Site Test Report

Contract No. – N-6166.1


New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116124
Contractor: CSE Equipment: 7SJ611 HV OC/EF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F512
Substation: 132/11 kV SS at ADNEC Page: 1 of 6

Inspection, Testing and Secondary Injection of


OC/EF Protection Relay 7SJ611
A - General Data:
Ordered MLFB: 7SJ6111-5EB90-1FA0 --0S Serial no.: BF1108116124

Built-in MLFB: 7SJ6111-5EB90-1FA0 --0S Firmware version: V4.81

Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 - Transformer T202

Built-in rated voltage VN: NA Software used: Digsi 4 V4.84

Built-in rated current IN: 1A Frequency: 50 HZ

Relay Designation : -F512 HV OC/EF Protection

B - General Inspection & Testing:

S NO General inspection & testing: Checked

1 Visual inspection of unit OK

2 Installation & wiring correct to relevant drawings OK

3 Relay case connected to local earth bar OK

4 Measured value check OK

5 Relay CT shorting contacts proved OK

6 Relay Binary inputs and outputs checked OK

7 Watch dog contact checked OK

8 Injection of current from terminal block with test plug OK

C- Configuration of protection function

Functions
Enabled Disabled
IEC No. Description

Description 50/51 Over Current Protection Enabled -

50N/51N Earth fault Protection Enabled -

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616912.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116124
Contractor: CSE Equipment: 7SJ611 HV OC/EF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F512
Substation: 132/11 kV SS at ADNEC Page: 2 of 6

D - Binary input function check

Bin. input Function Terminal Terminal Drawing Checked Remarks


(+)-X332:2
Relay Page No.
(-)-X332:19
BI 1 Spare F14-F16 -X332:44 /MAB3.2
BI 2 Spare F15-F16 -X332:45 /MAB3.3
BI 3 Test Mode F17-F18 -X332:46 /MAB3.3 Test plug inserted
BI 4 Spare R9-R7 -X332:47 /MAB3.4
BI 5 Spare R10-R7 -X332:48 /MAB3.4
BI 6 Spare R11-R13 -X332:50 /MAB3.5
BI 7 Spare R12-R13 -X332:51 /MAB3.6
BI 8 Spare R8-R7 -X332:49 /MAB3.5

E - Binary output check

Output Function Terminal Drawing Checked Remarks


Relay TB Page No.
BO1 OC/EF Trip F6-F7 X512:2 NAB1.4 Trip to TC2
BO2 OC/EF Trip F8-F9 X512:4-8 NEB1.3 Trip to MV2
BO3 OC/EF Trip F10-F11 X512:6 MBB1.4 Start BF protection
BO4 OC/EF Trip F12-F13 X512:16 NAB3.6 Trip to LOR 2
K325, permissive
BO5 OC/EF Pick-up R1-R3 X512:12 NBB1.2
trip from 11kV BBP
BO6 Spare R2-R3 - ZB3.3 -
BO7 OC/EF Trip R4-R5 X512:10 NAB3.8 Trip to K347
BO8 OC/EF Pick-up R6-R5 - ZB3.3 For testing only
Live Cont. F3-F4-F5 - RAB3.4 Cubicle alarm

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616912.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116124
Contractor: CSE Equipment: 7SJ611 HV OC/EF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F512
Substation: 132/11 kV SS at ADNEC Page: 3 of 6

F - LED function

S no Led no Function Checked Remarks


1 LED 1 OC Pickup - R /
2 LED 2 OC Pickup - Y /
3 LED 3 OC Pickup - B /
4 LED 4 EF Pickup /
5 LED 5 Phase OC Trip / 51, 50
6 LED 6 Earth Fault Trip / 51N, 50N
7 LED 7 Summary Alarm / summary alarm event

1. MEASURED VALUE TEST:

Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X512

CT RATIO: 400/1 A

Primary Current read on relay Secondary Current read on relay


Current display In (A) Display in (A)
Phase
injected
injected
(Amps)
IR IY IB IN IR IY IB IN

R-E 1.0 399 0 0 400 1.00 0.00 0.00 1.00

Y-E 1.0 0 399 0 400 0.00 1.00 0.00 1.00

B-E 1.0 0 0 399 399 0.00 0.00 1.00 1.00


R-0.2A
R-Y-B Y-0.4A 80 159 239 138 0.20 0.40 0.60 0.35
B-0.6A

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616912.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116124
Contractor: CSE Equipment: 7SJ611 HV OC/EF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F512
Substation: 132/11 kV SS at ADNEC Page: 4 of 6

2.1 Over current function (DMT):50-1

Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
I> (A) Current (A) Times of Iset (Sec)
(A)
R-Y 1.5 * * 1.0 *

Y-B 1.5 * * 1.0 *

R-B 1.5 * * 1.0 *

RYB 1.5 * * 1.0 *

* Note: Refer attached OMICRON Print out for Test results

2.2 Over current function (DMT):50-2

Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
I>> (A) Current (A) Times of Iset (Sec)
(A)
R-Y 2.0 * * 0.5 *

Y-B 2.0 * * 0.5 *

R-B 2.0 * * 0.5 *

RYB 2.0 * * 0.5 *

* Note: Refer attached OMICRON Print out for Test results

2.3 Over current function (IDMT- Normal Inverse): 51

0.14
T= .Tp [s]
(I/Ip) 0.02
-1

Operating time at current setting (Sec)


Test Relay Time
P/U D/O
phase setting multiplier 2*IP 5*IP 10*IP
(A) (A)
Ip (A) Tp in Sec
Act Cal Act Cal Act Cal

R-Y 1.00 * * 0.3 * 3.009 * 1.284 * 0.8912

Y-B 1.00 * * 0.3 * 3.009 * 1.284 * 0.8912

R-B 1.00 * * 0.3 * 3.009 * 1.284 * 0.8912

RYB 1.00 * * 0.3 * 3.009 * 1.284 * 0.8912

* Note: Refer attached OMICRON Print out for Test results

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616912.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116124
Contractor: CSE Equipment: 7SJ611 HV OC/EF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F512
Substation: 132/11 kV SS at ADNEC Page: 5 of 6

3.1 Earth Fault function (DMT):50N-1


Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
IE > (A) Current (A) Times of Iset (Sec)
(A)
E/F 0.2 * * 1.0 *
* Note: Refer attached OMICRON Print out for Test results

3.2 Earth Fault function (DMT):50N-2


Pick up
Relay setting Drop off Operating time @2
Test phase Current Time setting (Sec)
IE >> (A) Current (A) Times of Iset (Sec)
(A)
E/F 0.4 * * 0.75 *
* Note: Refer attached OMICRON Print out for Test results

3.3 Earth Fault function (IDMT- Normal inverse curve ): 51N 0.14
T= .TP [s]
[(I/IP)0.02 - 1]

Operating time at current setting [Sec]


Test Relay Time
P/U D/O
element setting multiplier 2*IEP 5*IEP 10*IEP
[A] [A]
IEp [A] Tp
Act Cal Act Cal Act Cal

E/F 0.50 * * 0.35 * 3.510 * 1.498 * 1.040

* Note: Refer attached OMICRON Print out for Test results

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616912.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108116124
Contractor: CSE Equipment: 7SJ611 HV OC/EF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F512
Substation: 132/11 kV SS at ADNEC Page: 6 of 6

Instrument Used

Equip. 1 Equip. 2 Equip. 3


Instrument: CMC256-6

Serial No.: JG697S

Calibration Date: 30.05.2012

Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Characteristics

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\641616912.doc