Professional Documents
Culture Documents
As can be seen in Table 4, the peak discharge rate is 96.2A. Divide this number by an ambient
temperature factor of one for a 77°F room, by a 0.8 battery-aging factor, and by 0.85 for the design
margin.
As can be seen in Table 5, the total Ampere-hour rate is 27.1 Ah. Divide by an ambient temperature
factor of one for a 77°F room, and by a 0.8 battery-aging factor.
Referring back to Table 2, a Model A battery has a 1-minute discharge rate of 177A and an 8-hour Ah
rate of 180 Ah, down to 1.75V. This type of battery is, therefore, more than sufficient for this
particular load. The 125VDC, 180 Ah battery bank would be composed of 60 Model A cells.
Figure 1 shows distance protection for a section of a power system. The I zone setting at A and B are
60 Ω and 30 Ω, respectively. Determine:
-the impedance seen by the relay at A for a fault at F1 and will the relay at A operate before the circuit
breaker at B has tripped?
-the impedance of relay B trip for a fault at F1 before the circuit breaker at A trip?
-the impedence relays A and B if the circuit breaker C2 fails for a fault at F2?
Figure 1
ans
therefore the relay at A will see the fault at F1 and trip before the circuit breaker at B has tripped
Thefore the relay at B will not trip before the circuit breaker at A has tripped.
When the circuit breaker at A has trip, the relay at B will measure the impedance =(30+150)=180Ω
and trip.
Ans
Zone 1 setting = 0.85 .80 Ω= 68 Ω ,primary ohm setting
CT ratio = 2000/5 = 400
VT ratio = 200,000/69 = 2900
Relay setting = primary setting (Ω) .CT ratio/VT ratio
= 68 .(400)/(2900)
= 9.38 relay ohms
Zone 2 setting = lengthx115% (minimum)
=line length+0.5 x length of shortest next
adjacent line (preferred)
Ans
A transformer has an impulse insulation level of 1050 kV and is to be operated with an insulation
margin of 15% under lightning impulse conditions. The transformer has a surge impedance of 1600 Ω
and is connected to a transmission line having a surge impedance of 400 Ω. A short length of overhead
earth wire is to be used for shielding the line near the transformer from direct strikes. Beyond the
shielded length, direct strokes on the phase conductor can give rise to voltage waves of the form 1000
e-0.05t
kV (where t is expressed in μs). If the corona distortion in the line is represented by the expression
t 1 e0
1 μs /m, where B = 110 m/μs and e0 = 200 kV, determine the minimum length of
x B e
shielding wire necessary in order that the transformer insulation will not fail due to lightning surges.
[transmission coefficient=1.6]
Ans
Transmission coefficient
Since the voltage is increased by the transmission coefficient 1.6 at the terminal equipment,
the maximum permissible incident voltage must be decreased by this factor.
Therefore,
1000 e-0.05t = 557.8. This gives the delay time t1 = ∆t = 11.6 μs.