RHS Purlin Design for Juba Mall

This document analyzes the design of a purlin section for a roof level in a shopping mall project. It summarizes the section properties and performs checks for bending capacity, shear capacity, and deflection under service loads. The analysis finds that the section is classified as plastic and has sufficient bending and shear capacity. However, the deflection under service loads exceeds the allowable limit.

Uploaded by

kkgc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
195 views3 pages

RHS Purlin Design for Juba Mall

This document analyzes the design of a purlin section for a roof level in a shopping mall project. It summarizes the section properties and performs checks for bending capacity, shear capacity, and deflection under service loads. The analysis finds that the section is classified as plastic and has sufficient bending and shear capacity. However, the deflection under service loads exceeds the allowable limit.

Uploaded by

kkgc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
  • Design Analysis
  • Structural Equations
  • Structural Equations (Continued)

Design of RHS to BS 5950:2000

Project JUBA SHOPPING MALL


Section PURLIN
Level ROOF LEVEL
Section 100X50X32.2

Section Properties
Width(B) 50 mm
Depth(D) 100 mm `
Web Thickness (t) 3.2 mm
Flange Thickness (T) 3.2 mm
Cross Sectional Area (A) 9.19 cm^2
Unit Weight 7.17 kg/m
Ixx 118.72 cm^4
Iyy 39.52 cm^4
rxx 3.59 cm
ryy 2.07 cm
Zxx 23.74 cm^3
Zyy 15.81 cm^3
Sxx 29.51 cm^3
Syy 18.02 cm^3

Results from the Analysis


Bending Moment 2.36 kN
Shear Force 3.15 kNm
Section Classification
b 40.4 mm
d 90.4 mm
b/t 12.63
d/t 28.25
Py 275 N/mm^2
ϵ 1
Flange(Plastic/Compact/Semi Compact) Flange is Plastic
Web(Plastic/compact/Semi Compact) Web is Plastic

Section Classification Cross Section is Plastic


Checks for shear
Shear Area 6.13 mm^2
Shear Capacity 101.145 kN
Applied Shear 3.15 kN
Shear Capacity is OK
Section is in Low Shear
Checks for Moment
Moment Capacity 8.11525 kNm
Applied Moment 2.36 kNm
Moment Capacity is OK
Checks for Lateral Torsional Buckling
For RHS there is no need to consider the lateral torsional Buckling.
Checks for Lateral Torsional Buckling
Span of the beam 3000 mm
Allowable Deflection (Span/360) 8.33 mm
Actual defelctions (SLS Combination) 10 mm
Deflection is not Ok