B1.1 MV SYSTEM
20KV, 1250A 25KA 1Sec, IP‐42 Indoor Five Panel switchboard 1
A)1924 KVA DG Incomers each cubicle comprising Of ;
- SCHNEIDER’ make Triple pole 20KV (22 KV), 25KA for 1 sec, 630A, Vacuum CB, Horizontal Isolation
& horizontal draw out type.
- Anti‐pumping relay (94) 2NO+2NC, 110VDC
- 20KV Cast Resin Insulated Wound type CT’s of ratio100/5‐5A
- Core Balance CT ratio: 100/1A; 7.5VA CL.5P10.
- Master trip relay (86), coil voltage110V DC. Alstom/JVS make
- Cast Resin Insulated Potential Trafo
B) BUS PT Cubicle comprising Of 1
- Cast Resin Insulated Potential Trafo.
C)500 KVA Transformer Feeder cubicle comprising Of ; 1
‐SCHNEDIER’ make Off load disconnect switch (manual) 20 KV 25KA, for 1 sec, 100A, 20 KV Cast
Resin Insulated Wound type CT’s of ratio
- ELR with CBCT
D) Outgoing Feeder cubicle comprising Of ; 1
- Anti‐pumping relay (94) 2NO+2NC, 110VDC
- 20 KV Cast Resin Insulated Wound type CT’s of ratio 200/5‐5A,.
- Core Balance CT ratio: 100/5A ; 2.5VA CL.5P10.
- Cast Resin Insulated Potential Trafos
- Master trip relay (86), coil voltage110V DC. Alstom/JVS make
- Complete with HT Fuses & LT MCBs.
E) Earthing truck Feeder cubicle comprising Of ;
- Earthing Truck suitable for Cable side Earthing
F) Miscellaneous 1
- Space heater, Thermostat with ON/OFF switch,
‐ Cubicle illumination lamp & Hooter.
‐ Socket & Plug & MCBs for AC/DC Control.
- Manuals.