Enclosure Integrity Door Fan Calibration Certificate Enclosure Integrity Door Fan Calibration Certificate

Issued by: Retrotec Certificate Number: 607331514 Issued by: Retrotec Certificate Number: 607331514
Calibration Date: 2018-06-05 Results: As Left Calibration Date: 2018-06-05 Results: As Left

This Retrotec Door Fan system been calibrated to comply with


NFPA 2001, ISO 14520, and EN15004 standards on clean agent fire extinguishing systems. Calibration laboratory:
Retrotec
1060 East Pole Rd.
Everson, WA, USA 98247
+1 (360) 738-9835
calibration@retrotec.com
www.retrotec.com
This calibration laboratory has been assessed by the ANSI-ASQ National Accreditation Board and meets the requirements of international standard
ISO/IEC 17025:2005. All pressure and flow devices used in this calibration are traceable to the National Institute of Standards and Technology.

Device being calibrated:


Description: Test Fan
Manufacturer: Retrotec Calibrated By:
Model Number: 6000
Shell Serial Number: 3PH600733 _____________________________
Mains Voltage: 240V AC ±10V Signature
Mains Frequency: 50Hz ±1Hz

Reference Flow:
Nozzle Chamber, in accordance with ANSI/AMCA 210-07:
Nozzles #2, #4, #5, #6 – 8” diameter
Nozzles #1, #3 – 7” diameter
Nozzle #7 – 6” diameter
Nozzle #8 – 4” diameter
Nozzle #9 – 3” diameter
Chamber Pressure measured on: DM-32 Gauge Serial number 401973-A
Device’s Fan Pressure measured on: DM-32 Gauge Serial number 401973-A
Nozzle Wall Pressure measured on: DM-32 Gauge Serial number 402091-B

Laminar Flow Elements (LFE) Chamber:


LFE#2, Model 50MC2-4LHL, Serial number 712110-A3, on DM32 Gauge Serial number 405308-B
LFE#3, Model 50MC2-2LHL, Serial number 712110-A2, on DM32 Gauge Serial number 401969-A
LFE#4, Model 50MH10-2, Serial number 712110-A1, on DM32 Gauge Serial number 401969-B
Chamber Pressure measured on: DM-32 Gauge Serial number 402118-A
Device’s Fan Pressure measured on: DM-32 Gauge Serial number 402118-B

Calibration Information:
The Device was calibrated against laboratory standards whose values are traceable to recognized national standards. The
results and uncertainty limits refer to the measured values only, with no account being taken of the instrument’s ability to
maintain its calibration. The reported expanded uncertainty is based on a standard uncertainty multiplied by a coverage
factor k=2, providing a level of confidence of approximately 95%. The uncertainty evaluation has been carried out in
accordance with ANSI/ISO/IEC 17025:2005 requirements.

Calibration Procedure: Procedure ID No. CP-CHB-01

This Calibration Certificate shall not be reproduced except in full, without written approval from Retrotec.

Page 4 of 4 Date of Form rev: 2018-06-26 Page 1 of 4 Date of Form rev: 2018-06-26
Enclosure Integrity Door Fan Calibration Certificate Enclosure Integrity Door Fan Calibration Certificate

Issued by: Retrotec Certificate Number: 607331514 Issued by: Retrotec Certificate Number: 607331514
Calibration Date: 2018-06-05 Results: As Left Calibration Date: 2018-06-05 Results: As Left

Calibration Results: Published Flow Equation Parameters:


Start of calibration: Barometric pressure= 101.6 kPa, Temperature= 19.9°C, Humidity= 46.3%
End of calibration: Barometric pressure= 101.6 kPa, Temperature= 20.0°C, Humidity= 45.0%
Range Serial number N, K, Minimum flow, Maximum flow,
Configuration exponent constant, CFM CFM
Flow rates are corrected to STP conditions of 20°C, 101.325 Pa and 50% RH. at 25 Pa
CFM/Pa N
Open 3PH600733 0.498 548 2722 7407
From Flow Chamber Reference Test Fan being Calibrated
Chamber Background Nozzles Used Nozzle Total STP Range Fan Fan STP STP Error
3PH600733-
Ring A 0.502 287 1444 4542
Pressure leakage wall ELA, Config- speed Pressure, Flow, ELA, A
(BP), at BP, pressure, uration 3PH600733-
Pa sq in Pa sq in Pa CFM sq in B8 0.54 113.25 830.1 2775
B
29.6 0.85 1,3,4,6,7 418.0 1254 Open 100% 187.0 7407 1266 1.0%
29.8 0.86 4,6,9 611.0 791.5 Ring A 100% 245.5 4542 773.6 -2.3% Flow, CFM = PN * K
Where P = Fan Pressure, in Pascals
30.4 0.86 5,8 629.5 465.0 B8 100% 374.5 2775 467.9 0.6%
30.1 0.86 7 650.5 214.6 B4 100% 391.5 1244 210.7 -1.8%
30.7 0.86 8 602.5 91.6 B2 100% 396.5 534.4 102.2 -2.1% Range Serial g f a b c d Minimum Maximum
30.8 0.86 9 515.0 48.3 B1 100% 405.5 279.7 50.5 -2.9% Configuration number flow, flow,
CFM CFM
Calibration and measurement capability (Expanded Uncertainty) is 1.2% of reading, based on a 95% confidence interval, using a coverage of k=2 at 25 Pa
3PH600733-
B4
B 0 0.70 0.00000662 -0.0078 4.75 205 319.0 1244

From Flow Chamber Reference Test Fan being Calibrated 3PH600733-


B2 145.8 534.4
Chamber Background LFE Used LFE Total STP Range Fan Fan STP STP Error B 40 0.85 3.00E-06 -0.0037 2.2 49
Pressure leakage pressure, ELA, Config- speed Pressure, Flow, ELA, 3PH600733-
(BP), at BP, uration B1 78.4 279.7
Pa sq in Pa sq in Pa CFM sq in
B 65 0.20 0.00000106 -0.001382 0.96511 38.5
29.8 0.006 2 241.5 26.9 B74 100% 435.0 159.5 27.2 1.0% B74 1096545 25 0.145 0.000000796 -0.0009501 0.59 18 41.1 159.5
100% -
30.5 0.006 3 460.0 12.1 B47 100% 428.5 71.0 12.0 -1.0% B47 1096859 25 0.09 2.69043E-07 0.000359055 0.2435 12.05
25.6 71.0
30.2 0.006 4 1225.0 4.4 B29 100% 449.5 25.8 4.4 -0.6% B29 1095746 25 -0.02 0.000000111 -0.000149 0.092 4.4 6.11 25.8

Calibration and measurement capability (Expanded Uncertainty) is 3.5% of reading, based on a 95% confidence interval, using a coverage of k=2 Flow, CFM = P3*a+P2*b+P*c+d+(g-|PrA|)*f
Where P = Fan Pressure, in Pascals

_________
Initial Published Flow Equation Parameters shown are designated as “Round B1” for traceability purposes.