You are on page 1of 1

1 Manufacturer Draeger

2 Series FD10
3 Model Dräger Flame 1300
4 Type Infra Red (Single channel IR)
5 Detection wavelengths 4.2 to 4.7 microns, sensor peak at 4.4 microns
6 Application Flame / Fire Detection of Hydrocarbon Fires only
GENERAL
7 Safety Integrity Level (SIL) N/A
8 MTBF ≥11.4 years
9 Measurements 275 mm x 155 mm / 10.8" x 6.1"
10 Weight Aluminium 3.5 Kg / 7.7 lbs
11 Weight Stainless Steel 5 Kg / 11 lbs
12
13 Sensitivity 0.1 m² n-heptane fire at 18 metres / 1 sq. foot fire at 60 feet
14 Field of View Horizontal 90°, vertical 90°
15 Electrical connection M20 x 2 or 3/4" NPT x 2
16 Wiring connections 2.5mm2
17 Hazardous area protection ATEX, IECEx, FM & CSA
18 Response time 3.5 seconds, typical, configurable up to 30 seconds
19 Output Signals:
20 Analog Fault 0 mA
21 Analog Optics/electronics check failure 2 mA
22 Analog Normal operation 4 mA
23 Analog Fire pre-warning 16 mA
24 Analog Fire 20 mA (factory configurable for latching/non-latching alarm)
25 Relay Relays for fault and alarm, ratings 125 VAC, 0.5 A; 30 VDC, 2 A
26 Digital RS 485 (Optional)
DETECTOR
27 Ambient Conditions: Temperature -40 to +70°C / -40 to +158°F
28 Ambient Conditions: Pressure 915 to 1055 hPa / 27.9 to 31.2 inch of Hg
29 Ambient Conditions: Humidity 0 to 99 %RH, non condensing
30 Power Supply 18 to 32 VDC
31 Power consumption 160mA quiescent current at 24 volts (maximum 230mA)
32 Maximum in-rush current 230 mA
33 Housing environmental protection IP 66 / NEMA 4X
34 Housing material Aluminium Alloy grade LM25 or Stainless Steel grade 316
35 Sunshade material Polycarbonate/ABS (supplied as standard)
36 Automatic fault diagnostic feature Yes
37 Cabling 3 wire 0-20 mA output, current source
38 Cabling 4 wire Isolated 0-20 mA output, current source
39 Cabling 4 wire Relay option for fire and fault outputs to a fire panel (NFPA 72)
40
41 Detector Part No. Dräger Flame 1300, Aluminium, M20 (Latching) 23 50 422
42 Detector Part No. Dräger Flame 1300, Stainless Steel, M20 (Latching) 23 50 425
43 Detector Part No. Dräger Flame 1300, Aluminium, 3/4 NPT (Latching) 23 50 441
44 Detector Part No. Dräger Flame 1300, Stainless Steel, 3/4 NPT (Latching) 23 50 444
ORDERING INFO 45 Detector Part No. Dräger Flame 1300, Aluminium, M20 (non-Latching) 23 07 009
46 Detector Part No. Dräger Flame 1300, Stainless Steel, M20 (non-Latching) 23 07 015
47 Detector Part No. Dräger Flame 1300, Aluminium, 3/4 NPT (non-Latching) 23 07 013
48 Detector Part No. Dräger Flame 1300, Stainless Steel, 3/4 NPT (non-Latching) 23 07 019
49
50 Accessory Part No. Draeger Flame Simulator FS-10 23 07 023
51 Accessory Part No. Mounting Bracket - SS 316 (supplied with detector as standard) 23 50 447
ACCESSORIES
52 Accessory Part No. Dräger Flame Detector FD10 Range Cover 23 50 448
53
54 Approvals (Performance & Area Classification) FM: Class 3260 & 3600.
55 Approvals (Area Classification) FM: Class I, Groups A,B,C,D & Class 1, Zone 1, Groups II A, B & C
56 Approvals (Area Classification & Temperature) CSA: Class I, Groups A,B,C,D, T6 (-50 to +60°C), T5 (-50 to +70°C)
APPROVALS 57 Approvals (Area Classification & Temperature) ATEX: II 2G EEx d IIC T6/T5; -50 ≤ Tamb ≤ +60 / +70°C
58 Approvals (Electromagnetic Compatibility) EN61000-6-3:2001 EN50130-4: 1995 + A1: 1998
59 Approvals (Area Classification & Temperature) IECEx Ex d IIC T6/T5; -50 ≤ Tamb ≤ +60 / +70°C
60

Dräger Flame 1300 Flame Simulator FS-10


PN 23 XX XXX PN 23 07 023

INSTRUMENT SPECIFICATION
Dräger Flame 1300
IR Flame Detector
Sheet 1 of 1
No. By Date Description Code : Dwg. No. : Rev:
Subject to correction/change. E&OE.

You might also like