N6166 E05 F512 OC EF Relay 7SJ61
N6166 E05 F512 OC EF Relay 7SJ61
Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 - Transformer T202
Functions
Enabled Disabled
IEC No. Description
F - LED function
Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X512
CT RATIO: 400/1 A
Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
I> (A) Current (A) Times of Iset (Sec)
(A)
R-Y 1.5 * * 1.0 *
Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
I>> (A) Current (A) Times of Iset (Sec)
(A)
R-Y 2.0 * * 0.5 *
0.14
T= .Tp [s]
(I/Ip) 0.02
-1
3.3 Earth Fault function (IDMT- Normal inverse curve ): 51N 0.14
T= .TP [s]
[(I/IP)0.02 - 1]
Instrument Used
Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Characteristics