Design of RHS to BS 5950:2000
Project JUBA SHOPPING MALL
Section PURLIN
Level ROOF LEVEL
Section 100X50X32.2
Section Properties
Width(B) 50 mm
Depth(D) 100 mm `
Web Thickness (t) 3.2 mm
Flange Thickness (T) 3.2 mm
Cross Sectional Area (A) 9.19 cm^2
Unit Weight 7.17 kg/m
Ixx 118.72 cm^4
Iyy 39.52 cm^4
rxx 3.59 cm
ryy 2.07 cm
Zxx 23.74 cm^3
Zyy 15.81 cm^3
Sxx 29.51 cm^3
Syy 18.02 cm^3
Results from the Analysis
Bending Moment 2.36 kN
Shear Force 3.15 kNm
Section Classification
b 40.4 mm
d 90.4 mm
b/t 12.63
d/t 28.25
Py 275 N/mm^2
ϵ 1
Flange(Plastic/Compact/Semi Compact) Flange is Plastic
Web(Plastic/compact/Semi Compact) Web is Plastic
Section Classification Cross Section is Plastic
Checks for shear
Shear Area 6.13 mm^2
Shear Capacity 101.145 kN
Applied Shear 3.15 kN
Shear Capacity is OK
Section is in Low Shear
Checks for Moment
Moment Capacity 8.11525 kNm
Applied Moment 2.36 kNm
Moment Capacity is OK
Checks for Lateral Torsional Buckling
For RHS there is no need to consider the lateral torsional Buckling.
Checks for Lateral Torsional Buckling
Span of the beam 3000 mm
Allowable Deflection (Span/360) 8.33 mm
Actual defelctions (SLS Combination) 10 mm
Deflection is not Ok
Fc m x M x m y M y
Pc Py Z x Py Z y
Fc mLT M LT m y M y
Pc y Mb Py Z y
Fc m x M x m y M y
Pc Py Z x Py Z y
Fc mLT M LT m y M y
Pc y Mb Py Z y