Professional Documents
Culture Documents
Increase in the X/R ratio, Using high speed circuit breakers, Using
Auto Re-closing, employing lightning arresters, high neutral grounding
impedance, single pole switching, quick Automatic Voltage Regulators
(AVRs).
Dynamic Stability:
The transient stability of the system can be determined by the help of the swing
equation. It describes the relative motion of the rotor with respect to the stator
field as a function of time.
Ta = Tm – Te ……..(1)
I. d2θ/dt2 = Ta ……..(2)
Since the angular position θ of the rotor is continuously varying with time,
then the value of is θ given by
Swing equation:
We know that relative angle between two machines, i.e., angle between two
rotor axis,
Where,
Similarly,
Similarly, H = H1 + H2
Therefore it is clear that the inertia constant of equivalent machine is the sum
of inertia constant of individual machines.
It is defined as the variation of steady state real power with power angle for
both generator and motor action for constant values of E, V and Xd.
Let
From equation (43) & (45), it is clear that both active and reactive power
depends on Generator voltage,(E), Bus bar voltage, (V), Total reactance, (X) and
Power angle, δ
Here, the stability conditions are stated by equating the two area segments
which is present in the power angle diagram.
The power angle curve is considered which is shown in fig.1. Imagine a system
delivering ‘Pm’ power on an angle of δ0 (fig.2) is working in a steady state. When
a fault occurs; the circuit breakers opened and the real power (Pe) is decreased
to zero. But the Pm will be stable. As a result, accelerating power,
The power differences will result in rate of change of kinetic energy stored
within the rotor masses. Therefore, due to the stable influence of non-zero
accelerating power, the rotor will accelerate. Consequently, the load angle (δ)
will increase.
Now, we can consider an angle δc at which the circuit breaker re-closes. The
power will then come back to the usual operating curve. At this moment, the
electrical power will be higher than the mechanical power. But, the accelerating
power (Pa) will be negative. Therefore, the machine will get decelerate. The load
power angle will still continue to increase because of the inertia in the rotor
masses. This increase in load power angle will stop in due course and rotor of
the machine will start to decelerate or else the synchronization of the system
will get lose.
Long question:
1. Write short notes on “Role of Automatic voltage regulator in improving
stability” (2017)
The automatic voltage regulator is used to regulate the voltage. It takes the
fluctuate voltage and changes them into a constant voltage. The fluctuation in
the voltage mainly occurs due to the variation in load on the supply system.
The variation in voltage damages the equipment of the power system. The
variation in the voltage can be controlled by installing the voltage control
equipment at several places likes near the transformers, generator, feeders,
etc., The voltage regulator is provided in more than one point in the power
system for controlling the voltage variations.
1. It controls the voltage of the system and has the operation of the
machine nearer to the steady state stability.
2. It divides the reactive load between the alternators operating in parallel.
3. The automatic voltage regulators reduce the overvoltages which occur
because of the sudden loss of load on the system.
4. It increases the excitation of the system under fault conditions so that
the maximum synchronising power exists at the time of clearance of the
fault.
For getting the quick response, the quick acting voltage regulators based on the
overshooting the mark principle are used. In overshoot mark principle, when
Prepared by Balaram Das, EE Dept., GIET, Gunupur Page 19
the load increase the excitation of the system also increase. Before the voltage
increase to the value corresponding to the increased excitation, the regulator
reduces the excitation of the proper value.
Solution:
No. of poles, N=4
Rating of Generator, G = 20 MVA
Rated voltage, V = 13.2 KV
Inertia constant, H = 9kW-sec/kVA20MVA
Electric power developed, Pe = 16 MW = 16000 kW
Mechanical power input,
Accelearating power,
7. Write short notes on Equal area criterion for power system stability analysis.(2016)
Ans: Refer class note.
8. A power station A consists of two synchronous consists of two
synchronous generators. The generator-1has a rating of 50 MVA, 50 Hz,
1500 rpm and has an inertia constant of 8MJ/MVA. The generator-2 has a
rating of 100MVA, 50 Hz, 3000 rpm and has inertia constant of 4
MJ/MVA.
i. Find the inertia constant for the equivalent generator on a base of
100MVA
ii. Another power station B has 4 generators two each of the above type.
Find the inertia constant for the equivalent generator on a base of
100MVA
iii. If the two power systems are connected through an inter connector,
find the inertia constant for the equivalent generator connected to
infinite bus bar. (2015) [10]
Ans:
Rating of Generatr-1=50MVA, 50Hz, 1500 rpm
Inertia constant = 8 MJ/MVA
Rating of Generator-2= 100MVA, 50Hz, 3000rpm
Inertia constant = 4 MJ/MVA
(i) Base=100 MVA
Inertia constant of generator-1 on a base of 100MVA,