BASIC INSTRUMENTATION &
CONTROL

1) Signal Transmission (Electric and


Pneumatic)
2) Transmitter Analog and Digital
3) Fieldbus

2
BASIC INSTRUMENTATION AND CONTROL

SIGNAL TRANSMISSION
(PNEUMATIC & ELECTRIC)
3
Pneumatic transmitters

4
Pneumatic Infrastructure

5
Pneumatic Signal Transmission

6
Connection Analog Transmitter

7
DCS Based Analog Infra-Structure

8
NAMUR Recommendation NE 43

9
Basic Wiring Scheme

10
Transmitter Minimum
Requirements

 In order to serve as a constant current source


transmitters need a minimum voltage at the terminals at
the maximum current draw of 20 (22) mA
 This minimum voltage is ~ 12 volt, but may vary from
manufacturer to manufacturer.
 Variation is ~10.5 – 12.5 volt
 Consult the spec sheets to find the correct value

11
Loop Calculation

12
Loop Calculation

 Always calculate the worst case : e.g. Power supply = 24


volt ±1.5 volt thus 22.5 volt
 Always calculate with the maximum current draw : 20
mA (even better 22 mA –fault condition current)
 Make allowance for deterioration of e.g. junction box
terminals ( increased resistance over time of the terminal
screws due to corrosion)
 Cable deterioration

13
Use of Safety Barrier

14
POWER SUPPLY EFFECT

Think about the influences of the variation of the power


 What is the operating limit for the transmitter
 Is there still enough energy available to power the
transmitter?
 Is other cable required?
 What about short power supply interruptions

15
LOAD EFFECT

 What is the maximum load we can put to e.g. a


transmitter?
 What are the impedances of the different components?

16
POWER SUPPLY AND LOAD
EFFECT

17
POWER SUPPLY AND LOAD EFFECT
EXAMPLE

The available voltage at the transmitter terminals is minimum 12


volt. The voltage loss across the input resistor for the DCS is 250*
0.02 = 5 volt.
The maximum allowable voltage loss across the cable is therefore
24 – 5 – 12 = 7 volts.
At maximum current of 20 mA the maximum cable resistance is
7/0.02 = 350 ohms.
At a typical value for the cable resistance of 40 ohm/km the total
length is 350/40 = 8.74 km.
The maximum distance between transmitter and DCS is 8.75/2 =
4.375 km

18
IEC 60529 Degree of Ingress
Protection

19
BASIC INSTRUMENTATION AND CONTROL

TRANSMITTER

20
Transmitter Overview

21
Types of Transmitter Outputs

22
Analog Transmitter

23
Analog Transmitter
How Analog Transmitters Works ?

24
Analog Transmitter
4-20 mA Current Loop

25
Smart Transmitter

26
Smart Transmitter
Analog vs Smart Transmitter

27
Smart Transmitter
HART® Protocol

28
Smart Transmitter
HART® Protocol: 4-20 mA Current Loop

29
Smart Transmitter
HART® Protocol: Communications

30
Smart Transmitter
HART® Protocol: Multidropping

31
Benefits of Smart Transmitter Against Analog
Transmitter

32
BASIC INSTRUMENTATION AND CONTROL

FIELDBUS

33
Fieldbus
What is Fieldbus?

34
Fieldbus
H1 - 31.25 kbit/s Field Devices

35
Fieldbus
H1 Signal Transmission

36
Fieldbus
Terminators

37
Fieldbus
Application

38
Fieldbus
Fieldbus Network Standard

39
Fieldbus
Fieldbus Supports Multiple Topology

40
Profibus
PROFIBUS (Process Field Bus) adalah standar untuk fieldbus
communication dipromosikan 1989 dipakai oleh Siemens.

Communication Protocol and Physical Layer Family


 Profibus FMS (Field bus Message Specification) dirancang untuk
tugas komunikasi yang kompleks. Profibus FMS digunakan untuk
komunikasi data antar Profibus Masters.
 Profibus DP (Decentralised Peripherals) adalah protokol dibuat
untuk komunikasi antara master Profibus dan remote I/O. Profibus
DP digunakan untuk mengoperasikan sensor dan aktuator melalui
pengontrol terpusat dalam aplikasi produksi (plant).
 Profibus PA (Process Automation) digunakan untuk memonitor
peralatan pengukuran melalui sistem kontrol dalam aplikasi otomasi
proses. PA memiliki tingkat transmisi data dari 31,25 kbit/s. Namun,
PA menggunakan protokol yang sama dengan DP, dan dapat
dihubungkan ke jaringan DP menggunakan perangkat coupler.
41
Profibus
Profibus Topology

42
FoundationTM Fieldbus

43
FoundationTM Fieldbus

FF Topology

44
FoundationTM Fieldbus

Control Anywhere

45
A Typical Plant Today

46