Professional Documents
Culture Documents
All data taken for this laboratory will be recorded on the score sheet that is included
on the last page this lab.
A. Ensure that the equalizer valves on both transmitters are closed by turning
the handles clockwise until snug.
B. Ensure that the High and Low pressure valves are open.
Equalizer Equalizer
Valve Valve
High and
High and Low Valves
Low Valves
3051S 3051SMV
E. Flip the switch to Position 3 to turn on the fan. Ensure that the black
temperature cable is connected to the 3051SMV and that the temperature
switch is facing away from the black control knob. Wait for the readings
to reach steady state. Record readings from the LCD’s (or AMS) for
3051S Flow, 3051SMV Flow, DP, SP and Temperature on the lab score
sheet.
F. Move the power knob of the fan to Position 2. Record readings from the
LCD’s (or AMS) for 3051S Flow, 3051SMV Flow, DP, SP and
Temperature on the lab score sheet.
G. Move the power knob of the fan to Position 1. Record readings from the
LCD’s (or AMS) for 3051S Flow, 3051SMV Flow, DP, SP and
Temperature on the lab score sheet.
DP ________________________________________
C. Open the equalizing valve on the 305 manifold that is connected to the
3051SMV by turning the handle counter-clockwise. (see image)
DP ________________________________________
Note: Many people incorrectly assume that you only need to open the
equalizing valve to zero the transmitter. This is not the proper procedure
and will add error into the measurement. The reasons for this and the
proper zeroing procedure will be explained in the next step below.
E. Close the low side isolation valve on the 305 manifold that is connected to
the 3051SMV by turning the handle clockwise.
DP ________________________________________
Note: The proper procedure to zero a transmitter would have been to first
close the low side, or high side (not both!), isolation valve prior to opening
the equalizing valve. This is especially important in a steam or other high
temperature application. If you open the equalizing valve first, you run the
risk of flushing the condensate legs/columns downstream into the process.
This would then allow the high temperature process fluid to come in
contact with the pressure transmitter, potentially causing sensor damage.
G. Close the equalizing valve on the 305 manifold that is connected to the
3051SMV by turning the handle clockwise.
H. Open the low side isolation valve on the 305 manifold that is connected to
the 3051SMV by turning the handle counter-clockwise.
3051SMV DP ________________________________________
Record the 3051S Differential Pressure Value from the 3051S LCD.
3051S DP__________________________________
C. Using the 3/8 in wrench, loosen the valve plug (by rotating
counterclockwise) from the low side drain vent valve that is part of the 305
manifold that is connected to the 3051SMV. There should be a small
amount of air (barely perceptible) escaping from the drain vent valve.
3051SMV DP ________________________________________
Record the 3051S Differential Pressure Value from the 3051S digital
display.
3051S DP__________________________________
E. Using the 3/8 in wrench, remove the valve plug from the low side drain
vent valve that is part of the 305 manifold that is connected to the
3051SMV
3051SMV DP ________________________________________
Record the 3051S Differential Pressure Value from the 3051S digital
display
3051S DP__________________________________
Note: The first scenario illustrates what happens when there is a small
leak in the connection system. The second scenario illustrates what
happens when there is a more significant leak in the connection system.
In the field, it is a good idea to check that all drain vent valve parts are
secured if the customer is experiencing low DP’s.
G. Re-install the valve plug into the low side drain vent valve that is part of
the 305 manifold that is connected to the 3051SMV.
H. Click “OK” to close out of the 3051SMV Process Variables screen and
return to AMS Device Connection View.
A. Turn on the fan and adjust the power knob until the Flow Rate on the
3051S reads approximately 2 lb/min (0.94 kg/min) or 1.85 inH2O (4.5
mbar) on the LCD of the 3051S.
- Somewhere between positions 1 and 2 on the fan power knob
*Note: The mA readings from the 3051SMV and the 3051S should be
approx. the same
E. Click on the “Basic Setup” tab. Navigate to the “Transfer Function” drop-
down under the Pressure Setup heading. Change the option to “Square
Root” as shown below. Click the “Apply” button and then “Yes” to apply
changes.
*Note: By changing the transfer function on the Basic Setup tab, you have
applied a double square root. This is because the Scaled Variable is already
setup with a square root relationship. Any time the Scaled Variable is used to
represent a flow rate, square root will be used.
*You will notice that the flow measurement readings in AMS or on the
transmitters LCDs did not change.
H. Compare the mA output for the 3051S from Step B. with the readings
taken in Step G. Were the readings different? If so, which mA reading
was higher (linear or sq-root)? Did the readings for the 3051SMV change?
I. Return the “Transfer function” to Linear as shown below. Click the “OK”
button and then “Yes”. You may now disconnect the HART modem from
the 3051S and reconnect it to the 3051SMV.
Temperature _____________________________________
E. Flip the switch on the temperature control box so that the switch is
positioned towards the black knob.
F. Turn the potentiometer (black knob on the temperature control box)
clockwise in quarter-turn increments until the temperature reading is
approximately
400 ± 50°F (200 ± 10°C).
G. Record readings from the LCD’s (or AMS) for 3051S Flow, 3051SMV
Flow, DP, SP and Temperature on the lab score sheet.
H. Move the power knob of the fan to Position 2. Allow the system time to
reach steady state. Record readings from the LCD’s (or AMS) for 3051S
Flow, 3051SMV Flow, DP, SP and Temperature on the lab score sheet.
I. Move the power knob of the fan to Position 1. Allow the system time to
reach steady state. Record readings from the LCD’s (or AMS) for 3051S
Flow, 3051SMV Flow, DP, SP and Temperature on the lab score sheet.
J. Compare the data for 3051SMV Flow to the Baseline data for the
3051SMV under the condition when the fan was at Position 3. Turn the
temperature control knob counter-clockwise to decrease the temperature to
150 ± 25°F
(65 ± 4°C). What happened to the calculated flow rate when the
temperature value was changed to 150°F (65°C)?
____________________________________________________________
____________________________________________________________
_____
K. Calculate the flow difference between the 3051SMV and 3051S at the
three fan positions that regulate flow.
Position 3: ______________________________________
Position 2: ______________________________________
Position 1: ______________________________________
L. Flip the switch on the temperature control box so that the switch is facing
away from the black knob (same as at the start of the lab).
N. Close AMS.
Page 11
(3051SMV)
DP
(3051SMV)
Orifice Product Line 1495/1595/1496
DP Flow Level 200 Product Training
SP
Self Guided Hands-On Trouble Shooting Module
(3051SMV)
Temp
(3051SMV)
9/24/2014