DI09 CONVENTIONAL FIRE DETECTION PANEL

The fire detection panel DI09 is conventional type product with 4 zones.
The total capacity of 10 detectors or manual call points per zone.
Quick to assemble and operate, easy to use, DNV
And WheelMark approved, the DI09 is a leader in its category.

Document reference: DI09 FP GB Rev1

DI09
Functions:

• Fire and failure detection (insulation fault, cut or short circuit on


1 zone)
• Normal power supply automatic switch/ emergency power
supply with alarm
• 3rd source (12V battery) activating the alarm in case of main
and emergency sources failure
• Day/night type dimmer
• Protected functions: 3 levels access, by access code on the
screen

Configuration:

Directly on the panel with the LCD and the keyboard:


DESCRIPTION
• Identification of the zones (20 characters).
Application • Some functions can be parameterized (enabled/disabled zones,
relay temporization, language...)
The fire alarm panel DI09 is a conventional type product with 4
zones. Outputs:
It has a total capacity of 10 detectors or manual call points per zone,
with standard or watertight base. (Optical smoke detectors, heat, 1. « External siren » output, immediate, monitored (24VDC
flame, or intrinsically safe detectors) monitored with 2k2 end of line resistor, 0.5A maxi) activated on
fire or fault alarm.
Functional characteristics 2. « Fire alarm » output, (dry contacts N.O., 0.35A max).
3. « fault » output (dry contacts N.C., 0.35A max)
Display: 4. Serial port RS485 for transfer on external equipment/ mimic
panel./extinction/V.D.R.
Functional conditions: LEDs + graphic backlighted Selectable Protocol: NMEA 0183 (IEC 61162-120) / MODBUS
LCD RTU
• User languages : programmable: English, 5. « General alarm » output
French, Spanish
• Serigraphy : 2 languages text (French,
English, Spanish in option)

Rédigé par MOB, 22/02/10 Approuvé par AL, 24/02/2010 DI09 FP GB REV 0.doc Page 1/2
Document non contractuel

MARINELEC TECHNOLOGIES Tel :33 (0) 2 98 52 16 44 Fax : 33(0) 2 98 64 74 05 marinelec@marinelec.com www.marinelec.com


Mechanical characteristics Outputs switching capacity:
• 0.5 A @ 24 VDC
Dimensions (LxWxH): •
Environment
• Case : 170x168x58 mm
• Front face : 270x10 mm Storage conditions:

• 30°C to 70°C

Functioning conditions:

• -10° C to 55°C

Maximum humidity:

• 95% RH - non condensable at 40°C

Mounting:

• Slot in (Standard model))

Approbations

Weight: • Wheelmark, DNV

• 0.6Kg Connection
Protection level:
22
General alarm output
21
• IP31 (back face)
20 -
• IP44 (front face) RS485
19 +
18 - detection line
Material: zone 4
17 +
16 - detection line
• ABS zone 3
15 +
14 - detection line
zone 2
Electrical characteristics 13 +
12 - detection line
11 + zone 1
Main power supply:
10
fault output
9
• 24 VDC (-25% +30%) 8
fire alarm output
7
Emergency power supply: MAXI 500mA / 24VCC 6 0VDC external buzzer
-

2k2
+ 5 +24VDC external buzzer
• 24 VDC (-25% +30%) 4 0VDC emergency power supply
3 +24VDC
rd
3 power supply source: 2 0VDC
main power supply
1 +24VDC
• 1 battery 12 VDC (type MN21)

Power supply commutation: Associated MARINELEC products

• Automatic Detectors: Call points: Sirens: Test equipment:

Power supply protection:

• Diodes and resettable fuses 1.2A

Consumption:

• 0,25 A maxi (+ outputs consumption)

Zones:

• Cable: shielded cable 2 conductors, section mini. recommended


0.75mm2
• Cable length maxi per loop = 50m
• Consumption = 0,01 A nominal, 0,05 A maxi.
• Protection against polarity inversion and short-circuits

Rédigé par MOB, 22/02/10 Approuvé par AL, 24/02/2010 DI09 FP GB REV 0.doc Page 2/2
Document non contractuel

MARINELEC TECHNOLOGIES Tel :33 (0) 2 98 52 16 44 Fax : 33(0) 2 98 64 74 05 marinelec@marinelec.com www.marinelec.com