You are on page 1of 5

0102-TL-C-TQU-101 : TECHNICAL PARTICULAR GUARANTEE FOR LATTICE TOWER REV.

00
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
A DESIGN CONDITIONS FOR DOUBLE CIRCUIT STEEL TOWER
General Design Conditions of the towers as follows:

a. Voltage kV 150
b. Number of circuit 2
c. Basic Span m 350
d. Loading Span
- Wind Span
All towers
- Normal Working m 500
- Broken Wire m 400
- Weight Span
Suspension towers
- Normal Working m 700
- Broken Wire m 500
Tension towers
- Normal Working m 700
- Broken Wire m 500
e. Phase conductor per phase mm2 2 x ACSR/AS 429/56
f. Maximum Working Tension (T) per Conductor kg 3400
g. Earth Wires mm2 GSW 70; AS 70 ; OPGW 70
f. Maximum Working Tension (T) per Earthwire kg 1600 ; 1600

BIDDER'S SIGNATURE MANUFACTURE'S SIGNATURE

1 of 5

(.........................................................) (..........................................................)
B ASSUMED ULTIMATE CONDITIONS OF TOWER
1.B Temperature of Conductor
a. Highest Temp °C 80 for ACSR/AS
b. Average Temp. °C 25
c. Lowest Temp. °C 10
2.B Wind Pressure
a. Conductors and Groundwires, on the protected area of each item kg/m3 40
b. Insulator strings, on the protected area each of them kg/m3 60
c. Tower, on 1.5 times the protected area of members of one side kg/m3 180

C ASSUMED ULTIMATE CONDITIONS OF TOWER


1.C Minimum thickness of members before galvanizing
a. Main angle members mm 5
b. Secondary members mm 4
b. Secondary unstressed members mm 4
d. Gusset plate mm 4.5
2.C Minimum diameter of bolts mm 16
3.C Minimum zinc mass Number of immersions in uniformity test
a. members g/m2 610
b. bolt, nuts, washer g/m2 375
4.C Slenderness ratio
a. Tower legs & main members in cross arm groundwire peaks 120
b. All other compression members 200
c. Secondary members of reinforcement of compression member 250
d. Tension members 400

BIDDER'S SIGNATURE MANUFACTURE'S SIGNATURE

2 of 5

(.........................................................) (..........................................................)
5.C Safety factors
a. Against normal loading conditions 1.5
a. Against broken wire conditions 1.1

D CLEARANCE
These clearance will be maintained for the line under conditions
corresponding at 80°C for ACSR (Max. conductor temperature)

1.D Minimum Vertical Clearance


a. Above normal ground, open and agricultural land m 13.5
b. Above pedestrian access m 13.5
c. At main road crossing m 9
d. Above trees m 5.5
e. At power circuit crossing regardless the voltage from shield wire m 4
f. At telephone line crossing m 4
g. Urban / inhabitet area m 13.5
h. Above bi river m 40

E MATERIALS FOR SUPPORTS


Standard Steel materials
Minimum tensile strength kg/mm2 245
minimum yield strength kg/mm2 355
Minimum elongation on 200 m %
Minimum bending diameter
(expressed as a function of thickness)
Maximum working stress :

BIDDER'S SIGNATURE MANUFACTURE'S SIGNATURE

3 of 5

(.........................................................) (..........................................................)
- Tensile stress kg/mm2
- Compressive stress kg/mm2
- Shears stress kg/mm2
Galvanizing :
- Minimum quantity of zinc coating g/m2 610
Minimum number of uniformity
(minutes x time)

F CLEARANCE INTERNAL TO LINES


The configuration of double and four circuit will take into account
the following internal clearance :
1.F Earth wire
a. Number per tower 2
b. Shield angle (max) deg. 15
2.F Distance between tower arm and jumper m 1.9
3.F Maximum allowable swing angle
a. Suspension deg. 40
b. Tension (jumper) deg. 20
4.F Minimum insulation spacing (under normal condition) m 1.8
5.F Minimum insulation spacing (under swing condition) m 1.3

G TOWER EARTHING
1.G Terminal and earthing angles for counterpoise wire
a. Terminals
- Manufacturer's name

BIDDER'S SIGNATURE MANUFACTURE'S SIGNATURE

4 of 5

(.........................................................) (..........................................................)
- Materials
- Type
b. Earthing angle
- Manufacturer's name
- Materials name
2.G Counterpoise wire (galvanized steel wire)
a. Manufacturer's name
b. Materials
c. Classification
d. Construction of wire, component steel wire (number/diameter)
e. Direction of standing of outermost layer
f. Length of one wire mm
- Tolerance in length %
g. Ultimate breaking strength kg
h. Componen steel wire
- Diameter mm
- Tolarance in length mm
- Minimum breaking strength kg
- Minimum number of twisting times
- Minimum weight of zinc coating g/m2

BIDDER'S SIGNATURE MANUFACTURE'S SIGNATURE

5 of 5

(.........................................................) (..........................................................)