STATIC LOAD ON BUILDING:

i) DEAD LOAD:
Unit wt. of Materials:
As per IS 875 Part I:
Reinforced Cement Concrete= 25 KN/m³
Local Brick Masonry= 18.85 KN/m³
Clear float glass= 25.5 KN/m3
Finishing Works:
Cement Plaster= 20.40 KN/m³
Screeding= 20.40 KN/m³
Marble Floor Finishing= 26.70 KN/m³
Dead Load due to the walls on the beam of the Building:
Dimensions
Total
S.No Depth (D) Finishing Self
Building Components Width (B) Unit Units Remarks
. or Height Load Weight
mm Weight
(H) mm

A 10"outer wall without opening 254 2668 1.36 12.77 14.13 KN/m
B 10" outer wall with opening 254 2668 1.16 10.86 12.01 KN/m 15% opening wall
C 10" inner wall with opening 254 2668 0.95 8.94 9.89 KN/m 30% opening
D 10" inner wall with opening 254 2668 0.82 7.66 8.48 KN/m 40% opening wall
E 5" inner wall with opening 127 2668 1.36 6.39 7.75 KN/m
F 5" Inner wall with opening 127 2668 1.22 5.43 6.65 KN/m 15% opening wall
G 5" Inner wall with opening 127 2668 0.95 4.47 5.42 KN/m 30% opening wall
H 5" Inner wall with opening 127 2668 0.82 3.83 4.65 KN/m 40% opening wall
5" parapet wall 127 1000 0.51 2.39 2.90 KN/m

ii) LIVE LOAD:


Imposed Floor load For Residential Building:
As per IS 875 part II:
Live Load Intensity for rooms with out separate storage= 2 KN/m²
Live Load for Staircase,Corridors,Passages and Lobbies= 3 KN/m²
Live Load for Bath and Toilet Rooms = 2 KN/m²
Live Load for Balconies = 3 KN/m² same as per the rooms that serves
Live Load for flat , sloping or curved Roof with slope upto 10
degree and Access Provided= 1.5 KN/m²
Floor Finising for Rooms, passages, balconys etc= 1.56 KN/m² Minimum loading for Floor Finishing
Floor Finising for Staircase (with steps)= 3 KN/m²