Site Test Report

Contract No. – N-6166.1


New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV
ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108110656
Contractor: CSE Equipment: 7SJ611 MV REF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F873
Substation: 132/11 kV SS at ADNEC Page: 1 of 4

Inspection, Testing and Secondary Injection of


Protection Relay 7SJ611 (REF)

A - General Data:

Ordered MLFB: 7SJ6112-5EB90-1FB0 --0S Serial no.: BF1108110656

Built-in MLFB: 7SJ6112-5EB90-1FB0 --0S Firmware version: V4.81

Built-in rated auxiliary voltage (DC): 110 -250 VDC Feeder : =E05 Transformer T202

Built-in rated voltage VN: NA Software used: Digsi 4 V4.84

Built-in rated current IN: 1A Frequency: 50 HZ

Relay Designation : -F873 MV REF RELAY

B - General Inspection & Testing:

S NO General inspection & testing: Checked

1 Visual inspection of unit OK

2 Installation & wiring correct to relevant drawings OK

3 Relay case connected to local earth bar OK

4 Measured value check OK

5 Relay CT shorting contacts proved OK

6 Relay Binary inputs and outputs checked OK

7 Watch dog contact checked OK

8 Injection of current from terminal block with test plug OK

C - Configuration of protection function

Functions
Enabled Disabled
IEC No. Description
Description
50 1Ph 1Ph OC Protection Enabled -

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\N6166_E05_F873_MV_REF_Relay_7SJ61.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV
ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108110656
Contractor: CSE Equipment: 7SJ611 MV REF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F873
Substation: 132/11 kV SS at ADNEC Page: 2 of 4

D - Binary input function check

Bin. input Function Terminal Terminal Drawing Checked Remarks


(+)-X332:3
Relay Page No.
(-)-X332:20
BI 1 Protection blocked F14-F16 -X332:36 /MAB2.2 key switch -"OUT"
BI 2 Spare F15-F16 -X332:37 /MAB2.3
BI 3 Test Mode F17-F18 -X332:38 /MAB2.3 Test plug inserted
BI 4 Spare R9-R7 -X332:39 /MAB2.4
BI 5 Spare R10-R7 -X332:40 /MAB2.4
BI 6 Spare R11-R13 -X332:42 /MAB2.5
BI 7 Spare R12-R13 -X332:43 /MAB2.6
BI 8 Spare R8-R7 -X332:41 /MAB2.5

E - Binary output check

Output Function Terminal Drawing Checked Remarks


Relay TB Page No.
BO1 REF Trip F6-F7 X873:2 NAB1.3 Trip to TC2
BO2 REF Trip F8-F9 X873:4-8 NEB1.3 Trip to MV2
BO3 REF Trip F10-F11 X873:6 MBB1.3 Start BF protection
BO4 REF Trip F12-F13 X873:10 NAB3.3 Trip to LOR 2
BO5 REF Trip R1-R3 X873:12 RC2.2 Signal to FMS
BO6 Spare R2-R3 - ZB2.3 -
BO7 REF Trip R4-R5 - RAB3.4 Cubicle alarm
BO8 Spare R6-R5 - ZB2.3 -
Live Cont. F3-F4-F5 - RAB3.4 Cubicle alarm

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\N6166_E05_F873_MV_REF_Relay_7SJ61.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV
ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108110656
Contractor: CSE Equipment: 7SJ611 MV REF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F873
Substation: 132/11 kV SS at ADNEC Page: 3 of 4

F - LED function

S no Led no Function Checked Remarks


1 LED 1 Trip / relay trip
2 LED 2 Pickup / relay pickup
3 LED 3 Spare /
4 LED 4 REF Trip / 87N
5 LED 5 Spare /not used
6 LED 6 Protection blocked /key switch -"OUT"
7 LED 7 Summary Alarm / summary alarm event

1. MEASURED VALUE TEST:

Inject current in the relay as per the table below. Observe the reading on the relay display, in secondary values and in
Primary values. Inject Current through the test switch -X872

CT RATIO: 2500/1 A

Primary Current read on relay Secondary Current read on relay


Current display In (A) Display in (mA)
Phase
injected
injected
(Amps)
IR IY IB IN IEE IR IY IB IN IEE

N 1.0 2.50kA 1000

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\N6166_E05_F873_MV_REF_Relay_7SJ61.doc
Site Test Report
Contract No. – N-6166.1
New 132/11kV Substations at E12, Zayed Sports City, CONSORTIUM
ADNEC Capital Centre, 132/22kV Substations at New SIEMENS-
Airport and Capital District and All Related 132kV
ELECTROMECHANICAL
Cable Works
Relay Sl.No: BF1108110656
Contractor: CSE Equipment: 7SJ611 MV REF
Consultant: ENERGO CONSULT Feeder/Circuit: =E05+R2-F873
Substation: 132/11 kV SS at ADNEC Page: 4 of 4

2.1 Earth Fault function (DMT):50N-1


Pick up
Relay setting Drop off Time setting Operating time @2
Test phase Current
IE > (A) Current (A) (mSec) Times of Iset (mSec)
(A)
E/F 200 * * 0.0 *

* Note: Refer attached OMICRON Print out for Test results

2.2 Earth Fault function (DMT):50N-2


Pick up
Relay setting Drop off Time setting Operating time @2
Test phase Current
IE >> (A) Current (A) (mSec) Times of Iset (mSec)
(A)
E/F 1.0 * * 500 *

* Note: Refer attached OMICRON Print out for Test results

Instrument Used

Equip. 1 Equip. 2 Equip. 3


Instrument: Omicron CMC256-6

Serial No.: JG697S

Calibration Date: 30.05.2012

Remark :
- Omicron print outs will be attached along with the test report for Pickup/Drop off & Operating time

TESTED BY WITNESSED BY WITNESSED/APPROVED BY


Signature Signature Signature
Name Josip Spolador Name C. Senthil Kumar Name
Date 23.08.2012 Date 23.08.2012 Date
CSE ENERGO CONSULT TRANSCO
\N6166_E05_F873_MV_REF_Relay_7SJ61.doc
SITE TEST REPORT
Contract No. N6166.1 CONSORTIUM
SIEMENS-
New 132/11 kV Substations at E12, Zayed Sports City, ADNEC Capital
ELECTROMECHANICAL
Centre, 132/22kV Substations at Ne w Airport and Capital District and
all related 132kV cable works
Station: 132/11 kV ADNEC Bay: =E05 Panel: +R2 Device: -F873 7SJ611 - MV REF

SITE TEST REPORT


TRANSFORMER MV RESTRICTED EARTHFAULT PROTECTION
7SJ611
Company: Siemens
Test Person: Josip Spolador

Testmodules Checked: 4
Testmodules Passed: 4

Scope of created test document (Applications/Functions):


50N-1 IE> - pickup/drop off test
50N-1 IE> - tripping time test (DT)
50N-2 IE>> - pickup/drop off test
50N-2 IE>> - tripping time test (DT)

Test Object - Device Settings

Substation/Bay:
Substation: 132/11 kV kV SS ADNEC Substation address:
Bay: 40MVA Transformer 2 Bay address: =E05-T202

Device:
Name/description: MV_REF 7SJ61 Manufacturer: SIEMENS
Device type: 7SJ6112-5EB90-1FB0 Device address: =E05+R2-F873
Serial/model number: BF1108110656
Additional info 1: MV Restricted Earthfault Relay
Additional info 2:

Hardware Configuration

Test Equipment
Type Serial Number
CMC256-6 JG655S

Hardware Check
Performed At Result Details
23/08/2012 14:36:36 Passed

Tested by Witnessed by Witnessed/Approved. by


Name: Josip Spolador C. Senthil Kumar
Date: 23.08.2012 23.08.2012
Signature:
CSE ENERGO CONSULT TRANSCO
N6166_E05_R02_F873_MV_REF_7SJ61.occ Page 1 of 4
SITE TEST REPORT
Contract No. N6166.1 CONSORTIUM
SIEMENS-
New 132/11 kV Substations at E12, Zayed Sports City, ADNEC Capital
ELECTROMECHANICAL
Centre, 132/22kV Substations at Ne w Airport and Capital District and
all related 132kV cable works
Station: 132/11 kV ADNEC Bay: =E05 Panel: +R2 Device: -F873 7SJ611 - MV REF

Test set connections


Instruction Text:
Test switch in test position

IE:
Current output 1 ---> -X873: 1-2 (-X610: 12-43)
VE
Voltage output 1 ---> -X610: 12-43

Omicron - Binary Inputs


BI 1 -> Trip TC2 -X873:1,2; (BO1) -X322:1-8
BI 2 -> Trip LOR2 -X873:9,10; (BO4) -X (110V=)
BI 3 -> Start BF -X873:5,6; (BO3) -X330:1-3
BI 4 -> Trip MV2 -X873:3,4-7,8 (BO2) -X322:18-20

87N without Rstab


Instruction Text:
Activate 1 Phase OC , and short Rstab!

testswitch -S873 in test position

Settings: I>=0.20A; t>=0.0 s, Rstab= 300 ohm, Us=60V


I>>=1.0A; t>>=0.5s

Tested by Witnessed by Witnessed/Approved. by


Name: Josip Spolador C. Senthil Kumar
Date: 23.08.2012 23.08.2012
Signature:
CSE ENERGO CONSULT TRANSCO
N6166_E05_R02_F873_MV_REF_7SJ61.occ Page 2 of 4
SITE TEST REPORT
Contract No. N6166.1 CONSORTIUM
SIEMENS-
New 132/11 kV Substations at E12, Zayed Sports City, ADNEC Capital
ELECTROMECHANICAL
Centre, 132/22kV Substations at Ne w Airport and Capital District and
all related 132kV cable works
Station: 132/11 kV ADNEC Bay: =E05 Panel: +R2 Device: -F873 7SJ611 - MV REF

50N-1 pickup I>:


Measurement Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up State 1 Trip TC2 0->1 I E 200.0 mA 200.0 mA 10.00 mA 10.00 mA 0.000 A + 30.80 ms
Drop-off State 2 Trip TC2 1->0 I E 180.0 mA 178.0 mA 10.00 mA 10.00 mA -2.000 mA + 32.10 ms
Assess: + .. Passed x .. Failed o .. Not assessed

50N-1 trip time:


Time Assessment
Name Ignore before Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
1_t I> 0.4A 0.4A Trip TC2 0>1 0.000 s 0.000 s 40.00 ms 31.70 ms 31.70 ms +
2_t I> 0.4A 0.4A Trip LOR2 0>1 0.000 s 0.000 s 40.00 ms 31.70 ms 31.70 ms +
3_t I> 0.4A 0.4A Start BF 0>1 0.000 s 0.000 s 40.00 ms 32.00 ms 32.00 ms +
4_t I> 0.4A 0.4A Trip MV2 0>1 0.000 s 0.000 s 40.00 ms 31.40 ms 31.40 ms +
Assess: + .. Passed x .. Failed o .. Not assessed

State 1 State 3
0.4A

CMC256-6 I A/mA
500
400
300
200
100
-0
-100 0.025 0.050 0.075 0.100 0.125 0.150 0.175 0.200
t/s
-200
-300
-400
-500
-600
IE

Trip TC2
Trip LOR2
Start BF
Trip MV2

0.025 0.050 0.075 0.100 0.125 0.150 0.175 0.200


t/s

Tested by Witnessed by Witnessed/Approved. by


Name: Josip Spolador C. Senthil Kumar
Date: 23.08.2012 23.08.2012
Signature:
CSE ENERGO CONSULT TRANSCO
N6166_E05_R02_F873_MV_REF_7SJ61.occ Page 3 of 4
SITE TEST REPORT
Contract No. N6166.1 CONSORTIUM
SIEMENS-
New 132/11 kV Substations at E12, Zayed Sports City, ADNEC Capital
ELECTROMECHANICAL
Centre, 132/22kV Substations at Ne w Airport and Capital District and
all related 132kV cable works
Station: 132/11 kV ADNEC Bay: =E05 Panel: +R2 Device: -F873 7SJ611 - MV REF

50N-2 pickup I>>:


Measurement Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
Pick-up State 1 Trip TC2 0->1 I E 1.000 A 1.000 A 50.00 mA 10.00 mA 0.000 A + 521.7 ms
Drop-off State 2 Trip TC2 1->0 I E 950.0 mA 952.0 mA 50.00 mA 10.00 mA 2.000 mA + 15.70 ms
Assess: + .. Passed x .. Failed o .. Not assessed

50N-2 trip time:


Time Assessment
Name Ignore before Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
1_t I> 2A 2A Trip TC2 0>1 500.0 ms 0.000 s 50.00 ms 521.4 ms 21.40 ms +
2_t I> 2A 2A Trip LOR2 0>1 500.0 ms 0.000 s 50.00 ms 521.3 ms 21.30 ms +
3_t I> 2A 2A Start BF 0>1 500.0 ms 0.000 s 50.00 ms 521.5 ms 21.50 ms +
4_t I> 2A 2A Trip MV2 0>1 500.0 ms 0.000 s 50.00 ms 521.0 ms 21.00 ms +
Assess: + .. Passed x .. Failed o .. Not assessed

State 1 State 3
2A

CMC256-6 I A/A

2.0

1.0

0.0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
t/s
-1.0

-2.0

-3.0
IE

Trip TC2
Trip LOR2
Start BF
Trip MV2

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8


t/s

End of Test

Tested by Witnessed by Witnessed/Approved. by


Name: Josip Spolador C. Senthil Kumar
Date: 23.08.2012 23.08.2012
Signature:
CSE ENERGO CONSULT TRANSCO
N6166_E05_R02_F873_MV_REF_7SJ61.occ Page 4 of 4