Professional Documents
Culture Documents
All was going to plan, until he started looking for the settings for lower range value (LRV) and
upper range value (URV). And then, in an all-too-familiar scenario, he hit a roadblock. The
instructions don’t actually mention URV and LRV, the terms he’s familiar with, by name or
acronym. So what’s a guy to do?
The Siemens mode codes for ranging a transmitter without applying pressure are:
The Up and Down arrow pushbuttons adjust the value. The M pushbutton saves the value once
you have it set to your required parameter.
M2: Set and adjust MA and M3: Set and adjust ME are for what I call ‘wet’ ranging, using for
ranging the pressure transmitters in level applications.
Apply a pressure corresponding to a low level (4.0 mA), and M2 will use that for the lower range
value. Apply the pressure corresponding to the high level (20.0 mA), and M3 uses that for the
high level range value.
The zero trim adjustment is aptly called M7 Zero adjustment. Zero trim is typically done on low
pressure range transmitters to compensate for any zero offset due to installation factors, like
out-of-plumb, elevation offset or not level. You’ll use the pushbutton Up and Down arrows to
bring the reading to zero (when the applied pressure is at zero). The M button locks in that
offset as the 4.000mA point.