CADANGAN PEMBINAAN STRUKTUR MUKASAUK BARU DI LOJI
RAWATAN AIR SEMANGAR, KOTA TINGGI JOHOR.
NO.CONTRACT: PAAB/J070/J/K/05/20
Table of Contents
CADANGAN PEMBINAAN STRUKTUR MUKASAUK BARU DI LOJI
RAWATAN AIR SEMANGAR, KOTA TINGGI JOHOR.
NO.CONTRACT: PAAB/J070/J/K/05/20
1. Introduction
1.1 System Architecture
The objective of this document is as a descriptive manual for operation and
monitoring functions of the SCADA and control system of Semangar New Intake
Plant.
System configuration between PLC, SCADA, and HMI devices in Semangar New
Intake Plant:
New SCADA PC
To existing SCADA
New PLC system
Location IP address
PLC 192.168.1.210
LCP HMI 192.168.1.211
Remote HMI 192.168.1.212
SCADA 192.168.1.220
Two Schneider touch panels are used, 15” touch panel in the Existing Raw Water
Intake Control Room, and 12” touch panel in the New Intake Electrical Room. These
touch panels contain the mimic drawing, equipment status and control, parameter
settings, and alarms.
Touch panel for
monitoring and control
Sand Ejector No. 1 Sand Ejector No. 2
Pump status and control Pump status and control
Sand Ejector No. 1 Sand Ejector No. 2
Valve status and control Valve status and control
Sand Ejector System LCP Panel
Auto/Manual Status Accept Alarm/Reset
and Selector Alarm/Lamp Test Button
CONTROL AVAILABLE
STATUS (WHITE) TRIPPED STATUS
(AMBER)
RUNNING STATUS
(RED) STOPPED STATUS
(GREEN)
MANUAL START MANUAL STOP
BUTTON BUTTON
Figure 2.2: Close-up of pump status and operation button
CONTROL AVAILABLE
STATUS (WHITE) FAILED STATUS
(AMBER)
FULLY OPEN
STATUS (RED) FULLY CLOSE
STATUS (GREEN)
MANUAL OPEN/CLOSE
SELECTOR SWITCH
Figure 2.3: Close-up of Valve status and operation switch
PLANT AUTO/MANUAL
SELECTOR SWITCH
Page Title Date and Time
Navigation button
Status display for equipment is displayed by the circle beside the equipment. Status
is displayed by colour of the circle as below:
Status Colour
No signal
Running/ Fully
Opened
Stopped/Fully Closed
Tripped/Failed
For changing
between pump 1/2
Running/Fully Opened
(Red)
Stopped/Fully Closed
(Green)
Tripped/Failed (Amber)
Start/Open button
(Green)
Stop/Close button (Red)
A
C
F
B E
D G
D) Archimedean Pumps Operation Time and Level setpoint for Auto Mode
E) Sand Ejector System Auto Mode status and Start/Stop push button
G) Sand Ejector Pumps Duration Time and Cycle Time setpoint for Auto Mode
Graphic Description
1 3
2
5
4
6
1) Menu
Menu dropdown for page navigation
2) Page title
Motors
Fans
Circuit
Breakers
For valves, there will be an indicator lamp beside the valve to indicate their status as
below:
Opened Closed
For EF/OC, and ELR, the same indicating lamp beside them to indicate their status
as below:
Tripped Normal
1
2
1
2
Figure 4.7: Plan View of New Intake Plant
1) Switch to Side View Page
1
2
5
3
6 7
4
4) Archimedean Pumps Level setpoint, Current River Level and Pump Duty
Amount
5) Sand Ejector System Auto Mode status and Start/Stop push button
7) Sand Ejector Pumps Duration Time and Cycle Time setpoint for Auto Mode
2) Set the Operation Time and Cycle Time for the Sand Ejector System from
the touch screen (Figure 3.11, G).
3) Press the “Auto Start” push button to start the Sand Ejector Auto System.
4) The Sand Ejector Pump 1 will Start, and the Sand Ejector Valve 1 will Open.
5) Sand Ejector Pump 1 will run for the half of set Operation Time, then Sand
Ejector Pump 1 will Stop, and the Sand Ejector Valve 1 will Close.
6) The Sand Ejector Pump 2 will Start, and the Sand Ejector Valve 2 will Open.
7) Sand Ejector Pump 2 will run for the half of set Operation Time, then Sand
Ejector Pump 2 will Stop, and the Sand Ejector Valve 2 will Close.
8) The Sand Ejector System operation will complete, and the system will wait
until set Cycle Time elapsed before starting again at Step 3.
2) Set the Level Setpoints and Operation Time for the Archimedean System
from the touch screen (Figure 3.11, D).
3) Press the “Auto Start” push button to start the Archimedean Auto System.
4) The previous running pump will be the duty pump. Else, the default duty pump
is Pump 1.
5) Depending on the current river level and setpoints, the set number of pumps
will run based on:
6) During 1 pump duty, if the pump has run for set Operation Time, or the pump
has tripped, the pump will stop and changeover to the other pump.