Professional Documents
Culture Documents
Sustainable Environment Building
Sustainable Environment Building
Chapter 5
Energy in Buildings
2
Introduction
This chapter, of the book Sustainable Environment Building, written
by van Bueren, E.M., van Bohemen, H., Itard, L. and Visscher, H. is
about presenting fundamental knowledge of the built environment.
This book approaches this topic from an ecosystems perspective. It
will learn you how to combine diverse practical elements into sus-
tainable solutions in the build environment.
Good luck!
3000000
2500000 2500
Combustible renew ables
Geothermal, solar & w ind
Population (million)
2000000 2000
TPES (ktoe)
Hydro
1500000 1500 Nuclear
Gas
1000000 1000
Crude oil
500
Coal & Peat
500000
0 0
OECD North America
OECD Europe
Former USSR
OECD Pacific
Middle East
China
Latin America
Asia
Africa
2000000
Non-energy use
1800000
Others
1600000
services
1000000 Residential
800000 Transport
600000 Industry
400000
200000
0
Africa
OECD Pacific
Former USSR
OECD North
OECD Europe
China
Asia
Latin America
Middle East
America
Lighting
5% Space heating
53%
Cooking
5%
Water heating
16%
Cooking
5%
Water heating
9%
Environmental
effects: Depletion of
emissions to natural
air, soil and resources
water
Combustible
non-
renewable
(energy content of the
resources
Primary energy
resources)
Energy Combustible
Energy Energy
storage & renewable
demand conversion
distribution resources
Non-
combustible
renewable
resources
5.2.1. Introduction
Considering the fact that the energy consumed in the built
environment is consumed for 92% within buildings, and
15
Local conditions
Next to this, the weather conditions of interest for the
building may be influenced by local circumstances like the
19
an albedo of approxi-
mately 0.9, stony Soil
building for a period of one year. This offers also the ad-
vantage of avoiding making calculations only for the win-
ter or only for the summer, by which the building design
may be sub-optimized for one season. To do this it is nec-
essary to use software simulation tools. A list of existing
tools may be found on
http://apps1.eere.energy.gov/buildings/tools_directory/ and
on www.ibpsa.org. Many simplified methods were devel-
oped as well in order to make quick estimations. In the
next sections we will give a basic understanding of these
simplified methods.
To To Ti To Ti
Ti Qtrans = αo αi
U λ3 λ2 λ1
d3 d2 d1
P= UA(To − Ti ) [W ]
trans , s
(1)
1
with U= [Wm −2 K −1 ]
1 1
+ Rc +
αi αo
(2)
d1 d 2 d 3
Rc = Rc1 + Rc 2 + Rc 3 = + + [m 2 KW −1 ] (3)
λ1 λ2 λ3
Thermal bridges
In addition to transmission losses through surface areas
there are also transmission losses occurring at the junction
of walls, or at the junction of wall and ceiling, wall and
floor or wall and window frame, window frame and glaz-
ing. Especially when the insulation material is poorly
placed, thermal leakage will occur, as it may be the case at
the junction of a balcony with a wall or with load bearing
columns going from outdoors to indoors. These losses are
called thermal bridges and cause not only additional heat
losses but also damages to construction and interiors be-
cause of condensation on the thermal bridge by cold
weather. Heat losses through thermal bridges can be cal-
culated using formula (4). See also Iso 2007
Infiltration losses
26
ρV
m = [kgs −1 ] (7)
3600
Where ṁ is the mass flow rate of air [kgs-1], ρ the density
of air in [kgm-3] and V the volume flow rate of air in [m3h-
1
]. The density of air varies with temperature but may be
assumed to be 1.2 kgm-3 at ambient temperature.
Typical air changes per hour varies from 0.1-0.2 for air-
tight large new buildings (floor area >10.000 m2), to 0.2-
0.3 for smaller buildings and 0.5-1 or more for old build-
ings. In Ashrae standard 62.2 more data may be found. In
many countries building regulations set maximal values to
infiltration air flow rates. For instance in the Netherland
the infiltration air flow rate should not exceed 0.2m3 per
500 m3 building’s volume.
Ventilation losses
There are basically three types of ventilation systems, see
figure 12.
• Natural ventilation though grilles and windows. In this
case no ventilator is used.
• Mechanical supply ventilation or mechanical exhaust
ventilation. In these cases one ventilator is used either
at the supply side or at the exhaust side.
• Mechanical supply and exhaust ventilation with heat
recovery, also called balanced ventilation. In this case
two ventilators are used.
Ventilator Ventilator Ventilators
Heat
exchanger
V .∆p
Pelec ,vent = [W ] (10)
η
Convection
Psol = ∑ g glass
i
. Awindow
i
.g shade
i
.Psoli [W ] (11)
i
33
Natural lighting
Solar radiation does not only affect the heat balance of a
building, is also affects the energy used for lighting. How-
34
People
The human body produces heat that must be dissipated to
the surrounding to maintain the normal body temperature.
Heat is dissipated through respiration, convection from
skin to air and sweating. The quantity of heat released de-
pends on the level of activity, the type of clothes worn (in-
sulation and permeability) and the temperature and humid-
ity of the surrounding air. For further reading, see Ashrae
Handboek (2009) or Indoor Climate fundamentals (2004)
Lighting
The total electrical lighting power to be installed in a
building (see section 5.3.5) does not depend on incoming
day light, but the instantaneous used electrical power may
do. Next to this, the electrical lighting power depends on
the type of lamps used and of the function of the building.
Note that the powers are average powers during one hour.
This means that the temperatures used in equations 1, 4, 6
and 9 should be mean temperatures during one hour. The
air flow rates used in equations 6 and 9 must be as well
averaged for one hour, as well as the solar radiation used
43
Capacity (kW)
Capacity (kW)
Capacity (kW)
Capacity (kW)
figure 14: this figure gives the hourly heating and cooling
capacities(above for the complete year, under for 10
days), that are also the hourly energy demand for heating.
The area under the upper curve equals the sum of all
hourly values and is equal to the yearly energy demand.
The maximum value in the graphics represent the capacity
(or peak load), in this case ~180 kW for heating and
140kW for cooling.
Simplified calculations
When hourly weather data are not available, simplified
calculation are possible using the degree day method or the
load factor method. For detailed explanation on this meth-
ods, see ASHRAE 2009.
heat gains are neglected to cover the case where the build-
ing must be maintained at temperature when both gains are
not present (for instance at night). The chosen outdoor
temperature must reflect the coldest temperature in the re-
gion. The cooling capacity Pcooling is calculated based ac-
cording to equation 16, based on the highest occurring
outdoor temperature (if this temperature is higher than the
indoor design temperature), and the highest occurring solar
gains and internal heat gains. The yearly energy demand is
then calculated using equations (17) and (18):
Where hheating the number of full load hours for heating and
hcooling the number of full load hours for cooling. The num-
ber of full load hours is the number of hours that the max-
imum heating (c.q. cooling) capacity would have been
needed to achieve the same yearly energy demand as in re-
ality. Practically the number of full load hours is statisti-
cally calculated from a large number of buildings from
which the annual energy demand and the installed capaci-
ties are known. This method may be used for a very rough
estimation, but is very inaccurate as the number of full
load hours does not relate to a specific building but is an
average. Table 11 gives some typical full load hours for
the Netherlands (moderate sea climate).
∑
365
=HDD 1
max(Tref − To , 0) (19)
∑
365
=CDD 1
max(To − Tref , 0) (20)
Indoor temperature
Considerable energy savings may be achieved by using an
indoor design temperature Ti that is not constant all over
the year. Because people have a large adaptation capacity,
an indoor temperature lower in winter than in summer is
acceptable – and even recommended, e.g. 20oC in winter
and 24oC in summer. The energy savings in comparison
with a building that would be maintained to 22oC all over
the year will be considerable. Lowering the design temper-
ature to 19oC in winter may be also effective, but may be
experienced as too low especially by the elderly. Accept-
ing higher indoor temperature in summer is a very efficient
way to reduce the cooling demand, but can only be done
with certain types of ventilation. In a completely air condi-
50
Insulation
In older (non-renovated) buildings, the heating demand is
for a large part determined by the transmission losses.
These losses can be strongly reduced by insulation. In so-
called passive dwellings Rc values above 8 W/m2K are
used and combined with a very high air-tightness. This
way the heating demand is reduced to almost zero (see
http://www.passiefhuisplatform.be). In countries with hot
summer temperatures, insulation will also help reducing
the cooling demand. However, in moderate climates, in
buildings with a high internal heat load that have cooling
demand also when the outdoor temperature is low, insula-
tion may prevent the heat to be released ‘freely’ outdoors.
Calculations of the yearly heating and cooling energy de-
mand should show which U-value is optimum for a specif-
ic building and a specific climate.
Solar gain
An increase in solar gains by placing large and well insu-
lated windows facing the south side (on the northern hemi-
sphere) or the west of east orientation, will decrease the
heating energy demand, but will increase the cooling de-
mand. This may be desirable in the heating season, but not
in the cooling season. The use of outdoor sun shades is
therefore very important to keep out the sun when it is too
hot. In buildings with a high internal heat load it may also
be worth placing only small windows on the south and
placing large ones on the north. Large windows on the
north face allow for the penetration of diffuse natural light.
On the south, the direct radiation produces glare that
should be avoided to ensure a good visual comfort. Fur-
thermore when the level of natural lighting is high, the sun
shades will be put down and artificial lighting will be put
on, which may be avoided by designing smaller windows
on the south.
Note also that greening the facades, roofs and the close
environment of the building can reduce considerably the
solar heat gains and therefore the cooling demand.
The yearly heating energy demand for hot tap water is cal-
culated using equation (23)
Table 12: Average daily hot water demand (in litre) in the
US
Residential Offices Schools
130-160 3.8 2-7
L/dwelling L/person L/student
To calculate the peak load for hot tap water (heating ca-
pacity of the hot tap water equipment), the maximum vol-
ume flow rate per minute must be known. In residential
buildings it will be approximately 0.01 litre per second per
person and the peak load in W can then be calculated using
equation (24):
6,00E+04
Energy demand (MJ/year)
5,00E+04
4,00E+04 Appliances
Lighting
3,00E+04 Room cooling
Room heating
2,00E+04
1,00E+04
0,00E+00
Dwelling A Dwelling B
3,00E+06
Energy demand (MJ/year)
2,50E+06
Appliances
2,00E+06
Ventilators
Lighting
1,50E+06
Room cooling
1,00E+06 Room heating
5,00E+05
0,00E+00
Office building A Office building B
Further readings:
Blok, K, 2007, Introduction to energy analysis, Techne
Press, Amsterdam, ISBN-13: 978-8594-016-6
References
ASHRAE, 1997, Ashrae Handbook - Fundamentals,
www.ashrae.org
59