You are on page 1of 1

LOAD SCHEDULE

LOAD COMPUTATION CKT No. LOAD DESCRIPTION


FIXTURES VA/ AMPS
BREAKER RATING WIRE SIZE
PIPE SIZE
QUANTITY WATTS VOLTS CKT FRAME TRIP POLE mm 2

1 LIGHTING OUTLET 8 72 230 576 2.5 50 15 2 2-3.5 THHN 20 MM0 PVC


By occupancy
Residential = 24 va/sq.m 2 LIGHTING OUTLET 9 72 230 720 2.82 50 15 2 2-3.5 THHN 20 MM0 PVC
Total floor area = 124.25 sq.m 3 LIGHTING OUTLET 9 72 230 720 2.82 50 20 2 2-3.5 THHN 20 MM0 PVC

General lighting load: 124.25 sq.m x 24 va/sq.m = 2,982 va 4 CONVENIENCE OUTLET 3 180 230 540 2.35 50 20 2 2-3.5 THHN 20 MM0 PVC
Small appliance load = 3,000 va
g h g h 5 ACU ( 1.0 HP ) 2 746 230 1865 8.12 50 30 2 2-3.5 THHN 20 MM0 PVC

6 5 1492 230 40.54 50 30 2 2-3.5 THHN 20 MM0 PVC


1 2 3 4 5 6 7 8 9 10 11 12 13 14
Applying demand factor ACU ( 2.0 HP ) 9325

UP first 3000 va @ 100 % d.f = 3000 va 7 S P A R E


remaining 2,982 va @ 35% d.f = 1043.7 va
Sghi

2
8 S P A R E
Sf
Se

1 2 3 4 5 6 7 8 9 10 11 12 13 14 9
d e f f DOWN
Net general lighting & small appliance load = 4,043.7 va
c i i
Sd Sj
D
2 Other Loads: 2- 1 hp acu = 1865 va TOTAL 56.33
PB TRANSACTION AREA
5- 2 hp acu = 9325 va

Sk
k k j j 15,233.7
c c c c
Sl IF = 56.33 + 8.0 (.25) x 85% D.F
Sabc IF = 49.58 AMPERES
3
Total computed current: 15,233.7 va / 230 v :66.23 amps
2
1 BALCONY Use :2 - 20.0 mm sq. THW wire in 20mm dia rsc pipe USE : 2- 20.0 MM THW WIRE IN 25 MM 0
l l l RSC PIPE AS MAIN CONDUCTOR
as main conductor
:one 60 amp circuit breaker, 2p, 240 volts : ONE- 60 AMPS CIRCUIT BREAKER 2P, 240V
as main protection AS MAIN PROTECTION
b a b a
WAITING AREA

GROUND FLOOR LIGHTING LAYOUT SECOND FLOOR LIGHTING LAYOUT


ONE LINE DIAGRAM :
²
Æ
LEGENDS :
SERVICE ENTRANCE Sa SINGLE GANG SWITCH

Sab DOUBLE GANG SWITCH


M M KILOWATT HOUR METER
Æ Sabc TRIPLE GANG SWITCH
PB PANEL BOARD
CONVENIENCE OUTLET
ACU 2hp

11
CIRCUIT HOMERUN
CIRCUIT LINE
60 AT/100AF
GROUND AIR CONDITIONER OUTLET
ACU
10 11 12 13 14

UP
1 2 3 4 5 6 7 8 9
15 AT 15 AT
1 2
10

15 AT 20 AT
ACU 1hp

1 2 3 4 5 6 7 8 9 10 11 12 13 14

8 DOWN
3 4
SPECIFICATION :
PB D
ACU 1hp ACU 2hp 2

ACU 2hp
ACU 2hp
20 AT 30 AT
13
7

5 6
9

TRANSACTION AREA
5

4
12

30 AT SPARE
6

ACU 2hp

7 7
SPARE
BALCONY
9

WAITING AREA

GROUND

GROUND FLOOR POWER LAYOUT SECOND FLOOR LIGHTING LAYOUT


RISER DIAGRAM
CONTRACTOR : SIGNED : CHECKED BY : SHEET CONTENTS : PROJECT TITLE: OWNER : SHEET NO.
LIGHTING LAYOUT
POWER LAYOUT
Trading and Engineering Services . DATE :
LEGEND
Purok 11 Maharlika Village Corales Compound, Ma-a Cavao City APPROVED BY : LOCATION:
Land Line : (082) 321-4392 Mobile No. 0928-1433869 SPECIFICATION
Email Address: zandy@zjbbtrading.com REG. NO. :
PTR NO. : TIN NO. : LOAD COMPUTATION
DATE ISSUED : PLACE ISSUED : DATE : RISER DIAGRAM

You might also like