VOLTAGE DROP SPREADSHEET SINGLE OR THREE PHASE

ENTER DATA HERE CALCULATED


LOAD KVA PHASE Voltage Power Factor Length WIRE SIZE R X CURRENT VOLTS %
1 OR 3 L-L KV 0.5-1.0 KFT AWG OHM/KFTOHM/KFT AMPS DROP VDROP
Generator to RV
based on 24A load
@120VAC 5.52 1 0.23 0.90 0.15 #10 1.200 0.050 24.00 7.93 3.45%

Generator to RV
based on 24A load
@120VAC 5.52 1 0.23 0.90 0.15 #8 0.780 0.052 24.00 5.22 2.27%
Generator to RV
based on 24A load
@120VAC 5.52 1 0.23 0.90 0.15 #6 0.490 0.051 24.00 3.34 1.45%
0.00 3 0.48 0.90 0.10 #8 0.000 0.000 0.00 0.00 0.00%
0.00 3 0.48 0.90 0.10 #8 0.000 0.000 0.00 0.00 0.00%