You are on page 1of 61

A

REPORT
ON
STRUCTURAL ANALYSIS AND DESIGN OF
RESIDENTIAL BUILDING

..

PREPARED FOR PREPARED BY


TYPE B PLOT B1 KHUSBU MAHARJAN
NEC NO:25101

LALITPUR METROPOLITAN CITY


06 April 2021
TO WHOM IT MAY CONCERN

This report comprises the summary of the structural design of Residential


Building. The report consists of design procedures adopted, assumptions made,
and the input assign in the design. During design it is assumed that the client will
completely followed the architectural as well as the structural design. It is also
assumed that the construction will be supervised by a professional engineer.
The designer will not be responsible if any alteration or change to the structural
system is made by the client or contractor without the prior permission from the
designer, or the alteration to the non-structural system is made such that the
weight of each individual floor or the weight of the whole building is altered by
more than 10% of the design weight of the floor and the total weight.
The design calculations and derivations are limited to only to let the concerned
people know the methodology adopted. However, the calculation may be
provided to the client or the concerned authorities when needed, upon request.

KHUSBU MAHARJAN

(DESIGNER)

NEC NO:25101

Structural analysis and design of Residential building in Lalitpur Page | i


TABLE OF CONTENTS
1 Introduction .................................................................................................. 6
1.1 General ........................................................................................................... 6
1.2 Salient Features............................................................................................... 6
1.2.1 Project Information ...................................................................................... 6
1.2.2 Building Features ........................................................................................ 6
1.2.3 Site Condition.............................................................................................. 8
2 Analysis Technology and Methodology ........................................................ 8
2.1 General ........................................................................................................... 8
2.2 Codes and Standard used............................................................................... 10
2.3 Software Used............................................................................................... 10
3 Analysis ....................................................................................................... 11
3.1 Material properties ........................................................................................ 11
3.1.1 Concrete .................................................................................................... 11
3.1.2 Reinforcement Steel .................................................................................. 11
3.2 Section Properties ......................................................................................... 11
3.3 Loadings ....................................................................................................... 11
3.3.1 Load Cases ................................................................................................ 12
3.3.2 Load Combination ..................................................................................... 12
3.4 Estimation of Load ........................................................................................ 13
3.4.1 Unit Weight (Dead Load) .......................................................................... 13
3.4.2 Live Load .................................................................................................. 17
3.4.3 Seismic Load ............................................................................................. 19
4 Analysis Output .......................................................................................... 20
4.1 Seismic Coefficient Method .......................................................................... 20
4.2 Story Drift..................................................................................................... 21
4.3 Modal time period and mass participation ..................................................... 22
4.4 Force Diagram .............................................................................................. 22
4.4.1 Axial Force Diagram ................................................................................. 22
4.4.2 Shear Force Diagram ................................................................................. 23
4.4.3 Moment Diagram ...................................................................................... 24
4.5 Joint Reactions .............................................................................................. 25
5 Design of Structural Members (Sample Design) ........................................ 26
5.1 Design Input and Output ............................................................................... 26
5.2 Design Output Diagram ................................................................................ 28

Structural analysis and design of Residential building in Lalitpur Page | ii


5.3 Design of Slab ................................................................................................. 33
5.4 Design of Beam ............................................................................................ 36
5.5 Design of Column ......................................................................................... 39
5.6 Design of Foundation .................................................................................... 42
6 References ................................................................................................... 54

Structural analysis and design of Residential building in Lalitpur Page | iii


LIST OF FIGURES
Figure 1:Ground FLoor Plan .................................................................................. 7
Figure 2:Top Floor Plan .......................................................................................... 7
Figure 3: Section of building ................................................................................... 8
Figure 4: Frame Load (Wall Load) on First Floor ............................................... 16
Figure 5: Frame Load (Wall Load) on D-D .......................................................... 17
Figure 6: Area Load (LL) on Floor Slab .............................................................. 18
Figure 7: Area Load (Floor Finishing and partition Load) on Floor Slab .......... 19
Figure 8: Story Displacement (Eqx) ...................................................................... 21
Figure 9: Story Displacement (Eqy)...................................................................... 21
Figure 10: Envelope - Axial Force diagram: Grid D-D........................................ 22
Figure 11: Envelope-Shear Force diagram: Grid D-D ......................................... 23
Figure 12: Envelope -Moment diagram: Grid D-D .............................................. 24
Figure 13: Joint Level and Reactions.................................................................... 25
Figure 14: Section Input in Frame along Grid D-D ............................................. 26
Figure 15: Section Input in First Floor ................................................................. 27
Figure 16: Design Output in First Floor ............................................................... 28
Figure 17: Design Output in Grid A-A ................................................................. 29
Figure 18: Design Output in Grid B-B.................................................................. 30
Figure 19: Design Output in Grid C-C ................................................................. 31
Figure 20: Design Output in Grid D-D ................................................................. 32
Figure 21:Foundation Layout ............................................................................... 53

Structural analysis and design of Residential building in Lalitpur Page | iv


LIST OF TABLES
Table 1: Load Cases .............................................................................................. 12
Table 2: Load Combination .................................................................................. 12
Table 3: Unit Weight of Materials ........................................................................ 13
Table 4: Dead Load Calculation ........................................................................... 14
Table 5: Live Load for Residential Building ........................................................ 17
Table 6: Fundamental Time period ...................................................................... 20
Table 7: Seismic coefficient and base shear .......................................................... 20
Table 8: Summary of slab ..................................................................................... 35
Table 9: Beam Reinforcement detail..................................................................... 38
Table 10: Summary of Design of Column ............................................................ 41
Table 11: Summary of Design of Footing ............................................................. 52

Structural analysis and design of Residential building in Lalitpur Page | v


1 Introduction
1.1 General
This report presents the structure analysis and design of residential Building. The building
is Special Reinforced Concrete Moment Resisting Frame (SMRF) type of building. It is
designed to meet both strength and serviceability requirements when subjected to gravity
and earthquake loads.
The analysis and design has been based on IS codes that are in practice in Nepal. This
report consists of the design assumptions, design methodology, design inputs and outputs,
and sample design of structural members.
1.2 Salient Features
1.2.1 Project Information

Type of building : Residential Building

Location : Lalitpur

Plinth Area : 592.319 sq.ft.

1.2.2 Building Features


The building has some special features which are listed below:
Type of Building : Special RC Moment Resisting Frame Structure

Shape : Regular Rectangular Shape

Plinth level : As per architectural drawing

Roof floor Type : Accessible, Terrace

Walls : Brick walls

Footing Type : Combined Footing With Strap Beam

Depth of Minimum 1.5m below ground level or as per site


:
foundation condition

Story Height : 10’

Total Height : 40’(without parapet)

No of Story : Ground Story +Two Story +Half Story

Structural analysis and design of Residential building in Lalitpur Page | 6


Figure 1:Ground FLoor Plan

Figure 2:Top Floor Plan

Structural analysis and design of Residential building in Lalitpur Page | 7


Figure 3: Section of building
1.2.3 Site Condition

Type of soil : Type II, Medium as per IS-1893(Part 1):2002

Allowable bearing pressure : 120 KN/m2(Assumed)

Seismic Zone Factor : 0.36 as per IS-1893(Part 1):2002

2 Analysis Technology and Methodology


2.1 General
After completion of Architectural design, the layout of columns and beams are done
without affecting the Architectural functions of building so far. Structure is modeled
using finite element method. A three-dimensional beam element having 12 DOF with
6 DOFs at each node were used for modeling beams and columns in the building,
while 24DOFs shell element with 6 DOFs at each node were used to model slab wall.

Structural analysis and design of Residential building in Lalitpur Page | 8


The structure is analyzed by the linear elastic theory to calculate internal actions
produced by anticipated design loads. The analysis is carried out using state of art
three dimensional structural analysis programs like ETABS 2015. The design loads
considered as per the relevant codes of practice comprise dead load due to permanent
structures, live load due to occupancy of the structure and seismic load due to
anticipated earthquake possible at the proposed location. A number of load
combinations are considered to obtain the maximum values of design stresses.
Following considerations is made during modeling, analysis and design.
 The structures are Special Reinforced Concrete Moment Resisting Frame
(SMRF) type. Beams and columns are considered as the structural load
resisting elements. Although non-structural components like wall plaster,
infill walls, floor finishing etc has comes effects on structural performance,
they are considered only as loading.
 For all structural elements, M20 grade concrete are used.
 Centre-line dimensions are followed for modeling, analysis and design.
 Floor slabs are assumed to be rigid in their own plane. The slab action has
been modeled by rigid floor diaphragms. Slabs are also considered in
modeling. Slab is modeled as shell element.
 Beam and columns are modeled as frame elements.
 The main beams rest centrally on columns to avoid local eccentricity.
 Foundation is assumed to be fully rigid at the plinth level.
 The beam-column joint is not modeled in detail.
 Preliminary sizes of structural components are assumed by experience.
 Seismic loads were considered acting in the horizontal direction (along either
of the two orthogonal directions of building) and not along the vertical
direction, since it is not considered to be significant for design of structural
members suitable load combinations as suggested by IS 1893– 2002 are used.

Structural analysis and design of Residential building in Lalitpur Page | 9


Figure 4: 3D-Modelof Building
2.2 Codes and Standard used
For the structural analysis and design, the following codes and standard are followed:
 IS 456- 2000 Code of practice for plain and reinforced concrete
 IS 875-1987 Code of practice for design loads (other than earthquake) for
buildings and structures
 IS 1893-2002 Criteria for Earthquake Resistant Design of Structures,
 IS 13920-1993 Code of practice for ductile detailing of reinforced concrete
structures subjected to seismic forces
 NBC Nepal Building Code

2.3 Software Used


The following software is used for the structural analysis and design. For structural
modeling of the present building, ETABS software was used. ETABS is a special purpose
finite element analysis and design program developed specifically for building systems.
With ETABS, models are defined logically floor-by-floor, column-by-column, bay-by-bay
and wall-by-wall and not as a stream of non-descript nodes and elements as in general
purpose programs. The software has very powerful numerical methods, design procedures
and international design codes, all working from a single comprehensive database. Among
others, ETABS can do model generation, seismic and wind load generation, finite element-
based linear and non-linear static and dynamic analysis, concrete frame design (column and
beam) and shear wall design.

Structural analysis and design of Residential building in Lalitpur Page | 10


3 Analysis
3.1 Material properties
3.1.1 Concrete
Column is designed for M25 grade of concrete. And all other components of plain
and reinforced concrete unless specified in design are M25 grade.
Modulus of Elasticity [Ec]= 5000 √fckN/mm2(Cl. 6.2.3.1, IS 456:2000)
= 25000 N/mm2 for M20 grade
Poisson’s Ratio [U] = 0.2
Unit Weight = 25 KN/m3
Characteristic Strength [ƒck] = 25 N/mm2 for M25 grade
The structural design strength is derived from the characteristic strength multiplied
by a coefficient 0.67 and divided by the material partial safety factor. The partial
factor for concrete in flexure and axial load is 1.5.
3.1.2 Reinforcement Steel
Characteristic strength of high yield steel is taken as 500MPa (TMT) for main rebar
and 500 MPa shear rebar and material partial safety factor is to be1.15.
Modulus of Elasticity [Es] = 2x105 N/mm2
Poisson’s Ratio [U] = 0.3
3.2 Section Properties
 Preliminary Size of Members
The preliminary sizes of Beam, Column, and Slab were chosen based on experience.
Tie beam : 230mm*350mm
Secondary beam: 230mm*350mm
Main Beam : 300 mm *450mm
Column : 400 mm *400 mm
Slab Thickness : 125 mm
During the analysis, beam and column are modeled as frame elements whereas slabs
are modeled as area element.

3.3 Loadings
The following considerations are made during the loading on the structural model:
 The loads distributed over the area are imposed on the area element and the
loads distributed over the length are imposed on the frame elements whenever
possible.
 Where such loading is not possible, equivalent conversion to different loading
distribution is carried to load the model near the real case as far as possible.
 For lateral load, necessary calculations are performed to comply with the
requirements of IS 1893-2002.

Structural analysis and design of Residential building in Lalitpur Page | 11


3.3.1 Load Cases
The following load cases are used for the loading during analysis.

Table 1: Load Cases


Load Name Load Type Description Unit Remarks
Dead Dead Self-weight of the structure KN/m2
Wall S. Dead Wall Load KN/m On floor & roof beam
Finish S. Dead Floor Finish Load KN/m2 On floor & roof slab
Partition S. Dead Partition Wall Load KN/m2 On floor slab
LL Floor Live Imposed Load KN/m2 On floor slab
LL Terrace Live Imposed Load KN/m2 On terrace slab
EQX Quake Seismic Coefficient IS1893 X+0.05Y
EQY Quake Seismic Coefficient IS1893 Y+0.05X

3.3.2 Load Combination


The load combinations are based on IS 1893 -2002. The following load
combinations are specified as per 1893 -2002:
Static Load Combination:
1.5(DL + LL)
Seismic Load Combination:
1.2(DL + LL ± EQx± EQy)
1.5(DL ± EQx± EQy)
0.9 DL ±1.5 EQx±1.5 EQy
The following load combinations are used during analysis
Table 2: Load Combination
S.N Name Type
1 1.5(DL + LL) 1.5(DL + LL)
2 1.2(DL + LL+ EQx) 1.2(DL + LL+ EQx)
3 1.2(DL + LL - EQx) 1.2(DL + LL - EQx)
4 1.2(DL + LL + EQy) 1.2(DL + LL + EQy)
5 1.2(DL + LL - EQy) 1.2(DL + LL - EQy)
6 1.5(DL + EQx) 1.5(DL + EQx)
7 1.5(DL - EQx) 1.5(DL - EQx)
8 1.5(DL + EQy) 1.5(DL + EQy)
9 1.5(DL - EQy) 1.5(DL - EQy)
10 0.9DL + 1.5EQx 0.9DL + 1.5EQx

Structural analysis and design of Residential building in Lalitpur Page | 12


11 0.9DL - 1.5EQx 0.9DL - 1.5EQx
12 0.9DL + 1.5EQy 0.9DL + 1.5EQy
13 0.9DL - 1.5EQy 0.9DL - 1.5EQy

3.4 Estimation of Load


The loads on the building are based on Indian codes of Practices. The unit weight of
different structural and non-structural elements are derived from IS 875 Part 1 and
presented in Table 3. The load calculations are based on actual measured drawings. The
self-weight of beams, columns and slabs are calculated by the program. Similarly the
imposed loads are applied on the slab as area load in KN/m2 and values of imposed
loads are tabulated in Table 5below.

 The weight of infill walls are calculated and applied on beams as line weight in
KN/m.
 Partition wall load are assigned as uniformly distributed area load in slab as area
load in KN/m2.
 Floor finishing load are assigned as area load in slab.
 Single type of Live load is assigned in each panel of slab.
 A frame load is applied as parapet loading on the exterior frame of the roof level.
 The roof is assumed accessible and loaded with roof live load as per Indian
Standard, IS 875 -1987(part2) but this load is not considered during seismic load.

3.4.1 Unit Weight (Dead Load)


Dead loads for analysis are calculated as per Indian Standard, IS 875 -1987(part1).
Unit weights of different material used are given below.

Table 3: Unit Weight of Materials


S.N Type Value
1 Reinforced Concrete 25 KN/m3
2 Brick Masonry 16.5 KN/m3
3 Screed 21.0 KN/m3
4 Marble 26.7 KN/m3
5 Mosaic finish 23.1 KN/m3
6 Plaster 20.4 KN/m3
7 Steel Rebar 78.6 KN/m3

Structural analysis and design of Residential building in Lalitpur Page | 13


Table 4: Dead Load Calculation
1 Unit Weights of materials
Brick masonry 16.50 kN/m3
Screed 21.00 kN/m3
Mosaic 23.10 kN/m3
Marble 26.70 kN/m3
Reinforced Concrete 25.00 kN/m3
Cement plaster 20.40 kN/m3

2 Heights of Beams, Walls & Parapet Walls


Depth of Beam 0.40 m
Height of Building 3.05 m
Height of Parapet Wall 0.99 m
Wall thickness 0.23 m
Plaster thickness (both interior and exterior) 0.03 m

3 Dead Loads of Walls


a) Dead load of 230 mm thick wall 10.05 kN/m
with inside and
outside plaster 1.756287 KN/m Total 11.81 KN/m
32.5 mm
Dead load of 230 mm thick wall with 25 %
7.54 kN/m
opening (Outer wall)
with inside and
outside plaster 1.756287 KN/m Total 9.30 KN/m
32.5 mm
Dead load of 230 mm thick wall with 15%
8.55 kN/m
opening (Inner wall)
with inside and
outside plaster 1.756287 KN/m Total 10.30 KN/m
32.5 mm
b) Dead load of 115 mm thick wall 5.03 kN/m
with inside and
outside plaster 1.756287 KN/m Total 6.78 KN/m
32.5 mm
Dead load of 115 mm thick wall with 25 %
3.77 kN/m
opening (Outer wall)
with inside and
outside plaster 1.756287 KN/m Total 5.53 KN/m
32.5 mm
Dead load of 115 mm thick wall with 15%
4.27 kN/m
opening (Inner wall)

Structural analysis and design of Residential building in Lalitpur Page | 14


with inside and
outside plaster 1.756287 KN/m Total 6.03 KN/m
32.5 mm
c) Dead load of parapet wall (230 mm thick) 3.76 kN/m
with inside and
outside plaster 0.39117 KN/m Total 4.15 KN/m
32.5 mm
Dead load of parapet wall (115 mm thick) 1.88 kN/m
with inside and
outside plaster 0.39117 KN/m Total 2.27 KN/m
32.5 mm

4 Floor Loads
Thickness of slab 0.125 m
Thickness of tile with
0.025 m
plaster
Thickness of Mosaic 0.020 m
Thickness of Marble 0.020 m
Thickness of Screed 0.040 m
Thickness of Cement
0.013 m
Plaster
Dead load of structural slab 3.125 kN/m2
Dead load of Tile 0.510 kN/m2
Dead load of Mosaic 0.462 kN/m2
Dead load of Marble 0.534 kN/m2
Dead load of screed 0.840 kN/m2
Dead load of Cement
0.255 kN/m2
Plaster
Total dead load of Floor
1.350 kN/m2
Finishes (Tile)
Total dead load of Floor
1.302 kN/m2
Finishes (Mosaic)
Total dead load of Floor
1.374 kN/m2
Finishes (Marble)
Total dead load of Floor
1.095 kN/m2
Finishes (Cement Punning)
Dead load of light
1.200 kN/m2
partition walls

Structural analysis and design of Residential building in Lalitpur Page | 15


Figure 4: Frame Load (Wall Load) on First Floor

Structural analysis and design of Residential building in Lalitpur Page | 16


Figure 5: Frame Load (Wall Load) on D-D

3.4.2 Live Load


The magnitude of live load depends upon the type of occupancy of the building.
These are to be chosen from code IS875:1987(part II) for various occupancies. The
live load distribution varies with time. Hence each member is designed for worst
combination of dead load and live loads. Live loads for residential building are
given below.
Table 5: Live Load for Residential Building
S.N Area type Load Unit
Rooms (Bed room, Living
1 2 KN/m2
Room)
2 Terrace (Accessible) 1.5 KN/m2
3 Balcony 3 KN/m2
4 Staircase and Passage 3 KN/m2

Structural analysis and design of Residential building in Lalitpur Page | 17


Figure 6: Area Load (LL) on Floor Slab

Structural analysis and design of Residential building in Lalitpur Page | 18


Figure 7: Area Load (Floor Finishing and partition Load) on Floor Slab

3.4.3 Seismic Load


The seismic load is applied to the building with auto lateral load pattern in ETABS
2016 as per IS 1893-2002. This load case is assumed static linear and all the
necessary data are given as per the following conditions.
To determine the seismic load, it is considered that the country lies in the seismic
zone V according to IS 1893:2002. The soil type is considered as soft with 5%
damping to determine average response acceleration. The building is analyzed as
moment resisting frame without consideration of infill wall.
Therefore the fundamental time period Ta is obtained by using the following
formula:

Ta = [Cl.7.6.2, IS 1893 -2002]

Other factors considered for seismic load calculations are as follows

Structural analysis and design of Residential building in Lalitpur Page | 19


Zone factor, Z = 0.36 for Zone V [Table 2, Cl6.4.2, IS 1893 -2002]

Importance factor, I = 1.0[Table 6, Cl6.4.2, IS 1893 -2002]

Response Reduction Factor = 5for special RC moment resisting frame


(SMRF) [Table 6, Cl6.4.2, IS 1893 -2002]

The seismic weight is determined based on the following mass source. (Table 6,
Cl.7.9.2, IS 1893 (Part 1):2002)

4 Analysis Output
The analysis results are discussed in this chapter. Both seismic coefficient and response
spectrum methods are used. The major discussion are focused on the eccentricity, story
shear, inter story drift, maximum displacement and base shear along two orthogonal
directions. The column and beam size and reinforcement are then checked.
4.1 Seismic Coefficient Method
The fundamental time period of the building as per IS code 1893: 2002, clause 7.6.2,
total seismic weight and base shear in both orthogonal directions are given in
. This result will be used to compare and scale the base shear from response spectrum
method.
Table 6: Fundamental Time period
Direction Time period (sec)

X 0.489

Y 0.489
Based on program/software calculated seismic coefficient, base shear and storey
shear are as shown in the Table 7. To calculate these parameters, the following
equation has been used as per code.
The coefficient is given by,\

And, base shear is given by,

These values in both the orthogonal direction are tabulated in the Table 7below.
Table 7: Seismic coefficient and base shear
Seismic Weight
2537.97
(KN)
Direction X Y
Seismic Coefficient 0.09 0.09
Vb (KN) 228.4171 228.4171

Structural analysis and design of Residential building in Lalitpur Page | 20


4.2 Story Drift
As per Cl. no. 7.11.1 of IS 1893-2002, the story drift in any story due to specified
design lateral force with partial load factor of 1.0, shall not exceed 0.004 times the
story height. In this building the story drift is limited to 12.195 mm.

Figure 8: Story Displacement (Eqx)

Figure 9: Story Displacement (Eqy)


It is seen that drift does not exceed the code prescribed value of 0.004 times story
height (i.e. permissible story displacement is 12.195mm). Thus the drift check
seems to comply with the safety value mentioned in the code.

Structural analysis and design of Residential building in Lalitpur Page | 21


4.3 Modal time period and mass participation
IS 1893: 2002 clause 7.8.4.2 states that number of modes to be used in the analysis
should be such that the sum total of modal masses of all modes considered is at least
90 percent of the total seismic mass of the structure. Analysis was carried out for first
10 modes so that the mass participation satisfies this criterion in both orthogonal
directions.
4.4 Force Diagram
The output of forces obtained from ETABS analysis for Envelope have presented
below as a sample only. The output forces are axial force, Shear force and Moments.

4.4.1 Axial Force Diagram

Figure 10: Envelope - Axial Force diagram: Grid D-D

Structural analysis and design of Residential building in Lalitpur Page | 22


4.4.2 Shear Force Diagram

Figure 11: Envelope-Shear Force diagram: Grid D-D

Structural analysis and design of Residential building in Lalitpur Page | 23


4.4.3 Moment Diagram

Figure 12: Envelope -Moment diagram: Grid D-D

Structural analysis and design of Residential building in Lalitpur Page | 24


4.5 Joint Reactions
The reactions at the support of column for load combination of 1.5 (DL + LL) are as
follows:

Figure 13: Joint Level and Reactions

Structural analysis and design of Residential building in Lalitpur Page | 25


5 Design of Structural Members (Sample Design)
5.1 Design Input and Output
Section Input Diagram

Figure 14: Section Input in Frame along Grid D-D

Structural analysis and design of Residential building in Lalitpur Page | 26


Figure 15: Section Input in First Floor

Structural analysis and design of Residential building in Lalitpur Page | 27


5.2 Design Output Diagram

Figure 16: Design Output in First Floor

Structural analysis and design of Residential building in Lalitpur Page | 28


Figure 17: Design Output in Grid A-A

Structural analysis and design of Residential building in Lalitpur Page | 29


Figure 18: Design Output in Grid B-B

Structural analysis and design of Residential building in Lalitpur Page | 30


Figure 19: Design Output in Grid C-C

Structural analysis and design of Residential building in Lalitpur Page | 31


Figure 20: Design Output in Grid D-D

Structural analysis and design of Residential building in Lalitpur Page | 32


5.3 Design of Slab
DESIGN OF TWO WAY SLAB:

1.0 General Data:


Depth of slab : (D) 125 mm
Grade of Concrete : (fck) 20 N/mm2
Grade of Steel : (fy) 500 N/mm2
Effective cover: (d') 20 mm
Effective depth of slab : (d) 105 mm
Effective length:
Shorter span: (lx) 3.048 m
Longer span: (ly) 4.5974 m

2.0 Loading:
Dead Load: (DL) 3.125 KN/m2
Other Dead Load: (ODL) 2 KN/m2
Live Load: (LL) 2 KN/m2
Total Load: (w) 7.125 KN/m2
Factored Load: (wu) 10.6875 KN/m2

3.0 Type of slab:

1.509

Type: Two way Slab

4.0 Calculation of Moments:


Moment coefficient:
Type of Slab Panel: 4
Short span coefficient: αx
Support S 0.07532
Mid Span M 0.05625
Long span coefficient: αy
Support S 0.047
Mid Span M 0.035
Moments:

Short span moments:


Support S 7.479 KN-m
Mid Span M 5.586 KN-m

Long span moments:

Structural analysis and design of Residential building in Lalitpur Page | 33


Support S 4.667 KN-m
Mid Span M 3.476 KN-m

5.0 Check depth for maximum Moments:


Maximum moments: Mu 7.479 KN-m
effective depth: d 53 < 105 mm
OK

6.0 Calculation of reinforcement:


6.1 For shorter span
Mim'm reinforcement (Ast)min 126 mm2
Design moment: Mx 7.479 KN-m
Neutral axis depth : x 11 mm
Area of steel required: Ast 172 mm2
Area of steel provided: Ø 8 mm
S 150 mm
Ast 336 mm2 Ok
Pt 0.32 %
For longer span
Effective depth d 97 mm
Mim'm reinforcement (Ast)min 117 mm2
Design moment: Mx 4.667 KN-m
Neutral axis depth : x 7 mm
Area of steel required: Ast 126 mm2
Area of steel provided: Ø 8 mm
S 150 mm
Ast 336 mm2 Ok
Pt 0.347 %

7.0 Check for shear stress:


Maximum shear force: Vu 16.288 KN
Shear Stress: tv 0.156 N/mm2
β 7.257
Concrete Shear Strength: tc 0.399 N/mm2
Shear Strength factor: K 1.3
Shear Strength of Slab: tc' 0.5187 > 0.156 N/mm2
OK

8.0 Check for development length:


Ultimate moment Capacity: M1 14.12 KN-m
Maximum Shear Force: V 16.288 KN

Structural analysis and design of Residential building in Lalitpur Page | 34


Bond Stress: tbd 1.92 N/mm2
Development length: Ld 454 mm
Anchorage length: L0 105 mm
Available length: 1232 > Ld
OK

9.0 Check for deflection:

length to eff. Depth ratio: l/d 29.029


Α 23
Β 1
ϒ 2.540 for fs = 148.452 N/mm2
Γ 1 and Pt = 0.32 %
Λ 1
Coefficient: 58.415
OK
Table 8: Summary of slab

Overall depth(D) 125mm (5”)


Effective depth(d) 105mm
Concrete grade M20(1:1.5:3)
Steel grade Fe500(TMT)
Reinforcement (top and bottom) 8mmø@150mmc/c

Structural analysis and design of Residential building in Lalitpur Page | 35


5.4 Design of Beam
ETABS 2016 Concrete Frame Design

IS 456:2000 Beam Section Design

Beam Element Details Type: Ductile Frame (Summary)


Unique Length
Level Element Section ID Combo ID Station Loc LLRF
Name (mm)
Beam 300X450-
s-2 B16 34 DCon7 6200.8 6400.8 1
M25

Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
300 450 300 0 60 60

Material Properties
Lt.Wt Factor
Ec (MPa) fck (MPa) fy (MPa) fys (MPa)
(Unitless)
25000 25 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Factored Forces and Moments


Factored Factored Factored Factored
Mu3 Tu Vu2 Pu
kN-m kN-m kN kN
-249.9995 1.3569 149.4986 3.295

Structural analysis and design of Residential building in Lalitpur Page | 36


Design Moments, Mu3 & Mt
Factored Factored Positive Negative
Moment Mt Moment Moment
kN-m kN-m kN-m kN-m
-249.9995 1.9954 0 -251.9949

Design Moment and Flexural Reinforcement for Moment, M u3 & Tu


Design Design -Moment +Moment Minimum Required
-Moment +Moment Rebar Rebar Rebar Rebar
kN-m kN-m mm² mm² mm² mm²
Top (+2
-251.9949 1826 0 1826 457
Axis)
Bottom (-2
0 913 0 199 913
Axis)

Shear Force and Reinforcement for Shear, Vu2 & Tu


Shear Ve Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
185.1812 87.9289 114.6976 88.8723 814.97

Torsion Force and Torsion Reinforcement for Torsion, Tu & VU2


Tu Vu Core b1 Core d1 Rebar Asvt /s
kN-m kN mm mm mm²/m
142.287
3.271 200 350 580.11
7

Structural analysis and design of Residential building in Lalitpur Page | 37


Table 9: Beam Reinforcement detail

Beam Reinforcement Detail


Reinforcement
Size of
S.N. Type of beam beam Dir Grid At support At center
(mm) Top Bottom Top Bottom
X-dir ALL 3-16ɸ R 3-16ɸR 3-16ɸ R 3-16ɸ R
1 Tie beam 230 x 350
Y-dir ALL 3-16ɸ R 3-16ɸ R 3-16ɸ R 3-16ɸ R
X-dir ALL 3-16ɸ R 3-16ɸ R 3-16ɸ R 3-16ɸ R
2 Secondary beam 230 x 350
Y-dir ALL 3-16ɸ R 3-16ɸ R 3-16ɸ R 3-16ɸ R
1-1 3-20ɸR+3-20ɸE 3-20ɸR 3-20ɸR 3-20ɸR
Main Beam Ground X-dir 2-2 3-20ɸR+3-20ɸE 2-20ɸR+1-16ɸR 3-20ɸR 2-20ɸR+1-16ɸR
3 300 X 450
& First Floor 3-3 3-16ɸR+3-16ɸE 2-16ɸR+1-20ɸR 3-16ɸ R 2-16ɸR+1-20ɸR
Y-dir ALL 2-16ɸR+2-20ɸE 3-16ɸ R 2-16ɸ R 3-16ɸ R
1-1 3-16ɸR+3-20ɸE 3-20ɸR 3-16ɸ R 3-20ɸR
Main Beam Second X-dir 2-2 3-16ɸR+3-20ɸE 2-20ɸR+1-16ɸR 3-16ɸ R 2-20ɸR+1-16ɸR
4 300 X 450
Floor 3-3 2-16ɸR+2-20ɸE 2-16ɸR+1-12ɸR 2-16ɸ R 2-16ɸR+1-12ɸR
Y-dir ALL 2-16ɸR+2-16ɸE 2-12ɸR+1-16ɸR 2-16ɸ R 2-12ɸR+1-16ɸR
1-1 2-16ɸR+2-20ɸE 2-16ɸR+1-20ɸR 2-16ɸ R 2-16ɸR+1-20ɸR
Main Beam Third X-dir 2-2 2-16ɸR+2-16ɸE 3-16ɸ R 2-16ɸ R 3-16ɸ R
5 300 X 450
Floor 3-3 2-16ɸR+1-12ɸE 3-12ɸR 2-16ɸ R 3-12ɸR
Y-dir ALL 2-12ɸR+2-12ɸE 3-12ɸR 2-12ɸ R 3-12ɸR

Structural analysis and design of Residential building in Lalitpur Page | 38


5.5 Design of Column
ETABS 2016 Concrete Frame Design

IS 456:2000 Column Section Design

Column Element Details Type: Ductile Frame (Summary)


Unique Length
Level Element Section ID Combo ID Station Loc LLRF
Name (mm)
Column 400x400-
s-1 C1 13 DCon8 0 3048 0.599
M25

Section Properties
Cover (Torsion)
b (mm) h (mm) dc (mm)
(mm)
400 400 60 30

Material Properties
Lt.Wt Factor
Ec (MPa) fck (MPa) fy (MPa) fys (MPa)
(Unitless)
25000 25 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Axial Force and Biaxial Moment Design For P u , Mu2 , Mu3


Rebar
Design Pu Design Mu2 Design Mu3 Minimum M2 Minimum M3 Rebar %
Area
kN kN-m kN-m kN-m kN-m %
mm²
816.32 22.9005 -184.18 16.3264 16.3264 3219 2.01

Structural analysis and design of Residential building in Lalitpur Page | 39


Axial Force and Biaxial Moment Factors
Initial Additional Minimum
K Factor Length
Moment Moment Moment
Unitless mm
kN-m kN-m kN-m
Major
0.77219 2598 -87.3542 0 16.3264
Bend(M3)
Minor
0.76036 2598 17.2468 0 16.3264
Bend(M2)

Shear Design for Vu2 , Vu3


Shear Vu Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
Major, Vu2 119.2785 139.5384 54.4003 119.2785 443.37
Minor, Vu3 63.6816 139.5384 54.4003 63.6816 443.37

Joint Shear Check/Design


Joint Shear Shear Shear Shear Joint Shear
Force VTop Vu,Tot Vc Area Ratio
kN kN kN kN cm² Unitless
Major Shear,
N/A N/A N/A N/A N/A N/A
Vu2
Minor Shear,
N/A N/A N/A N/A N/A N/A
Vu3

(1.1) Beam/Column Capacity Ratio


Major Minor
Ratio Ratio
N/A N/A

Additional Moment Reduction Factor k (IS 39.7.1.1)


Ag Asc Puz Pb Pu k
cm² cm² kN kN kN Unitless
3007.040 773.180
1600 32.2 816.32 0.980689
2 9

Additional Moment (IS 39.7.1)


Section KL/Dept KL/Dept Ma
Consider Length KL/Depth
Depth h h Moment (kN-
Ma Factor Exceeded
(mm) Ratio Limit m)
Major Bending
Yes 0.852 400 5.015 12 No 0
(M3 )
Minor Bending
Yes 0.852 400 4.939 12 No 0
(M2 )

Structural analysis and design of Residential building in Lalitpur Page | 40


Table 10: Summary of Design of Column

Grid Column
S.N. First Floor Second Floor Third Floor Fourth Floor Stirrups
Location Size
1 A1 400X400 4-25ɸ+4-20ɸ 2-25ɸ+6-20ɸ 8-20ɸ 4-20ɸ+4-16ɸ
2 B2 400X400 8-20ɸ 8-20ɸ 4-20ɸ+4-16ɸ 8-16ɸ 8mm Ø stirrups @ 100 mm
3 C3 400X400 8-20ɸ 4-20ɸ+4-16ɸ 8-16ɸ 8-16ɸ C/C (at top and bottom) &
4 D1 400X400 4-25ɸ+4-20ɸ 2-25ɸ+6-20ɸ 8-20ɸ 4-20ɸ+4-16ɸ @ 150 mm C/C (at mid
5 D2 400X400 8-20ɸ 8-20ɸ 4-20ɸ+4-16ɸ 8-16ɸ height) in all columns
6 D3 400X400 8-20ɸ 4-20ɸ+4-16ɸ 8-16ɸ 8-16ɸ

Structural analysis and design of Residential building in Lalitpur Page | 41


5.6 Design of Foundation

Combined Footing With Strap BeaM(CFSB1)


Given
A) Data, Size of column
Outer Inner
Bc = 400 400 mm
Dc = 400 400 mm
Factored Load (Pu) 424 438
Service Column Load (V) = 282.66667 292 KN
Column Spacing (S) = 4.7498 m
Bearing Capacity (qa) = 120 KN/m2
Grade of Concrete (fck) = 25 Mpa
Grade of Steel (fy)= 500 Mpa
Distance form property line From Outer
(x1)= 0 m Column
B) Proportion Footing Dimension
wt. of foundation = 57.466667 KN (10% of Total Column Load)
Total Load (P)= 632.13333 KN
Area of footing = 5.268 m2
*Note:Centre of area of footing should be Coincide with the load c.g.
C.G. of loads from center of
Inner column (X) = 2.3363285 m
Assumed,
Width of footing (B)= 1.7 m

Length of outer footing


(L1)= 1.784 m
Length of inner footing
(L2)= 1.315 m

Upward reaction (q') = 163.620 KN/m2


Width of strap beam= 400 mm
Cantilever Projection of Slab= 0.65 m

C) Check for Shear


Assumed,
Depth of footing (D)= 500 mm
Use Effective Cover= 60 mm
Effective depth (d) = 440 mm
1) One way Shear (Calculation for no shear reinforcement)

Structural analysis and design of Residential building in Lalitpur Page | 42


Outer footing / Inner footing
Max'm S.F. = 34.360 KN * Note: At the distance
"d" from face of Strap
One way Shear (τv) = 0.078 N/mm2 Beam
Provided Ast = 0.2 %
β= 14.51
Concrete Shear strength
(τc)= 0.331 N/mm2
ok
Ast = 880 mm2 (Min'm Ast to resist one
way shear)
2) Punching shear need not be considered due to presence of the strap beam

D) Check for Bending Moment

Moment capacity of
section= 0.134fck bd2
= 648.56 KN-m
Outer footing / Inner footing
Max'm B.M. = 34.565 KN-m * Note: At the face of
ok Column

E) Calculation for reinforcement

Outer footing / Inner footing


Ast = 183 mm2 By solving
2
Ast min = 528 mm
Ast required = 880 mm2
Provided, Size = 12 mm
Spacing = 125 mm
Ast Provided= 905 mm2
ok
For Shrinkage/Temperature in longitudional direction,
Ast min = 528 mm2
Provided, Size = 12 mm
Spacing = 125 mm
Ast Provided= 905 mm2
ok

Structural analysis and design of Residential building in Lalitpur Page | 43


E) Design of Strap Beam

Assumed,
Width of Beam (B)= 400 mm
Depth of Beam (D)= 500 mm
Effective depth (d) = 440 mm

Shear Force Diagram


300 4.9498, 255.11

200 4.2923, 72.23


1.78, 72.23
100 0.2, 55.63
Shear Force (KN)

0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6
-100

-200 4.9498, -182.89

-300
0.2, -368.37
-400
Disatance (m)

Bending Moment Diagram


300

250 1.524,
238.3590976
Bending Moment (KN-m)

200

150

100

50 4.5, 26.81425348

0 0.2, -5.56308
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6
-50 4.9498, -
59.79750567
-100
Disatance (m)

Point of Zero Shear Force


1) (x)
SF1= -368.37 KN
SF1= 368.37
SF2= 72.23 KN
x1= 1.584 m

Structural analysis and design of Residential building in Lalitpur Page | 44


x= 1.324 m From outer column

1) Bending Moment
Moment capacity of
section= 0.134fck bd2
= 259.424 KN-m

Max'm Sagging Moment = 59.80 KN-m


Design Singly
Reinforced Section
i) Singly reinforced Design
Design moment = 59.797506 KN-m
Ast = 325 mm2
ii) Doubly reinforced Design
Ultimate moment = 0.000 KN-m
Ast,1 = 0 mm2
Exceed Moment = 0.000 KN-m
d' = 35 mm
es = 0.00292
fsc = 425 N/mm2 *Note: Stress in steel
corresponding to strain
Asc = 0.000 mm2 es
Ast,2 = 0.000 mm2
Total Ast = 0.000 mm2

Max'm Hogging Moment = 238.36 KN-m


Design Singly
Reinforced Section
i) Singly reinforced Design
Design moment = 238.36 KN-m
Design moment= 238.36 KN-m
Ast = 1503 mm2
ii) Doubly reinforced Design
Ultimate moment = 0.000 KN-m
Ast,1 = 0 mm2
Exceed Moment = 0.000 KN-m
d' = 35 mm
es = 0.00292
fsc = 425 N/mm2 *Note: Stress in steel
corresponding to strain
Asc = 0.000 mm2 es
Ast,2 = 0.000 mm2
Total Ast = 0.000 mm2

Structural analysis and design of Residential building in Lalitpur Page | 45


Rebar Required
Bottom Bar= 325
Provided, Size = 16 mm
Number = 3
Ast Provided= 604 mm2 Pt = 0.343 %

ok
Top bar= 1503
Provided, Size = 20 mm
Number = 5
Ast Provided= 1571 mm2 Pt = 0.893 %
ok

2) Shear Force
Critical Shear Force = 255.11 KN
shear(τv) = 1.450 N/mm2
Provided Ast = 0.343 %
β= 8.46
Shear strength of
concrete(τc) = 0.418 N/mm2
Result = Shear reinforcement is required
Vsu = 181.557 KN
mm
Use, Size = 8 dia

Leg No = 2
Spacing (Sv) = 100 mm c/c
Provide 2L-8mm@100mmc/c as vertical stirrups
F) Check For Bearing strength of Column and footing concrete

Nominal bearing stress in Column


= 2.7375 N/mm2
Allowable bearing stress = 0.45fck
= 11.25 N/mm2
ok
Area of Dowel bar required
= 0 mm2

Structural analysis and design of Residential building in Lalitpur Page | 46


Combined Footing With Strap BeaM(CFSB2)
Given
A) Data, Size of column
Outer Inner
Bc = 400 400 mm
Dc = 400 400 mm
Factored Load (Pu) 904 916
Service Column Load (V) = 602.66667 610.667 KN
Column Spacing (S) = 5.5626 m
Bearing Capacity (qa) = 120 KN/m2
Grade of Concrete (fck) = 25 Mpa
Grade of Steel (fy)= 500 Mpa
Distance form property line From Outer
(x1)= 0 m Column
B) Proportion Footing Dimension
wt. of foundation = 121.33333 KN (10% of Total Column Load)
Total Load (P)= 1334.6667 KN
Area of footing = 11.122 m2
*Note:Centre of area of footing should be Coincide with the load c.g.
C.G. of loads from center of
Inner column (X) = 2.7629618 m
Assumed,
Width of footing (B)= 3 m

Length of outer footing


(L1)= 2.196 m
Length of inner footing
(L2)= 1.511 m

Upward reaction (q') = 163.654 KN/m2


Width of strap beam= 400 mm
Cantilever Projection of Slab= 1.3 m

C) Check for Shear


Assumed,
Depth of footing (D)= 500 mm
Use Effective Cover= 60 mm
Effective depth (d) = 440 mm
1) One way Shear (Calculation for no shear reinforcement)
Outer footing / Inner footing
Max'm S.F. = 140.742 KN * Note: At the distance
2
One way Shear (τv) = 0.320 N/mm "d" from face of Strap

Structural analysis and design of Residential building in Lalitpur Page | 47


Beam

Provided Ast = 0.2 %


β= 14.51
Concrete Shear strength
(τc)= 0.331 N/mm2
ok
Ast = 880 mm2 (Min'm Ast to resist one
way shear)
2) Punching shear need not be considered due to presence of the strap beam

D) Check for Bending Moment

Moment capacity of
section= 0.134fck bd2
= 648.56 KN-m
Outer footing / Inner footing
Max'm B.M. = 138.288 KN-m * Note: At the face of
ok Column

E) Calculation for reinforcement

Outer footing / Inner footing


Ast = 749 mm2 By solving
2
Ast min = 528 mm
Ast required = 880 mm2
Provided, Size = 12 mm
Spacing = 125 mm
Ast Provided= 905 mm2
ok
For Shrinkage/Temperature in longitudional direction,
Ast min = 528 mm2
Provided, Size = 12 mm
Spacing = 125 mm
Ast Provided= 905 mm2
ok

Structural analysis and design of Residential building in Lalitpur Page | 48


E) Design of Strap Beam

Assumed,
Width of Beam (B)= 400 mm
Depth of Beam (D)= 800 mm
Effective depth (d) = 740 mm

Shear Force Diagram


800
600 5.7626, 545.07
5.0071, 174.15
400 2.20, 174.15
Shear Force (KN)

200 0.2, 98.19


0
-200 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7

-400 5.7626, -370.93


-600
-800 0.2, -805.81
-1000
Disatance (m)

Bending Moment Diagram


700 1.841,
600 651.4599108
Bending Moment (KN-m)

500
400
300
200
100 5.3, 58.94306086

0 0.2, -9.81924
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7
-100 5.7626, -
-200 140.6757006
Disatance (m)

Point of Zero Shear Force


1) (x)
SF1= -805.81 KN
SF1= 805.81
SF2= 174.15 KN
x1= 1.996 m

Structural analysis and design of Residential building in Lalitpur Page | 49


x= 1.641 m From outer column

1) Bending Moment
Moment capacity of
section= 0.134fck bd2
= 733.784 KN-m

Max'm Sagging Moment = 140.68 KN-m


Design Singly
Reinforced Section
i) Singly reinforced Design
Design moment = 140.6757 KN-m
Ast = 451 mm2
ii) Doubly reinforced Design
Ultimate moment = 0.000 KN-m
Ast,1 = 0 mm2
Exceed Moment = 0.000 KN-m
d' = 35 mm
es = 0.00316
fsc = 425 N/mm2 *Note: Stress in steel
corresponding to strain
Asc = 0.000 mm2 es
Ast,2 = 0.000 mm2
Total Ast = 0.000 mm2

Max'm Hogging Moment = 651.46 KN-m


Design Singly
Reinforced Section
i) Singly reinforced Design
Design moment = 651.46 KN-m
Design moment= 651.46 KN-m
Ast = 2421 mm2
ii) Doubly reinforced Design
Ultimate moment = 0.000 KN-m
Ast,1 = 0 mm2
Exceed Moment = 0.000 KN-m
d' = 35 mm
es = 0.00316
fsc = 425 N/mm2 *Note: Stress in steel
corresponding to strain
Asc = 0.000 mm2 es
Ast,2 = 0.000 mm2
Total Ast = 0.000 mm2

Structural analysis and design of Residential building in Lalitpur Page | 50


Rebar Required
Bottom Bar= 451
Provided, Size = 20 mm
Number = 3
Ast Provided= 943 mm2 Pt = 0.319 %
ok
Top bar= 2421
Provided, Size = 25 mm
Number = 5
Ast Provided= 2455 mm2 Pt = 0.829 %
ok

2) Shear Force
Critical Shear Force = 545.07 KN
shear(τv) = 1.841 N/mm2

Provided Ast = 0.319 %


β= 9.11
Shear strength of
concrete(τc) = 0.405 N/mm2
Result = Shear reinforcement is required
Vsu = 425.220 KN
Use, Size = 10 mm dia

Leg No = 2
Spacing (Sv) = 110 mm c/c
Provide 2L-10mm@100mmc/c as vertical stirrups
F) Check For Bearing strength of Column and footing concrete

Nominal bearing stress in Column


= 5.725 N/mm2
Allowable bearing stress = 0.45fck
= 11.25 N/mm2
ok
Area of Dowel bar required
= 0 mm2

Structural analysis and design of Residential building in Lalitpur Page | 51


Table 11: Summary of Design of Footing

Footing Details
Soil Bearing Capacity =120 KN/m2
Concrete Grade: M20 Steel Grade: Fe500
Foundation Plan Thickness (mm) Reinforcement Detail
Grid
SN Footing Type: Edge
Location LXB (M) Overall (D) Both ways
(d1)
1.78m X
As per Outside(F1)
Combined Footing With Strap 1.7m
1 Footing 250mm 500mm 12 mm Ø @125mm c/c
Beam(CFSB1) 1.524m X
Layout
Inside(F2)
1.7m
SB1 of dimension 400mmX500mm with 5-20 Ø(T)+3-16 Ø(B) with stirrups 2L-8mm@100mmc/c spacing
As per Outside(F3) 2.2m X 3m
Combined Footing With Strap
2 Footing 250mm 500mm 12 mm Ø @125mm c/c
Beam(CFSB2) Inside(F4) 1.5m X 3m
Layout
SB2 of dimension 450mmX800mm with 5-25 Ø (T)+3-20 Ø(B) with stirrups 2L-10mm@100mmc/c spacing
As per Outside(F5)
1.9m X 2.9m
Combined Footing With Strap
3 Footing 1.524m X 250mm 500mm 12 mm Ø @125mm c/c
Beam(CFSB3) Inside(F6)
Layout 2.9m
SB3 of dimension 400mmX650mm with 5-25 Ø (T)+3-20 Ø(B) with stirrups 2L-8mm@100mmc/c spacing
Main bar 12 and 10 mm ɸ@ 6” c/c
Staircase slab thickness=125mm
distribution bar

Structural analysis and design of Residential building in Lalitpur Page | 52


Figure 21:Foundation Layout

Structural analysis and design of Residential building in Lalitpur Page | 53


6 References

 IS 456- 2000 Code of practice for plain and reinforced concrete


 IS 875-1987 Code of practice for design loads (other than earthquake) for
buildings and structures
 IS 1893-2002 Criteria for Earthquake Resistant Design of Structures,
 IS 13920-1993 Code of practice for ductile detailing of reinforced concrete
structures subjected to seismic forces
 NBC Nepal Building Code
 ETABS manual V 16

Structural analysis and design of Residential building in Lalitpur Page | 54


STRUCTURAL DESIGN (Type B)
As Per Submitted
Building Elements Remarks
Design
General

Building Structure Type Frame Structure


Number of story applied for permit (in
4
No’s)
Number of story considered in structure
4
design (in No’s)
If Computer Aided Design (CAD) is used,
please State the name of the software ETABS 2016
package
Number of story considered in structure
No.
design provision for further extension
Total height (h) 0f structure with extension
12.195m
(in m)
NBC 101-1994 MATERIALS SPECIFICATIONS

Materials to be used in structure (tick the


listed materials that will be used in
structure element
RCC
(Reinforcement Bar)

NBC 102-1994 UNIT WEIGHT of MATERIALS


Specified the design unit weight of
7850
materials: Steel (In kg/m^3)
Specified the design unit weight of
2500
materials:RCC (In kg/m^3)
Specified the design unit weight of
1920
materials: Brick Masonry (In kg/m^3)
NBC 103-1994 OCCUPANCY LOAD (Imposed Load)

For residential Buildings


Occupancy Load (Uniformly Distributed
2
load in KN/m^2) for Rooms and Kitchen
Occupancy Load (Uniformly Distributed
3
load in kN/m^2) for Staircase
Occupancy Load (Uniformly Distributed
3
load in kN/m^2) for Balcony

Structural analysis and design of Residential building in Lalitpur Page | 55


NBC 104-1994 Wind load

Wind Zone

Basic wind speed (in m/s)

NBC 105-1994 Seismic Design of Buildings in Nepal


Seismic
Coefficient
Approach
Method adopted for earthquake resistant design seismic
Adopted Code for Seismic Design IS 1893 1893

Type II
Subsoil category (Medium)

Seismic Weight (W) (in kN) 2537.97

Fundamental Time Period of the building


0.489
along X (Tx)(in Seconds)

Fundamental Time Period of the building


0.489
along Y(Ty)(in Seconds)

Response reduction factor (R) 5

Seismic zoning factor (Z) 0.36

Importance Factor (I) 1

Spectral acceleration coefficient (Sa/g) along X 2.5

Spectral acceleration coefficient (Sa/g) along Y 2.5

Design Horizontal Seismic Coefficient Along


0.09
X (Ah)

Design Horizontal Seismic Coefficient Along


0.09
Y (Ah)

Base Shear(VB) for Seismic Coefficient Along X 228.417

Base Shear(VB) for Seismic Coefficient Along Y 228.417


Base Shear Generated through dynamic
Due to seismic
Analysis Along X (if response spectrum
coefficient
method used)

Structural analysis and design of Residential building in Lalitpur Page | 56


Base Shear Generated through dynamic
Analysis Along Y (if response spectrum
method used)

Adopted Base Shear multiplication Factor


Along X(if response spectrum method used)

Adopted Base Shear multiplication Factor Along Y(if


response spectrum method used)

Base Shear after Scale Factor Along X

Base Shear after Scale Factor Along Y

Maximum Inter-story Drift 5mm

Corresponding Story height for Maximum Inter


3.049 m
Story Drift (h)
no
NBC 106-1994 Snow Load

Snowfall type or condition


No snowfall
Elevation of construction site (in m)

Design Depth of snow (in cm)

Design Density of snow (in g/cm3)


NBC 107-1994 Provisional Recommendation on Fire
safety
Yes
Have you considered fire safety requirement? no No no

NBC 108-1994 Site Consideration for Seismic Hazards

Whether Distance of construction site from Yes


no
toe/beginning of downward slope is within 50m? No

Whether Distance of construction site from river bank Yes


no
is within 50m? No
Yes
Availability of soil test report no
No
NBC 114-1994 Construction Safety

Are you sure that all safety measures will be fulfilled Yes
yes
in the construction site as per this code? No

Structural analysis and design of Residential building in Lalitpur Page | 57


Safety hard hat
Safety goggles
Safety wares used Safety boots yes
Safety belts
First aid facility

Structural Data for Framed RCC Structure

NBC 110-1994 Plain and Reinforced Concrete


M20
M25
Concrete grade in structure M20 for All

Fe-500
Reinforcement Steel Grade Fe500 for all

Slab design
1 long side
discontinuous

2 adjacent
side
continuous

2 adjacent side
continuous
Boundary condition of slab

Effective Thickness of slab (d) (in mm) 105 Is code

3048
Short span of Critical slab panel (L) (in mm)

mm
Calculated short span to effective depth ratio
29.03
(L/d) for the corresponding slab

Basic (L/d) ratio 23

Structural analysis and design of Residential building in Lalitpur Page | 58


Required modification factor for
1.26
tension reinforcement
Required Tension reinforcement (Ast)
Percentage (%) for short span bottom 0.12
reinforcement
Provided Tension reinforcement (Ast)
Percentage (%) for short span bottom 0.32
reinforcement
Actual Modification factor for
2.54
tension reinforcement

Check for Critical beam

Effective depth of beam (d) (in mm) 410

Critical span (L) (in mm) 6400.8

One side
Support condition continuous
Both side
continuous
Basic (L/d) ratio 23

Calculated critical span to effective depth


15.61
ratio (L/d) for corresponding slab

Check for Critical Column

Critical column height 3.0488 m


400 X 400
Minimum size of column (mm x mm)
Short column effect considered or not Yes
yes
No
Minimum longitudinal reinforcement
area
of 0.8
Provided
(%)
Design Limit state
Limit state method
Philosophy method
Load
Combinations
1: DL 1.5

1: LL 1.5

Structural analysis and design of Residential building in Lalitpur Page | 59


2: DL 1.5

2: EQ 1.5

3: DL 1.2

3: LL 1.2

3: EQ 1.2

4: DL 0.9

4: EQ 1.5
Whether sample design calculations of
Yes
foundations, columns, beams and slabs are yes
No
submitted
Combined
Footing With Strap
Beam

Type of Foundations
Minimum Depth of foundation from ground 1.5
1.5m
level to the bottom of footing (in m) m

Structural analysis and design of Residential building in Lalitpur Page | 60