Laying New Pipeline - Pressure Test CHECKLIST 2210

Project

NO. STANDARD CHECK REMARKS


1 All pipe installation works completed and inspected by OIC Y N NA
2 Method statement, calibration report of pressure gauge, testing Y N NA
equipment submitted to and approved by OIC
3 All necessary equipment, power, personnel, hand pumps, water Y N NA
and other materials are ready for the satisfactory testing of the
section of the pipeline
4 Adequate quantity of potable water (clean water) available for Y N NA
testing works at site
5 Enough backfilling, trust blocks/anchor blocks provided at all the Y N NA
necessary locations to hold the pipe
6 Sections or lengths of the pipe do not exceed 500m or shorter Y N NA
length as directed by OIC
7 Both ends of the pipe properly capped with pressure gauge Y N NA
installed properly
8 Length under test filled with clean water from the lowest point in Y N NA
order to ensure the complete elimination of air. Air has been fully
expelled
9 Pipeline pressure test with the potable water to a pressure of Y N NA
1.05 MN/m2 (150 psi) or specified. Pressure maintained for one
(1) hour without any drop
10 Leakage test carried out for 24 hours and reading taken at every Y N NA
30 minutes or as specified
11 Calculated pressure drop (leakage) is within allowable limit and Y N NA
approved
12 All pipelines tested for pressure and leakage test before the final Y N NA
connection
13 All valves, fire hydrants, air valves, connections, overcrossings Y N NA
and specials observed for any leaks
14 Both pressure and leak test carried out and recorded as per Y N NA
standard procedure/specification
15 Pipe pressured as per the requirements and witnessed by Water Y N NA
Services Control Unit (WSCU), DWS, PWD

Name of SS: Name of OIC:


Checked & Signed: Reviewed Non-compliance: Verified & Signed: Reviewed Non-compliance:

Date: Date: Date: Date: