H2S sensor on GNX hardware MFSD 055

Page 1/1

SUBJECT: Use the standard H2s sensor (General Monitor), 432.CC.020 on Geonext Hardware.

24VDC

Capteur

White
H
e
Red a
1 Cel t
Green e
2 r
GNX01
3
Black
4

R = 3,16kΩ

Hazardous area
Safe area

You have to use the 0-10V driver on gNA.

The signal range is: 0V (No H2S) to 4V (20ppm H2S), the measurement will be done through GNX01 module
positioned in the concentrator or connected directly in the field box located in the unit.(safe area)

Issued by Verified by Approved by


FSD Dept Technical Dept DT Manager
24/04/2006 24/04/2006 24/04/2006
Revision 0
MFSD 055 L14 220 T