SINGLE LINE DIAGRAM OF SECURITY ROOM

FEED FROM ------,


GROUND FLOOR, CB NO---
R Y B
INCOMING CABLE SIZE
32A P = 3 X 1C X 4 RM (NYY)
D/M
TP N = 1 X 1C X 4 RM (NYY)
MCCB E = 1 X 1C X 4 RM (BYA)
(set at )
1 2 3 4 5 6 7
6A 16A 6A 6A 16A 16A 10A
SP SP SP SP SP SP SP
MCB MCB MCB MCB MCB MCB MCB

N =1*1C*2.5 RM (BYA)

N =1*1C*2.5 RM (BYA)

N =1*1C*2.5 RM (BYA)

N =1*1C*2.5 RM (BYA)

N =1*1C*2.5 RM (BYA)

N =1*1C*2.5 RM (BYA)

N =1*1C*2.5 RM (BYA)
P =1*1C*2.5 RM (BYA)

P =1*1C*2.5 RM (BYA)

P =1*1C*2.5 RM (BYA)

P =1*1C*2.5 RM (BYA)

P =1*1C*2.5 RM (BYA)

P =1*1C*2.5 RM (BYA)

P =1*1C*2.5 RM (BYA)
Light Socket Light Ceiling Socket Light & Light &
Fan Fan Fan
Name of The Project Plant Name & Location Drawn By- Verified By- Approved By-
Revision No: 01 02 03 04
Latifpur Rest House
DBL-GROUP SLD OF SECURITY Revision Date: 24-10-2021
Latifpur, Kashimpur, ROOM Md.Abdul Mazed A.N.M Anwarul Azim Page No: 2 of 3
Gazipur AGM (Utility) Director (Technical)
Jinnat Complex DBL Group