02 -3.370E-07 1.252E+06 -2.340E-03 -1.722E+06
ROOF WINDY -6.877E-07 6.722E-09 -4.545E+01 -3.448E+05 1.363E+05 3.518E-03
STORY4 WINDY -1.477E-06 1.833E-08 -1.363E+02 -1.034E+06 5.454E+05 7.536E-03
STORY3 WINDY -2.028E-06 2.550E-08 -2.272E+02 -1.724E+06 1.227E+06 1.046E-02
STORY2 WINDY -3.417E-06 2.925E-08 -3.181E+02 -2.414E+06 2.181E+06 1.765E-02
STORY1 WINDY -4.178E-06 3.044E-08 -4.090E+02 -3.103E+06 3.409E+06 2.154E-02

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm August 18, 2015 17:46 PAGE 15

STORY DRIFTS

STORY DIRECTION LOAD MAX DRIFT

ROOF X WINDX 1/3086


ROOF Y WINDX 1/3738
STORY4 X WINDX 1/2985
STORY4 Y WINDX 1/3619
STORY3 X WINDX 1/3087
STORY3 Y WINDX 1/3742
STORY2 X WINDX 1/3713
STORY2 Y WINDX 1/4486
STORY1 X WINDX 1/6893
STORY1 Y WINDX 1/8160
ROOF Y WINDY 1/1843
STORY4 Y WINDY 1/1830
STORY3 Y WINDY 1/1950
STORY2 Y WINDY 1/2433
STORY1 Y WINDY 1/4992

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm August 18, 2015 17:46 PAGE 16

DISPLACEMENTS AT DIAPHRAGM CENTER OF MASS

STORY DIAPHRAGM LOAD UX UY RZ

ROOF D1 WINDX 2.7916 -0.8571 -0.00024


STORY4 D1 WINDX 2.1353 -0.6458 -0.00018
STORY3 D1 WINDX 1.4625 -0.4353 -0.00013
STORY2 D1 WINDX 0.8146 -0.2364 -0.00007
STORY1 D1 WINDX 0.2802 -0.0767 -0.00003
ROOF D1 WINDY -1.2551 3.4616 0.00029
STORY4 D1 WINDY -0.9376 2.6371 0.00022
STORY3 D1 WINDY -0.6238 1.8016 0.00014
STORY2 D1 WINDY -0.3310 1.0063 0.00008
STORY1 D1 WINDY -0.1010 0.3521 0.00002

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm August 18, 2015 17:46 PAGE 17

STORY MAXIMUM AND AVERAGE LATERAL DISPLACEMENTS

STORY LOAD DIR MAXIMUM AVERAGE RATIO

ROOF WINDX X 4.1709 2.7468 1.518


STORY4 WINDX X 3.2041 2.1034 1.523
STORY3 WINDX X 2.2047 1.4404 1.531
STORY2 WINDX X 1.2385 0.8019 1.544
STORY1 WINDX X 0.4352 0.2755 1.579
ROOF WINDY Y 6.6131 3.1685 2.087
STORY4 WINDY Y 4.9924 2.4214 2.062
STORY3 WINDY Y 3.3608 1.6587 2.026
STORY2 WINDY Y 1.8289 0.9310 1.964
STORY1 WINDY Y 0.6010 0.3293 1.825

48
SE1146-DC-01 Rev A

49
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV BLDG 209 Units:KN-mm

GMV 209 - SHEAR WALL DESIGN

SUMMARY OUTPUT DATA - UNIFORM REINFORCING PIER SECTIONS - CHECK (BS8110 97)

Story Pier Sta Edge End Edge D/C Pier Shear Asv
Label Label Loc Bar Bar Spacing Ratio Leg mm^2/m

STORY1 P1 Top 12d 16d 250.000 0.1691 Top Leg 1 203.555


Bot 12d 16d 250.000 0.2003 Bot Leg 1 203.555

STORY1 P2 Top 12d 16d 250.000 0.3338 Top Leg 1 203.555


Bot 12d 16d 250.000 0.3446 Bot Leg 1 203.555

STORY1 P1A Top 12d 16d 250.000 0.1328 Top Leg 1 203.555
Bot 12d 16d 250.000 0.1886 Bot Leg 1 203.555

STORY1 P1B Top 12d 16d 250.000 0.1302 Top Leg 1 203.555
Bot 12d 16d 250.000 0.1817 Bot Leg 1 203.555

STORY1 P2A Top 12d 16d 250.000 0.2838 Top Leg 1 203.555
Bot 12d 16d 250.000 0.3058 Bot Leg 1 203.555

STORY1 P2B Top 12d 16d 250.000 0.5597 Top Leg 1 203.555
Bot 12d 16d 250.000 0.8052 Bot Leg 1 203.555

50
SE1146-DC-01 Rev A

51
SE1146-DC-01 Rev A

52
SE1146-DC-01 Rev A

53
SE1146-DC-01 Rev A

54
SE1146-DC-01 Rev A

55
SE1146-DC-01 Rev A

GMV

BUILDING 210

56
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV_210 Units:KN-mm

S T O R Y D A T A

STORY SIMILAR TO HEIGHT ELEVATION

ROOF STORY3 3000.000 33000.000


STORY10 STORY3 3000.000 30000.000
STORY9 STORY3 3000.000 27000.000
STORY8 STORY3 3000.000 24000.000
STORY7 STORY3 3000.000 21000.000
STORY6 STORY3 3000.000 18000.000
STORY5 STORY3 3000.000 15000.000
STORY4 STORY3 3000.000 12000.000
STORY3 None 3000.000 9000.000
STORY2 None 3000.000 6000.000
STORY1 None 3000.000 3000.000
BASE None 0.000

S T A T I C L O A D C A S E S

STATIC CASE AUTO LAT SELF WT NOTIONAL NOTIONAL


CASE TYPE LOAD MULTIPLIER FACTOR DIRECTION

DEAD DEAD N/A 1.0000


LIVE LIVE N/A 0.0000
SDL SUPER DEAD N/A 0.0000
WINDX WIND BS6399-95 0.0000
WINDY WIND BS6399-95 0.0000

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDX

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 0 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 17565.358 16955.522 8682.573


STORY10 D1 17565.358 16955.522 8682.573
STORY9 D1 17565.358 16955.522 8682.573
STORY8 D1 17565.358 16955.522 8682.573
STORY7 D1 17565.358 16955.522 8682.573
STORY6 D1 17565.358 16955.522 8682.573
STORY5 D1 17565.358 16955.522 8682.573
STORY4 D1 17565.358 16955.522 8682.573
STORY3 D1 17565.358 16955.522 8682.573
STORY2 D1 17565.358 16955.522 8682.573
STORY1 D1 17565.358 16955.522 8682.573

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

57
SE1146-DC-01 Rev A

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 33.30 0.00 0.00 0.000 0.000 4566.466


STORY10 66.60 0.00 0.00 0.000 0.000 5792.711
STORY9 66.60 0.00 0.00 0.000 0.000 5792.711
STORY8 66.60 0.00 0.00 0.000 0.000 5792.711
STORY7 66.60 0.00 0.00 0.000 0.000 5294.334
STORY6 66.60 0.00 0.00 0.000 0.000 5792.711
STORY5 66.60 0.00 0.00 0.000 0.000 5792.711
STORY4 66.60 0.00 0.00 0.000 0.000 5792.711
STORY3 66.60 0.00 0.00 0.000 0.000 5792.711
STORY2 66.60 0.00 0.00 0.000 0.000 10372.872
STORY1 66.60 0.00 0.00 0.000 0.000 9823.585

A U T O W I N D B S 6 3 9 9 - 9 5
Case: WINDY

AUTO WIND INPUT DATA

Exposure From: Rigid diaphragm extents


Direction Angle = 90 degrees
Windward Cp = 0.8
Leeward Cp = 0.3

Top Story: ROOF


Bottom Story: BASE

No parapet is included

Effective Wind Speed, Ve = 42 m/s


Size Effect Factor, Ca = 1
Dynamic Augmentation Factor, Cr = 0.25

AUTO WIND EXPOSURE WIDTH INFORMATION (Exposure widths are from diaphragm extents)

STORY DIAPHRAGM WIDTH X Y

ROOF D1 34202.297 16955.522 8682.573


STORY10 D1 34202.297 16955.522 8682.573
STORY9 D1 34202.297 16955.522 8682.573
STORY8 D1 34202.297 16955.522 8682.573
STORY7 D1 34202.297 16955.522 8682.573
STORY6 D1 34202.297 16955.522 8682.573
STORY5 D1 34202.297 16955.522 8682.573
STORY4 D1 34202.297 16955.522 8682.573
STORY3 D1 34202.297 16955.522 8682.573
STORY2 D1 34202.297 16955.522 8682.573
STORY1 D1 34202.297 16955.522 8682.573

AUTO WIND CALCULATION FORMULAS

qs = dynamic pressure in Pa (1 Pa = 1 N/m^2)


qs = 0.613 Ve^2

pe = pressure acting on external surface of building


pe = qs Cp Ca

Psurface = net load on building surface


Asurface = area of building surface
Psurface = pe Asurface

P = overall load on building


P = 0.85 * SUM(Psurface) * (1 + Cr)

AUTO WIND CALCULATION RESULTS

qs = 1081.3320 Pa

58
SE1146-DC-01 Rev A

AUTO WIND STORY FORCES

STORY FX FY FZ MX MY MZ

ROOF 0.00 64.84 0.00 0.000 0.000 -59604.579


STORY10 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY9 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY8 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY7 0.00 129.68 0.00 0.000 0.000 -119417.268
STORY6 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY5 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY4 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY3 0.00 129.68 0.00 0.000 0.000 -113956.075
STORY2 0.00 129.68 0.00 0.000 0.000 -120085.293
STORY1 0.00 129.68 0.00 0.000 0.000 -115153.820

D I A P H R A G M M A S S D A T A

STORY DIAPHRAGM MASS-X MASS-Y MMI X-M Y-M

ROOF D1 2.028E-01 2.028E-01 1.955E+07 17874.812 8819.709


STORY10 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY9 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY8 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY7 D1 2.187E-01 2.187E-01 2.124E+07 17876.417 8762.071
STORY6 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY5 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY4 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY3 D1 2.161E-01 2.161E-01 2.121E+07 17834.302 8769.554
STORY2 D1 4.458E-01 4.458E-01 4.283E+07 17881.568 8838.328
STORY1 D1 2.210E-01 2.210E-01 2.150E+07 17843.539 8830.080

S T O R Y F O R C E S

STORY LOAD P VX VY T MX MY

ROOF WINDX -5.875E-05 -3.332E+01 -8.600E-05 2.893E+05 1.973E-02 -9.996E+04


STORY10 WINDX -1.239E-05 -9.991E+01 -1.227E-04 8.674E+05 8.529E-01 -3.997E+05
STORY9 WINDX 1.075E-04 -1.665E+02 -1.649E-04 1.446E+06 1.480E+00 -8.992E+05
STORY8 WINDX 4.985E-04 -2.331E+02 -2.286E-04 2.024E+06 3.303E+00 -1.598E+06
STORY7 WINDX 1.162E-03 -2.996E+02 -2.960E-04 2.602E+06 5.686E+00 -2.497E+06
STORY6 WINDX 1.831E-03 -3.662E+02 -3.352E-04 3.180E+06 7.473E+00 -3.596E+06
STORY5 WINDX 2.722E-03 -4.328E+02 -3.650E-04 3.758E+06 1.005E+01 -4.895E+06
STORY4 WINDX 3.486E-03 -4.994E+02 -3.858E-04 4.336E+06 1.227E+01 -6.393E+06
STORY3 WINDX 4.192E-03 -5.660E+02 -3.960E-04 4.914E+06 1.426E+01 -8.091E+06
STORY2 WINDX 5.214E-03 -6.326E+02 -2.653E-03 5.493E+06 2.228E+01 -9.989E+06
STORY1 WINDX 5.623E-03 -6.992E+02 -2.654E-03 6.071E+06 3.028E+01 -1.209E+07
ROOF WINDY 6.271E-03 3.765E-03 -6.484E+01 -1.099E+06 1.945E+05 -8.956E+01
STORY10 WINDY 1.302E-02 1.560E-03 -1.945E+02 -3.298E+06 7.780E+05 -1.914E+02
STORY9 WINDY 2.364E-02 7.862E-04 -3.242E+02 -5.497E+06 1.751E+06 -3.597E+02
STORY8 WINDY 3.545E-02 -1.185E-03 -4.539E+02 -7.695E+06 3.112E+06 -5.524E+02
STORY7 WINDY 4.918E-02 -8.061E-03 -5.835E+02 -9.894E+06 4.863E+06 -7.974E+02
STORY6 WINDY 6.089E-02 -9.862E-03 -7.132E+02 -1.209E+07 7.002E+06 -1.017E+03
STORY5 WINDY 7.285E-02 -1.118E-02 -8.429E+02 -1.429E+07 9.531E+06 -1.244E+03
STORY4 WINDY 8.183E-02 -1.341E-02 -9.726E+02 -1.649E+07 1.245E+07 -1.430E+03
STORY3 WINDY 8.985E-02 -1.375E-02 -1.102E+03 -1.869E+07 1.576E+07 -1.601E+03
STORY2 WINDY 1.055E-01 -1.400E-02 -1.232E+03 -2.089E+07 1.945E+07 -1.899E+03
STORY1 WINDY 1.092E-01 -1.564E-02 -1.362E+03 -2.309E+07 2.354E+07 -2.007E+03

ETABS v9.6.0 File:GMV_210 Units:KN-mm August 18, 2015 18:22 PAGE 15

STORY DRIFTS

STORY DIRECTION LOAD MAX DRIFT

ROOF X WINDX 1/1445


STORY10 X WINDX 1/1434
STORY9 X WINDX 1/1314
STORY8 X WINDX 1/1078
STORY7 X WINDX 1/919
STORY6 X WINDX 1/821
STORY5 X WINDX 1/777
STORY4 X WINDX 1/801
STORY3 X WINDX 1/982
STORY3 Y WINDX 1/1918
STORY2 X WINDX 1/1442
STORY2 Y WINDX 1/2883
STORY1 X WINDX 1/2519
STORY1 Y WINDX 1/4566

59
SE1146-DC-01 Rev A

ROOF Y WINDY 1/1202


STORY10 Y WINDY 1/1126
STORY9 Y WINDY 1/1046
STORY8 Y WINDY 1/976
STORY7 Y WINDY 1/926
STORY6 Y WINDY 1/904
STORY5 Y WINDY 1/920
STORY4 Y WINDY 1/1006
STORY3 Y WINDY 1/1280
STORY2 Y WINDY 1/1704
STORY1 Y WINDY 1/3703

ETABS v9.6.0 File:GMV_210 Units:KN-mm August 18, 2015 18:22 PAGE 16

DISPLACEMENTS AT DIAPHRAGM CENTER OF MASS

STORY DIAPHRAGM LOAD UX UY RZ

ROOF D1 WINDX 24.0584 -2.6501 -0.00060


STORY10 D1 WINDX 22.6445 -2.5774 -0.00059
STORY9 D1 WINDX 21.0048 -2.4849 -0.00056
STORY8 D1 WINDX 19.0246 -2.3315 -0.00053
STORY7 D1 WINDX 16.6697 -2.1299 -0.00048
STORY6 D1 WINDX 13.9727 -1.8195 -0.00042
STORY5 D1 WINDX 10.9995 -1.4686 -0.00034
STORY4 D1 WINDX 7.9037 -1.0773 -0.00025
STORY3 D1 WINDX 4.9418 -0.6839 -0.00016
STORY2 D1 WINDX 2.5647 -0.3758 -0.00008
STORY1 D1 WINDX 0.9164 -0.1435 -0.00003
ROOF D1 WINDY -4.1537 23.8938 0.00030
STORY10 D1 WINDY -4.0530 21.6966 0.00028
STORY9 D1 WINDY -3.9007 19.3957 0.00026
STORY8 D1 WINDY -3.6532 16.9570 0.00023
STORY7 D1 WINDY -3.2969 14.3917 0.00020
STORY6 D1 WINDY -2.8365 11.7102 0.00016
STORY5 D1 WINDY -2.2813 9.0066 0.00013
STORY4 D1 WINDY -1.6662 6.3798 0.00009
STORY3 D1 WINDY -1.0593 3.9832 0.00005
STORY2 D1 WINDY -0.5930 2.0481 0.00003
STORY1 D1 WINDY -0.2286 0.6874 0.00001

ETABS v9.6.0 File:GMV_210 Units:KN-mm August 18, 2015 18:22 PAGE 17

STORY MAXIMUM AND AVERAGE LATERAL DISPLACEMENTS

STORY LOAD DIR MAXIMUM AVERAGE RATIO

ROOF WINDX X 28.9906 23.8834 1.214


STORY10 WINDX X 27.5054 22.5026 1.222
STORY9 WINDX X 25.6853 20.8680 1.231
STORY8 WINDX X 23.4160 18.8963 1.239
STORY7 WINDX X 20.6530 16.5570 1.247
STORY6 WINDX X 17.4166 13.8721 1.256
STORY5 WINDX X 13.7952 10.9179 1.264
STORY4 WINDX X 9.9700 7.8433 1.271
STORY3 WINDX X 6.2628 4.9033 1.277
STORY2 WINDX X 3.2658 2.5519 1.280
STORY1 WINDX X 1.1910 0.9116 1.306
ROOF WINDY Y 28.6355 23.6529 1.211
STORY10 WINDY Y 26.1439 21.4825 1.217
STORY9 WINDY Y 23.4864 19.1988 1.223
STORY8 WINDY Y 20.6263 16.7803 1.229
STORY7 WINDY Y 17.5617 14.2302 1.234
STORY6 WINDY Y 14.3320 11.5840 1.237
STORY5 WINDY Y 11.0221 8.9095 1.237
STORY4 WINDY Y 7.7724 6.3127 1.231
STORY3 WINDY Y 4.7982 3.9440 1.217
STORY2 WINDY Y 2.4864 2.0256 1.227
STORY1 WINDY Y 0.7971 0.6821 1.169

60
SE1146-DC-01 Rev A

61
SE1146-DC-01 Rev A

ETABS v9.6.0 File:GMV_210 Units:KN-mm

GMV 210 - SHEAR WALL DESIGNS

SUMMARY OUTPUT DATA - UNIFORM REINFORCING PIER SECTIONS - DESIGN (BS8110 97)

Story Pier Sta Edge End Edge Required Current Pier Shear Asv
Label Label Loc Bar Bar Spacing Ratio Ratio Leg mm^2/m

STORY1 P1 Top 12d 16d 250.000 0.0025 0.0058 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0058 B 1 183.066

STORY1 P3 Top 12d 16d 250.000 0.0025 0.0058 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0058 B 1 183.066

STORY1 P2A Top 12d 16d 250.000 0.0025 0.0051 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0051 B 1 183.066

STORY1 P2B Top 12d 16d 250.000 0.0066 0.0076 T 1 183.066


Bot 12d 16d 250.000 0.0089 0.0076 B 1 183.066

STORY1 P2C Top 12d 16d 250.000 0.0025 0.0077 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0077 B 1 183.066

STORY1 P2D Top 12d 16d 250.000 0.0025 0.0052 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0052 B 1 183.066

STORY1 P1A Top 12d 16d 250.000 0.0025 0.0059 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0059 B 1 183.066

STORY1 P1B Top 12d 16d 250.000 0.0025 0.0059 T 1 221.637


Bot 12d 16d 250.000 0.0025 0.0059 B 1 183.066

STORY1 P1C Top 12d 16d 250.000 0.0025 0.0058 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0058 B 1 204.879

STORY1 P1D Top 12d 16d 250.000 0.0025 0.0058 T 1 183.066


Bot 12d 16d 250.000 0.0025 0.0058 B 1 183.066

62
SE1146-DC-01 Rev A

63
SE1146-DC-01 Rev A

64
SE1146-DC-01 Rev A

65
SE1146-DC-01 Rev A

66
SE1146-DC-01 Rev A

67
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 1 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Assessment to BS6399-2
Data Entry:-
Site Altitude 2.000 m Reference Height (Hr) Diagonal Dimension (a)
Basic Wind Speed 20.900 Roof 30.000 m Roof 70.000 m
Seasonal Factor (Ss) 1.000 m/s Side Walls 30.000 m Sides 76.000 m
Probability Factor(Sp) 1.000 Gables 30.000 m Gables 35.000 m
Site ID TQ401792

Dynamic Pressure Results


Wind Direction (deg) 0 30 60 90 120 150 180 210 240 270 300 330
Direction Factor Sd 0.78 0.73 0.73 0.74 0.73 0.80 0.85 0.93 1.00 0.99 0.91 0.82
Topographic
Location Factor s 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

Altitude Factor Sa 1.002 1.002 1.002 1.002 1.002 1.002 1.002 1.002 1.002 1.002 1.002 1.002
Effective Roof 26.80 26.80 26.80 30.00 26.80 26.80 26.80 26.80 26.80 30.00 30.00 30.00
Height
Sides 26.80 26.80 26.80 30.00 26.80 26.80 26.80 26.80 26.80 30.00 30.00 30.00
He (m)
Gable 26.80 26.80 26.80 30.00 26.80 26.80 26.80 26.80 26.80 30.00 30.00 30.00
Terrain Roof 1.775 1.781 1.805 1.917 1.772 1.811 1.797 1.755 1.746 1.856 1.856 1.856
& Building
Sides 1.775 1.781 1.805 1.917 1.772 1.811 1.797 1.755 1.746 1.856 1.856 1.856
Factor Sb
Gable 1.775 1.781 1.805 1.917 1.772 1.811 1.797 1.755 1.746 1.856 1.856 1.856
Site Wind Roof 16.33 15.29 15.29 15.50 15.29 16.75 17.80 19.48 20.94 20.73 19.06 17.17
Speed Vs
Sides 16.33 15.29 15.29 15.50 15.29 16.75 17.80 19.48 20.94 20.73 19.06 17.17
(m/s)
Gable 16.33 15.29 15.29 15.50 15.29 16.75 17.80 19.48 20.94 20.73 19.06 17.17
Effective Roof 28.99 27.23 27.59 29.71 27.10 30.33 31.99 34.18 36.57 38.49 35.38 31.88
Wind Speed
Sides 28.99 27.23 27.59 29.71 27.10 30.33 31.99 34.18 36.57 38.49 35.38 31.88
Ve (m/s)
Gable 28.99 27.23 27.59 29.71 27.10 30.33 31.99 34.18 36.57 38.49 35.38 31.88
Dynamic Roof 0.515 0.455 0.467 0.541 0.450 0.564 0.627 0.716 0.820 0.908 0.767 0.623
Pressure
Sides 0.515 0.455 0.467 0.541 0.450 0.564 0.627 0.716 0.820 0.908 0.767 0.623
q (kN/m²)
Gable 0.515 0.455 0.467 0.541 0.450 0.564 0.627 0.716 0.820 0.908 0.767 0.623
Size Effect Roof 0.800 0.800 0.800 0.835 0.800 0.835 0.835 0.800 0.800 0.800 0.800 0.800
Factor
Sides 0.794 0.794 0.794 0.832 0.794 0.832 0.832 0.794 0.794 0.794 0.794 0.794
Cae
Gable 0.855 0.855 0.855 0.880 0.855 0.880 0.880 0.855 0.855 0.855 0.855 0.855

68
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 2 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Assessment to BS6399-2

Xo

Hr
Ho

Ho= Obstruction Height or average height


of roof tops upwind of building under consideration
Hr= Maximum height of building (REFERENCE HEIGHT)
Xo= Distance to obstruction

Terrain Data

Wind Direction (deg) 0 30 60 90 120 150 180 210 240 270 300 330

Smallest Obstruction 6 6 6 0 6 6 6 6 6 0 0 0
Height Ho(m)

Distance to Obstruction
20 20 20 0 20 20 20 20 20 0 0 0
Xo(m)

Upwind distance to sea 200 172 130 54 200 77 80 102 200 200 200 200
(km)
Upwind Distance from
13.5 10.5 2.5 0.0 14.5 10.5 14.5 22.5 26.5 0.0 0.0 0.0
Edge of Town(km)

69
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 3 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Assessment to BS6399-2

Roof Orientation Unknown


North
Roof Type Flat Roof

1
4

2
3

Dynamic Pressure kN/m²

Orthogonal Orthogonal Orthogonal Orthogonal


Direction 1 Direction 2 Direction 3 Direction 4
0.908 0.908 0.908 0.908

70
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 4 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Assessment to BS6399-2

Wall Orientation Unknown deg.


North
Short Face 1 or 3 15.000 m (Gable)
Long Face 2 or 4 70.000 m (Side)

1
4

2
3

Dynamic Pressure kN/m²

Face 1 Face 2 Face 3 Face 4

0.908 0.908 0.908 0.908

71
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 5 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com

Wind Analysis to BS6399-2 - Cpe Results for Roofs


DATA ENTRY:-
Short Face Length of Building 15.000 m Reference Height 30.000m
Long Face of Building 75.000 m
Roof Type Flat roof- sharp eaves

75000
9000
-0.700
15000
6000

-1.400
-2.000 45000 -2.000
15000 15000

Wind

Wind 75000
3750 -2.000
-0.700 15000
7500 -1.400 -0.200
3750 -2.000 +0.200
6000
1500 67500

NB: All dimensions are in


72 millimetres, except Cpe values
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 6 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Cpe Results for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 1 (Gable)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face

15000
Wind on
Face 2
30000 -1.300 -0.800

12000 3000

15000
Wind on
30000 Face 4
-0.800 -1.300

3000 12000

-Cpe On Reference Face1


+Cpe On Reference Face =+0.739
-Cpe On Opposite(Leeward) Face =0.500

NB: All dimensions are in


73 millimetres, except Cpe values
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 7 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Cpe Results for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 2 (Side)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face
70000

Wind on
Face 3
30000 -1.300 -0.800 -0.500

3000 12000 55000

70000

Wind on
30000 Face 1
-0.500 -0.800 -1.300

55000 12000 3000

-Cpe On Reference Face2


+Cpe On Reference Face =+0.850
-Cpe On Opposite(Leeward) Face =0.500

NB: All dimensions are in


74 millimetres, except Cpe values
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 8 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Cpe Results for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 3 (Gable)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face

15000
Wind on
Face 4
30000 -1.300 -0.800

12000 3000

15000
Wind on
30000 Face 2
-0.800 -1.300

3000 12000

-Cpe On Reference Face3


+Cpe On Reference Face =+0.739
-Cpe On Opposite(Leeward) Face =0.500

NB: All dimensions are in


75 millimetres, except Cpe values
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 9 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Cpe Results for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 4 (Side)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face
70000

Wind on
Face 1
30000 -1.300 -0.800 -0.500

3000 12000 55000

70000

Wind on
30000 Face 3
-0.500 -0.800 -1.300

55000 12000 3000

-Cpe On Reference Face4


+Cpe On Reference Face =+0.850
-Cpe On Opposite(Leeward) Face =-0.500

NB: All dimensions are in


76 millimetres, except Cpe values
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 10 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Assessment to BS6399-2

Data Entry:-
Without Dominant Opening Reference Height (Hr)
Condition Roof 30.000 m
100.000 m³
Internal Volume Side Walls 30.000 m
Gables 30.000 m
-ve 0.300
Cpi
+ve 0.000

Size Effect Factors For Cpi

Wind Direction (deg) 0 30 60 90 120 150 180 210 240 270 300 330

Size Effect Factor


0.832 0.832 0.832 0.860 0.832 0.860 0.860 0.832 0.832 0.832 0.832 0.832
Cai (Roof)

77
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 11 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Assessment to BS6399-2

Data Entry:-
Without Dominant Opening Reference Height (Hr)
Condition Roof 30.000 m
100.000 m³
Internal Volume Side Walls 30.000 m
Gables 30.000 m
-ve 0.300
Cpi
+ve 0.000

Size Effect Factors For Cpi

Wind Direction (deg) 0 30 60 90 120 150 180 210 240 270 300 330

Size Effect Side 0.832 0.832 0.832 0.860 0.832 0.860 0.860 0.832 0.832 0.832 0.832 0.832
Factor
Cai Gable 0.832 0.832 0.832 0.860 0.832 0.860 0.860 0.832 0.832 0.832 0.832 0.832

78
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 12 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07, August, 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com

Wind Analysis to BS6399-2 - Wind Loads for Roofs


DATA ENTRY:-
Short Face Length of Building 15.000 m Reference Height 30.000m
Long Face of Building 75.000 m
Roof Type Flat roof- sharp eaves

75000
9000
-0.282
15000
6000

-0.790
-1.226 45000 -1.226
15000 15000

Wind

Wind 75000
3750 -1.226
-0.282 15000
7500 -0.790 0.372
3750 -1.226
6000
1500 67500

NB: All dimensions are in


79 millimetres and wind loads in kN/m²
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 13 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 1 (Gable)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face

15000
Wind on
Face 2
30000 -0.783 -0.394

12000 3000

15000
Wind on
30000 Face 4
-0.394 -0.783

3000 12000

Suction(kN/m²) On Reference Face1


Pressure (kN/m²) On Reference Face = +0.800
Pressure/Suction (kN/m²) On Opposite(Leeward) Face = -0.161
Note: The above loads are not applicable to parapets which must be designed separately.

NB: All dimensions are in


80 millimetres and wind loads in kN/m²
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 14 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 2 (Side)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face
70000

Wind on
Face 3
30000 -0.711 -0.350 -0.134

3000 12000 55000

70000

Wind on
30000 Face 1
-0.134 -0.350 -0.711

55000 12000 3000

Suction(kN/m²) On Reference Face2


Pressure (kN/m²) On Reference Face = +0.839
Pressure/Suction (kN/m²) On Opposite(Leeward) Face = -0.134
Note: The above loads are not applicable to parapets which must be designed separately.

NB: All dimensions are in


81 millimetres and wind loads in kN/m²
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 15 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 3 (Gable)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face

15000
Wind on
Face 4
30000 -0.783 -0.394

12000 3000

15000
Wind on
30000 Face 2
-0.394 -0.783

3000 12000

Suction(kN/m²) On Reference Face3


Pressure (kN/m²) On Reference Face = +0.800
Pressure/Suction (kN/m²) On Opposite(Leeward) Face = -0.161
Note: The above loads are not applicable to parapets which must be designed separately.

NB: All dimensions are in


82 millimetres and wind loads in kN/m²
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 16 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date 07/08/2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Walls

DATA ENTRY:-
1
Short Face 1 or 3 15.000 m
4
Long Face 2 or 4 70.000 m
Reference Face Face 4 (Side)
Reference Height 30.000 m 2
Gap Between Buildings 0.000 m 3

Reference Face
70000

Wind on
Face 1
30000 0.000 0.000 0.000

3000 12000 55000

70000

Wind on
30000 Face 3
0.000 0.000 0.000

55000 12000 3000

Suction(kN/m²) On Reference Face4


Pressure (kN/m²) On Reference Face = -0.000
Pressure/Suction (kN/m²) On Opposite(Leeward) Face = -0.000
Note: The above loads are not applicable to parapets which must be designed separately.

NB: All dimensions are in


83 millimetres and wind loads in kN/m²
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 17 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07 August 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Parapets

1
DATA ENTRY:-
Short Face 1 or 3 15.000 m
Long Face 2 or 4 70.000 m
4 2
Reference Face Face 1 (Gable)
Reference Height 30.000 m
Solidity 1.000
Parapet Height 1.000 m 3
Corner Condition Without return corners Reference Face

15000

1.397

Wind 0.932
1000

1.630 1.087

300 2000
1700 11000

Suction/Pressure(kN/m²) On Reference Face

NB: All dimensions are in millimetres and wind loads in kN/m²


84
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 18 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07 August 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Parapets

1
DATA ENTRY:-
Short Face 1 or 3 15.000 m
Long Face 2 or 4 70.000 m
4 2
Reference Face Face 2 (Side)
Reference Height 30.000 m
Solidity 1.000
Parapet Height 1.000 m 3
Corner Condition Without return corners Reference Face

70000

1.298
0.865

Wind
1.514 1.009
1000

300 2000
1700 66000

Suction/Pressure(kN/m²) On Reference Face

NB: All dimensions are in millimetres and wind loads in kN/m²


85
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 19 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07 August 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Parapets

1
DATA ENTRY:-
Short Face 1 or 3 15.000 m
Long Face 2 or 4 70.000 m
4 2
Reference Face Face 3 (Gable)
Reference Height 30.000 m
Solidity 1.000
Parapet Height 1.000 m 3
Corner Condition Without return corners Reference Face

15000

1.397

Wind 0.932
1000

1.630 1.087

300 2000
1700 11000

Suction/Pressure(kN/m²) On Reference Face

NB: All dimensions are in millimetres and wind loads in kN/m²


86
SE1146-DC-01 Rev A

/ MetSPEC /® Sheet No. 20 of 20


Job No. SE1146
DESIGN SUITE
MetSPEC12©Copyright 2009,Metsec Building Products Designer AJW
Date Friday, 07 August 2015
METSEC
Registered Details:-
/BUILDING PRODUCTS/
Iesis Special Structures
LIMITED 13 Austin Friars, Londion,
Broadwell Road, Oldbury, West Mids. B69 4HF London, EC2N 2HE
Tel:0121 601 6000 Fax:0121 601 6111 Tel: 0207 496 1630 Fax:
Email: purlin@metsec.com Email: alanwerrett@iesis.net
Website: http://www.metsec.com
Wind Analysis to BS6399-2 - Wind Loads for Parapets

1
DATA ENTRY:-
Short Face 1 or 3 15.000 m
Long Face 2 or 4 70.000 m
4 2
Reference Face Face 4 (Side)
Reference Height 30.000 m
Solidity 1.000
Parapet Height 1.000 m 3
Corner Condition Without return corners Reference Face

70000

1.298
0.865

Wind
1.514 1.009
1000

300 2000
1700 66000

Suction/Pressure(kN/m²) On Reference Face

NB: All dimensions are in millimetres and wind loads in kN/m²


87
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

GROUND FLOORS

The following pages cover the ETABS and SAFE floor slab analysis and designs.

88
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 206

Cladding load applied to slab

Applied Live loading

89
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H12 @ 200 c/c in B1

90
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B2

Required top steel in addition to H12 @ 200 c/c in T1

91
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T2

92
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 208

Cladding load applied to slab

Applied Live loading

93
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H12 @ 200 c/c in B1

94
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B2

Required top steel in addition to H12 @ 200 c/c in T1

95
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T2

96
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 209

Applied Live loading

Applied Superdead loads

97
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B1

Required bottom steel in addition to H12 @ 200 c/c in B2

98
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T1

Required top steel in addition to H12 @ 200 c/c in T2

99
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 210

Cladding load applied to slab

Applied Live loading

100
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H12 @ 200 c/c in B1

101
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B2

Required top steel in addition to H12 @ 200 c/c in T1

102
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T2

103
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 107

Cladding load applied to slab

Applied Live loading

104
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H10 @ 150 c/c in B1

105
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H10 @ 150 c/c in B2

Required top steel in addition to H10 @ 150 c/c in T1

106
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H10 @ 150 c/c in T2

107
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

FIRST FLOORS

The following pages cover the ETABS and SAFE floor slab analysis and designs as well as punching
shear checks using the TCC spreadsheets.

108
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 206

Cladding load applied to slab

Applied Live loading

109
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H12 @ 200 c/c in B1

110
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B2

Required top steel in addition to H12 @ 200 c/c in T1

111
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T2

Punching shear loadings

112
SE1146-DC-01 Rev A

113
SE1146-DC-01 Rev A

114
SE1146-DC-01 Rev A

115
SE1146-DC-01 Rev A

116
SE1146-DC-01 Rev A

117
SE1146-DC-01 Rev A

118
SE1146-DC-01 Rev A

119
SE1146-DC-01 Rev A

120
SE1146-DC-01 Rev A

121
SE1146-DC-01 Rev A

122
SE1146-DC-01 Rev A

123
SE1146-DC-01 Rev A

124
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 208

Cladding load applied to slab

Applied Live loading

125
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H12 @ 200 c/c in B1

126
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B2

Required top steel in addition to H12 @ 200 c/c in T1

127
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T2

Punching shear loadings

128
SE1146-DC-01 Rev A

129
SE1146-DC-01 Rev A

130
SE1146-DC-01 Rev A

131
SE1146-DC-01 Rev A

132
SE1146-DC-01 Rev A

133
SE1146-DC-01 Rev A

134
SE1146-DC-01 Rev A

135
SE1146-DC-01 Rev A

136
SE1146-DC-01 Rev A

137
SE1146-DC-01 Rev A

138
SE1146-DC-01 Rev A

139
SE1146-DC-01 Rev A

140
SE1146-DC-01 Rev A

141
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 209

Applied Live loading

Applied Superdead loads

142
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B1

Required bottom steel in addition to H12 @ 200 c/c in B2

143
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T1

Required top steel in addition to H12 @ 200 c/c in T2

144
SE1146-DC-01 Rev A

145
SE1146-DC-01 Rev A

146
SE1146-DC-01 Rev A

147
SE1146-DC-01 Rev A

148
SE1146-DC-01 Rev A

149
SE1146-DC-01 Rev A

150
SE1146-DC-01 Rev A

151
SE1146-DC-01 Rev A

152
SE1146-DC-01 Rev A

153
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

BUILDING 210

Cladding load applied to slab

Applied Live loading

154
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Applied Superdead loads

Required bottom steel in addition to H12 @ 200 c/c in B1

155
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required bottom steel in addition to H12 @ 200 c/c in B2

Required top steel in addition to H12 @ 200 c/c in T1

156
SE1146-DC-01 Rev A

Iesis Special Structures GMV2


Consulting Civil & Structural Engineers

Required top steel in addition to H12 @ 200 c/c in T2

Punching shear loadings

157
SE1146-DC-01 Rev A

158
SE1146-DC-01 Rev A

159
SE1146-DC-01 Rev A

160
SE1146-DC-01 Rev A

161
SE1146-DC-01 Rev A

162
SE1146-DC-01 Rev A

163
SE1146-DC-01 Rev A

164
SE1146-DC-01 Rev A

165
SE1146-DC-01 Rev A

166