N6166 - E05 - F873 - MV - REF - Relay - 7SJ61 Site Test Report
N6166 - E05 - F873 - MV - REF - Relay - 7SJ61 Site Test Report
A - General Data:
Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 Transformer T202
Functions
Enabled Disabled
IEC No. Description
Description
50 1Ph 1Ph OC Protection Enabled -
F - LED function
Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X872
CT RATIO: 2500/1 A
Instrument Used
Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Operating time
Testmodules Checked: 4
Testmodules Passed: 4
Substation/Bay:
Substation: 132/11 kV kV SS ADNEC Substation address:
Bay: 40MVA Transformer 2 Bay address: =E05-T202
Device:
Name/description: MV_REF 7SJ61 Manufacturer: SIEMENS
Device type: 7SJ6112-5EB90-1FB0 Device address: =E05+R2-F873
Serial/model number: BF1108110656
Additional info 1: MV Restricted Earthfault Relay
Additional info 2:
Hardware Configuration
Test Equipment
Type Serial Number
CMC256-6 JG655S
Hardware Check
Performed At Result Details
23/08/2012 14:36:36 Passed
IE:
Current output 1 ---> -X873: 1-2 (-X610: 12-43)
VE
Voltage output 1 ---> -X610: 12-43
State 1 State 3
0.4A
CMC256-6 I A/mA
500
400
300
200
100
-0
-100 0.025 0.050 0.075 0.100 0.125 0.150 0.175 0.200
t/s
-200
-300
-400
-500
-600
IE
Trip TC2
Trip LOR2
Start BF
Trip MV2
State 1 State 3
2A
CMC256-6 I A/A
2.0
1.0
0.0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
t/s
-1.0
-2.0
-3.0
IE
Trip TC2
Trip LOR2
Start BF
Trip MV2
End of Test