PERFORMANCE CERTIFICATE: Residential (Part 1 of 5) CF-1R PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1R PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF-1R

PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1R PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R
Project Name Building Type 4 Single Family Addition Alone Date Project Name Building Type 4 Single Family Addition Alone Date Project Name Building Type 4 Single Family Addition Alone Date Project Name Building Type 4 Single Family Addition Alone Date
Third Avenue Rowhomes Bldg A Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg A Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg A Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg A Multi Family Existing+ Addition/Alteration 2/10/2010
Project Address California Energy Climate Zone Total Cond. Floor Area Addition # of Stories ANNUAL ENERGY USE SU MMARY OPAQUE SURFACE DETAILS
San Diego CA Climate Zone 07 1,915 n/a 3 SPECIAL FEATURES INSPECTION CHECKLIST Standard Proposed Margin
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written Surface U- Insulation Joint Appendix
TDV 2
(kBtu/ft -yr)
FIELD INSPECTION ENERGY CHECKLIST justification and documentation, and special verification to be used with the performance approach. The enforcement agency Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of Space Heating 11.98 16.31 -4.33 Wall 612 0.102 R-13 180 90 New 4.3.1-A3 BLDG
Yes 4 No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form. the special justification and documentation submitted. Space Cooling 10.69 10.30 0.39 Door 20 0.500 None 180 90 New 4.5.1-A4 BLDG
Wall 901 0.102 R-13 90 90 New 4.3.1-A3 BLDG
Yes 4 No Special Features -- If Yes, see Part 2 of 5 of this form for details. Fans 4.25 4.30 -0.05
Wall 647 0.102 R-13 0 90 New 4.3.1-A3 BLDG
Domestic Hot Water 17.66 12.36 5.30
INSULATION Area Special Pumps 0.00 0.00 0.00
Wall 1,014 0.102 R-13 270 90 New 4.3.1-A3 BLDG

Construction Type Cavity (ft2) Features (see Part 2 of 5) Status Totals 44.57 43.27 1.31
Slab
Roof
72
720
0.730
0.035
None
R-30
0
0
180
0
New
New
4.4.7-A1
4.2.2-A17
BLDG
BLDG
Wall Wood Framed R-13 3,174 New Percent Better Than Standard: 2.9 % Floor 648 0.048 R-19 0 180 New 4.4.2-A4 BLDG
Door Opaque Door None 20 New
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED
Slab Unheated Slab-on-Grade None 72 New Fenestration
Building Front Orientation: (S) 180 deg Ext. Walls/Roof Wall Area Area
Roof Wood Framed Rafter R-30 720 New
Number of Dwelling Units: 1.00 (S) 708 76
Floor Wood Framed w/o Crawl Space R-19 648 New

GALLANT ENERGY CONSULTING


Fuel Available at Site: Natural Gas (W) 1,085 71
Raised Floor Area: 648 (N) 708 61
Slab on Grade Area: 72 (E) 1,085 184
Average Ceiling Height: 9.2 Roof 720 0 FENESTRATION SURFACE DETAILS
1 2
Fenestration Average U-Factor: 0.65 TOTAL: 392 ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments
FENESTRATION U- Exterior 1 Window 12.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
Average SHGC: 0.36 Fenestration/CFA Ratio: 20.5 %
Orientation Area(ft2) Factor SHGC Overhang Sidefins Shades Status 2 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
REMARKS 3 Window 16.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
Front (S) 76.0 0.650 0.36 none none Bug Screen New
4 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
Right (E) 184.0 0.650 0.36 none none Bug Screen New 5 Window 40.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
Rear (N) 61.0 0.650 0.36 none none Bug Screen New 6 Window 20.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
7 Window 20.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
Left (W) 71.3 0.650 0.36 none none Bug Screen New
8 Window 10.5 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
9 Window 25.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
HERS REQUIRED VERIFICATION 10 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a 11 Window 10.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
12 Window 37.5 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
completed CF-4R form for each of the measures listed below for final to be given.
13 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
STATEMENT OF COMPLIANCE
14 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
This certificate of compliance lists the building features and specifications needed 15 Window 25.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the 16 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
Efficiency Standards of the California Code of Regulations. (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
(2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
HVAC SYSTEMS

508 W Mission Ave Ste 201, Escondido,CA


EXTERIOR SHADING DETAILS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status The documentation author hereby certifies that the documentation is accurate and complete.
Window Overhang Left Fin Right Fin
1 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New Documentation Author ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt
Gallant Energy Consulting 1 Bug Screen 0.76
Company
2/10/2010 2 Bug Screen 0.76
Address 508 W Mission Ave Ste 201 Name Mark Gallant, CEPE 3 Bug Screen 0.76
4 Bug Screen 0.76
HVAC DISTRIBUTION Duct City/State/Zip Escondido, CA 92025 Phone 760-743-5408 Signed Date

760-743-5408 FAX 760-480-6246


5 Bug Screen 0.76
Location Heating Cooling Duct Location R-Value Status The individual with overall design responsibility hereby certifies that the proposed building design represented in this set 6 Bug Screen 0.76
HVAC System Ducted Ducted Attic, Ceiling Ins, vented 4.2 New of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and 7 Bug Screen 0.76
with any other calculations submitted with this permit application, and recognizes that compliance using duct design, 8 Bug Screen 0.76
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require 9 Bug Screen 0.76
installer testing and certification and field verification by an approved HERS rater. 10 Bug Screen 0.76
WATER HEATING 11 Bug Screen 0.76
Designer or Owner (per Business & Professions Code) 12 Bug Screen 0.76
Qty. Type Gallons Min. Eff Distribution Status Di Donato Associates 13 Bug Screen 0.76
Company
1 Instant Gas 0 0.84 No Pipe Insulation New 14 Bug Screen 0.76
Address 3939 First Avenue Ste 100 Name 15 Bug Screen 0.76
City/State/Zip San Diego, CA 92103 Phone 619-299-4210 Signed License # Date 16 Bug Screen 0.76

EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 1 of 10 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 2 of 10 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 3 of 10 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 4 of 10

CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-1R MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3) MF-1R MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3) MF-1R
Project Name Building Type 4 Single Family Addition Alone Date Project Name Building Type 4 Single Family Addition Alone Date Project Name Date Project Name Date
Third Avenue Rowhomes Bldg A Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg A Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg A 2/10/2010 Third Avenue Rowhomes Bldg A 2/10/2010
OPAQUE SURFACE DETAILS BUILDING ZONE INFORMATION NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
Surface U- Insulation Joint Appendix Floor Area (ft )
2 the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF-1R, CF-1R-ADD, or CF-
§150(m)1: All air-distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments 1R-ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
System Name Zone Name New Existing Altered Removed Volume Year Built 601, 602, 603, 604, 605 and Standard 6-5; supply-air and return-air ducts and plenums are insulated to a minimum installed level of R-
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
HVAC System BLDG 1,915 17,618 4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct-closure system that meets the
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF-1R
applicable requirements of UL 181, UL 181A, or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
Form with plans.
used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
Building Envelope Measures: §150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
§116(a)1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
§116(a)4: Fenestration products (except field-fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
Coefficient (SHGC), and infiltration that meets the requirements of §10-111(a). of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
§117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. unless such tape is used in combination with mastic and draw bands.
§118(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on CF-6R Form. §150(m)7: Exhaust fan systems have back draft or automatic dampers.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the §150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
installation of a Cool Roof is specified on the CF-1R Form. dampers.
*§150(a): Minimum R-19 insulation in wood-frame ceiling or equivalent U-factor. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150(b): Loose fill insulation shall conform with manufacturer’s installed design labeled R-Value. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
*§150(c): Minimum R-13 insulation in wood-frame wall or equivalent U-factor.
§150(m)10: Flexible ducts cannot have porous inner cores.
FENESTRATION SURFACE DETAILS *§150(d): Minimum R-13 insulation in raised wood-frame floor or equivalent U-factor. §150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
ID Type Area U-Factor
1
SHGC
2
Azm Status Glazing Type Location/Comments Totals 1,915 0 0 0

TITLE 24 ENERGY CALCULATIONS


§150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95(2000) when specified on the CF-1R Form. Quality in Low-Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
17 Window 20.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG HVAC SYSTEMS required in Section 4 of that Standard.
§150(g): Mandatory Vapor barrier installed in Climate Zones 14 or 16.
18 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status
§150(l): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance Pool and Spa Heating Systems and Equipment Measures:
19 Window 4.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG HVAC System 1 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New
rate is no greater than 2.0 perm/inch and shall be protected from physical damage and UV light deterioration. §114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
20 Window 4.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
21 Window 17.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG Fireplaces, Decorative Gas Appliances and Gas Log Measures: Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating or a pilot light.
22 Window 16.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG §150(e)1A: Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36” of pipe between filter and heater, or dedicated suction
23 Window 20.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG §150(e)1B: Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is and return lines, or built-up connections for future solar heating.
24 Window 13.3 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG equipped with a with a readily accessible, operable, and tight-fitting damper and or a combustion-air control device.
25 Window 16.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG §150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the §114(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
26 Window 10.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG HVAC DISTRIBUTION outside of the building, are prohibited. §114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
27 Window 12.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG Duct Ducts programmed to run only during off-peak electric demand periods.
Space Conditioning, Water Heating and Plumbing System Measures:
System Name Heating Cooling Duct Location R-Value Tested? Status §110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy §150(p): Residential pool systems or equipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150(p).
HVAC System Ducted Ducted Attic, Ceiling Ins, vented 4.2 New Commission. Residential Lighting Measures:
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High-Rise residential occupancies meet the air release §150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5. contained in Table 150-C and is not a low efficacy luminaire as specified by §150(k)2.
§115: Continuously burning pilot lights are prohibited for natural gas: fan-type central furnaces, household cooking appliances §150(k)3: The wattage of permanently installed luminaires shall be determined as specified by §130(d).
(1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
(2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
spa heaters. 20 kHz.
EXTERIOR SHADING DETAILS WATER HEATING SYSTEM S
Ext. §150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA. §150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
Window Overhang Left Fin Right Fin
Rated Tank Energy Standby Tank §150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line-voltage socket or line-
ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt
Input Cap. Factor Loss or Insul. R- voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
17 Bug Screen 0.76 §150(j)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
System Name Qty. Type Distribution (Btuh) (gal) or RE Pilot Value Status medium screw-base socket.
18 Bug Screen 0.76 with insulation having an installed thermal resistance of R-12 or greater.
19 Bug Screen 0.76 Takagi T-K3 FHR=181 1 Instant Gas No Pipe Insulation 199,000 0 0.84 n/a n/a New §150(j)1B: Unfired storage tanks, such as storage tanks or backup tanks for solar water-heating system, or other indirect hot water §150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the

WWW.TITLE-24.COM
20 Bug Screen 0.76 §150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
21 Bug Screen 0.76 tank. §150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
22 Bug Screen 0.76 §150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non-recirculating systems, and entire length of EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft 2 or 100 watts for dwelling units larger than 2,500 ft 2 may be
MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PI PING
23 Bug Screen 0.76 recirculating sections of hot water pipes are insulated per Standards Table 150-B. exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
Hot Water Piping Length §150(j)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
24 Bug Screen 0.76 sensor, dimmer, energy management system (EMCS), or a multi-scene programmable control system; and all permanently installed
Insulation

(ft)
Premium

25 Bug Screen 0.76 water tank shall be insulated to Table 150-B and Equation 150-A. luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
Add ½”

26 Bug Screen 0.76 §150(j)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table manual-on occupant sensor.
Eff.

27 Bug Screen 0.76 Pipe Pipe Insul. 123-A. §150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
Control Qty. HP Plenum Outside Buried System Name Length Diameter Thick. illuminated cabinet.
§150(j)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150(j)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
§150(j)4: Solar water-heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.

Registration Number: Registration Date/Time: HERS Provider:


Registration Number: Registration Date/Time: HERS Provider: EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 8 of 10
EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 5 of 10 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 6 of 10 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 7 of 10

T24.1
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3) MF-1R PERFORMANCE CERTIFICATE: Residential (Part 1 of 5) CF-1R PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1R
Project Name
Third Avenue Rowhomes Bldg A
Date
2/10/2010
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name
Third Avenue Rowhomes Bldg B
Building Type
4
Single Family
Multi Family
Addition Alone
Existing+ Addition/Alteration
Date
2/10/2010
Project Name
Third Avenue Rowhomes Bldg B
Building Type
4
Single Family
Multi Family
Addition Alone
Existing+ Addition/Alteration
Date
2/10/2010
Project Name Date Project Address California Energy Climate Zone Total Cond. Floor Area Addition # of Stories
San Diego CA Climate Zone 07 3,694 n/a 3 SPECIAL FEATURES INSPECTION CHECKLIST
§150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be Third Avenue Rowhomes Bldg A 2/10/2010 FIELD INSPECTION ENERGY CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual- determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less System Name Floor Area Yes 4 No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form. the special justification and documentation submitted.
than 1000 square feet located on a residential site is not required to comply with §150(k)11.
§150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters HVAC System 1,915 Yes 4 No Special Features -- If Yes, see Part 2 of 5 of this form for details.
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air INSULATION Area Special
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling. ENGINEERING CHECKS SYSTEM LOAD Construction Type Cavity (ft2) Features (see Part 2 of 5) Status
§150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more Wall Wood Framed R-13 6,186 New
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that Number of Systems 1 COIL COOLING PEAK COIL HTG. PEAK Door Opaque Door None 40 New

they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, Slab Unheated Slab-on-Grade None 200 New
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management Heating System CFM Sensible Latent CFM Sensible Roof Wood Framed Rafter R-30 1,400 New
Floor Wood Framed w/o Crawl Space R-19 1,296 New

GALLANT ENERGY CONSULTING


control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exception1 to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
Output per System 60,000 Total Room Loads 845 20,421 1,894 745 27,278
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires. Total Output (Btuh) 60,000 Return Vented Lighting 0
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw-base socket, and consume no FENESTRATION U- Exterior
more than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable Output (Btuh/sqft) 31.3 Return Air Ducts 923 1,601 Orientation Area(ft2) Factor SHGC Overhang Sidefins Shades Status
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable Front (S) 253.0 0.650 0.36 none none Bug Screen New
requirements of Sections 130, 131, 134, and 146.
§150(k)16: Permanently installed lighting in the enclosed, non-dwelling spaces of low-rise residential buildings with four or more Cooling System Return Fan 0 0 Rear (N) 361.0 0.650 0.36 none none Bug Screen New
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided Left (W) 20.0 0.650 0.36 none none Bug Screen New
that they are controlled by an occupant sensor(s) certified to comply with the applicable requirements of §119.
Output per System 41,500 Ventilation 0 0 0 0 0 Right (E) 20.0 0.650 0.36 none none Bug Screen New

Total Output (Btuh) 41,500 Supply Fan 0 0 HERS REQUIRED VERIFICATION


Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
Total Output (Tons) 3.5 Supply Air Ducts 923 1,601 completed CF-4R form for each of the measures listed below for final to be given.

Total Output (Btuh/sqft) 21.7


Total Output (sqft/Ton) 553.7 TOTAL SYSTEM LOAD 22,266 1,894 30,481 HVAC SYSTEMS

508 W Mission Ave Ste 201, Escondido,CA


Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
Air System 2 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New

CFM per System 1,400 HVAC EQUIPMENT SELECTION


HVAC DISTRIBUTION Duct
1,400 Rheem RGPN07NAMGR/13AJA042 35,229 5,782

760-743-5408 FAX 760-480-6246


Airflow (cfm) 60,000 Location Heating Cooling Duct Location R-Value Status
HVAC System Ducted Ducted Attic, Ceiling Ins, vented 4.2 New
Airflow (cfm/sqft) 0.73
Airflow (cfm/Ton) 404.8 WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
Outside Air (%) 0.0 % Total Adjusted System Output 35,229 5,782 60,000 2 Instant Gas 0 0.84 No Pipe Insulation New
(Adjusted for Peak Design conditions)
Outside Air (cfm/sqft) 0.00
Registration Number: Registration Date/Time: HERS Provider:
EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:06:08 ID: Page 9 of 10 Note: values above given at ARI conditions TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 1 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 2 of 8

PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R
Project Name Building Type Single Family Addition Alone Date Project Name Building Type Single Family Addition Alone Date Project Name Building Type Single Family Addition Alone Date Project Name Building Type Single Family Addition Alone Date
Third Avenue Rowhomes Bldg B 4 Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg B 4 Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg B 4 Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg B 4 Multi Family Existing+ Addition/Alteration 2/10/2010
ANNUAL ENERGY USE SU MMARY OPAQUE SURFACE DETAILS OPAQUE SURFACE DETAILS OPAQUE SURFACE DETAILS
Standard Proposed Margin Surface U- Insulation Joint Appendix Surface U- Insulation Joint Appendix Surface U- Insulation Joint Appendix
TDV 2
(kBtu/ft -yr) Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Space Heating 11.75 16.44 -4.69 Wall 682 0.102 R-13 180 90 New 4.3.1-A3 BLDG
Space Cooling 9.62 6.72 2.90 Door 20 0.500 None 180 90 New 4.5.1-A4 BLDG
3.91 3.29 0.62 Wall 892 0.102 R-13 90 90 New 4.3.1-A3 BLDG
Fans
Wall 648 0.102 R-13 0 90 New 4.3.1-A3 BLDG
Domestic Hot Water 18.99 13.72 5.27
Wall 872 0.102 R-13 270 90 New 4.3.1-A3 BLDG
Pumps 0.00 0.00 0.00
Slab 100 0.730 None 0 180 New 4.4.7-A1 BLDG
Totals 44.27 40.17 4.10 Roof 700 0.035 R-30 0 0 New 4.2.2-A17 BLDG
Percent Better Than Standard: 9.3 % Floor 648 0.048 R-19 0 180 New 4.4.2-A4 BLDG
Wall 682 0.102 R-13 180 90 New 4.3.1-A3 BLDG
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED Door 20 0.500 None 180 90 New 4.5.1-A4 BLDG
Fenestration Wall 892 0.102 R-13 270 90 New 4.3.1-A3 BLDG
Building Front Orientation: (S) 180 deg Ext. Walls/Roof Wall Area Area Wall 648 0.102 R-13 0 90 New 4.3.1-A3 BLDG
Number of Dwelling Units: 2.00 (S) 1,656 253 Wall 872 0.102 R-13 90 90 New 4.3.1-A3 BLDG
Fuel Available at Site: Natural Gas (W) 1,784 20 Slab 100 0.730 None 0 180 New 4.4.7-A1 BLDG
Raised Floor Area: 1,296 (N) 1,656 361 Roof 700 0.035 R-30 0 0 New 4.2.2-A17 BLDG
200 (E) 1,784 20 Floor 648 0.048 R-19 0 180 New 4.4.2-A4 BLDG
Slab on Grade Area:
Average Ceiling Height: 9.2 Roof 1,400 0 FENESTRATION SURFACE DETAILS FENESTRATION SURFACE DETAILS FENESTRATION SURFACE DETAILS
1 2 1 2 1 2
ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments

TITLE 24 ENERGY CALCULATIONS


Fenestration Average U-Factor: 0.65 TOTAL: 654
1 Window 8.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 17 Window 20.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG 33 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
Average SHGC: 0.36 Fenestration/CFA Ratio: 17.7 %
2 Window 40.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 18 Window 8.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 34 Window 20.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
REMARKS 3 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 19 Window 40.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
4 Window 37.5 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 20 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
5 Window 17.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 21 Window 37.5 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
6 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 22 Window 17.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
7 Window 16.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 23 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
8 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 24 Window 16.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
9 Window 10.5 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 25 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
10 Window 10.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 26 Window 10.5 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
11 Window 50.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 27 Window 10.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
12 Window 8.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 28 Window 50.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
13 Window 17.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 29 Window 8.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
STATEMENT OF COMPLIANCE
14 Window 25.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 30 Window 17.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
This certificate of compliance lists the building features and specifications needed 15 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 31 Window 25.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the 16 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 32 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG
Efficiency Standards of the California Code of Regulations. (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
(2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value (2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value (2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS EXTERIOR SHADING DETAILS EXTERIOR SHADING DETAILS
The documentation author hereby certifies that the documentation is accurate and complete.
Window Overhang Left Fin Right Fin Window Overhang Left Fin Right Fin Window Overhang Left Fin Right Fin
Documentation Author ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt
Gallant Energy Consulting 1 Bug Screen 0.76 17 Bug Screen 0.76 33 Bug Screen 0.76
Company
2/10/2010 2 Bug Screen 0.76 18 Bug Screen 0.76 34 Bug Screen 0.76
Address 508 W Mission Ave Ste 201 Name Mark Gallant, CEPE 3 Bug Screen 0.76 19 Bug Screen 0.76

WWW.TITLE-24.COM
4 Bug Screen 0.76 20 Bug Screen 0.76
City/State/Zip Escondido, CA 92025 Phone 760-743-5408 Signed Date
5 Bug Screen 0.76 21 Bug Screen 0.76
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set 6 Bug Screen 0.76 22 Bug Screen 0.76
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and 7 Bug Screen 0.76 23 Bug Screen 0.76
with any other calculations submitted with this permit application, and recognizes that compliance using duct design, 8 Bug Screen 0.76 24 Bug Screen 0.76
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require 9 Bug Screen 0.76 25 Bug Screen 0.76
installer testing and certification and field verification by an approved HERS rater. 10 Bug Screen 0.76 26 Bug Screen 0.76
11 Bug Screen 0.76 27 Bug Screen 0.76
Designer or Owner (per Business & Professions Code) 12 Bug Screen 0.76 28 Bug Screen 0.76
Di Donato Associates 13 Bug Screen 0.76 29 Bug Screen 0.76
Company
14 Bug Screen 0.76 30 Bug Screen 0.76
Address 3939 First Avenue Ste 100 Name 15 Bug Screen 0.76 31 Bug Screen 0.76
City/State/Zip San Diego, CA 92103 Phone 619-299-4210 Signed License # Date 16 Bug Screen 0.76 32 Bug Screen 0.76

EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 3 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 4 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 5 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 6 of 8

T24.2
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-1R PERFORMANCE CERTIFICATE: Residential (Part 1 of 5) CF-1R PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1R
Project Name
Third Avenue Rowhomes Bldg B
Building Type
4
Single Family
Multi Family
Addition Alone
Existing+ Addition/Alteration
Date HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name
Third Avenue Rowhomes Bldg C
Building Type
4
Single Family
Multi Family
Addition Alone
Existing+ Addition/Alteration
Date
2/10/2010
Project Name
Third Avenue Rowhomes Bldg C
Building Type
4
Single Family
Multi Family
Addition Alone
Existing+ Addition/Alteration
Date
2/10/2010 2/10/2010
BUILDING ZONE INFORMATION Project Name Date Project Address California Energy Climate Zone Total Cond. Floor Area Addition # of Stories
2 San Diego CA Climate Zone 07 3,186 n/a 3 SPECIAL FEATURES INSPECTION CHECKLIST
System Name Zone Name New
Floor Area (ft )
Existing Altered Removed Volume Year Built Third Avenue Rowhomes Bldg B 2/10/2010 FIELD INSPECTION ENERGY CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
HVAC System BLDG.L 1,847 16,992 determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
BLDG.R 1,847 16,992 System Name Floor Area Yes 4 No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form. the special justification and documentation submitted.

HVAC System 3,694 Yes 4 No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
ENGINEERING CHECKS SYSTEM LOAD Construction Type Cavity (ft2) Features (see Part 2 of 5) Status
Wall Wood Framed R-13 6,169 New

Number of Systems 2 COIL COOLING PEAK COIL HTG. PEAK Door Opaque Door None 40 New
Slab Unheated Slab-on-Grade None 160 New

Heating System CFM Sensible Latent CFM Sensible Roof Wood Framed Rafter R-30 1,512 New
Floor Wood Framed w/o Crawl Space R-19 1,296 New

GALLANT ENERGY CONSULTING


Output per System 60,000 Total Room Loads 1,692 40,890 3,711 1,399 51,341

Totals 3,694 0 0 0 Total Output (Btuh) 120,000 Return Vented Lighting 0


HVAC SYSTEMS FENESTRATION U- Exterior
System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status Output (Btuh/sqft) 32.5 Return Air Ducts 1,848 3,014 Orientation Area(ft2) Factor SHGC Overhang Sidefins Shades Status
HVAC System 2 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New Rear (N) 171.5 0.650 0.36 none none Bug Screen New

Cooling System Return Fan 0 0 Right (E) 118.0 0.650 0.36 none none Bug Screen New
Left (W) 89.0 0.650 0.36 none none Bug Screen New
Output per System 41,500 Ventilation 0 0 0 0 0 Front (S) 184.5 0.650 0.36 none none Bug Screen New

HVAC DISTRIBUTION Total Output (Btuh) 83,000 Supply Fan 0 0 HERS REQUIRED VERIFICATION
Duct Ducts Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
System Name Heating Cooling Duct Location R-Value Tested? Status
HVAC System Ducted Ducted Attic, Ceiling Ins, vented 4.2 New Total Output (Tons) 6.9 Supply Air Ducts 1,848 3,014 completed CF-4R form for each of the measures listed below for final to be given.

Total Output (Btuh/sqft) 22.5


Total Output (sqft/Ton) 534.1 TOTAL SYSTEM LOAD 44,586 3,711 57,369 HVAC SYSTEMS

508 W Mission Ave Ste 201, Escondido,CA


WATER HEATING SYSTEM S
Ext. Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
Rated Tank Energy Standby Tank Air System 2 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New
Input Cap. Factor Loss or Insul. R-
System Name Qty. Type Distribution (Btuh) (gal) or RE Pilot Value Status
Takagi T-K3 FHR=181 2 Instant Gas No Pipe Insulation 199,000 0 0.84 n/a n/a New CFM per System 1,400 HVAC EQUIPMENT SELECTION
HVAC DISTRIBUTION Duct
2,800 Rheem RGPN07NAMGR/13AJA042 70,487 11,524

760-743-5408 FAX 760-480-6246


Airflow (cfm) 120,000 Location Heating Cooling Duct Location R-Value Status
MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PI PING
Hot Water Piping Length HVAC System Ducted Ducted Attic, Ceiling Ins, vented 4.2 New
Airflow (cfm/sqft) 0.76
Insulation

(ft)
Premium

Add ½”

Airflow (cfm/Ton) 404.8


Eff.

Pipe Pipe Insul.


Control Qty. HP Plenum Outside Buried System Name Length Diameter Thick. WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
Outside Air (%) 0.0 % Total Adjusted System Output 70,487 11,524 120,000 2 Instant Gas 0 0.84 No Pipe Insulation New
(Adjusted for Peak Design conditions)
Outside Air (cfm/sqft) 0.00

EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:22:12 ID: Page 7 of 8 Note: values above given at ARI conditions TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 1 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 2 of 8

PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1R
Project Name Building Type Single Family Addition Alone Date Project Name Building Type Single Family Addition Alone Date Project Name Building Type Single Family Addition Alone Date Project Name Building Type Single Family Addition Alone Date
Third Avenue Rowhomes Bldg C 4 Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg C 4 Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg C 4 Multi Family Existing+ Addition/Alteration 2/10/2010 Third Avenue Rowhomes Bldg C 4 Multi Family Existing+ Addition/Alteration 2/10/2010
ANNUAL ENERGY USE SU MMARY OPAQUE SURFACE DETAILS OPAQUE SURFACE DETAILS OPAQUE SURFACE DETAILS
Standard Proposed Margin Surface U- Insulation Joint Appendix Surface U- Insulation Joint Appendix Surface U- Insulation Joint Appendix
TDV 2
(kBtu/ft -yr) Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Space Heating 13.96 18.40 -4.44 Wall 1,084 0.102 R-13 180 90 New 4.3.1-A3 BLDG
Space Cooling 11.48 9.48 2.00 Door 20 0.500 None 180 90 New 4.5.1-A4 BLDG
4.58 4.20 0.38 Wall 953 0.102 R-13 0 90 New 4.3.1-A3 BLDG
Fans
Wall 573 0.102 R-13 90 90 New 4.3.1-A3 BLDG
Domestic Hot Water 20.68 14.41 6.27
Wall 547 0.102 R-13 270 90 New 4.3.1-A3 BLDG
Pumps 0.00 0.00 0.00
Slab 108 0.730 None 0 180 New 4.4.7-A1 BLDG
Totals 50.71 46.49 4.21 Roof 756 0.035 R-30 0 0 New 4.2.2-A17 BLDG
Percent Better Than Standard: 8.3 % Floor 648 0.048 R-19 0 180 New 4.4.2-A4 BLDG
Wall 1,084 0.102 R-13 0 90 New 4.3.1-A3 BLDG
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED Wall 920 0.102 R-13 180 90 New 4.3.1-A3 BLDG
Fenestration Wall 487 0.102 R-13 90 90 New 4.3.1-A3 BLDG
Building Front Orientation: (S) 180 deg Ext. Walls/Roof Wall Area Area Wall 522 0.102 R-13 270 90 New 4.3.1-A3 BLDG
Number of Dwelling Units: 2.00 (S) 2,208 185 Door 20 0.500 None 270 90 New 4.5.1-A4 BLDG
Fuel Available at Site: Natural Gas (W) 1,178 89 Slab 52 0.730 None 0 180 New 4.4.7-A1 BLDG
Raised Floor Area: 1,296 (N) 2,208 172 Roof 756 0.035 R-30 0 0 New 4.2.2-A17 BLDG
160 (E) 1,178 118 Floor 648 0.048 R-19 0 180 New 4.4.2-A4 BLDG
Slab on Grade Area:
Average Ceiling Height: 9.2 Roof 1,512 0 FENESTRATION SURFACE DETAILS FENESTRATION SURFACE DETAILS FENESTRATION SURFACE DETAILS
1 2 1 2 1 2
ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments ID Type Area U-Factor SHGC Azm Status Glazing Type Location/Comments

TITLE 24 ENERGY CALCULATIONS


Fenestration Average U-Factor: 0.65 TOTAL: 563
1 Window 10.5 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 17 Window 25.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 33 Window 16.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG
Average SHGC: 0.36 Fenestration/CFA Ratio: 17.7 %
2 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 18 Window 25.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 34 Window 10.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG
REMARKS 3 Window 16.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 19 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 35 Window 17.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG
4 Window 4.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 20 Window 16.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG 36 Window 4.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG
5 Window 33.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 21 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
6 Window 16.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 22 Window 37.5 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
7 Window 12.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 23 Window 4.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
8 Window 40.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 24 Window 33.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
9 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG 25 Window 16.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
10 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG 26 Window 20.0 0.650 NFRC 0.36 NFRC 180 New Metal Lowe2 BLDG
11 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG 27 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
12 Window 4.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG 28 Window 10.5 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
13 Window 12.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG 29 Window 20.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
STATEMENT OF COMPLIANCE
14 Window 10.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG 30 Window 20.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
This certificate of compliance lists the building features and specifications needed 15 Window 20.0 0.650 NFRC 0.36 NFRC 270 New Metal Lowe2 BLDG 31 Window 37.5 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the 16 Window 20.0 0.650 NFRC 0.36 NFRC 0 New Metal Lowe2 BLDG 32 Window 10.0 0.650 NFRC 0.36 NFRC 90 New Metal Lowe2 BLDG
Efficiency Standards of the California Code of Regulations. (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
(2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value (2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value (2) SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS EXTERIOR SHADING DETAILS EXTERIOR SHADING DETAILS
The documentation author hereby certifies that the documentation is accurate and complete.
Window Overhang Left Fin Right Fin Window Overhang Left Fin Right Fin Window Overhang Left Fin Right Fin
Documentation Author ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt ID Exterior Shade Type SHGC Hgt Wd Len Hgt LExt RExt Dist Len Hgt Dist Len Hgt
Gallant Energy Consulting 1 Bug Screen 0.76 17 Bug Screen 0.76 33 Bug Screen 0.76
Company
2/10/2010 2 Bug Screen 0.76 18 Bug Screen 0.76 34 Bug Screen 0.76
Address 508 W Mission Ave Ste 201 Name Mark Gallant, CEPE 3 Bug Screen 0.76 19 Bug Screen 0.76 35 Bug Screen 0.76

WWW.TITLE-24.COM
4 Bug Screen 0.76 20 Bug Screen 0.76 36 Bug Screen 0.76
City/State/Zip Escondido, CA 92025 Phone 760-743-5408 Signed Date
5 Bug Screen 0.76 21 Bug Screen 0.76
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set 6 Bug Screen 0.76 22 Bug Screen 0.76
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and 7 Bug Screen 0.76 23 Bug Screen 0.76
with any other calculations submitted with this permit application, and recognizes that compliance using duct design, 8 Bug Screen 0.76 24 Bug Screen 0.76
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require 9 Bug Screen 0.76 25 Bug Screen 0.76
installer testing and certification and field verification by an approved HERS rater. 10 Bug Screen 0.76 26 Bug Screen 0.76
11 Bug Screen 0.76 27 Bug Screen 0.76
Designer or Owner (per Business & Professions Code) 12 Bug Screen 0.76 28 Bug Screen 0.76
Di Donato Associates 13 Bug Screen 0.76 29 Bug Screen 0.76
Company
14 Bug Screen 0.76 30 Bug Screen 0.76
Address 3939 First Avenue Ste 100 Name 15 Bug Screen 0.76 31 Bug Screen 0.76
City/State/Zip San Diego, CA 92103 Phone 619-299-4210 Signed License # Date 16 Bug Screen 0.76 32 Bug Screen 0.76

EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 3 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 4 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 5 of 8 EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 6 of 8

T24.3
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-1R
Project Name
Third Avenue Rowhomes Bldg C
Building Type
4
Single Family
Multi Family
Addition Alone
Existing+ Addition/Alteration
Date HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
2/10/2010
BUILDING ZONE INFORMATION Project Name Date
2

System Name Zone Name New


Floor Area (ft )
Existing Altered Removed Volume Year Built Third Avenue Rowhomes Bldg C 2/10/2010
HVAC System BLDG.1 NORTH 1,551 14,269
BLDG.2 SOUTH 1,635 15,042 System Name Floor Area
HVAC System 3,186
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems 2 COIL COOLING PEAK COIL HTG. PEAK
Heating System CFM Sensible Latent CFM Sensible

GALLANT ENERGY CONSULTING


Output per System 60,000 Total Room Loads 1,841 44,169 3,420 1,301 47,622

Totals 3,186 0 0 0 Total Output (Btuh) 120,000 Return Vented Lighting 0


HVAC SYSTEMS
System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status Output (Btuh/sqft) 37.7 Return Air Ducts 1,996 2,796
HVAC System 2 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New

Cooling System Return Fan 0 0

Output per System 35,000 Ventilation 0 0 0 0 0


HVAC DISTRIBUTION Total Output (Btuh) 70,000 Supply Fan 0 0
Duct Ducts
System Name Heating Cooling Duct Location R-Value Tested? Status
HVAC System Ducted Ducted Attic, Ceiling Ins, vented 4.2 New Total Output (Tons) 5.8 Supply Air Ducts 1,996 2,796
Total Output (Btuh/sqft) 22.0
Total Output (sqft/Ton) 546.2 TOTAL SYSTEM LOAD 48,161 3,420 53,213

508 W Mission Ave Ste 201, Escondido,CA


WATER HEATING SYSTEM S
Ext.
Rated Tank Energy Standby Tank Air System
Input Cap. Factor Loss or Insul. R-
System Name Qty. Type Distribution (Btuh) (gal) or RE Pilot Value Status
Takagi T-K3 FHR=181 2 Instant Gas No Pipe Insulation 199,000 0 0.84 n/a n/a New CFM per System 1,200 HVAC EQUIPMENT SELECTION

2,400 Rheem RGPN07NAMER/13AJA036 57,805 11,445

760-743-5408 FAX 760-480-6246


Airflow (cfm) 120,000
MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PI PING
Hot Water Piping Length
Airflow (cfm/sqft) 0.75
Insulation

(ft)
Premium

Add ½”

Airflow (cfm/Ton) 411.4


Eff.

Pipe Pipe Insul.


Control Qty. HP Plenum Outside Buried System Name Length Diameter Thick.

Outside Air (%) 0.0 % Total Adjusted System Output 57,805 11,445 120,000
(Adjusted for Peak Design conditions)
Outside Air (cfm/sqft) 0.00

EnergyPro 5.0 by EnergySoft User Number: 2875 RunCode: 2010-02-10T11:55:25 ID: Page 7 of 8 Note: values above given at ARI conditions TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM