Power car

Electrical panel-
1) Feeder ‘A ‘contactor (K1)- coil voltage-415 V
2) Bus coupler ‘contactor (K2)- coil voltage-415 V
3) Feeder ‘B ‘contactor (K3)- coil voltage-415 V
4) Working contactor (WP) feeder A- (K4) coil voltage-415 V
5) Non-Working contactor (NWP) feeder A-(K5) coil voltage-415 V
6) Working contactor (WP) feeder B- (K6) coil voltage-415 V
7) Non-Working contactor (NWP) feeder B-(K7) coil voltage-415 V
8) HOG-A main contactor- HOG A coil voltage-415 V
9) HOG-B main contactor- HOG B coil voltage-415 V
There are above 9 nos power contactor are provided in power car panel with
coil voltage 415 . But 415 V supply in not available in HOG as there is no
neutral ( where as netural are available when DG are working non HOG
power car).
For 415 voltage , 100 VA transformer are provided for each contactor
100 VA transformer-

1)K1- for Feeder A contactor


2)K2A- for Bus coupler contactor with feeder A
3)K2B- for Bus coupler with feeder B
4) K3- for Feeder B contactor
5)K4 for Working power car feeder A
6)K5 for non working power car feeder A
7)K6 for Working power car feeder B
8)K7 for non working power car feeder B
9)HOG A- for HOG A main contactor
10) HOG B- for HOG B main contactor
Auxiliary control contactor

Description coil voltage


S1 K08- ACB “A” control 24 V DC
S1K09 - ACB “B” control 24 V DC
S1K10- BUS coupler (k02) 24 V DC
S1K11- BUS coupler (k02) 24 V DC
S1K12-Feeder A(K1) control 24 V DC
S1K13- Feeder B (K3) control 24 V DC
S1K14- safety loop “A” control 24 V DC
S1K15- safety loop “A” control 24 V DC
S1K16-Feeder “A” overload control 24 V DC
S1K17- safety loop “B” control 24 V DC
S1K18- safety loop “B” control 24 V DC
S1K19- Feeder “B” overload control 24 V DC
S1K20- DC control supply 24 V DC ON 24 V DC
S1K21- Feeder “A” earth leakage 24 V DC
S1K22- Feeder “B” earth leakage 24 V DC
S1K25- Feeder ‘A” hooter control 24 V DC
S1K26- Feeder ‘B” hooter control 24 V DC

60 KVA transformer contractor for Radiator & Ventilator fan

Description coil voltage

1) S1 K44- 60 KVA transformer 1 415 V AC


2) S1 K46 60 KVA transformer 2 415V AC
Note- These two transformer works in DG mode. HOG mode is not required
to ON.
Neutral contactor

Description Coil voltage

1) FNA- Feeder”A” neutral contactor 415 V AC


2) FNB- Feeder”B” neutral contactor 415 V AC
3) BCNA- Bus-Coupler neutral contactor -A 415V AC
4) BCNB- Bus-Coupler neutral contactor -B 415V AC
Note- It is not applicable in HOG mode only applicable for NO-HOG
Feeder over load and earth fault relay relay
Description coil voltage
A04- Feeder “A” over load relay 24 VDC
A09 –Feeder “B” over load relay 24V DC
A05-Feeder “A” earth leakage relay 24V DC
A10 Feeder “B” earth leakage relay 24 V DC

FUSE
Description Rating
F- 8 Bus coupler (A to B) 6amps
F-8A Bus coupler neutral A (BCNA) 6 amps
F-9 Feeder “A” 6 amps
F-9 A Feeder neutral A( FNA) 6 amps
F-10 working power A(K04) 6 amps
F-11 Non working power A (NWP-K05) 2amps
F-17 Bus coupler (B to A) 6amps
F-17B Bus coupler neutral B (BCNB) 6 amps
F-18 Feeder “B” 6 amps
F-18B Feeder neutral B(FNB) 6 amps
F-19 safety loop- A control 1 amp
F-20 safety loop-B control 1 amp
F-21 working power B(K06) 6 amps
F-22 Non working power B (NWP-K07) 2amps

Fuse in front of panel S1

Description Rating
F-8 Battery charger 6amps
F-9 main +Ve 24 V DC for DG control 6 amps
F-10 positive 24 V for throttle motor 6 amps
F-11 main –VE 24V DC for DG control 6 amps
F-12 Negative 24 V for throttle motor 6 amps
F-13 Hooter circuit 6 amps
F- SP spare 6 amps

FUSE ON TOP of ACB PANNEL


Decription-

Transformer 250VA ,750 V/415V for metering and 750V/24 V for Alternator output
Transformers
 There are two no’s transformer of capacity 250 VA,3 ph 750 V/415 V for set A & Set B for
ACB UVR and metering units.
 There are two no’s transformer of 1 phase 750 V/24 V AC for Alternator out indication.

Important Rotary switch

Plant selection switch- S2S11- Mode A, A+B, B, OFF- This is use in selection D.G set
operation.
*Kept in “A” position for running Set A DG
* Kept in “B” position for running Set B DG
* Kept in “A+B” position for running both set A & B DG

Power supply ON (24VDC)- S2S23- This is most important switch . It is use in Both HOG
and DG mode. It on the 24 V main Dc supply for operation all relay, all auxiliary control
contactor, indication etc.

Battery charger ON Switch- S2S21- Keep this switch ON during HOG ,DG run & NWP for
24 V battery charging