UHC-01-dat-1/4
BASIC FEATURES AND VARIANTS
The UHC-01 converter is intended for connecting all In addition to the input and output for HART® communica-
probes supporting HART® communication of their config- tion, the converter also contains a power supply for meas-
uration and reading measured values via the appropriate uring probes (24 V / 45 mA) with short-circuit protection.
software on a PC. The software supplied by Dinel, s.r.o. or It can thus power and communicate theoretically with up
possibly other software capable of communication via the to 10 devices at a time, provided that the probes are in
HART® protocol through a virtual serial port can be used the fixed current mode and their current consumption is
as the software. 4 mA, which is the most common way of connecting mul-
tiple measuring probes at a time. However, it is necessary
The converter is housed in an aluminium box. One side
to count with a voltage drop across the communication
contains a USB-B connector for connection to a PC and the
HART resistor, which increases with each additional probe
other side contains a 3-pin connector with 5 mm spacing.
connected and it may happen that the prescribed mini-
A terminal block with screw contacts is supplied with this
mum supply voltage of the probe will not be complied
connector.
with.
Ongoing communication is indicated by two yellow LEDs.
The converter can also communicate with the probes that
The TX LED indicates ongoing communication from the
are powered by their own voltage sources. In this case, the
PC direction to the measuring device / probe and the RX
power supply of the converter is not connected.
LED indicates ongoing communication in the opposite
direction. The converter is delivered together 23.00
47.00with the relevant
20.00
[.906]
Dinel, s.r.o. software. This software
5.85 allows you to[.787]
[1.850] make
The converter allows you to turn the communication
settings, diagnostics[.230]
and display of the measured values
HART® resistor (250 Ω) ON or OFF using a mechanical
from the probes connected to this converter. A more de-
switch.
tailed description is available in the instruction manual
to this software.
51.00
DIMENSIONS [2.008]
23.00
20.00 23.00
47.00 20.00
47.00 80.00 80.00
[.906]
[.787] [.906]
.85 5.85
[1.850] [.787]
[1.850] [3.150] [3.150]
54.00
230] [.230]
[2.126]
51.00 51.00
[2.008] [2.008]
4 ... 20 mA 4 ... 20 mA A
HART® HART® 48.15
[1.896]
41.65 4 ... 20 mA
41.65 HART®
[1.640] [1.640] 57.13 1.60
A A 20.13 20.13 23.13 23.13
[.911]
6.00
[2.249] [.063]
[.793] [.911] [.236]
[.793]
6.82 6.82
[.268] B [.268] B Radar
B
level meter
B Capacitive
level meter
Ultrasonic
level meter
Ultrasonic
level meter
GRLM-70 CLM-70
26.13 26.13 ULM-70 ULM-54
[1.029] [1.029]
UHC-01-dat-2/4 54.13
[2.131]
ELECTRICAL CONNECTION
The connection of the converter to the computer is typically carried out using a standard USB-A <-> USB-B cable.
The connection of a measuring probe or multiple probes offers various variants of connection, either with the convert-
er’s power supply or with an external power supply with the internal HART® resistor ON or OFF. All possible variants of
connection are listed in the following chapters. All figures show the output side of the converter in the direction to the
measuring probe including communication LEDs and a switch for switching ON/OFF the communication HART® resistor
(hereinafter also referred to as shunt).
UHC-01-dat-3/4
CONNECTION OF TWO OR MORE PROBES POWERED BY CONNECTING TWO OR MORE PROBES POWERED BY AN
THE INTERNAL POWER SUPPLY EXTERNAL POWER SUPPLY
This wiring is used in case of connection of two and more This wiring is used in case of connection of two and more
probes where the power supply is not available or not re- probes where the use of an external power supply is re-
quired. The figure only shows the wiring using the internal quired. The figure only shows the wiring using the internal
communication resistor. The external communication re- communication resistor. The external communication re-
sistor would be connected in the same way as when using sistor would be connected in the same way as when using
1 probe. The rule is that the other probes are always 1 probe. The rule is that the other probes are always
connected in parallel to the existing ones. connected in parallel to the existing ones. The external
power supply is marked as U in the wiring.
ACCESSORIES
3-pin screw terminal block
included in the price
with contact spacing 5 mm
Dinel, s. r. o.
U Tescomy 249, 760 01 Zlín, Czech Republic
tel.: +420 577 002 003 version:
email: sale@dinel.cz www.dinel.cz 05/2020
UHC-01-dat-4/4